Annex I - SIL - Verification - Report
Annex I - SIL - Verification - Report
Refinery Expansion
Annex I
2
1
0 27/01/2020 First review AHT AHT JB
Rev. Date Description Prepared Reviewed Approved
1
Client name
SIF: SIF-2
Required Achieved Achieved Achieved PFDavg MTTFS (years)
SIL-1 SIL SIL-1 PFDavg SIL-2 sensor SIL-1 5,77E-04 836
20 RRF 373 Arch. C. SIL-1 logic solver SIL-3 1,67E-04 207
Route 1H PFDavg 2,68E-03 SC SIL-2 actuator SIL-2 1,94E-03 74
10 MTTFS (y) 51 other -- -- --
High High Tank Level on LT-1 closes feed valves XV-1A/B [1oo2]. Out of range sensor diagnostics in PLC (see main document)
LOGIC SOLVER
ESD-1 XV-1A
1oo1 1oo2 Output
LT-1 1oo2D
Input Input Output
voting Safety PLC voting XV-1B
group Model: Generic group Output
2
Client name
SIF: SIF-2
Subsystem Tags Logic PFDavg SIL (pfd) HFT SC SIL (arch) MTTFS (y)
sensor LT-1 1oo1 5,77E-04 3 0 2 1 836
sen_part transmitter -- -- 3 -- --
sen_part process -- -- -- --
sen_part interface -- -- 2 -- --
logicsolver ESD-1 1oo2D 1,67E-04 3 1 3 3 207
3
Client name
SIF: M4-PT-2312-06
Required Achieved Achieved Achieved PFDavg MTTFS (years)
SIL-2 SIL SIL-2 PFDavg SIL-2 sensor SIL-2 5,25E-05 3866
200 RRF 462 Arch. C. SIL-2 logic solver SIL-3 1,73E-04 201
Route 1H PFDavg 2,16E-03 SC SIL-3 actuator SIL-2 1,94E-03 74
10 MTTFS (y) 54 other -- -- --
High High Pressure on PT-6A/B/C [2oo3] closes feed valves XV-6A/B Out of range sensor diagnostics in PLC (see main document)
[1oo2]
PT-6A
Input LOGIC SOLVER
ESD-1 XV-6A
2oo3 1oo2 Output
PT-6B 1oo2D
Input Input Output
voting Safety PLC voting XV-6B
group Model: Generic group Output
PT-6C
Input
4
Client name
SIF: M4-PT-2312-06
Subsystem Tags Logic PFDavg SIL (pfd) HFT SC SIL (arch) MTTFS (y)
sensor PT-6 2oo3 5,25E-05 4 1 3 2 3.866
sen_part transmitter -- -- 3 -- --
sen_part seal -- -- 3 -- --
5
Client name
SIF: M5-FT-2312-30
Required Achieved Achieved Achieved PFDavg MTTFS (years)
SIL-2 SIL SIL-2 PFDavg SIL-2 sensor SIL-3 2,54E-05 4176
200 RRF 245 Arch. C. SIL-2 logic solver SIL-3 1,78E-04 197
Route 1H PFDavg 4,08E-03 SC SIL-3 actuator SIL-2 3,88E-03 37
10 MTTFS (y) 31 other -- -- --
Low Low Air Flow on FT-30A/B/C [2oo2] closes Fuel Gas Valves (1oo2 XV- Out of range sensor diagnostics in PLC (see main document)
30/31) & Natural Gas Valves (1oo2 XV-32/33) [2oo2 of FG & NG]
[FG] XV-30
1oo2 Output
FT-30A
Input LOGIC SOLVER Output
ESD-1 voting [FG] XV-31
2oo3 2oo2 group Output
FT-30B 1oo2D
Input Input Output
voting Safety PLC Group [NG] XV-32
group Model: Generic 1oo2 Output
FT-30C
Input Output
voting [NG] XV-33
group Output
6
Client name
SIF: M5-FT-2312-30
Subsystem Tags Logic PFDavg SIL (pfd) HFT SC SIL (arch) MTTFS (y)
sensor FT-30 2oo3 2,54E-05 4 1 3 3 4.176
sen_part transmitter -- -- 3 -- --
sen_part process -- -- -- --
7
Client name
Subsystem Tags Logic PFDavg SIL (pfd) HFT SC SIL (arch) MTTFS (y)
actuator [FG] XV-30/31 1oo2 1,94E-03 2 1 3 2 74
act_part valve -- -- 3 -- --
act_part actuator -- -- 3 -- --
act_part solenoid -- -- 3 -- --
act_part driver -- -- 3 -- --