INSTALLATION MANUAL

FRANÇAIS
AIR
CONDITIONER

DEUTSCH
ΕΛΛΗΝΙΚΆ
ČEŠTINA

Please read this installation manual completely before installing the product.
NEDERLANDS

Installation work must be performed in accordance with the national wiring


standards by authorized personnel only.
Please retain this installation manual for future reference after reading it thoroughly.
Ɠ This product contains Fluorinated Greenhouse Gases. (R410A)
MULTI
POLSKI

Original instruction
[Representative] LG Electronics Inc. EU Representative : LG Electronics European Shared Service Center B.V.
Krijgsman 1, 1186 DM Amstelveen, The Netherlands
[Manufacturer] LG Electronics Inc. Changwon 2nd factory 84, Wanam-ro, Seongsan-gu, Changwon-si,
Gyeongsangnam-do, KOREA
LIMBA ROMÂNĂ

For more information, Refer to the CD or LG Web site (www.lg.com).

www.lg.com
P/NO : MFL68883802
2 IMPORTANT SAFETY INSTRUCTIONS
ENGLISH

IMPORTANT SAFETY INSTRUCTIONS


READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
Always comply with the following precautions to avoid dangerous situations
and ensure peak performance of your product

! WARNING
It can result in serious injury or death when the directions are ignored

! CAUTION
It can result in minor injury or product damage when the directions are
ignored

! WARNING
• Installation or repairs made by unqualified persons can result in hazards to
you and others.
• Installation work must be performed in accordance with the National
Electric Code by qualified and authorized personnel only.
• The information contained in the manual is intended for use by a qualified
service technician familiar with safety procedures and equipped with the
proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result
in equipment malfunction, property damage, personal injury and/or death.

Installation
• Do not use a defective or underrated circuit breaker. Use the correctly
rated breaker and fuse. There is risk of fire or electric shock.
• For electrical work, contact the dealer, seller, a qualified electrician, or an
Authorized Service Center. Do not disassemble or repair the product by
yourself. There is risk of fire or electric shock.
• Always ground the product as per the wiring diagram. Do not connect the
ground wire to gas or water pipes lightening rod or telephone ground wire.
There is risk of fire or electric shock.
• Install the panel and the cover of control box securely. There is risk of fire
or electric shock due to dust , water etc.
• Use the correctly rated breaker or fuse. There is risk of fire or electric
shock.
• Do not modify or extend the power cable. If the power cable or cord has
scrathes or skin peeled off or deteriorated then it must be replaced. There
IMPORTANT SAFETY INSTRUCTIONS 3

ENGLISH
is risk of fire or electric shock.
• For installation, removal or reinstall , always contact the dealer or an
Authorized Service Center. There is risk of fire, electric shock, explosion,
or injury.
• Do not install the product on a defective installation stand. Be sure that
the installation area does not deteriorate with age. It may cause product to
fall.
• Never install the outdoor unit on a moving base or a place from where
it can fall down.
The falling outdoor unit can cause damage or injury or even death of a per-
son.
• In outdoor unit the step-up capacitor supplies high voltage electricity to the
electrical components. Be sure to discharge the capacitor completely
before conducting the repair work.
An charged capacitor can cause electrical shock.
• When installing the unit, use the installation kit provided with the product.
Otherwise the unit may fall and cause severe injury.
• Indoor/outdoor wiring connections must be secured tightly and the cable
should be routed properly so that there is no force pulling the cable from
the connection terminals. Improper or loose connections can cause heat
generation or fire.
• Safely dispose off the packing materials. Like screws, nails, batteries, bro-
ken things etc after installation or svc and then tear away and throw away
the plastic packaging bags. Children may play with them and cause injury.
• Be sure to check the refrigerant to be used. Please read the label on the
product. Incorrect refrigerant used can prevent the normal operation of the
unit.

Operation
• When the product is soaked (flooded or submerged) in water , contact an
Authorized Service Center for repair before using it again. There is risk of
fire or eletric shock.
• Be sure to use only those parts which are listed in the svc parts list.
Never attempt to modify the equipment. The use of inappropriate parts
can cause an electrical shock, excessive heat generation or fire.
• Do not touch , operate, or repair the product with wet hands. Hold the
plug by hand when taking out. There is risk of electric shock or fire.
• Do not place a heater or other heating appliances near the power cable.
There is risk of fire and electric shock.
4 IMPORTANT SAFETY INSTRUCTIONS
ENGLISH

• Do not allow water to run into electric parts. Install the unit away from
water sources. There is risk of fire, failure of the product, or electric shock.
• Do not store or use or even allow flammable gas or combustibles near the
product. There is risk of fire.
• Do not use the product in a tightly closed space for a long time. Perform
ventilation regularly. Oxygen deficiency could occur and hence harm your
health.
• Do not open the front grille of the product during operation. (Do not touch
the electrostatic filter, if the unit is so equipped.) There is risk of physical
injury, electric shock, or product failure.
• If strange sound, smell or smoke comes from product.Immediately turn
the breaker off or disconnect the power supply cable. There is risk of elec-
tric shock or fire.
• Ventilate the product room from time to time when operating it together
with a stove, or heating element etc. Oxygen deficiency can occur and
hence harm your health.
• When the product is not to be used for a long time, disconnect the power
supply plug or turn off the breaker. There is risk of product damage or fail-
ure, or unintended operation.
• Take care to ensure that nobody especially kids could step on or fall onto
the outdoor unit. This could result in personal injury and product damage.
• Take care to ensure that power cable could not be pulled out or damaged
during operation. There is risk of fire or electric shock.
• Do not place ANYTHING on the power cable. There is risk of fire or elec-
tric shock.
• When flammable gas leaks, turn off the gas and open a window for venti-
lation befor turning on the product. Do not use the telephone or turn
switches on or off. There is risk of explosion or fire.

! CAUTION
Installation
• Two or more people must lift and transport the product. Avoid personal
injury.
• Do not install the product where it will be exposed to sea wind (salt spray)
directly. It may cause corrosion on the product.
• Install the drain hose to ensure that the condensed water is drained away
properly. A bad connection may cause water leakage.
• Keep level even when installing the product. To avoid vibration or noise.
IMPORTANT SAFETY INSTRUCTIONS 5

ENGLISH
• Do not install the product where the noise or hot air from the outdoor unit
could damage or disturb the neighborhoods. It may cause a problem for
your neighbors and hence dispute.
• Always check for gas (refrigerant) leakage after installation or repair of
product. Low refrigerant levels may cause failure of product.
• Please install safely at a place that can sufficiently endure the weight of
the product.
If the strength is not sufficient, the product may fall and cause injury.

