Part CVol 02
Part CVol 02
Part C
Machinery, Electricity, Automation and
Fire Protection
Chapters 1 2 3 4
Chapter 1 MACHINERY
Chapter 2 ELECTRICAL INSTALLATIONS
Chapter 3 AUTOMATION
Chapter 4 FIRE PROTECTION, DETECTION AND EXTINCTION
April 2007
The English wording of these rules take precedence over editions in
other languages.
Unless otherwise specified, these rules apply to ships for which contracts are
signed after July 1st, 2007. The Society may refer to the contents hereof
before July 1st, 2007, as and when deemed necessary or appropriate.
Section 1 General
1 Application 19
1.1 General
1.2 References to other regulations and standards
2 Documentation to be submitted 19
2.1
3 Definitions 19
3.1 General
3.2 Essential services
3.3 Primary essential services
3.4 Secondary essential services
3.5 Safety voltage
3.6 Low-voltage systems
3.7 High-voltage systems
3.8 Basic insulation
3.9 Supplementary insulation
3.10 Double insulation
3.11 Reinforced insulation
3.12 Earthing
3.13 Normal operational and habitable condition
3.14 Emergency condition
3.15 Main source of electrical power
3.16 Dead ship condition
3.17 Main generating station
3.18 Main switchboard
3.19 Emergency switchboard
3.20 Emergency source of electrical power
3.21 Section boards
3.22 Distribution board
3.23 Final sub-circuit
3.24 Hazardous areas
3.25 High fire risk areas
3.26 Certified safe-type equipment
3.27 Environmental categories
7 Electrical protection 40
7.1 General requirements for overcurrent protection
7.2 Short-circuit currents
7.3 Selection of equipment
7.4 Protection against short-circuit
7.5 Continuity of supply and continuity of service
7.6 Protection against overload
7.7 Localisation of overcurrent protection
7.8 Protection of generators
7.9 Protection of circuits
7.10 Protection of motors
7.11 Protection of storage batteries
7.12 Protection of shore power connection
7.13 Protection of measuring instruments, pilot lamps and control circuits
7.14 Protection of transformers
8 System components 44
8.1 General
9 Electrical cables 44
9.1 General
9.2 Choice of insulation
9.3 Choice of protective covering
9.4 Cables in refrigerated spaces
9.5 Cables in areas with a risk of explosion
9.6 Cables in circuits required to be operable under fire condition
9.7 Cables for submerged bilge pumps
9.8 Internal wiring of switchboards and other enclosures for equipment
9.9 Current carrying capacity of cables
9.10 Minimum nominal cross-sectional area of conductors
9.11 Choice of cables
4 Description of test 53
4.1 Technical documentation and visual inspection
4.2 Insulation resistance measurement
4.3 Winding resistance measurement
4.4 Verification of the voltage regulation
4.5 Rated load test and temperature rise measurements
4.6 Overload/ overcurrent test
4.7 Verification of the steady short circuit current
4.8 Overspeed test
4.9 Dielectric strength test
4.10 No load test
4.11 Verification of degree of protection
4.12 Verification of bearings
Section 5 Transformers
1 Constructional and operational requirements 57
1.1 Construction
1.2 Terminals
1.3 Voltage variation, short-circuit conditions and parallel operation
1.4 Electrical insulation and temperature rise
1.5 Insulation tests
2 Testing 58
2.1 General
2.2 Tests on transformers
Section 11 Location
1 General 72
1.1 Location
1.2 Areas with a risk of explosion
2 Main electrical system 72
2.1 Location in relation to the emergency system
2.2 Main switchboard
Section 12 Installation
1 General 76
1.1 Protection against injury or damage caused by electrical equipment
1.2 Protection against damage to electrical equipment
1.3 Accessibility
1.4 Electrical equipment in environmentally controlled spaces
2 Earthing of non-current carrying parts 76
2.1 Parts which are to be earthed
2.2 Methods of earthing
2.3 Earthing connections
2.4 Connection to the ship’s structure
2.5 Earthed distribution systems
2.6 Aluminium superstructures
3 Rotating machines 78
3.1
