DATA SHEET

AC 800M Controller
Outline of all modules

AC 800M is a family of rail-mounted modules, consisting of CPU:s, communication


modules, power supply modules and various accessories. There are several CPU modules
to choose from, ranging from medium processor power and low cost to high processor
power and support for full redundancy.

The AC 800M family does also include IEC 61508-SIL3 certified


controllers PM857, PM863, PM865 and PM867, which sup-
ports controller configurations for:

• Safety application
• Combined Process Automation and Safety application

For updated information regarding System 800xA hardware


please visit our 800xA Hardware Selector. In the selector you
can compare different communication modules, S800 IO
modules, module termination units, controllers, power supplies
and voters, panels and also print your own pdf files.

www.800xahardwareselector.com

Features / CPUs PM851A PM856A PM858 PM860A PM861A PM862


Processor Unit PM851AK01 PM856AK01 PM858K01 incl: PM860AK01 incl: PM861AK01 incl: PM862K01 incl:
incl: incl: 1 PM858 CPU and 1 PM860A CPU 1 PM861A CPU and 1 PM862 CPU and required
1 PM851A CPU 1 PM856A CPU required optional items and required required optional items optional items.
and required and required PM858K02 incl: optional items PM861AK02 incl: PM862K02 incl:
optional items optional items 2 PM858K01 2 PM861AK01 2 PM862K01

Optional items TP830 Baseplate, TP850 CEX-bus term., TK850 CEX-bus cable, TB807, Modulebus term, Battery RAM backup, TB852/TB853 RCU-
(partly included in link term, TB851/TB855/TB856 RCU-link cable, SB822 External Battery Unit, TK212A Tool cable, TC562 Short Distance Modem,
Processor Units, see TK853V020 Modem cable, BC810K02, BC820K02, CEX-bus Interconnection unit; TK851V010 Connection cable, SD831/SD832/
Price List) SD833/SD853/SD854 Power Supply, SS832 Voting Unit, Mains Breaker Kit, SM811 Supervisory Module and SM812 Supervisory
Module.
High Integrity No No No No No No
Controller
Clock frequency 24 MHz 24 MHz 33 MHz 48 MHz 48 MHz 67 MHz
Memory (RAM) 8 MB 8 MB 16MB 8 MB 16 MB 32 MB
From 5.1 FP4 12 MB 16 MB 16 MB
RAM available for 2.282 MB 2.282 MB 7.147 MB 2.282 MB 7.155 MB 23.521 MB
application
From 5.1 FP4 6.253 MB 10.337 MB 10.346 MB
Processor type MPC860 MPC860 MPC866 MPC860 MPC860 MPC866
Flash memory Yes Yes Yes Yes Yes Yes
for storage of
application and
data
2 DATA SH E E T AC 800M CON T ROLL ER

Features / CPUs PM851A PM856A PM858 PM860A PM861A PM862


CPU redundancy support No No Yes No Yes Yes
Switch over time in red. conf. - - Max 10 ms - Max 10 ms Max 10 ms
No. controllers per control 32
projects
No. of applications per 1024
control project
No. of applications per 32
controller
No. of programs per 64
application
No. of tasks per controller 32
Number of different cycle 32
times
Cycle time per application Down to 1 ms (HI Integrity controllers 10 ms)
programs
Flash PROM for firmware 2 MB 2 MB 4 MB 2 MB 2 MB 4 MB
storage
Power supply 24 V DC (19.2-30 V DC) max 5 % ripple acc. to IEC 61131-2
Power consumption +24 V typ/max 180/300 typ/max 180/300 typ/max 210/360 typ/max 180/300 typ/max 250/430 typ/max 210/360
mA mA mA mA mA mA
Power dissipation typ. 4.32 W 4.32 W 5.1 W 4.32 W 6.0 W 5.1 W
Power Reservoir Internal 5 ms power reservoir, sufficient for the CPU to make a controlled power down
Power supply connector Detachable 4-pole screw terminal block
Redundant power supply Yes: 2 inputs designated SA, SB (Max 30 V, high level >15 V, low level < 8 V)
status inputs
Built-in back-up battery Type: Lithium, 3.6 V, 0.95 Ah, size 1/2 AA, 0.3 g Lithium content
Real-time clock stability 100 ppm (approx. 1 h/year)
Clock synchronization 1 ms between AC 800M controllers by CNCP protocol
Comm. modules on CEX bus 1 12 12 12 12 12
Supply current on CEX bus Supply current: Max 24 V - 2.4 A (fuse 3.15 A fast, PM891 has an embedded auto fuse)
I/O clusters on Modulebus 1 el. + 1 opt. 1 el. + 7 opt. 1 el. + 7 opt. 1 el. + 7 opt. 1 el. + 7 opt. 1 el. + 7 opt.
with non-redundant CPU
I/O clusters on Modulebus NA NA 7 optical NA 0 el. + 7 opt. 7 optical
with redundant CPU
I/O capacity on Modulebus Max 24/NA I/O Max 96/NA I/O Max 96/84 I/O Max 96/NA I/O Max 96/84 I/O Max 96/84 I/O
with non-redundant/ modules modules modules modules modules modules
redundant CPU

