Panasonic Electric Works, LTD.: Panasonic FP Series (SIO) Driver

Download as pdf or txt
Download as pdf or txt
You are on page 1of 52

EIO0000001206 04/2013

Panasonic Electric Works,


Ltd.
Panasonic FP Series (SIO) Driver
03/2014
EIO0000001206.01

www.schneider-electric.com
2 EIO0000001206 03/214
Table of Contents

Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Chapter 1 Panasonic FP Series (SIO) Driver . . . . . . . . . . . . . . . . . 9
System Structure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Target Machine Serial Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Cable Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Supported Device Addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Consecutive Equipment Addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Environment Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
I/O Manager Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Driver Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Equipment Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Device Address Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

EIO0000001206 03/214 3
4 EIO0000001206 03/214
Safety Information
§

Important Information

NOTICE
Read these instructions carefully, and look at the equipment to become familiar with
the device before trying to install, operate, or maintain it. The following special
messages may appear throughout this documentation or on the equipment to warn
of potential hazards or to call attention to information that clarifies or simplifies a
procedure.

EIO0000001206 03/214 5
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by
qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction
and operation of electrical equipment and its installation, and has received safety
training to recognize and avoid the hazards involved.

6 EIO0000001206 03/214
About the Book

At a Glance

Document Scope
This manual describes the device driver communication settings in the Vijeo
Designer screen editing software. Vijeo Designer enables you to design Magelis
target machines that communicate with PLCs, drives, field devices, and other
equipment.
For more information about Vijeo Designer and Magelis target machines, please
refer to Vijeo Designer user documentation.

Validity Note
The data and illustrations found in this book are not binding. We reserve the right to
modify our products in line with our policy of continuous product development. The
information in this document is subject to change without notice and should not be
construed as a commitment by Schneider Electric.

Documentation Conventions
Target Machine: Human-Machine Interface (HMI) that runs user applications
designed in Vijeo Designer screen editing software. A target machine is also known
as a terminal.

EIO0000001206 03/214 7
Product Related Information

WARNING
LOSS OF CONTROL
 The designer of any control scheme must consider the potential failure modes
of control paths and, for certain critical control functions, provide a means to
achieve a safe state during and after a path failure. Examples of critical control
functions are emergency stop and overtravel stop.
 Separate or redundant control paths must be provided for critical control
functions.
 System control paths may include communication links. Consideration must be
given to the implications of unanticipated transmission delays or failures of the
link.*
 Each implementation of a Magelis XBTGT, HMISTO, HMISTU, HMIGTO,
HMIGTU, XBTGH, XBTGK, XBTGC, iPC, and XBTGTW must be individually
and thoroughly tested for proper operation before being placed into service.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.

* For additional information, refer to NEMA ICS 1.1 (latest edition), “Safety
Guidelines for the Application, Installation, and Maintenance of Solid State Control.“

User Comments
We welcome your comments about this document. You can reach us by e-mail at
[email protected].

8 EIO0000001206 03/214
Panasonic FP Series (SIO) Driver
EIO0000001206 04/2013

Panasonic FP Series (SIO) Driver

1
Subject of this Chapter
This chapter explains the Panasonic FP Series (SIO) Driver.

What's in this Chapter?


This chapter contains the following topics:
Topic Page
System Structure 10
Target Machine Serial Interface 12
Cable Diagrams 21
Supported Device Addresses 41
Consecutive Equipment Addresses 43
Environment Setup 44
I/O Manager Configuration 45
Driver Configuration 46
Equipment Configuration 48
Device Address Configuration 50

EIO0000001206 03/214 9
Panasonic FP Series (SIO) Driver

System Structure

Overview
The following table describes the system setup for connecting the target machine to
Panasonic FP Series PLCs.
To view a cable connection diagram for a particular communication format, see
Cable Diagrams.

Connection

Series CPU Link I/F Comm. Format Diagram


Tool port of the control unit Cable Diagram 8
AFPG801*1 Cable Diagram 1
*1 RS-232C
AFPG802 Cable Diagram 2
FPΣ
AFPG806*1 Cable Diagram 4
AFPG803*1 Cable Diagram 3
RS-485 (2-wire)*3
AFPG806*1 Cable Diagram 5
Tool port of the control unit RS-232C Cable Diagram 8
FP0
RS-232C port of the control unit*5 RS-232C Cable Diagram 6
Tool port of the control unit RS-232C Cable Diagram 9
FP1
RS-232C port of the control unit*6 RS-232C Cable Diagram 7
Tool port of the control unit RS-232C Cable Diagram 8
FP-M
RS-232C port of the control unit*7 RS-232C Cable Diagram 7
Tool port of the control unit RS-232C Cable Diagram 8
RS-232C port of the control unit RS-232C Cable Diagram 7
FP2 AFP2462 RS-232C Cable Diagram 7
FP FP2SH AFP2803 RS-232C Cable Diagram 7
AFP2465*2 AFP2804 RS-422 (4-wire) Cable Diagram 11
AFP2805 RS-485 (2-wire) Cable Diagram 3
Tool port of the control unit RS-232C Cable Diagram 10
FP3
AFP3462 RS-232C Cable Diagram 7
Tool port of the control unit RS-232C Cable Diagram 8
AFPE224300
AFPE224305 RS-232C Cable Diagram 12
FP-e
AFPE214325
AFPE224302
RS-485 (2-wire)*4 Cable Diagram 13
AFPE214322
RS-232C port of the control unit RS-232C Cable Diagram 7
FP10S
AFP3462 RS-232C Cable Diagram 7
Tool port of the control unit RS-232C Cable Diagram 14
FP10SH RS-232C port of the control unit RS-232C Cable Diagram 7
AFP3462 RS-232C Cable Diagram 7

*1 AFPG801, AFPG802, AFPG803 and AFPG806 are Communication Cassettes


specifically made for FPΣ.

