100% found this document useful (1 vote)
578 views2 pages

DP Transmitter Calibration

To calibrate a pressure transmitter: 1. Calibrate the transmitter's 0% output to the lower range value (LRV) of 0 pressure and 100% output to the upper range value (URV) of the calibration pressure range. 2. Locate the zero and span adjustment screws and turn them between the maximum and minimum resistance points to set the mid-point at 50%. 3. Apply the minimum pressure, adjust the zero screw to the 4mA output, then apply maximum pressure and adjust the span screw to the 20mA output.

Uploaded by

supercontroller
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
578 views2 pages

DP Transmitter Calibration

To calibrate a pressure transmitter: 1. Calibrate the transmitter's 0% output to the lower range value (LRV) of 0 pressure and 100% output to the upper range value (URV) of the calibration pressure range. 2. Locate the zero and span adjustment screws and turn them between the maximum and minimum resistance points to set the mid-point at 50%. 3. Apply the minimum pressure, adjust the zero screw to the 4mA output, then apply maximum pressure and adjust the span screw to the 20mA output.

Uploaded by

supercontroller
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Steps to Calibrate a Pressure Transmitter 

After completing all the preliminary requirements, you can proceed in the following 
ways: 

 
● Calibrate the 0%, Lower Range Value (LRV) of the transmitter to the LRV of the 
calibration range. Calibrate the transmitters span to 100%, Upper Range Value 
(URV) of the calibration range. For example: If you are using a DP​ transmitter​ with 
power output 4-20mA to measure pressure in the range 0-300 PSIG, then the 
transmitter’s 0% LRV is 4mA, and is calibrated to 0PSIG. Similarly, the 100% URV 
is 20mA, and will be calibrated to 20 mA. 
● Locate the ZERO and SPAN/RANGE screws of the transmitter by referring the 
instruction manual. These screws are each connected to the potentiometer and 
can be turned easily. 
The potentiometer allows up to 20 turns between the maximum and minimum 
resistance. This means 20 clockwise or anticlockwise turns of ZERO and SPAN 
screw will cause the potentiometer to be at maximum or minimum. In many 
brands of DP transmitters, the ZERO and RANGE adjustments are 
interconnected. This means adjusting one screw may affect the other. 
● Turn the RANGE and ZERO screws clockwise 20 times. Next, turn the screws 10 
times in the counterclockwise direction to adjust the potentiometer between the 
maximum and minimum resistance. This step is performed to set the mid 
resistance point at 50%. 
● Apply the LRV 0% on the high side of the transmitter, and low vented side. This 
helps diminish the differential pressure across the DP cell of the transmitter. 
● Adjust the ZERO screw on the transmitter by observing the 4mA indication in the 
current meter. This is the LRV output of your transmitter. At times, this value may 
not be 4 mA, but you should get a value closer to that. 
● Next, apply pressure on the high side of the transmitter to increase the value to 
the 100% higher value (URV) of the calibration range. 
● Adjust the RANGE Screw by observing the meter’s current indication, which 
should show 20 mA, which is the 100% URV output of the transmitter. 
● In an ideal situation, 100% of the transmitter's input should correspond to the set 
standard readings of transmitters 100% output (4-20 mA). Accurately calibrated 
pressure is the one, where the values of input equals to the output for all values 
between 0-100percent. 

You might also like