HVAC Design For Healthcare Facilities: Course No: M06-011 Credit: 6 PDH
HVAC Design For Healthcare Facilities: Course No: M06-011 Credit: 6 PDH
HVAC Design For Healthcare Facilities: Course No: M06-011 Credit: 6 PDH
Facilities
A. Bhatia
P: (877) 322-5800
F: (877) 322-4774
[email protected]
SECTION #1
HVAC design for health care facilities is all about providing a safer environment for
patients and staff. The basic difference between air conditioning for healthcare facility
and that of other building types stem from:
1. The need to restrict air movement in and between the various departments (no cross
movement).
2. The specific requirements for ventilation and filtration to dilute and reduce
contamination in the form of odor, airborne micro organisms and viruses, and
hazardous chemical and radioactive substances. Ventilation effectiveness is very
important to maintain appropriate indoor air quality.
3. The different temperature and humidity requirements for various areas and the
accurate control of environmental conditions.
These requirements demand very high quantities of outside air along with significant
treatment of this ventilation air, including cooling, dehumidifying, reheating, humidifying
and filtration.
Infection Control
Infections, which may result from activities and procedures taking place within the
facility, are a cause for great concern. Three main routes responsible for infections are
contact, droplet, and airborne transmission, which are quite affected by room design and
construction factors.
Contact Transmission
a) Direct-contact transmission involves direct body to body contact for the transfer of
micro-organisms from an infected person to a susceptible host.
Droplet Transmission
Airborne Transmission
Airborne transmission occurs when either airborne droplet nuclei or dust particles
disseminate infectious agents.
a) Droplet nuclei - The high velocity with which coughing and sneezing expel droplets
from the respiratory tract results in large numbers of bacteria or viruses entering the
air in smaller droplets. These droplets rapidly evaporate in the air leaving a residue
of typically 5 µm or smaller in size. These droplet nuclei settle so slowly that they
remain airborne in occupied spaces and circulate on air currents until mechanically
removed by the ventilation system. Control of environmental factors (such as special
air handling and ventilation) is necessary to prevent nosocomial airborne
transmission of microorganisms.
ISOLATION ROOMS
The infected patient can contaminate the environment. A single room with appropriate
air handling and ventilation is particularly important to prevent direct or indirect contact
transmission and also for reducing the risk of airborne transmission of microorganisms
from a source patient to susceptible patients and other persons in hospitals. This is often
termed “Isolation Room” in medical terminology.
There are two types of isolation rooms: 1) airborne infection isolation (AII) rooms and 2)
protective environment (PE) rooms.
1. Airborne infection isolation (AII) refers to the isolation of patients infected with
organisms spread via airborne droplet nuclei <5 µm in diameter. These include
patients suffering form measles, chicken pox and tuberculosis. Other areas include:
the emergency department, intensive care units (adult, paediatric, newborn) and
procedure areas such as bronchoscopy suites or sputum induction rooms.
2. Protective environment (PE) is a specialized area for patients who have undergone
allogeneic hematopoietic stem cell transplant (HSCT). The patients whose immune
mechanisms are deficient because of immunologic disorders (e.g., human
immunodeficiency virus [HIV] infection or congenital immune deficiency syndrome),
chronic diseases (e.g., diabetes, cancer, chemotherapy, emphysema, or cardiac
failure), or immunosuppressive therapy (e.g., radiation, organ transplant, cytotoxic
chemotherapy, anti-rejection medication, or steroids) are also placed in protective
environment.
The differentiating factor between “AII” and “PE” rooms is the pressure relationships.
• The protective environments (PE) are set at POSITIVE air pressure relative to
adjoining spaces. These areas require frequent air exchanges (>12 per hour) and
require all supply air passing through high efficiency particulate air (HEPA) filters.
Both these areas require inline monitoring to ensure that they remain under set
pressure. Doors to the rooms should be self-closing, and the walls, windows, ceiling,
floor, and penetrations well sealed.
An airborne infectious isolation room is constructed to minimize the migration of air from
an isolation room to other areas of health care facilities. The risk of being infected
through the airborne route is a function of particle concentration. The chance of a
particle that is carrying an organism falling into an open wound increases with particle
concentration. By reducing the concentration we reduce the chance of infection and,
hence, the number of patients infected.
Four main factors affect the local concentration around a person in a room:
1. Firstly, the concentration of particles would tend to increase with rate of production of
particles in the room.
2. Secondly, the proportion of supply and exhaust air quantity in relation to the size of
the room.
3. Thirdly, the level of filtration of the supplied air will affect the ability of the ventilation
system to dilute the room air particle concentration and
4. Fourthly, air turbulence and air movement in the room can transport particles so the
method of air distribution will affect local concentrations.
The last three of these are attributes of the ventilation system that can be engineered to
limit the effect of the first. Recommendations for engineering controls to contain or
prevent the spread of airborne contaminants center on:
1. General ventilation
GENERAL VENTILATION
The most effective means of controlling contaminants, odor and indoor air pollution is
through ventilation, which requires simultaneous control of number of conditions:
1. Air change rates
Ventilation supply rates for health care facilities require large expenditure of fresh air to
dilute and remove the contaminants generated in the space. The ventilation rates for
healthcare facilities is expresses as air changes air per hour (ACH), which is a measure
of how quickly the air in an interior space is replaced by outside (or conditioned) air. For
example, if the amount of air that enters and exits in one hour equals the total volume of
the space, the space is said to undergo one air change per hour. Air flow rate is
measured in appropriate units such as cubic feet per minute (CFM) and is given by
In this equation,
Q is the volume flow rate of air being calculated, and ACH is the number of air changes
per hour
1) Calculate the room volume to be ventilated Width x Length x Height = ft3 (cubic feet).
2) Calculate the air volume requirement by multiplying the room volume by the air
change rate per hour = ft3/h.
Studies carried out be AIA, indicate that just one air-change with fresh air can remove
63% of suspended particles from the room air. If a ventilation system can perform 10 air
changes per hour (ACH), it takes 14 minutes to remove 90% of airborne contaminants in
a room and 28 minutes to remove 99%. Thus increased number of fresh air changes per
hour is effective for cleaning airborne contaminants. However, the higher air change rate
(>20 ACH) may cause turbulence and the cost for ventilation itself will be too high.
Therefore, a recommended compromise of 12 ACH is proposed which should be
achievable when the filters have reached their maximum pressure drop. Higher ACR
also equates to higher energy use.
The selection of 12 air changes per hour is largely a matter of convention. Ventilation
rates are voluntary unless a state or local government specifies a standard in healthcare
licensing requirements. These standards typically apply to only the design of a facility,
rather than its operation. Based on the scientific knowledge and professional judgment
reflected in the AIA guidelines, ASHRAE and the American National Standards Institute
(ANSI) have developed design recommendations for ventilation and pressure
relationships for various patient-care areas. Healthcare facilities without specific
ventilation standards should follow ANSI/ASHRAE Standard 62, Ventilation for
Acceptable Indoor Air Quality or otherwise in the absence of any specified supply air
change/hour following guidelines may be used:
Building room pressure gradient is achieved by controlling the quality and quantity of
intake and exhaust air, maintaining differential air pressures between adjacent areas,
and designing patterns of airflow for particular clinical purposes.
CLASS N – NEGATIVE PRESSURE ISOLATION ROOMS
The basic principle of pressurization for microbial contaminant control is to ensure that
air flows from less contaminated to more contaminated areas. Air in an open Class N
room, for example, should flow from corridors INTO the isolation room to prevent the
spread of airborne contaminants from the isolation room to other areas. The purpose of
this design is to eliminate the spread of infectious contaminants and pathogens into the
surrounding environment via the airborne route.
Class N is applicable to all infection isolation rooms where the patients known to or
suspected to have infections are placed.
The schematic above shows HVAC air flow arrangement for class N rooms. An
anteroom designed to provide an “air-lock” (no mix of air) between the infectious patient
and the common space is placed adjacent to the patient room. The air would flow from
the ante room to the isolation room. Pressure control is maintained by modulating the
main supply and exhaust dampers based on a signal from a pressure transducer located
inside the isolation room.
1. Ensure that the airborne infectious isolation rooms are designed to maintain negative
pressure.
2. Maintain continuous negative air pressure no less than (2.5 Pa [0.01 inch water
gauge]) in relation to the air pressure in the corridor. This is accomplished via a
separate exhaust system sized to remove at least 15% more air than that of the
supply system.