10 EIO0000001206 03/214
Panasonic FP Series (SIO) Driver

*2 2AFP2465 is a Multi Communication Unit used with FP2 / FP2SH.


AFP2803, AFP2804 and AFP2805 are communication blocks installed on the
AFP2465.
*3 The RS-485 port of AFPG806 is either 19200bps or 115200bps only. Also the
baud rate must be identically set by the system register and the dipswitch in the
communication cassette. For details, refer to the PLC manual (FPΣ User’s
Manual).
*4 The RS-485 (2-wire) port is either 9600bps or 19200bps only.
Set the communication format of RS-485 (2-wire) to both FP-e system register
and FP-e internal switch. For details, refer to the PLC manual (FP-e Control Unit
User’s Manual).
*5 FP0 (C10CRM/C10CRS/C14CRM/C14CRS/C16CT/ C16CP/C32CT/C32CP)
equipped with a RS-232C port.
*6 FP1 (C24/C40/C56/C72) equipped with a RS-232C port.
*7 FP-M (C20R/C20T/C32T) equipped with a R-S232C port.

EIO0000001206 03/214 11
Panasonic FP Series (SIO) Driver

Target Machine Serial Interface

Use the following serial interface diagrams in combination with the cable diagrams
in Section 3 to wire connections between the target machine and external
equipment.

Magelis iPC Series (Smart, Compact, and Flex) and XBTGTW Series
The iPC Series (Smart, Compact, and Flex) and the XBTGTW Series target
machines come with one to four COM ports. All serial ports use 9-pin D-Sub male
connectors and support RS-232C serial communication. The following table
illustrates the pin layout for these target machines.
COM1, COM2, COM3, OR COM4 (9-pin D-Sub Plug)
RS-232C
Pin Number Symbol Description
1 CD Carrier Detect
2 RD(RXD) Receive Data
3 SD(TXD) Transmit Data
4 ER(DTR) Data Terminal Ready
5 GND Common Ground
6 DR(DSR) Data Set Ready
7 RS(RTS) Request to Send
8 CS(CTS) Send Possible
9 CI(RI) Called status display

Magelis XBTGK, XBTGC2000, XBTGH2000, and XBTGT2000 Series or higher


All XBTGK and XBTGT2000 Series and higher target machines have two COM
ports: COM1 and COM2. The XBTGC2000 Series has one COM port: COM1.
XBTGH2000 Series (Junction Box) has one COM port: COM1.
COM1 is a 9-pin D-Sub male connector and COM2 is an RJ45 socket. The following
tables illustrate the pin layout for these target machines.
COM1 (9-pin D-Sub Plug)
This COM port can act as either an RS-232C or RS-422 interface.

12 EIO0000001206 03/214
Panasonic FP Series (SIO) Driver

RS-232C
Pin Number Symbol Description
1 CD Carrier Detect
2 RD(RXD) Receive Data
3 SD(TXD) Transmit Data
4 ER(DTR) Data Terminal Ready
5 GND Common Ground
6 DR(DSR) Data Set Ready
7 RS(RTS) Request to Send
8 CS(CTS) Send Possible
9 CI(RI) Called status display or +5V ±5%
output 0.25A

RS-422
Pin Number Symbol Description
1 RDA Receive Data A
2 RDB Receive Data B
3 SDA Send Data A
4 ERA Data Terminal Ready A
5 GND Common Ground
6 CSB Send Possible B
7 SDB Send Data B
8 CSA Send Possible A
9 ERB Data Terminal Ready B

Note:
 When making your own connections, attach a loop back between pins 6 (CSB)
and 9 (ERB), and between 4 (ERA) and 8 (CSA).
 To simplify the wiring, you can use the COM Port Conversion Adapter
(Schneider Electric: XBTZGCOM) and Terminal Block Conversion Adapter
(Schneider Electric: XBTZG949). These accessories allow access to the RS-
422 signals using screw terminals. For information on the signals of the screw
terminals, see the user manual for the XBTZG949.

EIO0000001206 03/214 13
Panasonic FP Series (SIO) Driver

COM2 (RJ45 Socket)

WARNING
UNINTENDED EQUIPMENT OPERATION
When making your own connections, use shielded RJ45 connectors. The shielded
connector provides isolation against electromagnetic interference and provides a
more secure physical connection in the RJ45 socket. Use of an improper RJ45
connection could lead to insecure connections.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.

COM2 supports RS-422/485 signals only.


Pin Number Symbol Description
1
2
3
4 D1(+) Send/Receive Data (Positive
Signal)
5 D0(-) Send/Receive Data (Negative
Signal)
6
7
8 GND Common Ground

Magelis HMIGTO Series


The HMIGTO target machines have two COM ports (COM1 and COM2), with the
exception of the HMIGTO1310. The HMIGTO1310 has one COM port (COM1),
which uses an RJ45 connector for RS-232/422/485 serial communication. For more
information, see Magelis XBTGT1000, XBTGT1005, HMIGTO1310, HMISTO, and
HMISTU Series.
COM1 is a 9-pin D-Sub male connector, and COM2 is an RJ45 socket. The following
tables illustrate the pin layout for these target machines.

