Calculation Months .................................... Jan to Dec Zone CFM Sizing ................ Sum of space airflow rates
Sizing Data ................................................ Calculated Space CFM Sizing ............ Individual peak space loads
Total coil load ....................................................... 36.3 Tons Load occurs at .................................................. Jul 1500
Total coil load ..................................................... 435.6 MBH OA DB / WB .................................................. 113.0 / 73.4 °F
Sensible coil load ................................................ 435.6 MBH Entering DB / WB .......................................... 108.0 / 72.1 °F
Coil CFM at Jul 1500 ........................................... 8250 CFM Leaving DB / WB ........................................... 59.0 / 55.6 °F
Max block CFM ................................................... 8250 CFM Coil ADP .................................................................. 57.1 °F
Sum of peak zone CFM ....................................... 8250 CFM Bypass Factor ........................................................ 0.038
Sensible heat ratio .............................................. 1.000 Resulting RH .............................................................. 42 %
ft²/Ton ................................................................... 65.9 Design supply temp. ................................................ 58.0 °F
BTU/(hr-ft²) ......................................................... 182.0 Zone T-stat Check ................................................. 1 of 1 OK
Water flow @ 10.0 °F rise ..................................... N/A Max zone temperature deviation ................................ 0.0 °F
Actual max CFM .................................................. 8250 CFM Fan motor BHP ........................................................ 6.78 BHP
Standard CFM ..................................................... 8238 CFM Fan motor kW .......................................................... 5.38 kW
Actual max CFM/ft² ............................................... 3.45 CFM/ft² Fan static ................................................................. 3.00 in wg
Calculation Months .................................... Jan to Dec Zone CFM Sizing ................ Sum of space airflow rates
Sizing Data ................................................ Calculated Space CFM Sizing ............ Individual peak space loads
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.078 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4739.9 BTU/(hr-CFM)
Site Altitude = 39.0 ft
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.078 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4739.9 BTU/(hr-CFM)
Site Altitude = 39.0 ft
0.012
6 7 0.010
3 45 2 1
8
0.008
0.006
0.004
0.002
0.000
30 40 50 60 70 80 90 100 110
Temperature ( °F )