4 Semiconductor convertors 78
4.1 Semiconductor power convertors
5 Vented type storage batteries 78
5.1 General
5.2 Protection against corrosion
6 Switchgear and controlgear assemblies 78
6.1 Main switchboard
6.2 Emergency switchboard
6.3 Section boards and distribution boards
Section 15 Testing
1 General 95
1.1 Rule application
1.2 Insulation-testing instruments
2 Type approved components 95
2.1
Section 6 Testing
1 General 117
1.1 General
Chapter 2
ELECTRICAL INSTALLATIONS
SECTION 1 GENERAL
SECTION 5 TRANSFORMERS
SECTION 9 CABLES
SECTION 11 LOCATION
SECTION 12 INSTALLATION
SECTION 15 TESTING
SECTION 1 GENERAL
1 Application 3 Definitions
3.6.1 Alternating current systems with rated voltages 3.15 Main source of electrical power
greater than 50 V r.m.s. up to 1000 V r.m.s. inclusive and
direct current systems with a maximum instantaneous value 3.15.1 A source intended to supply electrical power to the
of the voltage under rated operating conditions greater than main switchboard for distribution to all services necessary
50 V up to 1500 V inclusive. for maintaining the ship in normal operational and habitable
condition.
3.7 High-voltage systems
3.16 Dead ship condition
3.7.1 Alternating current systems with rated voltages
greater than 1000 V r.m.s. and direct current systems with a 3.16.1 The condition under which the main propulsion
maximum instantaneous value of the voltage under rated plant, boilers and auxiliaries are not in operation due to the
operating conditions greater than 1500 V. absence of power.
Note 1: Dead ship condition is a condition in which the entire 3.24.2 Hazardous areas are classified in zones based upon
machinery installation, including the power supply, is out of opera- the frequency and the duration of the occurrence of explo-
tion and the auxiliary services such as compressed air, starting cur- sive atmosphere.
rent from batteries etc., for bringing the main propulsion into
operation and for the restoration of the main power supply are not 3.24.3 Hazardous areas for explosive gas atmosphere are
available. classified in the following zones:
• Zone 0: an area in which an explosive gas atmosphere
3.17 Main generating station is present continuously or is present for long periods
• Zone 1: an area in which an explosive gas atmosphere
3.17.1 The space in which the main source of electrical is likely to occur in normal operation
power is situated.
• Zone 2: an area in which an explosive gas atmosphere
is not likely to occur in normal operation and if it does
3.18 Main switchboard occur, is likely to do only infrequently and will exist for
a short period only.
3.18.1 A switchboard which is directly supplied by the
main source of electrical power and is intended to distribute
3.25 High fire risk areas
electrical energy to the ship’s services.
3.25.1 The high fire risk areas are defined as follows:
3.19 Emergency switchboard a) machinery spaces as defined in Ch 4, Sec 1, [3.23]
b) spaces containing fuel treatment equipment and other
3.19.1 A switchboard which in the event of failure of the
highly inflammable substances
main electrical power supply system is directly supplied by
the emergency source of electrical power or the transitional c) galleys and pantries containing cooking appliances
source of emergency and is intended to distribute electrical d) laundry with drying equipment
energy to the emergency services. e) spaces as defined in Ch 4, Sec 5, [1.3.4] b) for ships car-
rying more than 36 passengers, as:
3.20 Emergency source of electrical power • (8) accomodation spaces of greater fire risk
• (12) machinery spaces and main galleys
3.20.1 A source of electrical power, intended to supply the
• (14) other spaces in which flammable liquids are
emergency switchboard in the event of failure of the supply
stowed
from the main source of electrical power.
f) enclosed or semi-enclosed hazardous spaces, in which
certified safe type electric equipment is required.