14 EIO0000001206 03/214
Panasonic FP Series (SIO) Driver

COM1 (9-pin D-Sub Plug)


This COM port supports RS-232C serial communication.

CAUTION
LOSS OF COMMUNICATION
 All connections to the communication ports must not put excessive stress on the
ports.
 Securely attach communication cables to the panel wall or cabinet.
 Use only D-Sub 9-pin cables with a locking tab in good condition.
Failure to follow these instructions can result in injury or equipment damage.

RS-232C
Pin Number Symbol Description
1 CD Carrier Detect
2 RD(RXD) Receive Data
3 SD(TXD) Transmit Data
4 ER(DTR) Data Terminal Ready
5 SG Signal Ground
6 DR(DSR) Data Set Ready
7 RS(RTS) Request to Send
8 CS(CTS) Send Possible
9 CI(RI/VCC) Called status display or +5V ±5%
output 0.25A
Shell FG Frame Ground (Common with SG)

Note:
 You can switch pin 9 between RI and VCC via software. The VCC output is not
protected against overcurrent. To prevent damage or a unit malfunction, use
only the rated current.
 You can use the Cable Connector (Omron Corporation: XMD-0901), Cable
Cover (Omron Corporation: XM2S-0913), and Jack Screw #4-40 UNC (Omron
Corporation: XM2Z-0073).

EIO0000001206 03/214 15
Panasonic FP Series (SIO) Driver

COM2 (RJ45 Socket)


This COM port supports RS-422/485 serial communication.

WARNING
UNINTENDED EQUIPMENT OPERATION
When making your own connections, use shielded RJ45 connectors. The shielded
connector provides isolation against electromagnetic interference and provides a
more secure physical connection in the RJ45 socket. Use of an improper RJ45
connection could lead to insecure connections.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.

RS-422/485
Pin Number Symbol Description
1 NC –
2 NC –
3 NC –
4 Line A Transfer Data (RS-485)
5 Line B Transfer Data (RS-485)
6 RS(RTS) Request to Send
7 NC –
8 SG Signal Ground

DANGER
ELECTRIC SHOCK
The serial port is not isolated. The SG (signal ground) and FG (frame ground)
terminals are connected inside the unit.
When using the SG terminal to connect an external device to the panel:
 Verify that a ground loop is not created when you set up the system.
 Connect the #8 SG terminal to remote equipment when the host (PLC) unit is
not isolated. Connect the #8 SG terminal to a known reliable ground connection
to reduce the risk of damaging the circuit.
Failure to follow these instructions can result in death or serious injury.

16 EIO0000001206 03/214
Panasonic FP Series (SIO) Driver

Magelis XBTGT1000, XBTGT1005, HMIGTO1310, HMISTO, and HMISTU Series


XBTGT1000, XBTGT1005, HMIGTO1310, HMISTO, and HMISTU Series machines
come with one COM port which uses an RJ45 connector. The RJ45 socket closest
to the power connector is the COM1 port. This COM port can act as an RS-422/485
interface.
COM1 (RJ45 Socket)

WARNING
UNINTENDED EQUIPMENT OPERATION
When making your own connections, use shielded RJ45 connectors. The shielded
connector provides isolation against electromagnetic interference and provides a
more secure physical connection in the RJ45 socket. Use of an improper RJ45
connection could lead to insecure connections.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.

RS-232C
Pin Number Symbol Description
1 RD(RXD) Receive Data
2 SD(TXD) Transmit Data
3
4
5
6
7
8 GND Common Ground

EIO0000001206 03/214 17
Panasonic FP Series (SIO) Driver

RS-422/485 (2-wire)
Pin Number Symbol Description
1
2
3
4 D1(+) Send/Receive Data (Positive
Signal)
5 D0(-) Send/Receive Data (Negative
Signal)
6
7
8 GND Common Ground

Magelis HMIGTU
All HMIGTU Series target machines have two COM ports: COM1 and COM2.
COM1 is an RJ45 socket and COM2 is a 9-pin D-Sub male connector. The following
tables illustrate the pin layout for these target machines.
COM1 (RJ45 Socket)

WARNING
UNINTENDED EQUIPMENT OPERATION
When making your own connections, use shielded RJ45 connectors. The shielded
connector provides isolation against electromagnetic interference and provides a
more secure physical connection in the RJ45 socket. Use of an improper RJ45
connection could lead to insecure connections.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.

18 EIO0000001206 03/214
Panasonic FP Series (SIO) Driver

COM1 supports RS-485 signals only.


Pin Number Symbol Description
1
2
3
4 D1(+) Send/Receive Data (Positive
Signal)
5 D0(-) Send/Receive Data (Negative
Signal)
6
7
8 GND Common Ground

COM2 (9-pin D-Sub Plug)


This COM port can act as either an RS-232C or RS-422/485 interface.
RS-232C
Pin Number Symbol Description
1 CD Carrier Detect
2 RD(RXD) Receive Data
3 SD(TXD) Transmit Data
4 ER(DTR) Data Terminal Ready
5 GND Common Ground
6 DR(DSR) Data Set Ready
7 RS(RTS) Request to Send
8 CS(CTS) Send Possible
9 CI(RI) Called status display or +5V ±5%
output 0.25A

EIO0000001206 03/214 19
Panasonic FP Series (SIO) Driver

RS-422/485
Pin Number Symbol Description
1 RDA Receive Data A
2 RDB Receive Data B
3 SDA Send Data A
4 ERA Data Terminal Ready A
5 GND Common Ground
6 CSB Send Possible B
7 SDB Send Data B
8 CSA Send Possible A
9 ERB Data Terminal Ready B

Note:
 When making your own connections, attach a loop back between pins 6 (CSB)
and 9 (ERB), and between 4 (ERA) and 8 (CSA).
 To simplify the wiring, you can use the COM Port Conversion Adapter
(Schneider Electric: XBTZGCOM) and Terminal Block Conversion Adapter
(Schneider Electric: XBTZG949). These accessories allow access to the RS-
422 signals using screw terminals. For information on the signals of the screw
terminals, see the user manual for the XBTZG949.

