How To Size Current Transformers PDF
How To Size Current Transformers PDF
com%2fnotes)
Login (https://myelectrical.com/login?returnurl=%2fnotes%2fentryid%2f99%2fhow-to-size-current-transformers)
(https://myelectrical.com/)
datasheetspdf.com
IEC 60044 specifies the requirements for protection CTs (in addition to measuring CT's, VTs and electronic sensors). Differential protection, the good old days
(https://myelectrical.com/notes/entryid/90/differential-
The key to CT dimensioning under the standard, is the symmetrical short circuit current and transient dimensioning factors: protection-the-good-old-days)
This morning I was explaining how differential protection
Kssc - rated symmetrical short-circuit current factor works to a junior engineer. To give him something to read I
K’ssc - effective symmetrical short-circuit current factor opened up the NPAG (Network Protection...
Ktd - transient dimensioning factor Voltage Levels to IEC 60038
(https://myelectrical.com/notes/entryid/203/voltage-
The factor Kssc is relatively easy to understand and relates to the liner portion levels-to-iec-60038)
Example IEC 60044 Calculation
of a CT characteristic. The voltage and current across a CT are linear only The standard aims to consolidate AC and traction voltages
up till a certain value (normally specified as a multiple of the nominal rating), within the industry and defines the following bands: band 1 -
Consider a CT with the following
after which the CT will saturate and the curve will level off. A CT rated at say A.C. systems 100 V to 1...
specification and protection
5P20 will stay linear to approximately 20 times its nominal current. This
requirements:
linear limit is the Kssc (i.e. Kssc = 20). As a reminder, the 5 [in the 5P20] Power Factor
would be the CT accuracy class and the ‘P’ signifies a protection class CT. (https://myelectrical.com/notes/entryid/197/power-
CT: 600/1 5P20 15 VA, Rct = 4
factor)
Ω
Slightly more complicated is the effective factor, K’scc. This is a calculated Power factor is the ratio between the real power (P in kW)
2
CT Leads: 6 mm , 50 m long
value which takes into account the burden (resistance) of the relay, and apparent power (S in kVA) drawn by an electrical load.
- use R=2 ρ l /a to calculate =
resistance of the CT windings and resistance of the leads: The reactive power (Q in kVAr)...
0.0179 Ω/m
Relay: Siemens 7SJ45, Ktd = 1
Bows and Arrows
Short circuit current, Iscc max =
(https://myelectrical.com/notes/entryid/42/bows-and-
30 kA
arrows)
It starts with me reading one of the Horrible History books
To find the lead resistance Rleads (two with my son (Groovy Greeks). Arrows were mentioned
leads – supply, return) we can use the which lead to the discussion of the bodkin...
standard formulae for resistivity:
Generator Sizing & Operation Limits
Rleads = 2 ρ l /a = 2 x 0.0175 x 50 / 6 = (https://myelectrical.com/notes/entryid/62/generator-
0.3 Ω operation-limits)
When selecting a generator, there are inherent limits on the
Numerical relays have low burdens, active and reactive power which can be delivered.
typically 0.1 Ω (where possible the relay Generators are normally sized for a certain...
manual should be consulted).
ABB Technical Guides - Motor Operation
Plugging everything into the equations: (https://myelectrical.com/notes/entryid/34/abb-
technical-guides-motor-operation)
2
Rb = 15 VA / 1 A = 15 Ω ABB has produced a range of technical guides that offer
concise explanations of the major technologies and
R’b = Rleads + Rrelay = 0.3 + 0.1 = 0.4 Ω technical issues in low voltage AC drives. ...
= 20 (4 + 15 )/ (4 + 0.4) = 86.4
(http://myelectrical.com/Portals/0/SunBlogNuke/2/WindowsLiveWriter/HowtoSizeCurrentTransformers_FC74/7345944727c6cb5e8f2423756b28f0bb_2.png)
Required K’scc > 1 x 30000/600 = 50
(http://myelectrical.com/Portals/0/SunBlogNuke/2/WindowsLiveWriter/HowtoSizeCurrentTransformers_FC74/c176f53a1ee1cd44331dd80e552366ff_2.png)
That it. Once you have confirmed the above is ok, you know your CT is ok.
There is a slight complication in the manufacturers know their relays better than we (or the IEC) do. As general advice, you
should always refer to the manufacturers information:
Connection Leads
In the sizing of protection transformers, the resistance (burden) of the connection leads can have a considerable effect. In
calculations, the resistance of the connection leads can be estimated from:
where:
BS 3938 and BS 7626 are older British Standards which deal the the specification and sizing of current transformers. Both
of these have been withdrawn and are superseded by the IEC 6044 standard.
The standards adopted the concept of knee voltage and it is still common to find knee voltage voltage being used as a CT
sizing parameter.