3.21 Section boards
3.21.1 A switchgear and controlgear assembly which is 3.26 Certified safe-type equipment
supplied by another assembly and arranged for the distribu-
3.26.1 Certified safe-type equipment is electrical equipment
tion of electrical energy to other section boards or distribu-
of a type for which a national or other appropriate authority
tion boards.
has carried out the type verifications and tests necessary to
certify the safety of the equipment with regard to explosion
3.22 Distribution board hazard when used in an explosive gas atmosphere.
3.22.1 A switchgear and controlgear assembly arranged for 3.27 Environmental categories
the distribution of electrical energy to final sub-circuits.
3.27.1 Electrical equipment is classified into environmental
3.23 Final sub-circuit categories according to the temperature range, vibration
levels, and resistance to chemically active substances and
3.23.1 That portion of a wiring system extending beyond to humidity.
the final required overcurrent protective device of a board. The designation of the environmental categories is indi-
cated by the EC Code in Tab 2.
3.24 Hazardous areas The first characteristic numeral indicates the temperature
range in which the electrical equipment operates satisfacto-
3.24.1 Areas in which an explosive atmosphere is or may rily, as specified in Tab 3.
be expected to be present in quantities such as to require The second characteristic numeral indicates the vibration
special precautions for the construction, installation and level in which the electrical equipment operates satisfacto-
use of electrical apparatus. rily, as specified in Tab 4.
Note 1: An explosive gas atmosphere is a mixture with air, under
atmospheric conditions, of flammable substances in the form of 3.27.2 The tests for verifying the additional and supple-
gas, vapour or mist, in which, after ignition, combustion spreads mentary letters and the characteristic numeral of the envi-
throughout the unconsumed mixture. ronmental categories are defined in Ch 3, Sec 6.
Table 2 : EC Code
Code letter First characteristic numeral Second characteristic numeral Additional letter Supplementary letter
EC (numerals 1 to 4) (numerals 1 to 3) (letter S) (1) (letter C) (2)
(1) The additional letter S indicates the resistance to salt mist (exposed decks, masts) of the electrical equipment.
(2) The supplementary letter C indicates the relative humidity up to 80% (air conditioned areas) in which the electrical equipment
operates satisfactorily.
Second Displacement
Frequency range, Acceleration
characteristic Brief description of location amplitude,
in Hz amplitude g
numeral in mm
1 Machinery spaces, command and control stations, from 2,0 to 13,2 1,0 −
accommodation spaces, exposed decks, cargo spaces
from 13,2 to 100 − 0,7
2 Masts from 2,0 to 13,2 3,0 −
from 13,2 to 50 − 2,1
3 On air compressors, on diesel engines and similar from 2,0 to 25,0 1,6 −
from 25,0 to 100 − 4,0
1.3.1 For ships classed for unrestricted service, the humid- 2.1.1 All electrical components supplied from the main
ity ranges shown in Tab 2 are applicable in relation to the and emergency systems are to be so designed and manufac-
various locations of installation. tured that they are capable of operating satisfactorily under
the normally occuring variations in voltage and frequency
Table 2 : Humidity specified from [2.2] to [2.4].
Machinery spaces, command and control stations, accommodation from 2,0 to 13,2 1,0 −
spaces, exposed decks, cargo spaces from 13,2 to 100 − 0,7
from 2,0 to 25,0 1,6 −
On air compressors, on diesel engines and similar
from 25,0 to 100 − 4,0
from 2,0 to 13,2 3,0 −
Masts
from 13,2 to 50 − 2,1
2.4.2 For components intended for systems fed by static teristics may be verified by means of the test cited in IEC
converters, and/or systems in which the static converter Publication 60092-101 or in other recognised standards.
load predominates, it is assumed that:
• the single harmonics do not exceed 5% of the nominal 4.2 Insulating materials for windings
voltage up to the 15th harmonic of the nominal fre-
quency, decreasing to 1% at the 100th harmonic (see 4.2.1 Insulated windings are to be resistant to moisture, sea
Fig 1), and that air and oil vapour unless special precautions are taken to
protect insulants against such agents.
