Operating Instructions Control Panels: CP620-x, CP620-WEB-x CP630-x, CP630-WEB-x CP635-x, CP635-WEB-x
Operating Instructions Control Panels: CP620-x, CP620-WEB-x CP630-x, CP630-WEB-x CP635-x, CP635-WEB-x
Operating Instructions Control Panels: CP620-x, CP620-WEB-x CP630-x, CP630-WEB-x CP635-x, CP635-WEB-x
Control Panels
CP620-x, CP620-WEB-x
CP630-x, CP630-WEB-x
CP635-x, CP635-WEB-x
Content
Introduction ........................................................................................................................ 2
Safety Notices........................................................................................................................... 3
Markups .................................................................................................................................... 3
Product Identification............................................................................................................... 5
Dimensions ............................................................................................................................. 10
Connections ..................................................................................................................... 14
Battery .............................................................................................................................. 17
Safety Notices
Indicates an imminent risk. It will lead to death or serious injury if not avoided.
DANGER!
Indicates a possible risk. It may lead to death or serious injury if not avoided.
WARNING!
Indicates a possible risk. It may lead to light or slight injury or material damage if not
avoided.
CAUTION!
Markups
Enumeration.
Precondition for an operation instruction or a description.
Operation instruction with one step.
1. Operation instruction with several steps.
Result of an operation.
NOTE
TIP
Product Identification
The Control Panel products are identified by a product label. The label reports several information, includ-
ing the model name, the part number, the power supply, the date of production (in the following format:
ywwy) and two barcodes. The first code is the version code, the second one the serial number (S.N.).
WEB 1.5.15.117 Version number of the MicroBrowser (only valid for CP6xx-WEB)
Fuse Automatic
Environmental Conditions
Parameter Value According to
*) The front face of the Control Panel unit, installed in a solid panel, has been tested using conditions
equivalent to the standards shown in the table above. Even though the Control Panel unit’s level of resis-
tance is equivalent to these standards, oils that should have no effect on the Control Panel can possibly
harm the unit. This can occur in areas where either vaporized oils are present, or where low viscosity cut-
ting oil are allowed to adhere to the unit for long periods of time. If the Control Panel’s front face protec-
tion sheet becomes peeled off, these conditions can lead to the ingress of oil into the Control Panel and
separate protection measures are suggested.
Also, if non-approved oils are present, it may cause deformation or corrosion of the front face. Therefore,
prior to installing the Control Panel be sure to confirm the type of conditions that will be present in the
Control Panel’s operating environment.
If the installation gasket is used for a long period of time, or if the unit and its gasket are removed from the
panel, the original level of the protection cannot be guaranteed. To maintain the original protection level,
be sure to replace the installation gasket regularly.
Backlight service life (CCFL type) MTBF value: 50,000 hrs or more
(time of continuos operation until the brightness of the backlight
reaches 50 % of the rated value when the sorrounding temperature is
1
25 °C), see
UV Resistance Indoor applications: After 300 hrs cycled humidity in QUV accelerated
weathering, some yellowing and brittleness may be present.
2
Touch panel 1,000,000 or more of activations, see
(resistive film, analog)
1
Extended use in environments where the surrounding air temperature is 40 °C or higher may degrade
backlight quality/reliability/durability.