20 EIO0000001206 03/214
Panasonic FP Series (SIO) Driver

Cable Diagrams

The cable diagrams illustrated below and the cable diagrams recommended by
Panasonic may differ, however, Schneider Electric recommends using the following
connection diagrams.
 Ground the PLC’s FG terminal according to your country’s applicable standard.
For details, refer to the PLC manual.
 When making your own communication cable, be sure to connect the SG signal.
Note:
 When signal lines overlap as drawn below, it indicates a twisted pair.

Diagram 1 - RS-232C
To connect the target machine and the PLC, use the recommended cables and
accessories in combination with the target pin specification in Target Machine Serial
Interface.

Target Machine Cable / Adaptor Comments

iPC or XBTGTW Series


(COM1/COM2/COM3/ COM4),
XBTGK Series (COM1), XBTGH Series
Cable length:
(COM1), XBTGC2000 Series or higher Connection Diagram
500m (1600 ft) max.
(COM1), XBTGT2000 Series or higher
(COM1), HMIGTO Series (COM1), or
HMIGTU Series (COM2)

Target Machine Shield


Signal Signal
RD SD
SD RD
CS RS
ER CS
SG SG
DR
RS
FG

EIO0000001206 03/214 21
Panasonic FP Series (SIO) Driver

Diagram 2 - RS-232C
To connect the target machine and the PLC, use the recommended cables and
accessories in combination with the target pin specification in Target Machine Serial
Interface.

Target Machine Cable / Adaptor Comments

iPC or XBTGTW Series


(COM1/COM2/COM3/ COM4), XBTGK
a Connection Diagram
Series (COM1), XBTGC2000 Series or
higher (COM1), XBTGH Series (COM1),
XBTGT2000 Series or higher (COM1), Cable length:
XBTGT1000 Series (COM1), 15m (50 ft) max.
XBTGT1005 Series (COM1), HMISTO
Series (COM1), HMISTU Series (COM1),
b Connection Diagram
HMIGTO Series (COM1), or HMIGTU
Series (COM2)

a. Connection Diagram
Target Machine Shield
Signal Signal
RD S1
SD R1
ER S2
DR R2
SG SG
RS
CS
FG

b. Cable Diagram
Target Machine Shield
Signal Signal
ER S1
DR R1
RD S2
SD R2
SG SG
RS
CS
FG

22 EIO0000001206 03/214
Panasonic FP Series (SIO) Driver

Note:
 When working with XBTGT1000 Series or XBTGT1005, HMIGTO1310,
HMISTO, HMISTU Series target machines, do not add the loopback connection
between RS(RTS) and CS(CTS) on the target machine.

EIO0000001206 03/214 23
Panasonic FP Series (SIO) Driver

Diagram 3 - RS-485 (4-wire)


To connect the target machine and the PLC, use the recommended cables and
accessories in combination with the target pin specification in Target Machine Serial
Interface.

Target Machine Cable / Adaptor Comments

iPC or XBTGTW Series


(COM1/COM2/COM3/ COM4),
XBTGK Series (COM1), XBTGH
Series (COM1), XBTGC2000 Series a Connection Diagram
or higher (COM1), XBTGT2000
Series or higher (COM1), or
HMIGTU Series
Cable length:
XBTGK Series (COM2), 1200m (4000 ft) max.
XBTGT2000 Series or higher
(COM2),
XBTGT1000 Series (COM1),
b Connection Diagram
XBTGT1005 Series (COM1),
HMIGTO1310 Series (COM1),
HMISTO Series (COM1), HMISTU
Series (COM1), or HMIG3U Series

DANGER
ELECTRIC SHOCK
Ensure that the ground connection for each component of interconnected
equipment is reliably connected to the same ground potential (within 100 ohms)
prior to connecting the equipment. There is a risk of electric shock when
connecting a PLC cable to a target machine, as the two may be at different
electrical potentials, even if both are separately connected to ground.
Failure to follow these instructions can result in death or serious injury.

WARNING
UNINTENDED EQUIPMENT OPERATION
To reduce electromagnetic interference, use shielded twisted-pair cables. Connect
the cable shields, then connect the cable to a single-point ground on the HMI side.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.

24 EIO0000001206 03/214
Panasonic FP Series (SIO) Driver

Note:
 Connect the “-” terminal and the “E” terminal with a lead wire to make the
termination resistance effective.

a. Connection Diagram
1:1 Connection

1:n Connection

EIO0000001206 03/214 25
Panasonic FP Series (SIO) Driver

b. Connection Diagram
1:1 Connection

1:n Connection

26 EIO0000001206 03/214
Panasonic FP Series (SIO) Driver

Diagram 4 - RS-232C
To connect the target machine and the PLC, use the recommended cables and
accessories in combination with the target pin specification in Target Machine
Serial Interface.