Operation
• Do not use the product for special purposes, such as preserving foods,
works of art, etc. It is a consumer air conditioner, not a precision refrigera-
tion system. There is risk of damage or loss of property.
• Do not block the inlet or outlet of air flow. It may cause product failure.
• Use a soft cloth to clean. Do not use harsh detergents, solvents or splash-
ing water etc. There is risk of fire, electric shock, or damage to the plastic
parts of the product.
• Do not touch the metal parts of the product when removing the air filter.
There is risk of personal injury.
• Do not step on or put anyting on the product. (outdoor units) There is risk
of personal injury and failure of product.
• Always insert the filter securely after cleaning. Clean the filter every two
weeks or more often if necessary. A dirty filter reduces the efficiency.
• Do not insert hands or other objects through the air inlet or outlet while
the product is operating. There are sharp and moving parts that could
cause personal injury.
• Be cautious when unpacking and installing the product. Sharp edges could
cause injury.
• If the refrigerant gas leaks during the repair, do not touch the leakaing
refrigerant gas. The refrigernat gas can cause frostbite (cold burn).
• Do not tilt the unit when removing or uninstalling it. The condensed water
inside can spill.
• Do not mix air or gas other than the specified refrigerant used in the sys-
tem. If air enters the refrigerant system, an excessively high pressure
results, causing equipment damage or injury.
• If the refrigerant gas leaks during the installation, ventilate the area imme-
diately. Otherwise it can be harmfull for your health.
• Dismantling the unit, treatment of the refrigerant oil and eventual parts
should be done in accordance with local and national standards.
6 IMPORTANT SAFETY INSTRUCTIONS
ENGLISH

• Replace the all batteries in the remote control with new ones of the same
type. Do not mix old and new batteries or different types of batteries.
There is risk of fire or product failure.
• Do not recharge or disassemble the batteries. Do not dispose off batteries
in a fire. They may burn or explode.
• If the liquid from the batteries gets onto your skin or clothes, wash it well
with clean water. Do not use the remote if the batteries have leaked. The
chemicals in batteries could cause burns or other health hazards.
• If you eat the liquid from the batteries, brush your teeth and see doctor.
Do not use the remote if the batteries have leaked. The chemicals in bat-
teries could cause burns or other health hazards.
• Do not let the air conditioner run for a long time when the humidity is very
high and a door or a window is left open. Moisture may condense and wet
or damage furniture.
• Do not expose your skin or kids or plants to the cool or hot air draft. This
could harm to your health.
• Do not drink the water drained from the product. It is not sanitary and
could cause serious health issues.
• Use a firm stool or ladder when cleaning, maintaining or repairing the
product at an height. Be careful and avoid personal injury.
TABLE OF CONTENTS 7

ENGLISH
TABLE OF CONTENTS
2 IMPORTANT SAFETY 26 AIR PURGING AND EVAC-
INSTRUCTIONS UATION
26 Checking method
8 INSTALLATION 27 Evacuation
9 INSTALLATION OF 28 PANEL FRONT ASSEM-
INDOOR, OUTDOOR BLY (ART COOL TYPE
UNIT ONLY)
9 Select the best location
10 Fixing Installation Plate 29 INSTALLATION PI485
11 Refrigerant charge
11 Piping length and elevation
30 TEST RUNNING
12 Preparing work for Installation (ART 31 FUNCTION
COOL Type Only)
31 Dip S/W Setting
13 INSTALLATION OF 32 Forced Cooling Operation
WIRED REMOTE CON- 33 Wiring Error Check
33 Saving Power Consumption
TROLLER 34 Night Quiet Mode
13 Drill a hole in the wall
35 Mode Lock
15 Wired remote controller installation
35 SLC (Smart Load Control) Mode
16 FLARING WORK AND 36 PCB Display(14/16/18/21k Model Only)

CONNECTION OF PIPING 37 MAX COMBINATION


16 Flaring work CAPACITY
17 Connection of piping - Indoor
19 Connection of piping - Outdoor 38 INSTALLATION GUIDE AT
20 CONNECTING THE CABLE THE SEASIDE
BETWEEN INDOOR UNIT 38 SEASONAL WIND AND
AND OUTDOOR UNIT CAUTIONS IN WINTER
20 Connect the cable to the Indoor unit 39 Model Designation
22 Connect the cable to the Outdoor unit 39 Airborne Noise Emission
39 Limiting concentration
24 CHECKING THE
DRAINAGE AND FORM-
ING THE PIPINGS
24 Checking the Drainage
25 Forming the Piping
8 INSTALLATION
ENGLISH

INSTALLATION
Installation Parts

Installation plate

Type "B" screws

Type "A" screw (6 EA) Type "A" screw (8 EA) Type "A" screw (7 EA) Type "A" screw and plastic anchors

Holder Remote Control

Clearance of side discharge unit [Unit : mm(inch)]


Do not install the product where sufficient ventilation is not secured.
The performance may be decreased or the product may not be operated.
1000(39-3/8) or more

s
r les
6) o
11/1
( 19-
5 00

300
or m(11-1
ore 3/16)
6)
-13
/1 /16)
(11 600 -13
(11 re
300 m ore (2
or m 3-19/3 3 0 0 or mo
or ore 2)

less
) or
1000(39-3/8) or more

1/16
(1 9-1
500
H

300(11-13/16)
or more

/16) 2000(78-3/4) or more


-13
(11 re
300 or mo
/8) 600(23-19/32) or more
9 -3
LD

0 (3
100 r more 1000(39-3/8) or more
o

h In case of series or another installation, please refer to related PDB.


INSTALLATION OF INDOOR, OUTDOOR UNIT 9

ENGLISH
INSTALLATION OF INDOOR, OUTDOOR UNIT
Read completely, then follow step by step. Outdoor unit
You need to select adequate installation location
considering the following conditions, and make 1 If an awning is built over the unit to prevent
sure to acquire the consent of the user. direct sunlight or rain exposure, make sure
that heat radiation from the condenser is not
Select the best location restricted.
2 Ensure that the spaces indicated by arrows
Indoor unit around front, back and side of the unit.
3 Do not place animals and plants in the path of
1 Do not have any heat or steam near the unit. the warm air.
2 Select a place where there are no obstacles 4 Take the air conditioner weight into account
in front of the unit. and select a place where noise and vibration
3 Make sure that condensation drainage can be are minimum.
conveniently routed away. 5 Select a place so that the warm air and noise
4 Do not install near a doorway. from the air conditioner do not disturb neigh-
5 Ensure the spaces indicated by arrows from the bors.
wall, ceiling, fence or other obstacles. 6 Place that can sufficiently endure the weight
6 Use a stud finder to locate studs to prevent and vibration of the outdoor unit and where
unnecessary damage to the wall. even installation is possible.
7 Place that has no direct influence of snow or
! CAUTION rain.
Install the indoor unit on the wall where 8 Place with no danger of snowfall or icicle
the height from the floors more than 2.3 drop.
meters. (ART COOL Type Only 1.5m) 9 Place without weak floor or base such as
decrepit part of the building or with a lot of
More than snow accumulation.
10cm More than 20cm
10 Sufficient ventilation is secured.