2
Solvent resistance:
Contact for ½ hour at 21 °C, no visible effect: Acetone, Butyl Cellosolve, Cyclohexanone, Ethyl Acetate,
Hexane, Isopropyl Alcohol, MEK, Methylene Chloride, Toluene, Xylene
Contact for 24 hours at 49 °C, no visible effect: Clorox, Coffee, Downy, Fantastik, Formula 409, Ketchup,
Lemon Juice, Mr. Clean, Mustard (slight yellow stain), Spray ‘N Wash, Tea, Tomato Juice, Top Job, Wisk
Display/Backlight TFT Color / LED TFT Color / LED TFT Color / LED
Colors 64 K 64 K 64 K
Recipe memory Yes. Flash memory Yes. Flash memory Yes. Flash memory
storage limited only by storage limited only by storage limited only by
available memory available memory available memory
Ethernet port 2 x 10/100 Mbit/s with 2 x 10/100 Mbit/s with 2 x 10/100 Mbit/s with
integrated switch integrated switch integrated switch
Weight 1 kg 1 kg 1 kg
Model A B C H L
CP630(-WEB)-x 176 6.90” 136 5.35” 45 1.77” 147 5.79” 187 7.36”
CP635(-WEB)-x 176 6.90” 136 5.35” 47 1.85” 147 5.79” 187 7.36”
Model CSD: Minimum compass safe dis- CSD2: Minimum compass safe distance
tance of standard compass of steering compass, standby steering
compass and emergency compass
mm inches mm inches
Screw each fixing screw until the bezel corner gets in contact with the panel.
CAUTION!
It is always necessary to use the correct cable type to connect on the PLC.
If the proper cable is not used, communication with the PLC will not be possible.
NOTE
The serial port is software programmable. Make sure you select the appropriate interface in the pro-
gramming software.
Serial port.
1 GND 1 GND
2 2
3 TX 3 CHA-
4 RX 4 CHB-
5 5
6 +5 V output 6 +5 V output
7 CTS 7 CHB+
8 RTS 8 CHA+
9 9
The communication cable must be chosen for the type of device being connected.
Ethernet Port
The Ethernet port has two status indicators.
Ethernet Port
DC Power Connector, Female - R/C Terminal Blocks (XCFR2), manufactured by Weidmüller Inc.,
Cat. No. BLZ 5.08, torque 4.5 lb-in
Ensure that the power supply has enough power capacity for the operation of the equipment.
NOTE
The unit must always be grounded to earth. Grounding helps limit the effects of noise due to electromag-
netic interference on the control system.
1. Do the earth connection using either the screw or the faston terminal located near the power supply
terminal block. A label helps identify the ground connection.
2. Connect to ground the terminal 3 on the power supply terminal block.
3. The power supply circuit may be floating or grounded. In the latter case, connect to ground the power
source common as shown in the figure below with a dashed line.
When using the floating power scheme, note that the panes internally connects the power common to
ground with a 1 MΩ resistor in parallel with a 4,7 nF capacitor.
The power supply must have double or reinforced insulation.
All the electronic devices in the control system must be properly grounded. Grounding must be performed
according to applicable regulations.
When the battery is charged, it assures a period of 3 month of data back-up at 25 °C.
On the right side, on the “Info” pane, the information about the selected option is shown.
For example the version of the Main OS component.
The system settings tool has two operating modes: User Mode and System Mode. The difference be-
tween them is the number of available options.
System settings in User Mode is activated from the contextual menu, accessible by clicking and holding
any unused area on the touchscreen for a few seconds. Default holding time is 2 sec. This is a runtime
parameter that could have been changed.
System settings in System Mode can be activated with the so-called emergency system access proce-
dure. This procedure consist in tapping in the middle of the touchscreen with a finger at a high frequency
while the systemis powering up. The emergency procedure can only be accessed at powerup.
User Mode
User Mode is the simplest possible interface where a generic user can get access to the basic settings of
the panel:
Calibrate Touch: allows to calibrate the touchscreen interface
Network: allows to change the options of the panel on-board network card
Time: allows to change the panel RTC options, including time zone and DST
Display settings: automatic backlight turnoff and brightness adjustment
BSP settings: allows to check the BSP (Board Support Package) version (example 2.37), check the
operating hours timers for the unit and separately for the backlight, enable/disable the buzzer, ena-
ble/disable the use of the “low battery” front LED indicator
On Hardware fault
On Normal operation
ABB Automation Products GmbH
Wallstadter Str. 59
68526 Ladenburg, Germany
Telephone +49 (0 ) 6221 701-1444
Telefax +49 (0 ) 6221 701-1382
E-Mail [email protected]
Internet http://www.abb.com/PLC