• the total harmonic distortion does not exceed 10%.
4.2.2 The insulation classes given in Tab 8 may be used in
Figure 1 : accordance with IEC Publication 60085.
10
5
Table 8 : Insulation Classes
A 105
Uν
E 120
U
B 130
0,1
1 3 10 15 100
F 155
ν H 180
2.4.3 Higher values for the harmonic content (e.g. in elec- 4.3 Insulating materials for cables
tric propulsion plant systems) may be accepted on the basis
of correct operation of all electrical devices. 4.3.1 See Ch 2, Sec 9, [1.3].
5.2 Degree of protection of enclosures • oil-immersed apparatus (only when required by the
application): Ex(o).
5.2.1 Electrical equipment is to be protected against the
ingress of foreign bodies and water.
6.1.3 Other equipment complying with types of protection
The minimum required degree of protection, in relation to
other than those in [6.1.2] may be considered by the Soci-
the place of installation, is generally that specified in Ch 2,
Sec 3, Tab 2. ety, such as:
5.2.2 The degrees of protection are to be in accordance • simple electrical apparatus and components (e.g. ther-
with: mocouples, photocells, strain gauges, junction boxes,
• IEC Publication No. 60529 for equipment in general switching devices), included in intrinsically-safe circuits
• IEC Publication No. 60034-5 for rotating machines. not capable of storing or generating electrical power or
energy in excess of limits stated in the relevant rules
5.2.3 For cable entries see [4.3.1].
• electrical apparatus specifically designed and certified
6 Protection against explosion hazard by the appropriate authority for use in Zone 0 or spe-
cially tested for Zone 2 (e.g. type “n” protection)
6.1 Protection against explosive gas or • equipment the type of which ensures the absence of
vapour atmosphere hazard sparks and arcs and of “hot spots” during its normal
6.1.1 Electrical equipment intended for use in areas where operation
explosive gas or vapour atmospheres may occur (e.g. oil
• pressurised equipment
tankers, liquefied gas carriers, chemical tankers, etc.), is to
be of a "safe type" suitable for the relevant flammable • equipment having an enclosure filled with a liquid die-
atmosphere and for shipboard use. lectric, or encapsulated.
6.1.2 The following “certified safe type” equipment is con-
sidered: 6.2 Protection against combustible dust
• intrinsically-safe: Ex(ia) - Ex(ib)
hazard
• flameproof: Ex(d)
• increased safety: Ex(e) 6.2.1 Electrical appliances intended for use in areas where
• pressurised enclosure: Ex(p) a combustible dust hazard may be present are to be
• encapsulated: Ex(m) arranged with enclosures having a degree of protection and
• sand filled: Ex(q) maximum surface temperature suitable for the dust to
• special protection: Ex(s) (apparatus not conforming with which they may be exposed.
IEC 60079 may be considered safe by a national or
other authorised body for use in potentially explosive Note 1: Where the characteristics of the dust are unknown, the
atmospheres. In such cases, the apparatus is identified appliances are to have a degree of protection IP6X. For most dusts a
with the symbol “s”) maximum surface temperature of 200°C is considered adequate.
1 Supply systems and characteristics 1.2.3 For high voltage systems see Ch 2, Sec 13.
of the supply
2 Sources of electrical power
1.1 Supply systems
2.1 General
1.1.1 The following distribution systems may be used:
a) on d.c. installations: 2.1.1 Electrical installations are to be such that:
• two-wire insulated a) All electrical auxiliary services necessary for maintaining
• two-wire with one pole earthed the ship in normal operational and habitable conditions
and for the preservation of the cargo will be assured
b) on a.c. installations: without recourse to the emergency source of electrical
• three-phase three-wire with neutral insulated power.