More than Rooftop Installations


10cm
More than 2.3m
If the outdoor unit is installed on a roof structure,
More than be sure to level the unit. Ensure the roof struc-
10cm ture and anchoring method are adequate for the
More than 20cm
unit location. Consult local codes regarding
rooftop mounting.
More than
more than 60cm
10cm
More than 2.3m
more than more than
30cm 30cm
More than
10cm More than 20cm

more than more than


70cm 60cm
More than
10cm
More than 2.3m more than 60cm
more than
30cm
More More than 20cm
more than
than 50cm 30cm

More
than 50cm more than
More than 1.5m 70cm
more than
60cm
10 INSTALLATION OF INDOOR, OUTDOOR UNIT
ENGLISH

Fixing Installation Plate Capacity


Indoor Type Type
The wall you select should be strong and solid (kBtu/h)
enough to prevent vibration
Wall mounted 7, 9, 12 1, 3
1 Mount the installation plate on the wall /ART COOL
with type "A" screws. If mounting the unit Mirror 18, 24 2, 4
on a concrete wall, use anchor bolts.
- Mount the installation plate horizontally
by aligning the centerline using a level. <Type 1>

Installation plate
<Type 1>
Installation Plate

105mm 105mm

Chassis Ø65 Ø65


Hook 65mm 55mm
Left rear piping Right rear piping

Type “A”
<Type 2>
2 Measure the wall and mark the centerline. Installation plate
It is also important to use caution concern-
ing the location of the installation plate-
routing of the wiring to power outlets is
101mm 101mm
through the walls typically. Drilling the hole
through the wall for piping connections Ø65 Ø65
must be done safely. 133mm 100mm
Left rear piping Right rear piping
<Type 2> Installation Plate

Chassis <Type 3>


Hook

Ø65
Type “A”

<Type 3> Installation plate


Installation Plate 45mm 45mm
Ø65 65mm
140mm 65mm
Left rear piping Right rear piping

<Type 4>
Type “A”
460 567

<Type 4> Unit


Outline
Installation Plate Ø65 Ø65
Place a level on raised tab

Left Rear
Piping
Installation plate Right Rear
184 156 Piping
220 (Unit : mm) 307
Type "A" Screws

Chassis
Hook
65mm
INSTALLATION OF INDOOR, OUTDOOR UNIT 11

ENGLISH
Piping length and elevation
Multiple Piping Models (Unit: m)
Max Elevation In - In Elevation
Phase Capacity(kBtu/h) Total Length Max Length(A/B)
(h1) (h2)
14/16 30 20 15 7.5
18 50 25 15 7.5
21 50 25 15 7.5

24/27 70 25 15 7.5
30 75 25 15 7.5
40 85 25 15 7.5

A ! CAUTION
Capacity is based on standard length and
maximum allowance length is on the
basis of reliability. If outdoor unit is at
h2 higher elevation than the indoor units,
after 24m of vertical height, 1 oil trap is
h1 required.

Multiple Piping Type

Refrigerant charge
The calculation of the additional charge should be taken in account for the length of extra pipe.

Multiple Piping Models (Unit: m)


Standard Max Piping for Max total Piping Additional
Phase Capacity(kBtu/h)
Length(m) one room(m) Length Charge(g/m)
14/16 7.5 20 30 20
18 7.5 25 50 20
21 7.5 25 50 20

24/27 7.5 25 70 20
30 7.5 25 75 20
40 7.5 25 85 20
• Multiple Piping Models
Additional charge (g) = ((A Room Installation Length – Standard Length ) x 20g/m
+ (B Room Installation Length – Standard Length ) x 20g/m +.. )
- CF(Correction Factor) x 150
h CF = Max. number of connectable indoor unit – Total number of connected indoor unit
12 INSTALLATION OF INDOOR, OUTDOOR UNIT
ENGLISH

Preparing work for Installation (ART COOL Type Only)


Open panel front
1 First, push the front panel backward and lift it up to remove the two screws.
2 The moment of lifting the both lower parts of panel front, you can hear sound this panel came
out, In this time panel front is separated
3 After pull down this panel a bit, and separate connecting wire with product.

Panel Front
Connector

Panel Front
Connector

Remove cover pipe and cover side


1 Remove two screws(for fixing cover pipe)
2 Pull up the cover side of desired connecting direction, then
cover side is separated. Pipe hole

3 In case of connecting direction is left or right, path through


the hole of cover side.

! CAUTION ! NOTE
After removing the pipe hole, cut the burr When connecting pipe path through rear
for safety. wall, don’t remove the hole.

Drain hose junction


1 Remove the rubber stopple of desired direction of drainage.
2 As the following picture, Insert drain hose in the handle of
drain pan, and join drain hose and connecting hose.
Adhesive Only one
desiring direction

Connecting
part
Drain rubber cap
hose
INSTALLATION OF WIRED REMOTE CONTROLLER 13

ENGLISH
Drill a hole in the wall
Drill the piping hole with a Ø65mm hole core drill. Drill the piping hole at either the right or the
left with the hole slightly slanted to the outdoor side.

WALL
Indoor Outdoor

(3/16"~5/16")
5-7mm
INSTALLATION OF WIRED REMOTE CON-
TROLLER
1 Please fix tightly using provided screw after placing remote controller setup board on the
place where you like to setup.
- Please set it up not to bend because poor setup could take place if setup board bends.
Please set up remote controller board fit to the reclamation box if there is a reclamation box.

2 Can set up Wired remote controller cable into three directions.


- Setup direction: the surface of wall reclamation, upper, right
- If setting up remote controller cable into upper and right side, please set up after removing
remote controller cable guide groove.
2 2
h Remove guide groove with long nose.
3
① Reclamation to the surface of the wall 1 3
② Upper part guide groove
③ Right part guide groove
<Wire guide grooves>
14 INSTALLATION OF WIRED REMOTE CONTROLLER
ENGLISH

3 Please fix remote controller upper part into the <Connecting order>
setup board attached to the surface of the wall,
as the picture below, and then, connect with
setup board by pressing lower part.
- Please connect not to make a gap at the remote
Wall Wall
controller and setup board’s upper and lower,
Side Side
right and left part.

<Separating order>
When separating remote controller from setup
board, as the picture below, after inserting into
the lower separating hole using screw driver and
then, spinning clockwise, remote controller is Wall Wall
separated. Side Side
- There are two separating holes. Please individu-
ally separate one at a time.
- Please be careful not to damage the inside
components when separating.

4 Please connect indoor unit and remote controller using connection cable.

Please check if connector is normally connected.

Indoor
Unit side
Connecting cable
5 Please use extension cable if the distance between wired remote controller and indoor unit is
more than 10m.