Modulebus scan rate 0 - 100 ms (actual time depending on number of I/O modules)
Supply current on Electrical Supply current: Max 24 V - 1.0 A (short circuit proof, fuse 2.0 A), Max 5 V - 1.5 A (short circuit proof)
Modulebus
I/O capacity on PROFIBUS Max 99 I/O stations (max 62 redundant I/O stations), max 24 I/O modules per I/O station (max 12 redundant I/O pairs)
(remote I/O)
Ethernet channels 1 2 2 2 2 2
Ethernet interface Ethernet (IEEE 802.3), 10 Mbit/s, RJ-45, female (8-pole)
Control Network protocol MMS (Manufacturing Message Service) and IAC (Inter Application Communication)
Recommended Control 100 Mbit/s switched Ethernet
Network backbone
No. of controllers on Control Max 50
Network
RS-232C interface 2 (one general, 1 for service tool)
RS-232C interface (COM3) RS-232C, 75-19 200 baud, RJ-45 female (8-pole), not opto isolated, full RTS-CTS support
(non red.conf. only)
RS-232C interface (COM4) RS-232C, 9 600 baud, RJ-45 female (8-pole), opto isolated, no RTS-CTS support
(non red.conf. only)
Temperature
• Operating +5 to +55 °C (+41 to +131 °F)
• Storage -40 to +70 °C (-40 to +158 °F)
Temperature changes 3 °C/minutes according to IEC/EN 61131-2
Altitude 2000 m according to IEC/EN 61131-2
Pollution degree Degree 2 according to IEC/EN 61131-2
Corrosion protection G3 compliant to ISA 71.04
Vibration 10 < f < 50 Hz: 0.0375 mm amplitude, 50 < f < 150 Hz: 0.5 g acceleration, 5 < f < 500 Hz: 0.2 g acceleration
Emitted noise < 55 dB (A)
Shock, no package 150 m/s2 in 11 ms, 20 g in 3 ms
A C 8 0 0 M C O N T R O L L E R D ATA S H E E T 3

Features / CPUs PM851A PM856A PM858 PM860A PM861A PM862


Relative humidity 5 to 95 %, non-condensing
Isolation voltage Type test voltage: 500 V AC (corresponding to 700 V DC)
Environmental Industrial
conditions
Protection class IP20 according to EN 60529, IEC 529
Certificates and CE- marking: Meets EMC directive 2004/108/EC acc. to EN 61000-6-4, EN 61000-6-2 and Low Voltage Directive acc. to EN 61131-2
Standards(1) Electrical Safety: EN 50178, IEC 61131-2, UL 508
Hazardous location: UL 60079-15, cULus Class 1, Zone 2, AEx nA IIC T4, ExnA IIC T4Gc X
RoHS compliance: EN 50581:2012
WEEE compliance: DIRECTIVE/2012/19/EU

TÜV Approval No No No No No No
Emission Tested according to EN 61000-6-4 EMC – Generic Emission Standard, Part 2 – Industrial Environment
Immunity Tested according to EN 61000-6-2 EMC – Generic Immunity Standard, Part 2 – Industrial Environment
Dimensions Width 119 x Height 186 x Depth 135 mm (4.7 x 7.3 x 5.3 in.)
Weight 1100 g (2.4 lbs) 1100 g (2.4 lbs) 1200 g (2.6 lbs) 1100 g (2.4 lbs) 1200 g (2.6 lbs) 1200 g (2.6 lbs)
(including base)
(1) For detailed information on each module, please visit: www.800xAhardwareselector.com