• three-phase three-wire with neutral directly earthed b) Electrical services essential for safety will be assured
or earthed through an impedance under various emergency conditions.
• three-phase four-wire with neutral directly earthed
c) When a.c. generators are involved, attention is to be
or earthed through an impedance given to the starting of squirrel-cage motors connected
• single-phase two-wire insulated to the system, particularly with regard to the effect of the
• single-phase two-wire with one phase earthed. magnitude and duration of the transient voltage change
produced due to the maximum starting current and the
1.1.2 Distribution systems other than those listed in [1.1.1] power factor. The voltage drop due to such starting cur-
(e.g. with hull return, three-phase four-wire insulated) will rent is not to cause any motor already operating to stall
be considered by the Society on a case by case basis. or have any adverse effect on other equipment in use.
1.1.3 The hull return system of distribution is not to be used
for power, heating or lighting in any ship of 1600 tons gross 2.2 Main source of electrical power
tonnage and upwards.
2.2.1 A main source of electrical power is to be provided,
1.1.4 The requirement of [1.1.3] does not preclude under of sufficient capability to supply all electrical auxiliary serv-
conditions approved by the Society the use of: ices necessary for maintaining the ship in normal opera-
tional and habitable conditions and for the preservation of
a) impressed current cathodic protective systems
the cargo without recourse to the emergency source of elec-
b) limited and locally earthed systems, or trical power.
c) insulation level monitoring devices provided the circu-
lation current does not exceed 30 mA under the most 2.2.2 For vessels propelled by electrical power and having
unfavourable conditions. two or more constant voltage propulsion generating sets
Note 1: Limited and locally earthed systems such as starting and
which constitute the source of electrical energy for the
ignition systems of internal combustion engines are accepted pro- ship’s auxiliary services, see Ch 2, Sec 14.
vided that any possible resulting current does not flow directly
through any dangerous spaces. 2.2.3 The main source of electrical power is to consist of at
least two generating sets.
1.1.5 For the supply systems of ships carrying liquid devel- The capacity of these generating sets is to be such that in the
oping combustible gases or vapours, see Pt D, Ch 7, Sec 5, event of any one generating set being stopped it will still be
Pt D, Ch 8, Sec 10 or Pt D, Ch 9, Sec 10. possible to supply those services necessary to provide:
1.1.6 For the supply systems in HV Installations, see Ch 2, a) normal operational conditions of propulsion and safety
Sec 13. (see [2.2.4])
b) minimum comfortable conditions of habitability (see Ch 2,
1.2 Maximum voltages Sec 1, [3.4.2])
c) preservation of the cargo, i. e. all the equipment which
1.2.1 The maximum voltages for both alternating current
are needed for refrigerated cargo or operation of any
and direct current low-voltage systems of supply for the
safety device, such as inert gas generator.
ship’s services are given in Tab 1.
Such capacity is, in addition, to be sufficient to start the
1.2.2 Voltages exceeding those shown will be specially largest motor without causing any other motor to stop or
considered in the case of specific systems. having any adverse effect on other equipment in operation.
2.2.4 Those services necessary to provide normal opera- in operation to permit propulsion and steering and to
tional conditions of propulsion and safety include primary ensure safety.
and secondary essential services.
For the purpose of calculating the capacity necessary for 2.2.8 Where the electrical power is normally supplied by
such services, it is essential to consider which of them can one generator, provision shall be made, upon loss of power,
be expected to be in use simultaneously. for automatic starting and connecting to the main switch-
board of stand-by generator(s) of sufficient capacity with
For a duplicated service, one being supplied electrically automatic restarting of the essential auxiliaries, in sequen-
and the other non-electrically (e.g. driven by the main tial operation if required. Starting and connection to the
engine), the electrical capacity is not included in the above main switchboard of the stand-by generator is to be prefera-
calculation. bly within 30 seconds, but in any case not more than 45
2.2.5 The services in [2.2.4] do not include: seconds after loss of power.
• thrusters not forming part of the main propulsion Where prime movers with longer starting time are used, this
(except in manoeuvring conditions) starting and connection time may be exceeded upon
approval from the Society.