! CAUTION
When installing the wired remote controller, do not bury it in the wall.
(It can cause damage in the temperature sensor.)
Do not install the cable to be 50m or above.
(It can cause communication error.)
• When installing the extension cable, check the connecting direction of the connector of
the remote controller side and the product side for correct installation.
• If you install the extension cable in the opposite direction, the connector will not be con-
nected.
• Specification of extension cable: 2547 1007 22# 2 core 3 shield 5 or above.
INSTALLATION OF WIRED REMOTE CONTROLLER 15

ENGLISH
Wired remote controller installation
- Since the room temperature sensor is in the remote controller, the remote controller box should
be installed in a place away from direct sunlight, high humidity and direct supply of cold air to
maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor
in an area with good air circulation at an average temperature.
Do not install the remote controller where it can be affected by:
- Drafts, or dead spots behind doors and in corners.
- Hot or cold air from ducts.
- Radiant heat from sun or appliances.
- Concealed pipes and chimneys.
- Uncontrolled areas such as an outside wall behind the remote controller.
- This remote controller is equipped with a seven segment LED. display. For proper display of the
remote controller LED's, the remote controller should be installed properly as shown in Fig.1.
(The standard height is 1.2~1.5 m from floor level.)

yes

no

no
5feet
(1.5meters)

no

Fig.1 Typical locations for remote controller


16 FLARING WORK AND CONNECTION OF PIPING
ENGLISH

FLARING WORK AND CONNECTION OF PIP-


ING
Flaring work
Main cause for gas leakage is due to defect in flaring work. Carry out correct flaring work in the
following procedure.

Cut the pipes and the cable


- Use the piping kit accessory or the pipes pur-
chased locally. Copper
- Measure the distance between the indoor tube 90° Slanted Uneven Rough
and the outdoor unit.
- Cut the pipes a little longer than measured
distance.
- Cut the cable 1.5m longer than the pipe
length.

Burrs removal Pipe


- Completely remove all burrs from the cut Reamer
cross section of pipe/tube.
- Put the end of the copper tube/pipe in a
downward direction as you remove burrs in Point down
order to avoid dropping burrs into the tubing.

Putting nut on Flare nut


- Remove flare nuts attached to indoor and
outdoor unit, then put them on pipe/tube
having completed burr removal. Copper tube
(not possible to put them on after flaring
work)

Flaring work
- Carry out flaring work using flaring tool as
shown below. Handle

Outside diameter A Bar Bar


"A" Yoke
mm inch mm
Cone
Ø6.35 1/4 1.1~1.3
Ø9.52 3/8 1.5~1.7
Copper pipe
Ø12.7 1/2 1.6~1.8
Ø15.88 5/8 1.6~1.8 Clamp handle
Red arrow mark
Ø19.05 3/4 1.9~2.1

Firmly hold copper pipe in a bar in the


dimension shown in the table below.
FLARING WORK AND CONNECTION OF PIPING 17

ENGLISH
Check Smooth all round
- Compare the flared work with figure below. Inside is shining without scratches.
- If flare is noted to be defective, cut off the
flared section and do flaring work again.
= Improper flaring =

Inclined Surface Cracked Uneven


damaged thickness
Even length
all round

Connection of piping - Indoor


Preparing the indoor unit's piping and drain hose for installation through the wall.
1 Route the indoor tubing and the drain hose in the direction of rear left or right

Drain hose

Drain hose

Drain hose

2 Tape the tubing, drain hose and the connecting cable. Be sure that the drain hose is located at
the lowest side of the bundle. Locating at the upper side can cause drain pan to overflow
inside the unit.

Loop
Tape Tape
Connecting Connecting Gas side
pipe pipe Connecting piping
cable
Drain hose Drain hose Liquid side
Connecting cable Connecting cable Drain hose piping

! CAUTION
If the drain hose is routed inside the room, insulate the hose with an insulation material* so
that dripping from "sweating"(condensation) will not damage furniture or floors.
*Foamed polyethylene or equivalent is recommended.
18 FLARING WORK AND CONNECTION OF PIPING
ENGLISH

Indoor unit installation


Hook the indoor unit onto the upper portion of
the installation plate.(Engage the two hooks of
the rear top of the indoor unit with the upper Connecting

edge of the installation plate.) Ensure that the


hooks are properly seated on the installation
Drain hose
plate by moving it left and right.
Press the lower left and right sides of the unit
against the installation plate until the hooks
engage into their slots(clicking sound).

Connecting the pipings to the indoor unit and


drain hose to drain pipe
- Align the center of the pipings and sufficient-
ly tighten the flare nut by hand. Indoor unit tubing Flare nut Pipings
- Tighten the flare nut with a wrench.
Outside diameter Torque
mm inch N.m Spanner (fixed)
Ø6.35 1/4 16±2
Flare nut
Ø9.52 3/8 38±4
Ø12.7 1/2 55±6 Torque wrench Connection pipe
Ø15.88 5/8 75±7
Ø19.05 3/4 110±10 Indoor unit tubing

- When extending the drain hose at the indoor


unit, install the drain pipe.
Drain pipe

Indoor unit drain hose

Vinyl tape(narrow)
Adhesive

Plastic bands
Wrap the insulation material around the con- Insulation material
necting portion.
- Overlap the connection pipe insulation mate-
rial and the indoor unit pipe insulation materi-
al. Bind them together with vinyl tape so that
there is no gap.
- Wrap the area which accommodates the rear Connection Indoor
pipe unit pipe
piping housing section with vinyl tape.
Vinyl tape Wrap with vinyl tape
(wide)
Connecting cable

Pipe

Vinyl tape(narrow)
FLARING WORK AND CONNECTION OF PIPING 19

ENGLISH
- Bundle the piping and drain hose together by Wrap with vinyl tape
wrapping them with vinyl tape over the
range within which they fit into the rear pip- Pipe

ing housing section.

Vinyl tape(wide)
Drain hose

! CAUTION
Installation Information (For right piping) For right piping, follow the instruction below.

Good case Bad case


Press on the upper side of clamp and unfold Following bending type from left to right could
the tubing to downward slowly. cause problem of pipe damage.

Connection of piping - Outdoor


Align the center of the piping and sufficiently
tighten the flare nut by hand.

Connecting pipe order


1) ROOM A~E gas side pipe
2) ROOM A~E liquid side pipe
Ø12.7(1/2 inch) Connector

Finally, tighten the flare nut with torque wrench


until the wrench clicks. Outdoor unit
- When tightening the flare nut with torque Main gas
Main liquid side valve
wrench ensure the direction for tightening fol-
side valve
lows the arrow on the wrench. Gas side piping
ROOM A
Outside diameter Torque Liquid
mm inch N.m side piping ROOM B
Ø6.35 1/4 16±2 ROOM C
Ø9.52 3/8 38±4
Ø12.7 1/2 55±6 ROOM D
Ø15.88 5/8 75±7 ROOM E
Ø19.05 3/4 110±10
20 CONNECTING THE CABLE BETWEEN INDOOR UNIT AND OUTDOOR UNIT
ENGLISH

CONNECTING THE CABLE BETWEEN INDOOR


UNIT AND OUTDOOR UNIT
Connect the cable to the Indoor unit
Connect the cable to the indoor unit by connecting the wires to the terminals on the control
board individually according to the outdoor unit connection. (Ensure that the color of the wires of
the outdoor unit and the terminal No. are the same as those of the indoor unit.)
The earth wire should be longer than the common wires.
The circuit diagram is not subject to change without notice.
When installing, refer to the circuit diagram behind the panel front of Indoor Unit the wiring dia-
gram on the Control Cover Inside Outdoor Unit.