Knee voltage is defined as the point at which a 10% increase in voltage across the terminals, causes a 50%
increase in excitation current
Utilising the British Standards, CTs were defined by the knee point voltage UKN and the internal secondary resistance Ri. To
convert an IEC design the following can be used:
ANSI/IEEE C57.13
The IEEE standard C57.13 covers the requirements for CT sizing in the North American markets.
Class C of the standard defines CTs by their secondary terminal voltage at 20 times nominal current (for which the ratio error
shall not exceed 10%). Standard classes are C100, C200, C400 and C800 for 5 A nominal secondary current.
This terminal voltage can be calculated from the IEC data as follows:
with
and
If anyone has any questions, comments or suggestions on how to improve the post, please add them below.
(http://myelectricalengineering.co.uk)
Popular Tags
Automation (https://myelectrical.com/notes/tag/automation) Batteries (https://myelectrical.com/notes/tag/batteries)
Buildings (https://myelectrical.com/notes/tag/buildings) Cable Sizing (https://myelectrical.com/notes?tag=cable+sizing)
Cables (https://myelectrical.com/notes/tag/cables) Circuit Breakers (https://myelectrical.com/notes?tag=circuit+breakers)
Commissioning (https://myelectrical.com/notes/tag/commissioning) Control Systems (https://myelectrical.com/notes?tag=control+systems)
Earth Fault (https://myelectrical.com/notes?tag=earth+fault) Editing (https://myelectrical.com/notes/tag/editing)
Education (https://myelectrical.com/notes/tag/education) Electrical Installations (https://myelectrical.com/notes?tag=electrical+installations)
Electronics (https://myelectrical.com/notes/tag/electronics) Energy (https://myelectrical.com/notes/tag/energy)
Equipment (https://myelectrical.com/notes/tag/equipment)
Equipment Data (https://myelectrical.com/notes?tag=equipment+data)
Equipment Ratings (https://myelectrical.com/notes?tag=equipment+ratings)
Equipment Sizing (https://myelectrical.com/notes?tag=equipment+sizing)
Fault Calculation (https://myelectrical.com/notes?tag=fault+calculation)
Fundamentals (https://myelectrical.com/notes/tag/fundamentals) Generation (https://myelectrical.com/notes/tag/generation)
High Voltage (https://myelectrical.com/notes?tag=high+voltage) History (https://myelectrical.com/notes/tag/history)
IEC Standards (https://myelectrical.com/notes?tag=iec+standards) Innovation (https://myelectrical.com/notes/tag/innovation)
Lighting (https://myelectrical.com/notes/tag/lighting) Materials (https://myelectrical.com/notes/tag/materials)
Medium Voltage (https://myelectrical.com/notes?tag=medium+voltage) Motor Control (https://myelectrical.com/notes?tag=motor+control)
Motors (https://myelectrical.com/notes/tag/motors)
myElectrical (https://myelectrical.com/notes/tag/myelectrical)
Off-Topic (https://myelectrical.com/notes/tag/off-topic) Power Quality (https://myelectrical.com/notes?tag=power+quality)
Power Systems (https://myelectrical.com/notes?tag=power+systems)
Protection (https://myelectrical.com/notes/tag/protection) Protective Devices (https://myelectrical.com/notes?tag=protective+devices)
Relays (https://myelectrical.com/notes/tag/relays) Safety (https://myelectrical.com/notes/tag/safety)
Scientists (https://myelectrical.com/notes/tag/scientists) Software (https://myelectrical.com/notes/tag/software)
Standards (https://myelectrical.com/notes/tag/standards) Switchboards (https://myelectrical.com/notes/tag/switchboards)
Testing (https://myelectrical.com/notes/tag/testing)
Theory (https://myelectrical.com/notes/tag/theory)
Transformers (https://myelectrical.com/notes/tag/transformers) Voltage (https://myelectrical.com/notes/tag/voltage)
Wire Sizes (https://myelectrical.com/notes?tag=wire+sizes) Writing (https://myelectrical.com/notes/tag/writing)
COPYRIGHT (C) 2020 MYELECTRICAL HOME (/) CONTACT (/HOME/CONTACT-US) TERMS OF USE (HTTPS://MYELECTRICAL.COM/TERMS)
PRIVACY STATEMENT (HTTPS://MYELECTRICAL.COM/PRIVACY)
REGISTER (HTTPS://MYELECTRICAL.COM/REGISTER?
RETURNURL=HTTPS%3A%2F%2FMYELECTRICAL.COM%2FNOTES)
LOGIN (HTTPS://MYELECTRICAL.COM/LOGIN?RETURNURL=%2FNOTES%2FENTRYID%2F99%2FHOW-TO-
SIZE-CURRENT-TRANSFORMERS)