3. Monitor air pressure periodically, preferably daily, with audible manometers or smoke
tubes at the door (for existing AII rooms), or with a permanently installed visual
monitoring mechanism.
4. Provide ventilation to ensure >12 ACH for renovated rooms and new rooms, and >6
ACH for existing AII rooms, when supply or exhaust air filters are at their maximum
pressure drop.
5. The recommended air filtration for the class N, airborne infectious isolation rooms is
MERV 14 rating air filters (90% dust spot test filters) on the supply side and HEPA
(99.97% @ 0.3µm DOP) on the exhaust side.
6. Recirculation of exhausted air is discouraged, from class N rooms. The exhaust air
should be directed to outside, away from air-intakes and populated areas. However,
where recirculation may be deemed acceptable in some circumstances, HEPA filters
(99.97% @ 0.3µm DOP) capable of removing airborne contaminants on the supply
side must be incorporated.
7. The disposal of effluents should not create a hazard to persons outside or the staff
maintaining these systems. Where supplemental engineering controls for air cleaning
are indicated from a risk assessment of the “AII” area, also install Ultraviolet
Germicidal Irradiation (UVGI) units in the exhaust air ducts of the HVAC system to
supplement HEPA filtration. For example in TB clinics, the air is often HEPA filtered
and sometimes given UVGI exposure before exhausting to the outside, though the
reasons for this are primarily because of litigation concerns and not based on any
known realities.
8. Consider UVGI fixtures on or near the ceiling to irradiate upper room air. Note that
UVGI, may be used to augment HEPA filters, but cannot be used in place of HEPA
filters, as their effectiveness on airstreams is limited.
9. The supply air should be located such that clean air is first passed over the
staff/other occupants and then to the patient. Air distribution should reduce the staff’s
exposure to potential airborne droplet nuclei from infectious patients, accounting for
the positions of the staff and the patient, and the procedures undertaken in the
isolation room.
10. Insider patient room, the supply air should be from the ceiling diffuser located at the
perimeter near to the entry and the exhaust air should be drawn at lower levels
approximately 6 inches above the floor in the room.
11. Exhaust air ducts should be independent of the building’s common exhaust air
system to reduce the risk of contamination from back draught.
12. Locate the exhaust fan at a point in the duct system that will ensure the duct is under
negative pressure throughout its run within the building.
13. The makeup air intakes should be located so that no contaminated air from nearby
exhaust stacks or any sources of air contaminants is drawn into the makeup air
system.
14. Ensure supply air ducts are independent of the building’s common supply air system.
If sharing of supply ducts with other isolation rooms is unavoidable, provide the ducts
with terminal HEPA filters (or other failsafe back draught prevention system). Install a
high efficiency bag filter as a pre-filter to protect the HEPA filter.
15. Design the supply air and exhaust systems to be of a constant volume system.
Variable air volume (VAV) systems are NOT recommended.
17. Ensure that rooms are well-sealed for better maintenance of pressure gradients that
will also eventually reduce load on the air handling plant. Ensure air tightness by
• Maintain plasterboard ceilings that are smooth and free of fissures, open joints,
and crevices
• Sealing all penetrations on the walls above and below the ceiling
18. Install self-closing devices on all ‘AII’ room exit doors considering the direction of
door swing in relation to room pressure.
19. Provide a staff hand-wash basin in the anteroom and include personal respiratory
protection for persons entering these rooms and for staff who lack immunity to
airborne viral diseases (e.g., measles or varicella zoster virus [VZV] infection).
20. Do not use a room with a through-the-wall ventilation unit unless it can be
demonstrated that all required ‘AII’ engineering controls are met.
21. Maintain backup ventilation equipment (e.g. portable units for fans or filters) for
emergency provision of ventilation requirements for AII rooms, and take immediate
steps to restore the fixed ventilation system.
In public areas of a health care facility such as an emergency room, reception and
waiting areas, persons with undiagnosed active infection can come in contact with and
infect others prior to examination and treatments. The likelihood of airborne
contaminants leaving these rooms is reduced by keeping these rooms under NEGATIVE
pressure, relative to surrounding areas. Air is exhausted from these rooms either directly
to the outside or through high efficiency particulate air (HEPA) filters.
Class P - positive pressure isolation rooms are set at positive pressure relative to
ambient pressure, meaning that air flow must be from the “cleaner” area towards the
adjoining space (through doors or other openings). This is achieved by the HVAC
system providing more air into the “cleaner” space than is mechanically removed from
that same space. Class P is applicable to all protective environments housing severely
neutropenic and immuno-suppressed patients.
Use AIA guidelines as minimum standards where state or local regulations are not in
place for design and construction of ventilation systems in new or renovated health-care
facilities. Recommended elements include:
1. Ensure that the protective environment room is designed to maintain positive
pressure.
2. Maintain positive room air pressure (>2.5 Pa [0.01-inch water gauge]) in relation to
the corridor. Ideally it should be >8 Pa (0.03 inch-water gauge).
3. Ventilate the room to maintain > 12 ACH or 145 liters per second per patient
(whichever results in the greatest air quantity), when the supply air filter is at the
maximum pressure drop.
4. Class P rooms can be either 100% fresh air or can use recirculated air usually a
60/40 mix of outdoor air/recirculated air. As rule of thumb, air pressure should be
maintained positive with respect to any adjoining rooms by supplying 10 to 15%
excess air.
5. The recommended air filtration for the class P, protective rooms is HEPA (99.97% @
0.3µm DOP) on the supply side and NO filtration is needed on the exhaust side. The
HEPA filter could be centrally located at the air handling unit or point-to-use HEPA
filters may be used. A terminal HEPA filter at the point of use is recommended.
6. UVGI systems are sometimes used in conjunction with HEPA filters. When ultraviolet
germicidal irradiation (UVGI) is used as a supplemental engineering control, install
fixtures 1) on the wall near the ceiling or suspended from the ceiling as an upper air
unit; 2) in the air-return duct of an ‘AII’ area; or 3) in designated enclosed areas or
booths for sputum induction.
7. The supply air should be located such that clean air is first flows across the patient
bed and exits from the opposite side of the room. Air distribution should reduce the
patient’s exposure to potential airborne droplet nuclei from occupants.
10. Ensure that rooms are well-sealed for better maintenance of pressure gradients that
will also eventually reduce load on the air handling plant. Ensure air tightness by
• Properly constructing windows, doors, and intake and exhaust ports
• Maintain plasterboard ceilings that are smooth and free of fissures, open joints,
and crevices
• Sealing all penetrations on the walls above and below the ceiling
11. Maintain airflow patterns and monitor these on a daily basis by using permanently
installed visual means of detecting airflow in new or renovated construction, or by
using other visual methods (e.g., flutter strips or smoke tubes) in existing PE units.
Plan for automatic documentation of the monitored results.
12. Install self-closing devices on all room exit doors in PE rooms. All emergency exits
(e.g., fire escapes, emergency doors) in PE wards should be kept closed (except
during emergencies) and equipped with alarms.
13. Do not use laminar air flow systems in newly constructed PE rooms.
15. Install an ensuite bathroom along with a staff hand-wash basin in the anteroom.
The room pressure requirement for operating rooms is similar to PE rooms with following
exceptions:
2. Filter all recirculated and fresh air through the appropriate filters, providing 90%
efficiency (dust-spot testing) at a minimum.
3. In rooms not engineered for horizontal laminar airflow, introduce air at the ceiling and
exhaust air near the floor.
4. Do not use ultraviolet (UV) lights to prevent surgical-site infections.
Special Challenges
A unique challenge occurs when a patient needs both the positive and negative room
isolation. For example when there is an immune compromised patient who also has a
communicable infectious disease such as TB. Studies indicate that approximately 15%
of HIV patients also suffer from TB, and this presents a unique design problem. This
patient needs to be in a protective environment for his own health but also needs to be
isolated to protect others from his communicable disease.
Caution: Avoid designing systems to switch between positive and negative pressure.
ANTE ROOMS
An ante room is always recommended for both positive and negative isolation rooms for
three main reasons:
There are three possible airflow / control designs which differ in pressure relationship of
anteroom to the isolation room and the corridor.
Design # 1:
Anteroom negative to both isolation room and corridor
This design has two advantages: There is no need to supply air to and delicately
balance the anteroom, and if the anteroom becomes contaminated there is still a
pressure buffer between the anteroom and the corridor. The disadvantage is: Since the
anteroom is negative with respect to the corridor, the chance of contaminating the
anteroom is higher.