! CAUTION
• The circuit diagram is not subject to change without notice.
• Be sure to connect wires according to the wiring diagram.
• Connect the wires firmly, so that not to be pulled out easily.
• Connect the wires according to color codes by referring the wiring diagram.

2 Unit 3 Unit

4 Unit 5 Unit
CONNECTING THE CABLE BETWEEN INDOOR UNIT AND OUTDOOR UNIT 21

ENGLISH
5 Unit

! CAUTION
Main power source
Provide a circuit breaker between power source
and the unit as shown below.
Air Circuit Breaker
Conditioner Use a circuit breaker
or time delay fuse.

! CAUTION
The power cord connected to the outdoor unit should be complied with the following speci-
fications (Cable type approved by HAR or SAA).

Phase 1Ø
Capacity (kBtu/h) 14 16 18 21 24 27 30 40 GN
/YL
NORMAL CROSS SECTIONAL AREA 2.5 2.5 2.5 2.5 2.5 2.5 2.5 3.5
20
mm
Cable Type H07RN-F
ø7.5mm

The power connecting cable connected to the indoor and outdoor unit
should be complied with the following specifications (This equipment
shall be provided with a cord set complying with the national regula- GN
tion). /YL

20
NORMAL mm
CROSS-SECTIONAL
AREA 0.75mm2

H07RN-F
22 CONNECTING THE CABLE BETWEEN INDOOR UNIT AND OUTDOOR UNIT
ENGLISH

Connect the cable to the Outdoor unit


1 Remove the cover control from the unit by
Outdoor unit
loosening the screw.
Terminal block
Connect the wires to the terminals on the
control board individually as the following.
Over 15mm
2 Secure the cable onto the control board
with the holder (clamper). Holder for
3 Refix the cover control to the original posi- power supply
cord
tion with the screw.
4 Use a recongnized circuit breaker between
the power source and the unit. A discon-
Cover control
nection device to adequately disconnect all
Power cord
supply lines must be fitted.
Connecting cable

1Ø Models Loosen terminal screw

Capacity (kBtu/h) 14 16 18 21 24 27 30 40
Circuit Breaker (A) 15 15 20 20 25 25 25 30

Terminal block

! CAUTION
After the confirmation of the above conditions, prepare the wiring as follows.
1 Never fail to have an individual power circuit specifically for the air conditioner. As for the
method of wiring, be guided by the circuit diagram posted on the inside of control cover.
2 Firmly tighten the terminal screws to prevent them loosening. After tightening, pull the
wires lightly to confirm that they do not move. (If they are loose the unit, the unit will not
operate normally or it can cause burn-out of the wires.)
3 Specification of power source.
4 Confirm that electrical capacity is sufficient.
5 See to that the starting voltage is maintained at more than 90 percent of the rated volt-
age marked on the name plate.
6 Confirm that the cable thickness is as specified in the power source specification.
(Particularly note the relation between cable length and thickness.
7 Do not install an earth leakage circuit breaker in a wet or moist area.
8 The following would be caused by voltage drop.
- Vibration of a magnetic switch, which will damage the contact point, fuse breaking, dis-
turbance of the normal function of the overload.
9 The means for disconnection from a power supply shall be incorporated in the fixed wiring
and have an air gap contact separation of at least 3mm in each active(phase) conductors.
10 The Power cord connected to the unit should be selected according to the following
specifications.
CONNECTING THE CABLE BETWEEN INDOOR UNIT AND OUTDOOR UNIT 23

ENGLISH
Precautions when laying power wiring

Use round pressure terminals for connections to the power terminal block.

Power wire
Round pressure terminal

When none are available, follow the instructions below.


- Do not connect wiring of different thicknesses to the power terminal block. (Slack in the power
wiring may cause abnormal heat.)
- When connecting wiring which is the same thickness, do as shown in the figure below.

Connect same thickness It is forbidden to connect It is forbidden to


wiring to both sides. two to one side. connect wiring of
different thicknesses.

- For wiring, use the designated power wire and connect firmly, then secure to prevent outside
pressure being exerted on the terminal block.
- Use an appropriate screwdriver for tightening the terinal screws. A screwdriver with a small
head will strip the head and make proper tighterning impossible.
- Over-tightening the terminal screws may break them.
24 CHECKING THE DRAINAGE AND FORMING THE PIPINGS
ENGLISH

CHECKING THE DRAINAGE AND FORMING


THE PIPINGS
Checking the Drainage 2 Do not make drain piping.

To check the drainage.


1 Pour a glass of water on the evaporator.
Do not raise
2 Ensure the water flows through the drain
hose of the indoor unit without any leak-
age and goes out the drain exit.

Connecting area
Water
drain hose leakage
Accumulated
Leakage
drain water
checking Air

Drain pan

Water
Waving
leakage
Drain
hose
Leakage
checking
Tip of drain hose
dipped in water

Water
leakage Ditch

Less than
50mm gap

Drain piping
1 The drain hose should point downward for
easy drain flow.

Downward slope
CHECKING THE DRAINAGE AND FORMING THE PIPINGS 25

ENGLISH
Forming the Piping In cases where the Outdoor unit is installed
above the Indoor unit perform the following.
Form the piping by wrapping the connecting
portion of the indoor unit with insulation mate-
1 Tape the piping and connecting cable from
down to up.
rial and secure it with two kinds of vinyl tape.
- If you want to connect an additional drain
2 Secure the taped piping along the exterior
wall. Form a trap to prevent water entering
hose, the end of the drain outlet should be
the room.
routed above the ground. Secure the drain
hose appropriately. 3 Fix the piping onto the wall by saddle or
equivalent.

In cases where the outdoor unit is installed


below the indoor unit perform the following.
1 Tape the piping, drain hose and connecting
cable from down to up. Seal a small opening
around the pipings
2 Secure the tapped piping along the exterior with gum type sealant.
wall using saddle or equivalent.
Trap

Seal a small opening


around the pipings Taping
Trap
with gum type
Drain hose
sealer.