Features / CPUs PM864A PM866A PM867 PM891


Processor Unit PM864AK01 incl: PM866AK01 incl: PM867K01 incl: PM891K01 incl:
1 PM864A CPU and required 1 PM866A CPU and required 1 PM867 CPU and required 1 PM891 CPU and required
optional items optional items optional items optional items
PM864AK02 incl: PM866AK02 incl: PM867K02 incl: PM891K02 incl:
2 PM864AK01 2 PM866AK01 2 PM867K01 2 PM891K01

Optional items TP830 Baseplate, TP850 CEX-bus term., TK850 CEX-bus cable, TB807, Modulebus term, Battery RAM backup, TB852/
(partly included in Processor TB853 RCU-link term, TB851/TB855/TB856 RCU-link cable, SB822 External Battery Unit, TK212A Tool cable, TC562 Short
Units, see Price List) Distance Modem, TK853V020 Modem cable, BC810K02, BC820K02, CEX-bus Interconnection unit; TK851V010 Connection
cable, SD831/SD832/SD833/SD853/SD854 Power Supply, SS832 Voting Unit, Mains Breaker Kit, SM811 Supervisory
Module and SM812 Supervisory Module.

High Integrity Controller No No Yes No


Clock frequency 96 MHz 133 MHz 133 MHz 450 MHz
Memory (RAM) From 5.1 FP4 32 MB 64 MB 64 MB 256 MB
RAM available for application 23.522 MB 51.389 MB 46.559 MB 208.985 MB
Processor type MPC862 MPC866 MPC866 MPC8270
Flash memory for storage Yes Yes No Yes
of application and data
CPU redundancy support Yes Yes Yes Yes
Switch over time in red. conf. max 10 ms max 10 ms max 10 ms max 10 ms
Performance, 1000 boolean 0.15 ms 0.09 ms 0.09 ms 0.043 ms
operations (a:=b and c)
No. controllers per control 32
projects
No. of applications per control 1024
project
No. of applications per 32
controller
No. of programs per 64
application
No. of tasks per controller 32
Number of different cycle 32
times
Cycle time per application Down to 1 ms (HI Integrity controllers 10 ms)
programs
Flash PROM for firmware 2 MB 4 MB 18 MB 16 MB
storage
Power supply 24 V DC (19.2-30 V DC) max 5 % ripple acc. to IEC 61131-2
Power consumption +24 V typ/max 287/487 mA typ/max 210/360 mA typ/max 210/360 mA typ/max 660/750 mA
Power dissipation typ. 6.9 W 5.1 W 5.1 W 15.8 W
Power Reservoir Internal 5 ms power reservoir, sufficient for the CPU to make a controlled power down
Power supply connector Detachable 4-pole screw terminal block
4 DATA SH E E T AC 800M CON T ROLL ER