Design # 2:
This design also has two advantages. There is no need to exhaust air from and
delicately balance the anteroom, and since the anteroom is positive with respect to the
corridor, the change of contaminating the anteroom is lower. The disadvantage is: If the
anteroom does become contaminated, it is likely that the isolation room will become
contaminated as well. So, this design is not recommended.
Design # 3:
This design incorporates the best features of the other two designs. The advantages are:
Since the anteroom is positive with respect to the corridor, the chance of contaminating
the anteroom is lower, and if the anteroom becomes contaminated, there is still a
pressure buffer between the anteroom and the isolation room. The disadvantage is
increased cost and complexity of the controls and balancing.
Dynamic pressure differential monitoring must take place in order to ensure the room is
at appropriate pressure. The two common methods of differential pressure control are 1)
flow tracking measurement & control and 2) differential pressure measurement & control.
In flow tracking system, the exhaust and supply flow rates “from” and “to” space are
measured and controlled to produce a desired infiltration or exfiltration.
In differential pressure system, the actual differential pressure between the isolation
room and the corridor is taken by measuring the velocity of air induced through a hole in
the envelope between the isolation room and corridor created by the differential
pressure. However, the magnitude of this differential pressure being too small, it is
affected by other factors like building stack effects, elevator effects, wind etc., and as
such it is difficult to measure. There are accurate ultra-low-differential pressure
transducers available, but their cost is very high. Neither OSHA, nor CDC requires the
use of room differential pressure monitors but both agencies accept their use, provided
that they measure down to 0.001” wg.
Codes require that as minimum, air pressure relationships from the isolation room to the
adjacent anteroom or corridor should be indicated with a mechanical gauge. Air pressure
drop across filters should be indicated with a mechanical gauge or manometer.
Proper room pressurization can be checked using a smoke stick or smoldering match at
doors held open approximately 1/4 inch to visually see which direction air is moving.
Care must be taken when checking this to make sure that the door is not moving during
the test since a door swinging can move more air than the design ventilation differential
in the room. It should be an obvious rule of thumb that if you can't detect air movement
via this method then no significant, practical pressurization of the room exists.
DIRECTIONAL CONTROL OF AIRFLOW
The design principle of pressurization control is to exhaust air from those areas which
have the greatest contamination potential, and allow air to be staged, or cascaded, from
progressively cleaner areas. Figure below illustrates the basic principle of cascading
airflows from clean areas to relatively contaminated areas.
In the above diagram, a facility is depicted which has offices and isolation rooms,
separated by corridors and other areas (storage rooms, labs). Air is supplied to the
areas, usually offices, maintained at the greatest positive pressure (marked with a ‘++’),
and exhausted from the areas maintained at the greatest negative pressure (marked
with a '- -'). Transfer air (exfiltration/infiltration) is identified with blue arrows. The
unlabeled rooms in the diagram above could be laboratories, which usually have
independently operating exhaust hoods or separate ventilation systems. If not, they
would be generally designed as double negative pressurization areas.
AIR DISTRIBUTION
In conventional air conditioning, filtered air is typically distributed from the ceiling, with
return air is collected from the ceiling on the other side of the room.
In special situations in health care facility (e.g., operating rooms, delivery rooms,
catheterization laboratories, angiography rooms, HEPA-filtered rooms for immune-
suppressed patients) the direction of air movement needs to be controlled. The air is
introduced from ceiling registers on the perimeter and is returned or exhausted through
registers located at least 6 inches above the floor. This arrangement provides a
downward movement of clean air through the breathing and working zones to the
contaminated floor area for exhaust.
Figure below shows the introduction of low velocity air near the ceiling at the entrance of
the room, flowing past the patient, and exhausted or returned close to the floor at the
head of the patient bed. An airflow pattern is thus established which helps to move
microorganisms from the point of patient’s expulsion to the exhaust / return air terminal
to prevent health care workers or visitors from inhaling the bacteria.
The diffuser should be placed away from patient bed, preferably near the point where a
health care worker or visitor would enter the room.
Do not place diffuser immediately over the patient bed as it would result in
uncomfortable drafts projected directly at the patient.
Laminar Flow
Laminar flow systems use perforated ventilation grills across the entire ceiling or side
wall at air flow rates significantly greater than normal to force a steady constant stream
of air across the entire room, similar to a smooth steady flow out of an open water faucet
versus one that splashes as the water comes out of the faucet.
Laminar flow distribution requires a very high volume of air flow and is designed for an
air velocity of 90 + 20 ft/min. This unidirectional approach optimizes airflow and
minimizes air turbulence and ensures that any contamination that is generated within the
area is quickly and effectively removed. Laminar airflow systems are often used in
operating rooms to help reduce the risk for healthcare-associated airborne infections.
Note: The data that demonstrate a bona-fide application and support of laminar airflow in
PE rooms is lacking. Given the high cost of installation and operation, the value of
laminar airflow is questionable and shall be ascertained through life cycle analysis.
AIR FILTRATION
All of the air that is drawn into an air handling system is "contaminated" to some degree.
It is commonly accepted that airborne particles (solid particles, liquids, fumes, smoke, or
bacteria) that are larger than 5 microns in size tend to settle quickly out of the air onto
horizontal surfaces. Airborne particles that are less than 5 microns in size (especially
those less than 2 microns in size) tend to settle slowly out of the air and remain
suspended (airborne) for larger period of time.
Concerns over hospital-acquired infections have propelled filtration solutions into the
forefront as a primary tool for infection control. There are five methods of filtration.
1. Straining - Particles in the air are larger than the openings between the filter fibers.
This technique is suitable for gross removal of large particles. Filtration efficiency is
low.
2. Impingement – Particles collide with filter fibers and remain attached to the filter. The
fibers may be coated with adhesive. Filtration efficiency is low.
3. Interception – Particles enter into the filter and become entrapped and attached to
the filter fibers. Filtration efficiency is medium.
4. Diffusion – Small particles, moving in erratic motion, collide with filter fibers and
remain attached. Filtration efficiency is high.
All public areas of health care facilities are required to have two banks of filters — a 30%
(ASHRAE 52.1) prefilter and 90% final filter. Provided that the final filter is properly
installed and maintained and provided that there is little or no bypass around the filter,
the combined efficiency of two bank filters is nearly 100% in removing particles of 1µm -
5 µm in diameter. This filtration system is adequate for most patient-care areas in
ambulatory care facilities, and the operating room environment.
A common metric for filter performance is the minimum efficiency reporting value
(MERV), a rating derived from a test method developed by ASHRAE. The MERV rating
indicates a filter’s ability to capture particles between 0.3 and 10.0 microns in diameter.
A higher MERV value translates to better filtration, so a MERV-13 filter works better than
a MERV-8 filter. In health care facilities a final filter of MERV-14 is satisfactory.
HEPA filters have a minimum initial efficiency of 99.97% for removing particles 0.3
microns in size. This is a critical point as these filters are being used to remove mold and
bacteria, typically 1 to 5 microns in size when airborne, as well as viral particles which
are submicron in size (as a reference, Aspergillus spores are 2.5 - 3 µm in diameter).
Each HEPA filter is individually tested at the factory in order to confirm their
conformance to this standard. They may also be field-tested in order to confirm their
ongoing adherence to efficiency requirements.
2. On the return air of the infectious isolation rooms when the air is recirculated within
the space in order to increase ACH while reducing the total exhaust requirements.
Ideally the infectious isolation rooms should be designed for 100% fresh air and
exhaust.
3. On the exhaust of the infectious isolation rooms and local exhaust hoods when
exhausting air to the outside is not practical or when the exhaust is located near a
potential air intake. (Refer note below)
4. When the HVAC system configuration dictates recirculation of air from the isolation
room to other parts of the facility.
Note - The guidelines do not mandate the exhaust air from an infectious isolation room
to be HEPA filtered before being discharged outdoors unless there is any chance that
the exhaust air could reenter the system. However, there is always a possibility of
exhaust re-entry under certain wind and climatological conditions. It is, therefore,
preferable to filter all exhaust air.
HEPA Maintenance
Efficiency of the filtration system is dependent on the density of the filters that may
create a pressure drop unless compensated by stronger and more efficient fans so that
flow of air is maintained. When HEPA filters are used in infection control applications it is
imperative to have a meticulous maintenance program in place. For optimal
performance, it is critical that:
1. HEPA filters to be installed in equipment which seals the filter in place in order to
prevent contaminated air from bypassing the filter.