Pipings
Plastic Connecting
band cable

Power supply
cord

• Trap is required to prevent water from entering


into electrical parts.
26 AIR PURGING AND EVACUATION
ENGLISH

AIR PURGING AND EVACUATION


The air and moisture remaining in the refriger-
ant system have undesirable effects as indi- ! CAUTION
cated below. To avoid nitrogen entering the refrigerant
- Pressure in the system rises. system in a liquid state, the top of the
- Operating current rises. cylinder must be higher than its bottom
when you pressurize the system. Usually,
- Cooling(or heating) efficiency drops.
the cylinder is used in a vertical standing
- Moisture in the refrigerant circuit may freeze position.
and block capillary tubing.
- Water may lead to corrosion of parts in the
refrigeration system. - Do a leakage test of all joints of the
Therefore, after evacuating the system, take a tubing(both indoor and outdoor) and both gas
leak test for the piping and tubing between and liquid side service valves.
the indoor and outdoor unit. Bubbles indicate a leak. Be sure to wipe off
the soap with a clean cloth.
- After the system is found to be free of leaks,
Checking method relieve the nitrogen pressure by loosening
the charge hose connector at the nitrogen
cylinder. When the system pressure is
Preparation reduced to normal, disconnect the hose from
the cylinder.
Check that each tube(both liquid and gas side
tubes) between the indoor and outdoor units
have been properly connected and all wiring
for the test run has been completed. Remove Indoor unit
the service valve caps from both the gas and
Manifold valve
the liquid side on the outdoor unit. Check that
Pressure
both the liquid and the gas side service valves Lo Hi
gauge
on the outdoor unit are kept closed at this
Outdoor unit
stage.
Charge hose

Leakage test
Nitrogen gas
Connect the manifold valve(with pressure cylinder(in vertical
gauges) and dry nitrogen gas cylinder to this standing position)
service port with charge hoses.

! CAUTION
Be sure to use a manifold valve for leakage
test. If it is not available, use a stop valve for
this purpose. The "Hi" knob of the manifold
valve must always be kept close.
- Pressurize the system to no more than
551 P.S.I.G. with dry nitrogen gas and
close the cylinder valve when the gauge
reading reached 551 P.S.I.G. Next, test
for leaks with liquid soap.
AIR PURGING AND EVACUATION 27

ENGLISH
! WARNING - Replace the valve caps at both gas and liquid
side service valves and fasten them tight.
Use a vacuum pump or Inert (nitrogen) This completes air purging with a vacuum pump.
gas when doing leakage test or air purge. The air conditioner is now ready to test run.
Do not compress air or Oxygen and do
not use Flammable gases. Otherwise, it
may cause fire or explosion.
- There is the risk of death, injury, fire or Indoor unit
explosion.
Manifold valve

Lo Hi
Pressure
Evacuation gauge
Open
- Connect the charge hose end described in Outdoor unit
Open
the preceding steps to the vacuum pump to
evacuate the tubing and indoor unit.
Confirm the "Lo" knob of the manifold valve
is open. Then, run the vacuum pump.
The operation time for evacuation varies with
tubing length and capacity of the pump. The
following table shows the time required for
evacuation.

Required time for evacuation when 30 gal/h


vacuum pump is used
Vacuum pump
If tubing length is
If tubing length is
longer than 10m (33
less than 10m (33 ft)
ft)
Less than 0.5 Torr Less than 0.5 Torr

- When the desired vacuum is reached, close


the "Lo" knob of the manifold valve and stop
the vacuum pump.

Finishing the Job

- With a service valve wrench, turn the valve


stem of liquid side valve counter-clockwise to
fully open the valve.
- Turn the valve stem of gas side valve counter-
clockwise to fully open the valve.
- Loosen the charge hose connected to the gas
side service port slightly to release the pressure,
then remove the hose.
- Replace the flare nut and its bonnet on the gas
side service port and fasten the flare nut secure-
ly with an adjustable wrench. This process is
very important to prevent leakage from the sys-
tem.
28 PANEL FRONT ASSEMBLY (ART COOL TYPE ONLY)
ENGLISH

PANEL FRONT ASSEMBLY


(ART COOL TYPE ONLY)
1 First, Check the side cover assembly 3 Suspend hook of front panel in the groove
exactly, Fix power cord in the bottom after contract lower of 2 screws.
groove of cover side left.

2 Assemble connecting lead wire with con-


troller and first fix the upper part of panel
front, then match the lower part of panel
front

Panel Front
Connector

Panel Front
Connector
INSTALLATION PI485 29

ENGLISH
INSTALLATION PI485
Fix the PI485 PCB as shown in Fig.
Detailed installation method refer to PI485 Installation Manual.

18kBtu/h, 21kBtu/h

24kBtu/h, 27kBtu/h, 30kBtu/h

where
This label is should be applied in the location
installed.
LGAP(Sub PCB for Central Controller is
the LGAP.
Please connect the wire after installing

1Ø : 40kBtu/h
Screw Hole

Gateway.
n of PI485
for installatio
the space
This is y) PI485
(Accessor after installing
the wire
connect
Please
Gateway.
Screw Hole

802
MEZ30171
30 TEST RUNNING
ENGLISH

TEST RUNNING
- Check that all tubing and wiring have been - For reference, the gas side pressure of opti-
properly connected. mum condition is as below.(Cooling)
- Check that the gas and liquid side service
valves are fully open. The pressure of
Outside ambi-
Refrigerant the gas side
ent TEMP.
service valve.
Prepare remote control 8.5~9.5kg/cm2G
R410A 35°C (95°F)
(120~135 P.S.I.G.)
Remove the battery cover by pulling it accord-
ing to the arrow direction.
Insert new batteries making sure that the (+) ! NOTE
and (–) of battery are installed correctly.
Reattach the cover by pushing it back into If the actual pressure are higher than
position. shown, the system is most likely over-
charged, and charge should be removed.
If the actual pressure are lower than
shown, the system is most likely under-
charged, and charge should be added.
The air conditioner is now ready for use.

Intake temperature
! NOTE
• Use 2 AAA(1.5volt) batteries. Do not Discharge air
use rechargeable batteries.
• Remove the batteries from the remote
control if the system is not going to be
used for a long time.
Discharge
temperature
Bolt
Intake temperature

Discharge air

Tubing connection
Discharge
temperature
Evaluation of the performance
Intake temperature
Discharge air
Operate unit for 15~20 minutes, then check
the system refrigerant charge:
- Measure the pressure of the gas side service
valve.
- Measure the temperature of the intake and
discharge of air.
- Ensure the difference between the intake
temperature and the discharge is more than Discharge
temperature
8°C.
FUNCTION 31

ENGLISH
FUNCTION
Dip S/W Setting
If you set the Dip Switch when power is on, the change in setting is not
applicable. The changing setting is enabled only when Power is reset.