Features / CPUs PM864A PM866A PM867 PM891


Redundant power supply Yes: 2 inputs designated SA, SB (Max 30 V, high level >15 V, low level < 8 V)
status inputs
Built-in back-up battery Type: Lithium, 3.6 V, 0.95 Ah, size 1/2 AA, 0.3 g Lithium content No
Real-time clock stability 100 ppm (approx. 1 h/year) 50 ppm
Clock synchronization 1 ms between AC 800M controllers by CNCP protocol
Comm. modules on CEX bus 12 12 12 12
Supply current on CEX bus Supply current: Max 24 V - 2.4 A (fuse 3.15 A fast, PM891 has an embedded auto fuse)
I/O clusters on Modulebus 1 el. + 7 opt. 1 el. + 7 opt. 1 el. + 7 opt. 0 el. + 7 opt.
with non-redundant CPU
I/O clusters on Modulebus 0 el. + 7 opt. 0 el. + 7 opt. 0 el. + 7 opt. 0 el. + 7 opt.
with redundant CPU
I/O capacity on Modulebus Max 96/84 I/O modules Max 96/84 I/O modules Max 96/84 I/O modules Max 84/84 I/O modules
with non-redundant/
redundant CPU
Modulebus scan rate 0 - 100 ms (actual time depending on number of I/O modules), 0 - 300 for PM865 and PM867
Supply current on Electrical Supply current: Max 24 V - 1.0 A (short circuit proof, fuse 24 V : max 1.0 A Not supported
Modulebus 2.0 A), Max 5 V - 1.5 A (short circuit proof) 5 V : max 1.5 A
I/O capacity on PROFIBUS Max 99 I/O stations (max 62 redundant I/O stations), max 24 I/O modules per I/O station (max 12 redundant I/O pairs)
(remote I/O)
Ethernet channels 2 2 2 2
Ethernet interface Ethernet (IEEE 802.3), 10 Mbit/s, RJ-45, female (8-pole) 10/100 Mbit/s
Control Network protocol MMS (Manufacturing Message Service) and IAC (Inter Application Communication)
Recommended Control 100 Mbit/s switched Ethernet
Network backbone
No of controllers on Control Max 50
Network
RS-232C interface 2 (one general, 1 for service tool) 1 for service tool (COM 4)
RS-232C interface (COM3) RS-232C, 75-19 200 baud, RJ-45 female (8-pole), not opto isolated, full RTS-CTS support Not supported
(non red.conf. only)
RS-232C interface (COM4) RS-232C, 9 600 baud, RJ-45 female (8-pole), opto isolated, no RTS-CTS support
(non red.conf. only)
Temperature
• Operating +5 to +55 °C (+41 to +131 °F)
• Storage -40 to +70 °C (-40 to +158 °F)
Temperature changes 3 °C/minutes according to IEC/EN 61131-2
Altitude 2000 m according to IEC/EN 61131-2
Pollution degree Degree 2 according to IEC/EN 61131-2
Corrosion protection G3 compliant to ISA 71.04
Vibration 10 < f < 50 Hz: 0.0375 mm amplitude, 50 < f < 150 Hz: 0.5 g acceleration, 5 < f < 500 Hz: 0.2 g acceleration
Emitted noise < 55 dB (A)
Shock, no package 150 m/s2 in 11 ms, 20 g in 3 ms
Relative humidity 5 to 95 %, non-condensing
Isolation voltage Type test voltage: 500 V AC (corresponding to 700 V DC)
Environmental conditions Industrial
Protection class IP20 according to EN 60529, IEC 529
Certificates and Standards (1) CE- marking: Meets EMC directive 2004/108/EC acc. to EN 61000-6-4, EN 61000-6-2 and Low Voltage Directive acc. to
EN 61131-2
Electrical Safety: EN 50178, IEC 61131-2, UL 508
Hazardous location: UL 60079-15, cULus Class 1, Zone 2, AEx nA IIC T4, ExnA IIC T4Gc X
RoHS compliance: EN 50581:2012
WEEE compliance: DIRECTIVE/2012/19/EU

TÜV Approval No No IEC 61508 SIL3 No


Emission Tested according to EN 61000-6-4 EMC – Generic Emission Standard, Part 2 – Industrial Environment
Immunity Tested according to EN 61000-6-2 EMC – Generic Immunity Standard, Part 2 – Industrial Environment
Dimensions Width 119 x Height 186 x Depth 135 mm (4.7 x 7.3 x 5.3 in.) Width 174 x Height 186 x
Depth 94 mm
Weight (including base) 1100 g (2.4 lbs) 1200 g (2.6 lbs) 1200 g (2.6 lbs) 1600 g (3.5 lbs)
(1) For detailed information on each module, please visit: www.800xAhardwareselector.com
A C 8 0 0 M C O N T R O L L E R D ATA S H E E T 5

Supported PROFIBUS FOUNDATION RS-232 C MB300 INSUM Drivebus S100 I/O Genius Satt I/O MODBUS IEC
Communication DP FIELDBUS TRIO TCP 61850
modules I/O

Module CI854B CI860 CI853 CI855 CI857 CI858 CI856 CI862 CI865 CI867 CI868
Protocol DP-V1 FF HSE MODBUS RTU MasterBus IEEE ABB’s ABB’s Genius ABB’s MODBUS IEC
(PA via (H1 via master, COMLI 300 802.3 DriveBus S100 I/O Satt I/O TCP 61850
Linking Linking master/ slave,
Device) Device) Siemens 3964R
master, User
defined protocols