2. HEPA filters to be tested on site when they are first installed and every six months
thereafter to confirm that they are operating at their design efficiency.
HEPA filters are a costly budget item. In order to extend the life of a HEPA filter and
reduce ongoing replacement costs, it is strongly recommended to provide a roughing
prefilter prior to the HEPA. Studies indicate that a low-efficiency prefilter may extend the
life of a HEPA filter by 25%, while adding higher efficiency intermediate filters such as a
MERV 14 (95% by ASHRAE 52.1 dust spot test) filter can extend the life of the HEPA
filter by as much as 900%. This concept, called "progressive filtration," allows HEPA
filters in special care areas to be used for 10 years or more. HEPA filter efficiency is
monitored with the dioctylphthalate (DOP) particle test using particles that are 0.3 µm in
diameter.
Caution: HEPA filters replacements require bag-in / bag-out procedures to minimize risk
of exposure of the maintenance personnel to the infectious material.
Portable, industrial grade HEPA units are recommended for use during construction and
renovation. These industrial grade portable HEPA filters are capable of filtration rates in
the range of 300--800 CFM and are used to:
The effectiveness of the portable unit for particle removal depends on: 1) the
configuration of the room; 2) the furniture and persons in the room; 3) the placement of
the units relative to the contents and layout of the room; and 4) the location of the supply
and exhaust registers or grilles.
If portable, industrial-grade units are used, they should be capable of recirculating all or
nearly all of the room air through the HEPA filter, and the unit should be designed to
achieve the equivalent of >12 air changes per hour (ACH). (An average room has
approximately 1600 cu-ft of airspace).
Portable HEPA units are useful engineering controls when the central HVAC system is
undergoing repairs, but these units do not satisfy fresh air requirements. Portable HEPA
filter units placed in construction zones can be used later in patient-care areas, provided
all internal and external surfaces are cleaned, and the filter replaced or its performance
verified by appropriate particle testing.
Odor Control
There are several areas within a health care facility where odors or gaseous
contaminants are common. Some of these contaminants may only be nuisance or
comfort related, while others may represent a threat to personal health.
Fumes and smells can be removed from air by chemical processes such as “gas
sorption” which control compounds that behave as gases rather than as particles (e.g.,
gaseous contaminants such as formaldehyde, sulfur dioxide, ozone, and oxides of
nitrogen). Gas sorption involves one or more of the following processes with the sorption
material (e.g., activated carbon, activated alumina or chemically treated active clays):
Gas sorption units are available in variety of chemical treated clays, each performing
differently for different gases. A prefilter is recommended upstream of the gas sorption
unit to ensure that filter pores are not blocked with particulates. There are currently no
standards for rating the performance of gaseous air cleaners, making the design and
evaluation of such systems problematic.
Air Filtration to Protect HVAC Equipment
Accumulation of dust and moisture within HVAC systems increases the risk of spread of
healthcare-associated environmental fungi and bacteria. The components of air handling
units such as cooling coil, filters, and ductwork can be the ideal environments for
breeding bacteria, fungus and mold. It not properly maintained, these will become
reservoirs for infection causing molds. Common practices for protecting HVAC coils
include locating the filter upstream of the coil and having a filter rating of at least MERV
8. The filters should fit snugly into the holding frames; be of rigid, moisture resistant
construction; and be constructed from materials that will not support microbial growth.
Care should be taken to ensure that no air bypasses around the filters. Bypass can be
reduced by gasketing the filters to seal them in place and by installing filter blanks in
spaces were the filter track does not contain filters.
Most commercially available UV lamps used for germicidal purposes are low-pressure
mercury vapor lamps that emit radiant energy predominantly at a wave-length of 253.7
nm. Two systems of UVGI have been used in healthcare settings -- duct irradiation and
upper-room air irradiation. In duct irradiation systems, UV lamps are placed inside ducts
whereas in upper-room air irradiation, UV lamps are either suspended from the ceiling or
mounted on the wall.
Bacterial inactivation studies using BCG mycobacteria and Serratia marcescens have
estimated the effect of UVGI as equivalent to 10 ACH - 39 ACH. Another study,
however, suggests that UVGI may result in fewer equivalent ACH in the patient-care
zone, especially if the mixing of air between zones is insufficient.
Because the clinical effectiveness of UV systems may vary, UVGI is not recommended
for air management prior to air recirculation from airborne isolation rooms and also in
operating rooms.
Regular maintenance of UVGI systems is crucial and usually consists of keeping the
bulbs free of dust and replacing old bulbs as necessary. Understand the safety issues
associated with the use of UVGI systems from suppliers and manufacturer’s.
Local exhaust ventilation is designed to capture toxic gases, vapors, dusts, fumes and
mists near its source, before the contaminant has a chance to disperse into the
workplace air. A proper design of an exhaust ventilation system is necessary for
effective removal of airborne contaminants that would otherwise pollute the work
environment resulting in health hazards.
A local exhaust ventilation system usually consists of number of separate exhaust hoods
applied to several different operations and connected by system of branch and main
ducts to a central air cleaning device and exhaust fan and discharge stack to the
outside. A local exhaust system is most effective for laboratories and special procedure
rooms. It has following benefits:
Laboratories and special procedure rooms that are known to contain toxic and
hazardous contaminants are typically designed under negative pressure to prevent
these gases from spreading throughout the facility. Examples of these areas include
cytology labs where xylene and toluene may be part of the process, autopsy exhaust,
ethylene oxide (ETO) sterilizer exhaust, X-ray film processing areas, infectious materials
in waste (including regulated medical waste), steam sterilizers, areas using high-level
disinfectants or morgues, where formalin may be used. These chemicals are both
irritants and carcinogenic. Such areas typically employ 100% pass-through ventilation
where no air is recirculated within the facility.
Conditions do occur, however, where it is possible for these chemicals to be re-entrained
into the facility due to the close proximity of exhaust to potential air intakes. In
applications like this, gas phase or multi-stage filtration equipment may also be
considered. In a morgue where formalin is used, we must not only be concerned with
gas phase filters to deal with the formalin, but we must also be concerned with the
removal of potentially infectious airborne bacteria. There have been documented cases
of transmission of m. tuberculosis from viable TB bacteria which may become airborne
during the autopsy procedure. In situations where air from a morgue must be filtered at
the exhaust point, it is important to utilize a system with both HEPA and gas phase
filtration.
Kitchen Ventilation
Extract systems from kitchen equipment (cooking stove, ovens, dishwasher etc) should
be separate from any other and the extracted air should not be recirculated. The
following design guidelines should be noted:
2) Hood velocities (not less than 50 fpm over face area between hood and cooking
surface)
3) Extend hood beyond cook surface 0.4 x distance between hood and cooking surface
Filters
2) Recommend filter quantity: Typically 2 CFM exhaust for each sq. in. of filter area
maximum
The ventilation of locker rooms, toilets, and shower spaces is important in removing odor
and humidity. Legal minimum requirements should be consulted when designing these
facilities. In toilets recommended rates of exhaust ventilation are 10 ACH or 2cfm /sq-ft
whichever is higher. Supply air may be introduced through door grilles and/or undercuts.
Do not transfer more than 4.2 Cu M/Min (150 CFM) of air per door undercut.
Public toilets and congregate baths do require ducted supply air up to 8.5 air changes
per hour maximum. The balance air should be drawn from the corridors to maintain
negative pressure and to ensure exhaust of 10 air changes per hour.
Two essential components of conditioned air are temperature and humidity. After outside
air passes through a low - or medium-efficiency filter, the air undergoes conditioning for
temperature and humidity control.
Temperature Control
Control of temperature includes the operation of both heating and cooling systems to
maintain temperature setpoints in the different areas of the building. Cool temperatures
(68°F - 73°F) are usually associated with operating rooms, clean workrooms, and
endoscopies suites. A warmer temperature (75°F) is needed in areas requiring greater
degrees of patient comfort. Most other zones use a temperature range of 70°F - 75°F.
Temperatures outside of these ranges may be needed on limited occasions in limited
areas depending on individual circumstances during patient care.
The more common dual-duct system consists of parallel ducts, one with a cold air
stream and the other providing a hot air stream. A mixing box in each room or group of
rooms mixes the two air streams to achieve the desired temperature. Temperature
standards are given as either a single temperature or a range, depending on the specific
healthcare zone.