Target Machine Cable / Adaptor Comments

iPC or XBTGTW Series


(COM1/COM2/COM3/ COM4),
XBTGK Series (COM1), XBTGH
Series (COM1), XBTGC2000 Series
or higher (COM1), XBTGT2000
Cable length:
Series or higher (COM1), Connection Diagram
15m (50 ft) max.
XBTGT1000 Series (COM1),
XBTGT1005 Series (COM1),
HMISTO Series (COM1), HMISTU
Series (COM1), HMIGTO Series
(COM1), or HMIGTU Series (COM2)

Connection Diagram
Target Machine Shield
Signal Signal
RD SD
SD RD
ER +
DR -
SG SG
RS
CS
FG

EIO0000001206 03/214 27
Panasonic FP Series (SIO) Driver

Diagram 5 - RS-485 (2-wire)


To connect the target machine and the PLC, use the recommended cables and
accessories in combination with the target pin specification in Target Machine Serial
Interface.

Target Machine Cable / Adaptor Comments

iPC or XBTGTW Series


(COM1/COM2/COM3/ COM4), XBTGK
Series (COM1), XBTGH Series
Connection
(COM1), XBTGC2000 Series or higher a
Diagram
(COM1), XBTGT2000 Series or higher
(COM1), HMIGTO Series (COM1), or
HMIGTU Series
Cable length:
1200m (4000 ft)
XBTGK Series (COM2),
max.
XBTGC2000 Series or higher (COM1),
XBTGT2000 Series or higher (COM2),
XBTGT1000 Series (COM1), Connection
b
XBTGT1005Series (COM1), Diagram
HMIGTO1310 Series (COM1), HMISTO
Series (COM1), HMISTU Series
(COM1), or HMIG3U Series

DANGER
ELECTRIC SHOCK
Ensure that the ground connection for each component of interconnected
equipment is reliably connected to the same ground potential (within 100 ohms)
prior to connecting the equipment. There is a risk of electric shock when
connecting a PLC cable to a target machine, as the two may be at different
electrical potentials, even if both are separately connected to ground.
Failure to follow these instructions can result in death or serious injury.

WARNING
UNINTENDED EQUIPMENT OPERATION
To reduce electromagnetic interference, use shielded twisted-pair cables. Connect
the cable shields, then connect the cable to a single-point ground on the HMI side.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.

28 EIO0000001206 03/214
Panasonic FP Series (SIO) Driver

Note:
 Use the dip switch in the communication cassette to set the termination
resistance. Set SW1-1 of the equipment, which terminates the connection, to
ON.

a. Connection Diagram
1:1 Connection

1:n Connection

EIO0000001206 03/214 29
Panasonic FP Series (SIO) Driver

b. Connection Diagram
1:1 Connection

1:n Connection

30 EIO0000001206 03/214
Panasonic FP Series (SIO) Driver

Diagram 6 - RS-232C
To connect the target machine and the PLC, use the recommended cables and
accessories in combination with the target pin specification in Target Machine Serial
Interface.

Target Machine Cable / Adaptor Comments

iPC or XBTGTW Series


(COM1/COM2/COM3/ COM4),
XBTGK Series (COM1), XBTGH Series
(COM1), XBTGC2000 Series or higher
(COM1), XBTGT2000 Series or higher Cable length:
Connection Diagram
(COM1), XBTGT1000 Series (COM1), 15m (50 ft) max.
XBTGT1005 Series (COM1), HMISTO
Series (COM1), HMISTU Series (COM1),
HMIGTO Series (COM1), or HMIGTU
Series (COM2)

Connection Diagram
Target Machine Shield
Signal Signal
RD SD
SD RD
SG SG
ER
DR
RS
CS
FG

Note:
 When working with XBTGT1000 Series or XBTGT1005, HMIGTO1310,
HMISTO, HMISTU Series target machines, do not add the loopback connection
between RS(RTS) and CS(CTS) on the target machine.

EIO0000001206 03/214 31
Panasonic FP Series (SIO) Driver

Diagram 7 - RS-232C
To connect the target machine and the PLC, use the recommended cables and
accessories in combination with the target pin specification in Target Machine Serial
Interface.

Target Machine Cable / Adaptor Comments

iPC or XBTGTW Series


(COM1/COM2/COM3/ COM4),
XBTGK Series (COM1), XBTGC2000
Cable length:
Series or higher (COM1), XBTGH Series Connection Diagram
15m (50 ft) max. *1
(COM1), XBTGT2000 Series or higher
(COM1), HMIGTO Series (COM1), or
HMIGTU Series (COM2)

WARNING
*1 LOSS OF CONTROL
Communication links may be compromised when you exceed the manufacturer’s
recommended maximum cable length 3m (10 ft) for multicommunication units
(AFP2465 in FP2 and FP2SH), that communicate at transmission speeds 115200
bps or greater.
Because excess electromagnetic interference is the result of such a setup, the
system may become unpredictable as it experiences periodic interference and
intermittent loss of control.
When using multicommunication units at a fast transmission speed, make sure the
cable length is less than 3m (10ft).
Failure to follow these instructions can result in death, serious injury, or
equipment damage.

Connection Diagram
Target Machine
Signal Shield 9 Pin Signal
DR 1 FG
RD 2 SD
SD 3 RD
RS 4 RS
ER 5 CS
SG 7 SG
CS 9 ER
FG

32 EIO0000001206 03/214
Panasonic FP Series (SIO) Driver

Diagram 8 - RS-232C
To connect the target machine and the PLC, use the recommended cables and
accessories.