Master or slave Master Master Master/slave Master/slave Master Master Master Master Master Master/ Master
slave
Number of 2 1 2 2 1 1 main, 1 1 1 2 1
channels 2 aux
Max units on 12 12 12 12 6 2 12 12 4 12 4
CEX bus
Transmission 9.6 - 10/100 75 - 19 200 b/s 10 Mbit/s, 200 10 Mbit/s 4 Mbit/s - 38.4 - - 10/100 10/100
speed 12,000 Mbit/s Datasets/s 153.6 Mbit/s Mbit/s
kbit/s kbit/s (Ch1),
10 Mbit/s
(Ch2)
Cable Yes No No Yes No No No No No No No
redundancy
Module Yes Yes No No No No No No No Yes No
redundancy
Hot Swap Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
Used together Yes No Yes Yes Yes No No No No Yes Yes
with High
Integrity
Controller
Connectors DB female RJ-45 female RJ-45 female RJ-45 female RJ-45 Fiberoptic Miniribbon Phoenix BNC RJ-45 RJ-45
(9-pin ) (8-pin) (8-pin) (8-pin) female (36-pin) (4-pin) female (8- female
(8-pin) pin) (8-pin)

24 V current typ typ typ typ typ typ typ typ typ typ typ
consumption 190 mA 100 mA 100 mA 150 mA 150 mA 200 mA 200 mA 190 mA 120 mA 160 mA 160 mA
Protection class IP20 according to EN60529, IEC 529
Certification (1)
• CE-marked Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
• UL 508 Yes Yes Yes Yes Yes Yes Yes No Yes Yes Yes
• UL 60079-15 Yes Yes Yes Yes Yes Yes Yes No Yes Yes Yes
(Class 1 Zone 2)
• RoHS EN 50581:2012
compliance
• WEEE DIRECTIVE/2012/19/EU
compliance
Dimensions Width 58 x Height 186 x Depth 135 mm (2.3 x 7.3 x 5.3 in.)
Weight 700 g 455 g 520 g 700 g 600 g 700 g 600 g 600 g 600 g 700 g 700 g
(including base) (1.5 lbs) (0.9 lbs) (1.2 lbs) (1.5 lbs) (1.3 lbs) (1.5 lbs) (1.3 lbs) (1.3 lbs) (1.3 lbs) (1.5 lbs) (1.5 lbs)
(1) For detailed information on each module, please visit: www.800xAhardwareselector.com
Supported Communication modules AF100 PROFINET IO EtherNet/IP DeviceNet
Module CI869 CI871 CI873
Protocol Advant Fieldbus 100 PROFINET IO EtherNet/IP DeviceNet (via LD800DN)
Master or slave Slave Master Master
Number of channels 2 1 1
Max units on CEX bus 4 12 4
Transmission speed Up to 500 Kbit/s 10/100 Mbit/s 10/100 Mbit/s
Cable redundancy Yes No No
Module redundancy Yes No No
Hot Swap Yes Yes Yes
Used together with High Integrity Yes Yes Yes
Controller
Connectors Phoenix (4-pin) RJ-45 female (8-pin) RJ-45 female (8-pin)
24 V current consumption typ 160 mA typ 160 mA typ 160 mA
Protection class IP20 according to EN60529, IEC 529
UL 508 Yes Yes Yes
UL 60079-15 (Class 1 Zone 2) Yes Yes Yes
Dimensions Width 58 x Height 186 x Depth 135 mm (2.3 x 7.3 x 5.3 in.)
Weight (including base) 700 g (1.5 lbs) 700 g (1.5 lbs) 700 g (1.5 lbs)

— —
800xA is a registered or pending trademark We reserve all rights to this document
abb.com/800xA of ABB. All rights to other trademarks reside and the items and images it contains.
abb.com/controlsystems with their respective owners. The reproduction, disclosure to third parties
or the use of the content of this document
We reserve the right to make technical – including parts thereof – are prohibited
changes to the products or modify the without ABB’s prior written permission.
3BSE063691 en L

contents of this document without prior


notice. With regard to purchase orders, Copyright© 2018 ABB
the agreed particulars shall prevail. All rights reserved
ABB does not assume any responsibility
for any errors or incomplete information
in this document.

You might also like