Dip Switch
Function
1 2 3 4
Normal Operation (No Function)

Forced Cooling Operation

Wiring Error Check

Saving Power Consumption (Step 1)

Saving Power Consumption (Step 2)

Mode Lock (Cooling)

Mode Lock (Heating)

Night Quiet Mode (Step 1)

Night Quiet Mode (Step 2)

Mode Lock (Cooling) + Night Quiet Mode (Step 1)

Mode Lock (Cooling) + Night Quiet Mode (Step 2)

Mode Lock (Cooling) + Saving Power Consumption (Step 1)

Mode Lock (Cooling) + Saving Power Consumption (Step 2)

Mode Lock (Heating) + Saving Power Consumption (Step 1)

Mode Lock (Heating) + Saving Power Consumption (Step 2)

SLC (Smart Load Control) Mode

! WARNING
When you set the dip switch, you should turn off the circuit breaker or shut the power
source of the product down.

! CAUTION
• Unless the applicable dip switch is set properly, the product may not work.
• If you want to set a specific function, request that the installer sets the dip switch appropriately
during installation.
32 FUNCTION
ENGLISH

14/16/18/21(1Ø) kBtu/h 40(1Ø) kBtu/h

DIP SW2

Forced Cooling Operation


Adding the refrigerant in winter.
DIP-SW

Setting Procedure
1 Set the Dip Switch as follow after shutting
the power source down.

24/27/30(1Ø) kBtu/h

2 Reset the power.


3 Check that the Red LED of PCB is on dur-
ing work.
(The indoor unit is operated by force.)
4 Add the specific amount of refrigerant.

! CAUTION
- When the green LED of PCB is on,
SW01N compressor is going to be off because
of low pressure.
- You should return the Dip Switch to
operate normally after finishing the
operation.
FUNCTION 33

ENGLISH
Wiring Error Check ! CAUTION
You can check whether or not the wiring is correct.
• If Indoor unit doesn’t communicate to out-
door Unit, function could not be operated
Setting Procedure correctly.
1 Set the Dip Switch as follow after shutting • Only the wrong wiring connection is dis-
the power source down. played. You should change connection cor-
rectly to operate the product.
• If Outdoor and Indoor temperature is too
low in winter, the wiring error check func-
tion will not be operated.
(Red LED is lighting)
2 Reset the power.
3 Check that the Re and Green LED of PCB
are on during work. (The indoor unit is
operated by force.)
Saving Power Consumption
4 If the wiring is correct, the Green LED will
light up. Saving Power Consumption operation is the
If the wiring is wrong, display as below function which enables efficient operation by
(Display only wrong connection.) lowering the maximum power consumption
value.
• Red LED : Piping Number
• Green LED : Wiring Number (Room) Power
consumption
and current Nomal
Example)
If the Red LED blinks twice and the Green
LED blinks 3 times, 2nd pipe is connected to
3rd room.

Time
LED1 2 3
(Red) Setting Procedure
1 Set the Dip Switch as follow after shutting
1sec 1sec the power source down.
3 2
LED1
(Green)

1sec 1sec
Step 1 Step 2

5 You should return the Dip Switch to oper- 2 Reset the power.
ate normally after finishing wiring error
check.
34 FUNCTION
ENGLISH

Saving Power Consumption Current level.

Phase 1Ø
Model 14k 16k 18k 21k 24k 27k 30k 40k
Step1(A) 8 8 9 9 12 13 15 22
Step2(A) 7 7 8 8 10 11 13 18

Saving Power Consumption with Mode Lock.

Saving Power Saving Power


Consumption (step 1) Consumption (step 1)
+ Mode Lock (Cooling) + Mode Lock (Heating)

Saving Power Saving Power


Consumption (step 2) Consumption (step 2)
+ Mode Lock (Cooling) + Mode Lock (Heating)

Night Quiet Mode


Night Quiet Mode operation lowers the noise level of the outdoor unit by changing the comp fre-
quency and fan speed. This function is operated all night long.

Setting Procedure
1 Set the Dip Switch as follow after shutting the power source down.

h Noise level :Step 1 > Step 2

Step 1 Step 2

2 Reset the power.

Night Quiet Mode with Mode Lock.

Mode Lock (Cooling) Mode Lock (Cooling)


+ Night Quiet Mode + Night Quiet Mode
(step 1) (step 2)

! CAUTION
• If comp frequency and fan speed are down, the cooling capacity may decrease accordingly.
• This function is only available for Cooling Mode.
• If you want to stop the Night Quiet Mode, Change the Dip Switch.
• If operating indoor unit is set by the fan speed “Power”, Night Quiet Mode will be stopped
until fan speed “Power” is changed.
FUNCTION 35

ENGLISH
Mode Lock
Setting Procedure
1 Set the Dip Switch as follow after shutting the power source down.

Only Cooling Mode Only Heating Mode

2 Reset the power.

Mode Lock with Night Quiet Mode

Mode Lock (Cooling) Mode Lock (Cooling)


+ Night Quiet Mode + Night Quiet Mode
(step 1) (step 2)

Saving Power Consumption with Mode Lock.

Mode Lock (Cooling) Mode Lock (Heating)


+ Saving Power + Saving Power
Consumption (step 1) Consumption (step 1)

Mode Lock (Cooling) Mode Lock (Heating)


+ Saving Power + Saving Power
Consumption (step 2) Consumption (step 2)

SLC (Smart Load Control) Mode ※ 18~40(1Ø) kBtu/h


Through the most efficient operation accord- Setting Procedure
ing to the in/outdoor load, must minimize the 1 Set the Dip Switch as follow after the
energy consumption. power source down.

Power
N ormal
consumption SLC
(Smart Load Control)

2 Reset the power.

Time

! CAUTION
• The cooling/heating capacity may decrease depending on the in/outdoor load.
• If you want to stop the SLC Mode, Change the Dip Switch.
36 FUNCTION
ENGLISH

PCB Display(14/16/18/21k Model Only)


It is useful to check the cycle data without LGMV.

Operating Method
Whenever you push the Tact Switch, the cycle information will be shown as below.
h After 1page is displayed, subsequently 2page is displayed.

Tact S/W Display


Item
14/16k 18/21k Example 1page 2page
- 1 time Low Pressure 890kpa ‘LP’ ’ 89’
- 2 time Hi Pressure 2900kpa ‘HP’ ‘290’
1 time 3 time Discharge Temp. 85°C ‘DS’ ’ 85’
2 time 4 time Cond Out Temp. -10°C ‘CS’ ‘-10’
3 time 5 time Suction Temp. -10°C ‘SS’ ‘-10’
4 time 6 time ODU Air Temp. -10°C ‘AS’ ‘-10’
5 time 7 time Current 15A ‘A’ ‘ 15’
6 time 8 time Voltage 230V ‘V’ ‘230’
7 time 9 time Comp Hz 100Hz ‘F’ ‘100’
8 time 10 time DC Link Voltage 230V ‘dc’ ‘230’

TACT-SW1

! WARNING
When you push the Tact Switch, use the material non-conducting electricity.
MAX COMBINATION CAPACITY 37

ENGLISH
MAX COMBINATION CAPACITY
Multi Piping Type
Capacity Combination Indoor Capacity Max Combination Capacity
Max Room No.
(kBtu/h) (kBtu/h) (kBtu/h)
14 2 5,7,9,12 21
16 2 5,7,9,12 24
18 3 5,7,9,12,18 30
21 3 5,7,9,12,18 33
24 4 5,7,9,12,18,24 39
27 4 5,7,9,12,18,24 41
30 5 5,7,9,12,18,24 48
40 5 5,7,9,12,18,24 52

The combination of indoor unit is to be decided that the sum of indoor unit capacity index must
be smaller than the maximum combination capacity of outdoor unit. We recommend to calculate
indoor unit capacity like below.
If you do not follow our recommendation, it will have some problems in low ambient condition
i.e. some indoor unit will not be able to heat very well in heating mode.

