Module 4 - Basic of Design & Approaches
Module 4 - Basic of Design & Approaches
DESIGN APPROACHES
WATER SUPPLY
Gridded Sprinkler System- a type of sprinkler system in which
parallel cross mains are connected by multiple branch lines. An
operating sprinkler will receive water from both ends of its branch line
while other branch lines help transfer water between cross mains
WATER SUPPLY
Tree Sprinkler System – a type of sprinkler system in which multiple
branch lines are directly connected to the cross main. An operating
sprinkler will receive water only from its branch lines. Branch lines are
not tied together. Most widely used design.
WATER SUPPLY
The 2012 Philippine Mechanical Engineering Code requires that
Automatic Fire Sprinkler Systems shall be designed and
installed in accordance with NFPA-13, Standard for the
Installation of Automatic Sprinkler System
Ordinary
Low Moderate Moderate None
Group 1
Extra Hazard
Very High Very High Very High Little amount
Group 1
This is the most common design approach used in Automatic Fire Sprinkler
System. There are two ways to design a sprinkler system:
This design approach shall be applied for the protection of the following:
a. Plastic commodities
b. Commodities that are stored in Wooden or Plastic Pallets, Solid Piled,
Bin Boxes, Shelf and Multiple Racks storage
c. Plastic, Rubber Tires and Rolled Paper and related hazard commodities
(Class 1 to Class 4 commodities)
NFPA 13 Chap. 13 defines that Special Occupancy Design Approach shall only be
apply to meet the requirements of arrangements and commodities that includes:
a. Flammable and Combustible Liquids
b. Aerosol Products
c. Solvent Extraction Plants
d. Nitrate Film
e. Storage or vaults containing Pyroxylin Plastics
f. Laboratories Using Chemicals
g. Oxygen-Fuel Gas Systems for Welding, Cutting and Allied Processes
h. Acetylene Cylinder Charging Plants
i. Production, Storage and Handling of Liquefied Natural Gas
j. Electronic Computer Systems and Data Centers
k. Ventilation Control and Fire Protection of Commercial Cooking Operations
l. Piers, Terminals and Wharves
m. Aircraft Hangars
n. Storage of Organic Peroxides
The use of Wet Type Automatic Sprinklers has to be carefully studied since the
use of water in some of the above occupancies is not advisable.
The fire protection design for this should meet the requirement of separate NFPA
standards.
The use of Pipe Schedule is also a recognized method in
installing Automatic Fire Sprinkler System under the
Occupancy Hazard Fire Control Approach (NFPA 13, Chap. 11)
Pipe Schedule Method shall not be used, except in existing systems or extensions to
existing systems.
Pipe Schedule Method shall be permitted only for new installations of 5,000 ft 2 (465 m 2 )
or less or for additions or modifications to the existing pipe systems that is sized according
to Pipe Schedule.
Pipe Schedule Method shall be permitted for use in systems exceeding 5,000 ft 2 (465m 2)
where the flows required as specified in the table below are available at a minimum
residual pressure of 50 psi (3.4 bar) at the highest elevation of sprinkler.
The residual pressure requirement shall be met at the elevation of the highest sprinkler.
The lower flow value shall be permitted only where the building is of non-
combustible construction or the potential areas of fire are limited by building size
or compartmentation such that no open areas exceeded 3000 ft 2 (279 m2) for
light hazard or 4000 ft2 (372 m2) for ordinary hazard.
The use of Pipe Schedule method is limited only for Light and Ordinary Hazard
occupancies.
Pressures and flow requirements for extra hazard occupancies shall be based on
the hydraulic calculation methods.
Sprinkler systems having sprinklers with K-factors other than 5.6 nominal, extra
hazard Groups 1 and 2 systems, and exposure protection systems shall be
hydraulically calculated.
In using the pipe schedule design method, the number of
sprinkler heads on a given pipe size on one floor shall not
exceed the number specified for each classification of
occupancies.
On Branchlines
Sprinkler heads for each branch line shall not exceed eight (8) on either
side of a cross main.
STEEL COPPER
SIZE NO. OF SPRINKLER SIZE NO. OF SPRINKLER
HEADS HEADS
1 in. 2 heads 1 in. 2 heads
1-1/4 in. 3 heads 1-1/4 in. 3 heads
1-1/2 in. 5 heads 1-1/2 in. 5 heads
2 in. 10 heads 2 in. 12 heads
2-1/2 in. 30 heads 2-1/2 in. 40 heads
3 in. 60 heads 3 in. 65 heads
3-1/2 in. 100 heads 3-1/2 in. 115 heads
4 in. See Section 8.2 4 in. See Section 8.2
STEEL COPPER
The water supply requirement for sprinklers shall be calculated from the
density/area curve as shown below:
The minimum water supply requirement for a hydraulically
designed occupancy hazard fire control sprinkler system shall
be determined by adding the hose stream demand to the water
requirement as determined using the Density/Area Curve
Total Combined
Occupancy Inside Hose Inside and Outside Duration
(gpm) Hose (gpm) (minutes)
• Add the hose demand for the highest hazard classification within
the system, or
• Where the higher classification only lies within single room less
than or equal to 400 ft2 (37.18 m2 ) in area with no such rooms
adjacent, add the hose demand for the principal occupancy for the
remainder of the system.
NFPA 13, Chapter 8, Section 8.2 states that the maximum floor area
on any one floor to be protected by sprinklers supplied by any one
sprinkler system riser or combined system riser shall be as follows:
3. Extra hazard
a) Pipe schedule – 25,000 square feet (2,323 square meter)
b) Hydraulically calculated – 40,000 square feet (3,716 square
meter)