Humidity Control
Efforts to limit excess humidity and moisture in the infrastructure and on air stream
surfaces in the HVAC system can minimize the proliferation and dispersion of fungal
spores and waterborne bacteria throughout the indoor air. Control of humidity includes
the operation of both humidification and dehumidification systems to maintain a
minimum and maximum humidity level in the facility.
Four measures of humidity are used to quantify different physical properties of the
mixture of water vapor and air. These are relative humidity, specific humidity, dew point
and vapor pressure. The most common of these is "relative humidity," which is the ratio
of the amount of water vapor in the air to the amount of water vapor air can hold at that
temperature. At 100% relative humidity, the air is saturated. For most areas within
healthcare facilities, the designated comfort range is 30% - 60% relative humidity.
Relative humidity levels >60%, in addition to being perceived as uncomfortable, promote
fungal growth.
Dehumidification
If the moisture is not controlled sufficiently by the HVAC system, this could spell disaster
with regard to trying to keep significant mold growth out of the facility. Dehumidification is
typically accomplished by cooling air below the dew point.
For a facility only trying to maintain the space at 75° DB and 50% RH (i.e., 55° dew-
point), the coils must still be capable of delivering air with a dew-point less than 55° in
order to absorb the space latent gain. Where humidity control is solely by cooling,
consider cooling coils with higher rows (more surface area, although this will increase
the air pressure drop and the fan power) and restrict the face velocity to 400 feet per
minute or lower.
Humidification
Recommended elements:
c. Locate all duct takeoffs sufficiently downstream from the humidifier so that
moisture is completely absorbed.
Serious consideration must then be given to the controllability of the systems. As is far
too often the case, most HVAC systems are installed with the primary function of either
cooling or heating, with the humidity control simply as a secondary function of the
system. This is evidenced by the fact that most HVAC systems are installed only with a
thermostat installed to operate the system. Including humidity control devices in the
controls package for the HVAC system is almost non-existent. Logic says that you can
not control something which is not measured. Always install a humidistat to measure the
humidity levels. Many design issues can lead to a lack of moisture control within the
hospital that can potentially lead to mold problems and infections.
REFERENCE STANDARDS
Designing HVAC systems for hospitals is a specialist skill and it requires knowledge of
specific regulations.
The American Institute of Architects (AIA) has published guidelines for the design,
construction, and renovation of healthcare facilities that include indoor air-quality
standards (e.g., ventilation rates, temperature levels, humidity levels, pressure
relationships, minimum air changes per hour [ACH]) specific to each zone or area in
healthcare facilities (e.g., operating rooms, laboratories, diagnostic areas, patient-care
areas, support departments). These guidelines represent a consensus document among
authorities having jurisdiction (AHJ), governmental regulatory agencies (i.e., Department
of Health and Human Services [DHHS], Occupational Safety and Health Administration
[OSHA]), healthcare professionals, professional organizations (e.g., American Society of
Heating, Refrigeration, and Air-conditioning Engineers [ASHRAE], American Society of
Healthcare Engineers [ASHE]), and accrediting organizations (i.e., Joint Commission on
Accreditation of Healthcare Organizations [JCAHO]).
Many state or local agencies that license healthcare facilities have either incorporated or
adopted by reference these guidelines into their state standards. The JCAHO, through
its surveys, assures that facilities are in compliance with the space and square footage
requirements of this standard for new construction.
There are a number of issues that must be resolved before the proper HVAC system can
be designed, whether it is intended for the isolation rooms, surgical suite, the patient
rooms, or the administration offices.
Initially, the proper ambient design conditions must be selected. Too often, only the peak
cooling design conditions are considered for sizing the capacity requirements of the
system. These ambient conditions are listed in the ASHRAE Handbook – Fundamentals
as the dry-bulb temperatures with mean coincident wet-bulb temperatures, representing
conditions on hot, mostly sunny days. These conditions are used in sizing cooling
equipment such as chillers or package equipment for cooling control. In some climates,
this might be satisfactory; however, in geographic areas known for higher humidity
levels, considering only this cooling condition might not be sufficient. Extreme dew-point
temperature conditions may occur on days with moderate dry-bulb temperatures,
resulting in high relative humidity’s and peak absolute moisture loads from the weather.
These values from tables found in the Fundamentals Handbook are useful for humidity
control applications, such as desiccant cooling and dehumidification, cooling-based
dehumidification, and fresh air ventilation systems. These values can also be used as a
checkpoint when analyzing the behavior of cooling systems at part load conditions,
particularly when such systems are used for humidity control as a byproduct of
temperature control.
For the critical areas such as isolation rooms, intensive care units and operating rooms,
critical diagnostic and examination rooms, consider only the centralized HVAC system
encompassing “all air systems”.
In all air systems, the outdoor air enters the system via a low - efficiency or "roughing"
filters, which removes the large particulate matter. It is mixed with the return air and is
made to pass the fine filters, which removes small size particles and many
microorganisms. The air is than conditioned and delivered to each zone of the building.
After the conditioned air is distributed to the designated space, it is withdrawn through a
return duct system and delivered back to the HVAC unit. A portion of this "return air" is
exhausted to the outside while the remainder is mixed with outdoor air and filtered for
dilution and removal of contaminants. In some critical areas the air again filtered through
HEPA filters located downstream the cooling/heating coil or at the terminal end of the
duct.
All air systems can be classified as single-zone, multi-zone, dual-duct and reheat
systems.
Single-zone systems: Single-zone systems serve just one zone having unique
requirement of temperature, humidity and pressure. This is the simplest of all air
systems. For this type of system to work properly, the load must be uniform all through
the space, or else there may be a large temperature variation.
Multi-zone systems: Multi-zone systems are used to serve a small number of zones with
just one central air handling unit. The air handling unit for multi-zone systems is made up
of heating and cooling coils in parallel to get a hot deck and a cold deck. For the lowest
energy use, hot and cold deck temperatures are, as a rule, automatically changed to
meet the maximum zone heating (hot deck) and cooling (cold deck) needs. Zone
thermostats control mixing dampers to give each zone the right supply temperature.
Dual-duct systems: Dual-duct systems are much like multi-zone systems, but instead of
mixing the hot and cold air at the air handling unit, the hot and cold air are both brought
by ducts to each zone where they are then mixed to meet the needs of the zone. It is
common for dual-duct systems to use high-pressure air distribution systems with the
pressure reduced in the mixing box at each zone.
Reheat systems: Reheat systems supply cool air from a central air handler as required
to meet the maximum cooling load in each zone. Each zone has a heater in its duct that
reheats the supply air as needed to maintain space temperatures. Reheat systems are
quite energy-inefficient and have been prohibited by various codes. Energy may though
be saved through the recovery of the refrigeration system's rejected heat and the use of
this heat to reheat the air.
Caution
Air from infectious patient rooms is normally NOT recirculated and is exhausted directly
to the outside via a HEPA filter.
Use of terminal heating and cooling units such as fan coil units is NOT acceptable in
isolation rooms, surgical suites and other critical areas where maintaining the room
pressure relationships is important.
Type of HVAC System - Normal Patient Care Rooms, Administrative and Non-
critical Areas
For the patient bedrooms and other non-critical areas, any one of the following HVAC
systems can be used.
2. Terminal heating and cooling units, such as fan coil units or radiant ceiling panels.
The amount of outdoor air and how it is supplied to the occupied spaces would depend
upon the type of HVAC system used. When the fan coil units or radiant ceiling panels
are used, a central ventilation unit supplies conditioned air to the spaces. With this
arrangement, the source of outdoor air being external to the principle cooling and
heating equipment, it is possible to ensure the predetermined amount of outdoor air
distribution to all the spaces.
CHILLERS
The chiller is the heart of an air conditioning plant. In a typical water-cooled chiller plant,
it accounts for as much as 60% of the total HVAC power requirement. It is even higher
(at 80%) in an air-cooled chiller plant. Chillers are specified by their design capacity in
tons (1 ton = 12,000 Btu/hr) and their design efficiency in kW/ton.
Today chillers are available to operate at as low as 0.470 kW per ton. Given that annual
energy costs for a chiller may amount to as much as one-third of their purchase price,
even a modest improvement in efficiency can yield substantial energy savings and
attractive paybacks. ASHRAE Standard 90.1 establishes minimum energy efficiency
levels.
Four types of electrical chillers dominate the market:
1. Reciprocating compressors
• In a hermetic unit, the motor and compressor are enclosed in a common housing,
which is sealed. Because the components are not accessible for repair, the entire
compressor unit must be replaced if it fails.