Target Machine Cable / Adaptor Comments

iPC or XBTGTW Series


(COM1/COM2/COM3/ COM4),
XBTGK Series (COM1), XBTGH
Series (COM1), XBTGC2000 Series Connection Cable
or higher (COM1), XBTGT2000 (Matsushita: AFB85853
Series or higher (COM1), HMIGTO (3m/10ft))
Series (excluding HMIGTO1310)
(COM1), or HMIGTU Series
(COM2)

Connection Diagram

EIO0000001206 03/214 33
Panasonic FP Series (SIO) Driver

Diagram 9 - RS-232C
To connect the target machine and the PLC, use the recommended cables and
accessories.

Target Machine Cable / Adaptor Comments

iPC or XBTGTW Series RS232C Cable


(COM1/COM2/COM3/ COM4), (Schneider Electric: XBTZG9731
XBTGK Series (COM1), XBTGH (5m/16ft)),
Series (COM1), XBTGC2000 Series RS422/232C Conversion Adaptor
or higher (COM1), XBTGT2000 (Matsushita: AFP8550), and
Series or higher (COM1), HMIGTO Programming Cable
Series (COM1), or HMIGTU Series (Matsushita: AFP1523 (3m/10ft) or
(COM2) AFP15205 (0.5m/1.6ft))

Connection Diagram

34 EIO0000001206 03/214
Panasonic FP Series (SIO) Driver

Diagram 10 - RS-232C
To connect the target machine and the PLC, use the recommended cables and
accessories.

Target Machine Cable / Adaptor Comments

iPC or XBTGTW Series


RS232C Cable
(COM1/COM2/COM3/ COM4),
(Schneider Electric: XBTZG9731
XBTGK Series (COM1),
(5m/16ft)),
XBTGC2000 Series or higher
RS422/232C Conversion Adaptor
(COM1), XBTGH Series (COM1),
(Matsushita: AFP8550), and
XBTGT2000 Series or higher
Programming Cable (Matsushita:
(COM1), HMIGTO Series (COM1),
AFP5523 (3m/10ft))
or HMIGTU Series (COM2)

Connection Diagram

Diagram 11 - RS-422 (4-wire)


To connect the target machine and the PLC, use the recommended cables and
accessories in combination with the target pin specification in Target Machine Serial
Interface.

Target Machine Cable / Adaptor Comments

iPC or XBTGTW Series


(COM1/COM2/COM3/ COM4),
XBTGK Series (COM1), XBTGH
Series (COM1), XBTGC2000 Series Cable length:
Connection Diagram
or higher (COM1), XBTGT2000 400m (1200 ft) max.
Series or higher (COM1), HMIGTO
Series (COM1), or HMIGTU Series
(COM2)

EIO0000001206 03/214 35
Panasonic FP Series (SIO) Driver

DANGER
ELECTRIC SHOCK
Ensure that the ground connection for each component of interconnected
equipment is reliably connected to the same ground potential (within 100 ohms)
prior to connecting the equipment. There is a risk of electric shock when
connecting a PLC cable to a target machine, as the two may be at different
electrical potentials, even if both are separately connected to ground.
Failure to follow these instructions can result in death or serious injury.

WARNING
UNINTENDED EQUIPMENT OPERATION
To reduce electromagnetic interference, use shielded twisted-pair cables. Connect
the cable shields, then connect the cable to a single-point ground on the HMI side.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.

Connection Diagram

36 EIO0000001206 03/214
Panasonic FP Series (SIO) Driver

Diagram 12 - RS-232C
To connect the target machine and the PLC, use the recommended cables and
accessories in combination with the target pin specification in Target Machine Serial
Interface.

Target Machine Cable / Adaptor Comments

iPC or XBTGTW Series


(COM1/COM2/COM3/ COM4),
XBTGK Series (COM1), XBTGH Series
(COM1), XBTGC2000 Series or higher
(COM1), XBTGT2000 Series or higher Cable length:
Connection Diagram
(COM1), XBTGT1000 Series (COM1), 15m (50 ft) max.
XBTGT1005 Series (COM1), HMISTO
Series (COM1), HMISTU Series
(COM1), HMIGTO Series (COM1), or
HMIGTU Series (COM2)

Connection Diagram
Target Machine Shield
Signal Signal
RD SD
SD RD
SG SG
ER +
DR -
RS
CS
FG

Note:
 When working with XBTGT1000 Series or XBTGT1005, HMIGTO1310,
HMISTO, HMISTU Series target machines, do not add the loopback connection
between RS(RTS) and CS(CTS) on the target machine.

EIO0000001206 03/214 37
Panasonic FP Series (SIO) Driver

Diagram 13 - RS-485 (2-wire)


To connect the target machine and the PLC, use the recommended cables and
accessories in combination with the target pin specification in Target Machine Serial
Interface.

Target Machine Cable / Adaptor Comments

iPC or XBTGTW Series


(COM1/COM2/COM3/ COM4),
XBTGK Series (COM1), XBTGH
Series (COM1), XBTGC2000 Series a Connection Diagram
or higher (COM1), XBTGT2000
Series or higher (COM1), or
HMIGTU Series
Cable length:
XBTGK Series (COM2), 1200m (4000 ft) max.
XBTGT2000 Series or higher
(COM2),
XBTGT1000 Series (COM1),
b Connection Diagram
XBTGT1005 Series (COM1),
HMIGTO1310 Series (COM1),
HMISTO Series (COM1), HMISTU
Series (COM1), or HMIG3U Series

DANGER
ELECTRIC SHOCK
Ensure that the ground connection for each component of interconnected
equipment is reliably connected to the same ground potential (within 100 ohms)
prior to connecting the equipment. There is a risk of electric shock when
connecting a PLC cable to a target machine, as the two may be at different
electrical potentials, even if both are separately connected to ground.
Failure to follow these instructions can result in death or serious injury.