CALCULATION METHOD FOR THE CONNECTABLE TOTAL CAPACITY OF INDOOR UNIT

Sum up the capacity of all indoor unit, but high static duct type indoor unit capacity weights 1.3
times

Ex) 1 Outdoor unit : A9UW566FA3(FM56AH)(connectable maximum capacity is 73kBtu)


Indoor unit:
AMNH186BHA0[MB18AH],AMNH246BHA0[MB24AH],AMNH246BHA0[MB24AH]
(18 + 24 + 24) x 1.3 = 66 x 1.3 = 85.8kBtu: this combination has a some problem
2 Out door unit: FM56AH
Indoor unit:
AMNH186BHA0[MB18AH],AMNH246BHA0[MB24AH],AMNH18GD5L0[MS18AH]
(18 + 24) x 1.3 + 18 + 72.6: this combination can be ok
38 INSTALLATION GUIDE AT THE SEASIDE
ENGLISH

INSTALLATION GUIDE
AT THE SEASIDE Windbreak

! CAUTION
• Air conditioners should not be installed Sea wind
in areas where corrosive gases, such as
acid or alkaline gas, are produced.
• Do not install the product where it could
be exposed to sea wind (salty wind)
directly. It can result corrosion on the
product. Corrosion, particularly on the - It should be strong enough like concrete to
condenser and evaporator fins, could prevent the sea wind from the sea.
cause product malfunction or inefficient - The height and width should be more than
performance. 150% of the outdoor unit.
• If outdoor unit is installed close to the - It should be keep more than 70 cm of space
seaside, it should avoid direct exposure between outdoor unit and the windbreak for
to the sea wind. Otherwise it needs easy air flow.
additional anticorrosion treatment on the
Place with fluent water draining
heat exchanger.
- Install at a place with fluent water draining to
prevent damage from localized heavy rain
and avoid frequent flooded area.
Selecting the location(Outdoor Unit)
• Periodic ( more than once/year ) clean-
If the outdoor unit is to be installed close to ing of the dust or salt particles stuck on
the seaside, direct exposure to the sea wind the heat exchanger by using water.
should be avoided. Install the outdoor unit on
the opposite side of the sea wind direction.

SEASONAL WIND AND


Sea wind CAUTIONS IN WINTER
- Sufficient measures are required in a snow
area or severe cold area in winter so that
product can be operated well.
- Get ready for seasonal wind or snow in win-
ter even in other areas.
- Install a suction and discharge duct not to let
in snow or rain.
- Install the outdoor unit not to come in con-
Sea wind
tact with snow directly. If snow piles up and
freezes on the air suction hole, the system
may malfunction. If it is installed at snowy
area, attach the hood to the system.
- Install the outdoor unit at the higher installa-
tion console by 50cm than the average
snowfall (annual average snowfall) if it is
In case, to install the outdoor unit on the installed at the area with much snowfall.
seaside, set up a windbreak not to be - Where snow accumulated on the upper part
exposed to the sea wind. of the Outdoor Unit by more than 10cm,
always remove snow for operation.
SEASONAL WIND AND CAUTIONS IN WINTER 39

ENGLISH
1 The height of H frame must be more Airborne Noise Emission
than 2 times the snowfall and its width The A-weighted sound pressure emitted by
shall not exceed the width of the prod- this product is below 70 dB.
uct. (If width of the frame is wider than
that of the product, snow may accumu- ** The noise level can vary depending on the
late) site.
2 Don't install the suction hole and dis- The figures quoted are emission level and are
charge hole of the Outdoor Unit facing not necessarily safe working levels. Whilst
the seasonal wind. there is a correlation between the emission
and exposure levels, this cannot be used reli-
ably to determine whether or not further pre-
cautions are required. Factor that influence
Model Designation the actual level of exposure of the workforce
include the characteristics of the work room
Indoor unit and the other sources of noise, i.e. the num-
ber of equipment and other adjacent process-
M S 09 AWR N B 0
es and the length of time for which an opera-
Serial number
Chassis name
tor exposed to the noise. Also, the permissi-
Indoor ble exposure level can vary from country to
Detailed product type country. This information, however, will
AQ : Deluxe SQ : Standard
AH* : Panel type color_Gallery(1), Silvr(V),
enable the user of the equipment to make a
Red(E), Gold(G), White Silver(H) better evaluation of the hazard and risk.
AW* : Mirror type color_Mirror(R), Silver(
White(W)
AH : Ceiling cassette
L : Low static
No mark for Standard Inverter indoor units Limiting concentration
Nominal Capacity
EX) 9,000 Btu/h Class ➝ ’09’
Limiting concentration is the limit of Freon gas
24,000 Btu/h Class ➝ ’24’ concentration where immediate measures can
Type be taken without hurting human body when
S : Wall mounted/ARTCOOL Mirror
J : Wall mounted A : ARTCOOL Panel refrigerant leaks in the air. The limiting con-
T : Cassette B : Duct V : Floor-ceiling
Q : Console
centration shall be described in the unit of
Model Type
kg/m3 (Freon gas weight per unit air volume)
M : Multi Indoor unit for facilitating calculation.
C : Common Indoor unit for
Universal and Multi
Limiting concentration: 0.44kg/m3(R410A)
Outdoor unit Calculate refrigerant concentration
MU4 M 27 U4 2 Total amount of replenished refrig-
Refrigerant = erant in refrigerant facility (kg)
Serial number
Outdoor unit chassis name concentration Capacity of smallest room where
Nominal capacity indoor unit is installed (m3)
Ex) 18,000 Btu/h Class → ’18’
Pipe Connecting Type
M : Multiple pipes
Indicates that this is multi system
outdoor unit using R410A
Ex) MU3 : Connectable max. 3 indoor units
MU4 : Connectable max. 4 indoor units

FM 40 A H U3 2

Serial number
Outdoor unit chassis name
Model type
H : Heat pump
Type of refrigerant
A : R410A
Nominal capacity
Ex) 48,000 Btu/h Class → ’48’
Model type
FM : Inverter multi ststem of
Distributor Box type
40