• In the semi-hermetic unit the motor is also part of the unit, however it is not
sealed so it is serviceable.
• In a direct drive unit the motor and compressor are separated by a flexible
coupling. These types of units utilize older technology and are not commonly
used today.
2. Scroll compressors
Inside the scroll compressor, two spiral-shaped members fit together forming
crescent shaped gas pockets. One member remains stationary while the other orbits
relative to first. This movement draws gas into the outer pocket and seals off an open
passage. As the spiral movement continues, gas is forced toward the center of the
scroll design, creating a nearly continuous compression cycle.
3. Screw compressors
The screw compressor’s suction, compression and discharge all occur in one
direction. Suction gas is pressed into one grooved rotor by the second similar rotor.
The screw-like rotor motion continues toward the end of the compressor’s working
space. In this way, refrigerant volume steadily reduces or compresses until it reaches
the stationary end of the compressor. These chillers are common in high capacity
ranges up to 1000 tons and are available in both air-cooled and water cooled
options.
4. Centrifugal compressors
Centrifugal compressors are used in chillers with typical capacities of 150 to 2,000
tons. Centrifugal chillers are the most efficient of the large-capacity chillers but are
ONLY used in water cooled configurations.
The most effective chiller is primarily a function of chiller size and in general the following
guidelines apply:
Chillers operate more efficiently when they are loaded close to their full rating than when
they are only lightly loaded. It is imperative to determine which portion of the total load
required 24 hours operations.
Recommended Elements:
• Peak load demand determines the overall capacity of the system. The total chiller
capacity in tons of refrigeration shall match or exceed the peak building load or in
other words, shall be the sum of the total cooling requirements of all connected
air handling units.
• Part load requirements determine the number and size of chillers required.
Cooling load profile will help to determine the type of chiller to use and if single or
multiple chillers should be installed. Multiple chiller installations allow facilities
professionals to stage their operation to match building loads while keeping the
chillers operating at energy efficient loading.
• Adopt standby or (N+ 1) strategy. For health care facilities continuity of supply is
critical, therefore the provision of cooling cannot be relied on a single chiller. One
back up unit would be required.
An air handling systems is a means of providing conditioned air to the space in order to
maintain the environmental requirements. Often termed as the heart and lungs of the
health care facility, these must be selected and sized properly for its very important task.
And that task is to control the environment to promote the healthiest conditions possible
for the patients and other occupants.
Air must be delivered at design volume to maintain pressure balances. The air handling
equipment must be sized in accordance with the following guidelines:
1. Load Calculations: Heat gain calculations must be done in accordance with the
procedure outlined in the latest ASHRAE Handbook of Fundamentals. The
calculations performed either manually or with a computer program.
2. The calculated supply air shall be the sum of all individual peak room air quantities
without any diversity.
3. Safety Margin: A safety factor of 5 percent shall be applied to the calculated room air
quantity to allow for any future increase in the room internal load.
4. The adjusted supply air shall be, thus, 5 percent in excess of the calculated supply
air.
5. Air leakage: The air leakage through the supply air distribution ductwork shall be
computed on the basis of the method described in the SMACNA Air Duct Leakage
Test Manual. The maximum leakage amount shall not exceed 4 percent of the
adjusted supply air.
6. Supply Air Fan Capacity: The capacity of the supply air fan shall be calculated per
the following example:
8. Air Distribution:
• The main supply air ductwork shall be sized to deliver the supply air fan capacity,
21,840 CFM as calculated in the example above.
• The individual room air distribution system including supply, return, exhaust air
ductwork, air terminal units, reheat coils and air outlets/inlets shall be sized and
selected on the basis of the adjusted supply air volume, 21,000 CFM.
• The fan and motor selection shall be based on the supply air fan capacity and
static pressure adjusted, as necessary, for the altitude, temperature, fan inlet and
discharge conditions, and the AMCA 201 System Effect Factors. The fan
selection shall be made within a stable range of operation at an optimum static
efficiency. The fan motor W (BHP), required at the operating point on the fan
curves, shall be increased by 10 percent for drive losses and field conditions to
determine the fan motor horsepower. The fan motor shall be selected within the
rated nameplate capacity and without relying upon NEMA Standard Service
Factor.
System/Motor Voltages
2400 -- 2300
4160 -- 4000
The air handling equipment requires special attention to disinfection, and cleanliness;
clusters of infections due to Aspergillus spp., Pseudomonas aeruginosa, Staphylococcus
aureus, and Acinetobacter spp. have been linked to poorly maintained and/or
malfunctioning air conditioning systems.
The failure or malfunction of any component of the HVAC system may subject patients
and staff to discomfort and exposure to airborne contaminants. AIA guidelines prohibit
United States hospitals and surgical centers from shutting down their HVAC systems for
purposes other than required maintenance, filter changes, and construction. Often the
routine maintenance and troubleshooting functions need to be addressed without
necessarily disabling the units.
The following key elements need to be addressed when procuring these units.
1. Specify the cabinet construction with stainless steel or galvanized steel sheets
polyester-coated both from the inside and outside. Ensure cabinet framework is
constructed from aluminum profiles for increased rigidity.
2. Specify a layer of non-flammable mineral wool between the inside and outside
sheets for the cabinet casing.
3. Specify oblique floors for the air handling unit, tubs for the cooling units and drip
channels made of stainless steel construction. Specify vacuum seal P-trap on the
drain pan.
4. Specify all edges and offsets to be filled with fungicidal silicon certified for hygienic
applications in health care facilities which precludes formation of the microbe
expansion centers.
5. Specify provision for pressure gauges on the filter section casing of AHU along with
audible alarm. This is to confirm that NO air stream will elude filtration, if openings
are present because of filter damage or poor fit.
6. Specify access and inspection openings with the lighting elements installed in covers
of the sections for humidification, filtration, heat exchangers and fans.
8. Specify a drum fan with an inspection flap and an outflow pipe which enables the
drum cleaning OR a centrifugal and axial-flow fan with an open rotor.
10. Specify multistage filtration with minimum of MERV 14 final filtration installed in
plastic frames and mounted in frameworks made of resistant materials. The filters
shall be provided with differential pressure gauge and pollution level indicators.
12. Specify cable glands providing connection of motors and the lighting system,
ensuring the appropriate tightness and cleanliness class.
Exhaust Fans
Exhaust fan must be selected to produce the rate of airflow required by the exhaust
system. The flow must be developed against the total system resistance, including
pressure losses through the air distribution network including air cleaning devices. A fan
of proper size and operating speed should than be selected from the ratings published
by the fan manufacturer.
The exhaust fan should be located downstream of the air cleaning filter and as close to
the discharge point as possible. The preferred location for an exhaust fan is outdoors,
normally on the roof. A straight duct section of at least 6 equivalent duct diameters and 3
equivalent duct diameters should be used when connecting to the fan inlet and outlet
respectively before any bend or fittings. When this is impractical due to space
constraints, corrective devices such as turning vanes or flow dividers should be used, or
the associated loss must be accounted for.
Fan selection should consider long term contaminant effects on the fan and the fan
wheel. Where severe conditions of abrasion or corrosion are present, special lining or
metals could be used in fan construction. Safe means should be provided to allow the
wheel of an exhaust fan to be examined without removing the connecting ducts.
A flexible sleeve or band should be incorporated onto the fan inlet and outlet ducts to
minimize vibration of the ductwork.
Recommended Elements:
1. In an effort to save installation dollars, the return duct is often deleted from the plans
and the interstitial space between the suspended ceiling and the roof assembly, or
the floor assembly above, is used as a return plenum. Open return air path directly
over the false ceiling is NOT recommended for isolation rooms or elsewhere in
health care facilities.
2. Any air leakage through duct joints will disrupt the pressure balance raising
possibility of infectious material entraining into the air supply. The supply and return
air ducts should be properly sealed and insulated during construction. On the return
side of the equipment, leaky ducts will draw in far more moisture than the cooling
coils were designed to remove. The result is a higher than designed and desired
humidity level in the space.
3. Supply and exhaust systems should be designed as failsafe (for example, using
duplex fans) to prevent contamination of any area within the facility in the event of
fan failure.
4. The ductwork of a negative pressure isolation room must not communicate with the
ductwork of the rest of the hospital. Ductwork should be designed to reduce the
possibility of cross contamination in the event of fan failure. This can be
accomplished by ducting each negative pressure isolation room separately from the
air-handling unit.