WARNING
UNINTENDED EQUIPMENT OPERATION
To reduce electromagnetic interference, use shielded twisted-pair cables. Connect
the cable shields, then connect the cable to a single-point ground on the HMI side.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.

38 EIO0000001206 03/214
Panasonic FP Series (SIO) Driver

Note:
 Connect the “-” terminal and the “E” terminal with a lead wire to make the
termination resistance effective.

a. Connection Diagram
1:1 Connection

1:n Connection

EIO0000001206 03/214 39
Panasonic FP Series (SIO) Driver

b. Connection Diagram
1:1 Connection

1:n Connection

Diagram 14 - RS-232C
To connect the target machine and the PLC, use the recommended cables and
accessories.

Target Machine Cable / Adaptor Comments

iPC or XBTGTW Series


(COM1/COM2/COM3/ COM4),
XBTGK Series (COM1), XBTGH Series
Connection Cable
(COM1), XBTGC2000 Series or higher
(Matsushita: AFB85853
(COM1), XBTGT2000 Series or higher
(3m/10ft))
(COM1), HMIGTO Series (excluding
HMIGTO1310) (COM1), or HMIGTU
Series (COM2)

Connection Diagram

40 EIO0000001206 03/214
Panasonic FP Series (SIO) Driver

Supported Device Addresses

Overview

WARNING
UNINTENDED EQUIPMENT OPERATION
Read and understand the instructions in this section to ensure data is properly
transferred. If you do not follow these instructions, incorrect data could be written
to the PLC and the target machine.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.

The following table lists the device address ranges you can enter from the Device
Address Keypad. For actual device address ranges supported by the PLC, refer to
the corresponding PLC manual.

*1
Device Bit Address Word Address 16 bits 32 bits
*2 *3 *4
External input relay X0000-X999F W X000-WX999
*3 *4
External output relay Y0000-Y999F W Y000-WY999
*3
Internal relay R0000-R899F W R000-WR899*4
*3
Link relay L0000-L999F W L000-WL999*4
Special internal relay*2 R9000-R999F*3 W R900-WR999*4
*2* 5
Timer (Contact) T0000-T9999 —
*5
Counter (Contact) C0000-C9999 —
*8 *8
Timer/Counter L/H L/H
— SV0000-SV9999
*5
(Set value)
Timer/Counter
— EV0000-EV9999
(Elapsed value)*5
*6 *1*3
Data register DT000000-DT89999F DT00000-DT89999
*1*3
Link register LD00000-LD9999F LD0000-LD9999
*1*3
File register FL000000-FL99999F FL00000-FL99999
Special data register*7 DT900000-DT99999F *1*3 DT90000-DT99999

*1 Read-modify-write. When you write to one of these bit addresses, the target
machine reads the entire word address, sets the defined bit, then returns the new
value to the PLC. If the ladder program writes data to this word address during
the bit read/write process, the resulting data may be incorrect.
*2 Read only.
*3 You can define a bit address by defining the bit position using a hexadecimal
value at the end of a word address.
*4 Relay (bit) devices can only be used in Discrete or Integer data type variables.
*5 When using Timer and Counter devices with FP-M CPUs, set up each device
range in the system register.

EIO0000001206 03/214 41
Panasonic FP Series (SIO) Driver

*6 The following CPU types use word address DT09000 and higher as the Special
data register: FP0 (C10/C14/C16/C32/SL1), FP1, FP-e, FP-M, and FP3.
*7 This device is available for the following CPU types: FP0(T32C), FP¶ð, FP2,
FP2SH, and FP10SH.
*8 16-bit and 32-bit data, High and Low, refer to data as defined in the following
examples.

42 EIO0000001206 03/214
Panasonic FP Series (SIO) Driver

Consecutive Equipment Addresses

Overview
The following table lists the maximum number of consecutive addresses that can be
read by each PLC. Refer to this table when using block transfers.
Note:
 To speed up data communication, use consecutive equipment addresses on
the same panel screen.
 The following situations increase the number of times that the equipment is
read, and reduces the data communication speed between the target machine
and the PLC:
 when the number of consecutive addresses exceeds the maximum
 when an address is designated for division
 when different device types are used

Maximum Consecutive
Device Addresses Gap span
Long Short
External input relay (X, W X)
External output relay (Y,W Y)
Internal relay (R,W R)
Link relay (L,WL)
Special internal relay (R,WR)
Timer (Contact) (T)
Counter (Contact) (C)
Timer/Counter 507 words 24 words 15 words
(Set value) (SV)
Timer/Counter
(Elapsed value) (EV)
Data register (DT)
Link register (LD)
File register (FL)
Special data register (DT)

EIO0000001206 03/214 43
Panasonic FP Series (SIO) Driver

Environment Setup

Overview

WARNING
UNINTENDED EQUIPMENT OPERATION
Read and understand the instructions in this section to ensure data is properly
transferred. If you do not follow these instructions, incorrect data could be written
to the PLC and the target machine.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.

The following table lists the recommended communication settings for the
Panasonic FP Series (SIO) Driver.
For details, see Driver Configuration, and Equipment Configuration.

