WIND02 v2-21: Detailed Wind Load Analysis Per ASCE 7-10
WIND02 v2-21: Detailed Wind Load Analysis Per ASCE 7-10
WIND02 v2-21
Detailed Wind Load Analysis per ASCE 7-10
Analysis by: R.M Company Name:
Description:
Condition Gcpi
Max + Max -
Open Buildings 0.00 0.00
Partially Enclosed Buildings 0.55 -0.55
Enclosed Buildings 0.18 -0.18
Enclosed Buildings 0.18 -0.18
WIND02 v2-21
Detailed Wind Load Analysis per ASCE 7-10
6.5.12.2.1 Design Wind Pressure - Buildings of All Heights
Theta
B h
z
L L
WIND02 v2-21
Detailed Wind Load Analysis per ASCE 7-10
Dist from Windward Edge: 15.79 ft to 31.58 ft - Min Cp -0.90 -12.33 -7.63
Dist from Windward Edge: 31.58 ft to 63.16 ft - Min Cp -0.50 -7.89 -3.20
Dist from Windward Edge: > 63.16 ft -0.30 -5.67 -0.98
* Horizontal distance from windward edge
Kh = 2.01*(Ht/zg)^(2/Alpha) = 0.99
Kht = Topographic factor (Fig 6-2) = 1.00
Qh = 0.00256*(V)^2*ImpFac*Kh*Kht*Kd = 13.04
Theta = Angle of Roof = 14.0 Deg