5. The exhaust fan should be located at a point in the duct system that will ensure that
the entire duct is under negative pressure within the building.
6. Position the exhaust discharge duct to prevent the contamination of intake air. In
acute cases, the discharge plume may need to be modeled to prevent entrainment.
7. Round duct should be used for the construction of the exhaust system. Rectangular
ducts, if used, should be as square as possible.
8. All branches should enter the main duct at gradual expansions at an angle not
exceeding 45 and preferably 30 or less. Connections should be to the top or side of
the main and directly opposite each other. Elbows and bends should be at a
minimum of 2 gauges heavier than straight length ducts of equal diameter and have
a centerline radius of at least 2 and preferably 2.5 times the duct diameter. The
smaller branches should enter the main near the high suction end, closer to the fan
inlet.
9. Exhaust stacks should be vertical and terminated at a point where height or air
velocity would preclude re-entry of the contaminated air into the work environment.
10. Duct velocities should be sufficient to prevent the settling of dry aerosols. The
recommended minimum duct velocity for most areas of the healthcare facility is 2500
fpm.
11. Ductwork should be located so that it is readily accessible for inspection, cleaning
and repairs; Keep provisions for routine test ports for appropriate airflow and
pressure balance.
Insulation
The dew-point temperature of the air surrounding the cooler ducts and pipes could easily
be higher than the surface temperature of the ducts and pipes. Condensation will occur
when this happens. If the ducts and piping happen to be in the ceiling space, the
condensate can drip onto a surface that is loaded with mold food (ceiling tiles, dry wall
boards, insulation, plywood, etc.) and all of the necessary elements are there for mold
growth.
Care must be taken to ensure that the supply air ducts, the chilled water lines (supply
and return) and the refrigerant lines are well insulated with non-flammable mineral wool.
Noise Criteria
1. The noise level should be restricted to 35 NC level for all patient rooms, operating
rooms (major or minor), diagnostic rooms, audio suites, examination rooms,
conference rooms, large offices, lobbies and waiting areas.
2. The noise level should be restricted to 40 NC level for all small private offices,
nursing stations, auditoriums, treatment areas, corridors, pharmacy and general work
rooms.
3. The noise level should be restricted to 45 NC level for all laboratories, Dining, Food
Service/Serving , Therapeutic Pools
4. The noise level should be restricted to 50 NC level for all gymnasiums, recreation
rooms, laundries and HVAC plant rooms.
Duct systems should be designed in accordance with the general rules outlined in the
latest ASHRAE Guide and Data Books, SMACNA Manuals and Design Guide Section of
the Associated Air Balance Council Manual.
1. Supply duct system, with total external static pressure 2 inches – w.g and larger,
shall be designed for a maximum duct velocity of 2500 fpm for duct mains and a
maximum static pressure of 0.25 inch-w.g. per 100 ft duct length. Static pressure
loss and regain shall be considered in calculating the duct sizes. Size supply branch
ducts for a maximum duct velocity of 1500 fpm.
2. All other duct systems such as return and exhaust, including branch ducts, shall be
designed for a maximum velocity of 1500 fpm for the duct mains and a maximum
static pressure of 0.10 inch- w.g. per 100 ft duct length, with the minimum duct area
of 48 sq in ( or 8 in x 6 in) size.
All piping required for HVAC systems shall be sized based on the following criteria:
Water losses, pressure loss, etc., for sizing piping shall be based on "Cameron Hydraulic
Data": With C = 100 for open (cooling tower) systems and C = 150 for closed systems.
For closed systems, the maximum friction loss shall be 4 ft of water per 100 ft of pipe
with maximum velocity of 14 fps for systems in occupied areas, and up to 8 fps for mains
and large branches. For open systems, the maximum friction loss shall be 4 ft of water
per 100 ft of pipe and a maximum velocity of 8 to 10 fps. The minimum pipe size shall be
3/4-inch.
The effect that equipment noise or vibration might have on areas adjacent to, above, and
below equipment shall be considered. Design shall comply with specified room sound
ratings.
Make provisions for all necessary stairs, cat walks, platforms, steps over roof mounted
piping and ducts, etc., that will be required for access, operation and maintenance.
Access to roofs by portable ladder is not acceptable.
Air handling units and similar equipment shall be housed in a mechanical equipment
room or in a mechanical penthouse enclosure. Penthouse type of fully weatherized roof
top units constructed in standard sections of modules would be acceptable in lieu of the
mechanical equipment rooms or mechanical penthouses. These units shall provide
excess sections for walk through servicing, maintenance, and shall ensure that the
piping connections and electrical conduits are fully enclosed within the units.
Cooling Towers
Select and locate cooling towers to avoid problems with aesthetics, noise, vibrations, air
recirculation or drift. Include a noise analysis of the proposed cooling tower relative to
adjacent occupancies and consider alternative cooling tower selections, if necessary, to
meet noise level of 60 dB(A) at 15 m (50 feet) which may be lowered for critical
locations. Consider provisions for security and maintenance lights and receptacles.
Provide a permanent service platform and ladders for access to cooling tower basin
access doors.
Water treatment of cooling tower water is very important because the cooling tower
operation is associated with Legionella disease and lower respiratory tract infections.
Effective methods for disinfecting the hospital water supply include chlorination, thermal
eradication, UV light, ozone treatment and metal (copper –silver) ionization system.
b. Locate outdoor air intakes >6 ft above ground or >3 ft above roof level… (The air
intake shall be located as high as practical or not less than stated).
c. Locate exhaust outlets from contaminated areas above roof level to minimize
recirculation of exhausted air.
2. Operating Room system air intakes shall be at least 30 ft above the ground.
3. Laboratory and Research exhaust shall be terminated at the highest point of the
building (NFPA 99, 5-3.3.4).
4. Outside air intake shall not be near hot exhaust discharging horizontally or deflected
down, nor be near plumbing vents, animal room exhausts, generator exhausts,
loading docks, automobile entrances, driveways, passenger drop-offs, cooling
towers, incinerator and boiler stacks.
5. Louvers shall be designed for a maximum velocity of 750 fpm through the free area
of 35 percent. Drainable louvers may be designed for a maximum velocity of 1000
fpm and 45 percent free area.
6. Ensure that the intakes are kept free from bird droppings, especially those from
pigeons.
SECTION # 4
Loss of Power
The loss of normal power at a medical facility whether the result of a natural disaster
(thunderstorm, earthquake, hurricane….) or system failure (due to any eventuality such
as short circuiting, inappropriate maintenance, maintenance crew digging in the wrong
place, a squirrel/rat causing electrical disruptions…) , is a situation that an HVAC
engineer must anticipate.
The National Electric Code (NEC) and National Fire Protection Association Standard for
Healthcare Facilities (NFPA 99) require certain HVAC systems to be connected to the
emergency power system in a hospital.
Generator-related equipment
• Fuel pumps
• Kitchen hoods
Heating equipment to maintain inside design temperature where the outside design
temperature is lower than +20°F
• Recovery areas
• Nurseries
Supply, return, and exhaust air systems serving the following areas
• Clinical laboratories
• Refrigeration system and controls for food storage and clinical laboratory
refrigerators and freezers.
The HVAC systems and equipment listed above are considered to be the minimum
requirements in an acute care hospital. Additional state and local requirements as
addressed by authority having jurisdiction (AHJ) will add to the minimum requirements.
These requirements should be understood prior to the start of any design.
HVAC systems have a significant impact on the emergency power system of a hospital.
The connected load of the HVAC equipment can range from 3 to 6 W/sq ft in an acute
care facility. This is generally 50% to 60% of the entire load on the emergency generator
plant. With the typical cost of an emergency generator plant ranging from $800 to
$1,200/kW of generator capacity, the cost of adding 100 hp of motor load could be as
high as $90,000.
It goes without saying that care must be taken when determining what HVAC equipment
is required to be connected to the emergency power system. Establishing an appropriate
balance between the cost of adding equipment to the emergency generator and the risk
of not having HVAC service during a loss of power is a difficult task. Major system
decisions are dependent on an early understanding of these issues. As an example, the
number of air-handling units (AHU) and what departments they will serve can have an
impact on the size of the mechanical rooms, as well as the size of the emergency
generator.
SECTION # 5
ENERGY CONSERVATION
Depending on the climate, between 35% and 60% of the annual energy costs of the
typical healthcare facility are related to the operation of the HVAC systems.