Target Machine Settings PLC Settings


Serial RS-422 (4-Wire)
RS-232C
Interface RS-485 (2-Wire) --
Flow Control DTR(ER)/CTS None
Transmission
19200 bps Baud Rate 19200 bps
Speed
Retry Count 2 --
Driver Parity Bit Odd Parity Odd
Stop Bit 1 bits Stop Bit 1
Data Length 8 bits Char. Bit 8 bits
Rcv Timeout 10 sec --
TX Wait Time 0 msec --
No.412 Computer
--
Comm. Mode Link
Equipment Unit No. 1 Unit No. 1

44 EIO0000001206 03/214
Panasonic FP Series (SIO) Driver

I/O Manager Configuration

Overview
The driver and equipment, which enable communication between the target
machine and the PLC, depends on the PLC type.
Note:
 For information on how to display the [New Driver] dialog box, see the Vijeo
Designer Help.

Screen example of I/O Manager Configuration

EIO0000001206 03/214 45
Panasonic FP Series (SIO) Driver

Driver Configuration

Overview

WARNING
UNINTENDED EQUIPMENT OPERATION
Read and understand the instructions in this section to ensure data is properly
transferred. If you do not follow these instructions, incorrect data could be written
to the PLC and the target machine.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.

To configure the communication settings of the serial driver in the target machine,
use the [Driver Configuration] dialog box. Make sure the settings match those of the
PLC.

For an overview of the driver and device settings, see Environment Setup.
Note:
 For information on how to display the [Driver Configuration] dialog box, see the
Vijeo Designer Help.

Screen example of Driver Configuration

46 EIO0000001206 03/214
Panasonic FP Series (SIO) Driver

Screen Description

Area Description
Manufacturer Displays the name of the PLC manufacturer.
Driver Displays the type of serial connection used to connect the target
machine to the PLC. This property is read-only.
COM Port Defines which COM port to use on the target machine, for connecting to
the PLC.
Serial Interface Defines the serial connection: RS-232C, RS-485 (2-wire) or RS-422 (4-
wire).
For details about the supported connections, see Magelis HMIGTU.
Flow Control Defines the signals that control the data flow.
Transmission Sets the communication speed in bits per second. This setting must
Speed match the PLC baud rate.
Retry Count Defines the number of times the driver tries to send or receive data when
an error has been detected.
Parity Bit Sets either a parity bit [Even or Odd] for use in detecting communication
errors, or [None] at all.
Stop Bit Defines the stop bit: 1, 1.5, or 2 bits.
Data Length Defines the length of each unit of data: 7 bit or 8 bit.
Rcv. Timeout Defines the length of time the target machine waits for a response before
it outputs a timeout error or sends another communication.
TX Wait Time Defines the number of milliseconds that the target machine waits, after
receiving a communication packet, before sending a response.

EIO0000001206 03/214 47
Panasonic FP Series (SIO) Driver

Equipment Configuration

Overview

WARNING
UNINTENDED EQUIPMENT OPERATION
Read and understand the instructions in this section to ensure data is properly
transferred. If you do not follow these instructions, incorrect data could be written
to the PLC and the target machine.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.

To set up details about the communication process between the target machine and
the PLC, use the [Equipment Configuration] dialog box.

For an overview of the driver and equipment settings, see Environment Setup.
Note:
 For information on how to display the [Equipment Configuration] dialog box, see
the Vijeo Designer Help.

Screen example of Equipment Configuration

48 EIO0000001206 03/214
Panasonic FP Series (SIO) Driver

Screen Description

Area Description
Unit No. Enter a value (1-99) to identify the PLC unit.
Frame Length Select either long or short to specify frame length.
Enable Monitor Select to use Monitor Registration with the PLC in order to increase
Registration communication efficiency.
Double Word word The default value is Low word first.
order To define the transmit order for 16-bit words:
 least significant = byte n
 most significant = byte n + 1
(Check that the connected equipment uses the same format.)
To define the transmit order for 32-bit words:
 least significant = word n
 most significant = word n + 1
(Check that the connected equipment uses the same format.)
If High word first is selected, the most significant word and the least
significant word are inverted. For example, to be consistent with
Premium PLC format, use the default value Low word first.
ASCII Display The default value is High byte first.
Byte order Inside PLCs, a STRING is usually an array of words for which every
word contains two characters (one character per byte). For example,
the HELLO! string representation is the following:

 If Low byte first option is selected, the string displayed on the target
machine screen is: HELLO!.
 If High byte first option is selected, the string displayed on the
target machine screen is: EHLL!O.

Note:
 Not all FP Series PLCs support Frame Length and Enable Monitor Registration.
For details, refer to the PLC manual.

EIO0000001206 03/214 49
Panasonic FP Series (SIO) Driver

Device Address Configuration

Overview

WARNING
UNINTENDED EQUIPMENT OPERATION
Read and understand the instructions in this section to ensure data is properly
transferred. If you do not follow these instructions, incorrect data could be written
to the PLC and the target machine.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.

To set up a PLC variable in the Variable List, use the Device Address Keypad from
the variable properties.

See Supported Device Addresses.


Note:
 For information on how to display the Device Address Keypad, see the Vijeo
Designer Help.

Screen example of Device Address Keypad

50 EIO0000001206 03/214
Panasonic FP Series (SIO) Driver

Screen Description

Area Description
Device Lists the PLC’s discrete and word device types.
Address Enter the device address for the PLC variable. The keypad ensures
that you enter the correct format for bit and word devices.

EIO0000001206 03/214 51
Panasonic FP Series (SIO) Driver

52 EIO0000001206 03/214

You might also like