Recommended Elements:
Room Pressurization
The significant airflow requirements and high air changes per hour that are necessary to
maintain sterile and healthy environments are also the major contributor to the significant
energy usage of healthcare facilities. As a result, the HVAC systems not only use higher
fan energy to move the air from the air-handling system, but these also use significant
energy to cool and dehumidify outdoor air to maintain space temperature and humidity
requirements. It is important to build the spaces tight and avoid over pressurization. Let’s
see one example to show the energy loss due to over pressurization.
One-inch water gauge pressure is equivalent to wind velocity of 4005 feet per minute
(~45 miles/hr).
High pressurization will result in higher leakage rates. The amount of expected leakage
can be calculated from the following equation:
= 0.223 x 4005
= 895 fpm
= 0.316 x 4005
= 1265 fpm
Leakage Rate = 2 x 1265 = 2530 CFM [This is 40% increase in leakage rate.]
For the same example above, assume the outside makeup air is at 95°F DB/72°F WB
which needs to be conditioned to 72°F DB/60°F WB. From the psychrometric charts, the
enthalpy difference (heat to be removed to bring outside air to clean room conditions) is
9.5 BTU/lb of air.
This is equivalent to 6.4 TR* [*Note 1 ton of refrigeration (1 TR) is equivalent to heat
removal rate of 12000 BTU’s/hr]
Therefore the client will incur an extra capital cost equivalent to 9- 6.4 = 2.6 TR. Not only
the capital cost, higher pressurization (case-2) will incur recurring higher energy costs of
nearly 4 kWh [@ 1.5 kWh per TR of cooling load], which translates to 35000kWh per
annum on 24/7 operations.
The room pressure should be limited to 0.01 inch-w.g for PE and operating rooms.
Positive pressurization can be maintained only if the sealing integrity of the building is
maintained. The building should be air tight for low air leakage performance.
Uncontrolled leakages areas in the building are door undercuts; pass through, walls,
ceilings and duct joints etc; that should be restricted as far as possible.
Fan power is proportional to the cube of airflow rate or fan speed. The fan laws state:
A reduction in the supply air volume by 10% will result in a power reduction of
approximately 27% [1 – (0.9)3]. Significant energy savings can be achieved by designing
the air handling systems as variable air volume (VAV) tracking systems with variable
frequency drive fan motor. Except in spaces where constant air change rate and/or
critical pressure differential relationship are essential, variable air volume terminal units
with or without reheat coils shall be used.
The VAV system is applicable to all non-critical care spaces such as dining areas, out-
patient administrative offices, maintenance areas, many out-patient therapy areas and
many common areas, which do not have continuous pressurization control requirements.
Caution
VAV system is NOT recommended for critical care spaces where continuous directional
pressurization control is required (either positive or negative) and significant minimum
airflow rates are required constantly irrespective of the occupancy. These include
spaces such as isolation rooms, surgical suites, laboratories or pharmacy areas,
intensive-care units and patient rooms, etc
Although AIA and ASHRAE allow ventilation rates to be reduced to 25% of the occupied
period rates, as long as continuous directional control and space pressurization is
maintained at all times and the full (occupied) ventilation air change rates can be re-
established at any time, VAV is NOT advisable due to safety concerns.
a. Most engineers size air handlers with a “rule of thumb” of 500 fpm. This saves time,
but increases cost of ownership. Pressure drop in a duct or air handler is
approximately proportional to the face velocity squared. Fan power requirement
decreases approximately as the velocity decrease. To reduce the pressure drop,
specify a low face velocity unit in the 250 to 450 fpm range.
c. Size the equipment to avoid efficiency penalties at part load conditions. Often this will
involve unequal unit sizing and/or modular approach.
Fan energy use is directly proportional to the pressure drop that the fan is pushing air
through. Thus, the more restrictive the supply system, the higher the pressure drop, and
the higher the fan energy use. Carefully evaluate the air distribution system. The major
energy savings can accrue from the air distribution. Strategies for lower pressure drop
include:
a. Minimize obstructions to air flow, run straight duct lengths and avoid arbitrary
zigzags. Pressure drop in ductwork is inversely proportional to the fifth power of duct
diameter for e.g. substituting a 16 inch duct for a 12 inch duct reduces pressure drop
by about 75%.
b. Select cooling coils, sound attenuators and filters with low air pressure drop
d. Select high efficiency filters. Higher-performance air filters clean supply air more
efficiently, resulting in a reduction of energy consumption.
Efficient Filtration
Filtration also has a substantial impact on energy efficiency. With static pressure drops
of up to 0.072 pounds per square inch (psi), filters can consume an enormous amount of
fan power. As with other air-handling components, the key to efficient filtration is to
consider the details, especially face velocity (airflow per unit area of filter media). The
efficiency of a filter refers not to energy efficiency, but to how well it removes particles
from the airstream. Pressure drop is the measure that determines how much fan power
is required to move air through the filter, and it varies by the square of the air speed
through it. For typical HVAC-duty filters (30 percent ASHRAE dust-spot efficiency) a
reasonable target pressure drop is 0.0036 psi. Dirty, thick, or poorly designed filters can
have pressure drops as high as 0.072 psi—as much as the entire frictional drag of the
duct system.
Use economizer cycle for free cooling. Air conditioning systems shall be designed to
operate without refrigeration whenever the ambient temperature drops below 48°F.
For all locations where the outdoor winter design temperatures are below –1°C (30°F)
and the winter degree days are in excess of 3000, heat recovery devices, comprising of
either heat recovery wheels, air to air plate heat exchangers or glycol run around loop
heat recovery coils, shall be installed. This applicable to all 100 percent outdoor air
systems and exhaust air systems whenever the capacity is in excess of 3000 CFM and
are of continuous duty.
Caution
Do not provide heat recovery systems in the following special exhausts (where mixing is
a concern):
a. Specify high efficiency components, including high efficiency motors and fans,
chillers and other equipment
Chiller work is proportional to the vapor pressure work of the compressor – this work is
lowered if chilled water temperatures are raised and/or condenser water temperatures
are lowered. The majority of health care chilled water requirements are best served by
medium chilled water temperature at 44 to 52°F chilled water.
Caution
Oftentimes in an effort to conserve energy, the chiller is allowed to operate with a slightly
elevated leaving water temperature (e.g., elevating from 44° to 46°, possibly). While this
will indeed save on the energy bill, and it might be sufficient for keeping the space
temperature under control, it could fail miserably at controlling the moisture within the
space (especially within the operating rooms). If the humidity within the space should
exceed the desired maximum acceptable level (e.g. 55% to 60% RH), then there should
be a humidity sensor and transmitter within the space that could override the
temperature controls and then lower the chilled water temperature in order to keep the
humidity under control.
The cooling can be provided with electric chiller, gas engine driven chiller or alternatively
through vapor absorption machines using natural gas/fuel oil firing or steam. Other
strategies include thermal storage systems using chilled water reservoirs or ice banks.
A carefully thought-out energy strategy that does not rely on any single energy source
for all heating or cooling needs can have many benefits. The ability to switch to the least
expensive fuel to produce chilled water during times of peak demand will lead to lower
utility costs than the competing hospital who has decided to take the lowest first cost
approach to chilled water and steam production. A secondary benefit to the
diversification of energy usage is the ability to produce chilled water for the critical areas
of the hospital with minimal investment when compared to the cost of electrically driven
chillers or direct-expansion equipment connected to the emergency power system.
CONCLUSION
Engineering guidelines for ventilation control for ‘Protective Environment’ and ‘Airborne
Infection Isolation Areas’ are given as follows:
Pressure differentials > 2.5 Pa (0.01 in-water > 2.5 Pa (0.01 in-water
gauge) gauge)
Air changes per hour (ACH) >12 > 12 (for renovation or new
construction)
Filtration efficiency Supply 99.97% @ 0.3µm Supply 90% dust spot test
DOP
Exhaust – 99.97% @
Exhaust – None required 0.3µm DOP
Clean-to-dirty airflow in Away from the patient (high Towards the patient
room risk patient or immune- (airborne disease patient)
suppressed patient)
Notes
Involve infection control professionals with a clinical background from the inception of
the project. This allows for identifying potential infection control issues early and
provides an opportunity to design solutions prospectively. Infection control professionals
set forth the design criteria, policies and procedures for efficient design and regularly
conduct assessment of facilities. They play an important role in educating architects,
engineers, and construction workers about potential infection control risks and
appropriate methods for reducing them. The optimum Indoor Air Quality (IAQ) level is
the responsibility of the architects and mechanical engineers.