• cargo handling gear
• cargo pumps 2.2.9 Load shedding or other equivalent arrangements
• refrigerators for air conditioning. should be provided to protect the generators required in the
present Article against sustained overload.
2.2.6 Further to the provisions above, the generating sets
The load shedding should be automatic.
shall be such as to ensure that with any one generator or its
primary source of power out of operation, the remaining The non-essential services, services for habitability and, if
generating sets shall be capable of providing the electrical necessary, the secondary essential services may be shed in
services necessary to start the main propulsion plant from a order to make sure that the connected generator set(s) is/are
"dead ship" condition. not overloaded.
2.2.7 Where the electrical power is normally supplied by 2.2.10 The emergency source of electrical power may be
more than one generator set simultaneously in parallel used for the purpose of starting from a "dead ship" condi-
operation, provision of protection, including automatic dis- tion if its capability either alone or combined with that of
connection of sufficient non-essential services and, if neces- any other source of electrical power is sufficient to provide
sary, secondary essential services and those provided for at the same time those services required to be supplied in
habitability, should be made to ensure that, in case of loss accordance with the provisions of [3.6.3], items a), b), c)
of any of these generating sets, the remaining ones are kept and d), or Pt D, Ch 11, Sec 5 for passenger ships.
2.2.11 The arrangement of the ship’s main source of electri- former not in operation, the remaining transformer(s) is (are)
cal power shall be such that essential services can be main- sufficient to ensure the supply to the services stated in
tained regardless of the speed and direction of rotation of [2.2.3].
the main propulsion machinery or shafting. Each transformer required is to be located as a separate unit
with separate enclosure or equivalent, and is to be served
2.2.12 Generators driven by the propulsion plant (shaft
by separate circuits on the primary and secondary sides.
generators) which are intended to operate at constant speed
Each of the primary and secondary circuits is to be provided
(e.g. a system where vessel speed and direction are control-
with switchgears and protection devices in each phase.
led by varying propeller pitch) may be accepted as forming
part of the main source of electrical power if, in all sailing Suitable interlocks or a warning label are to be provided in
and manoeuvring conditions including the propeller being order to prevent maintenance or repair of one single-phase
stopped, the capacity of these generators is sufficient to pro- transformer unless both switchgears are opened on their pri-
vide the electrical power to comply with [2.2.3] and all fur- mary and secondary sides.
ther requirements, especially those of [2.2.6]. They are to
be not less effective and reliable than the independent gen- 2.2.15 For ships intended for operation with periodically
erating sets. unattended machinery spaces, see Part E, Chapter 3.
2.2.13 Shaft generator installations which do not comply 2.2.16 For starting arrangements for main generating sets,
with the provisions of [2.2.12] may be used as additional see Ch 1, Sec 2, [3.1].
sources of electrical power with respect to the power bal-
2.2.17 Where single phase transformers are used, only one
ance provided that:
spare element is required if special precautions are taken to
a) in the event of a loss of power from the shaft genera- rapidly replace the faulty one.
tor(s), e.g. due to a sudden stopping of the propulsion
plant, a standby generating set is started automatically 2.2.18 Generators and generator systems, having the ship
b) the capacity of the standby set is sufficient for the loads propulsion machinery as their prime mover but not forming
necessary for propulsion and safety of the vessel part of the ship main source of electrical power, may be
used whilst the ship is at sea to supply electrical services
c) the time required to restore these services is not longer required for normal operational and habitable conditions
than 45 s. provided that:
2.2.14 Where transformers, converters or similar appli- a) there are sufficient and adequately rated additional gen-
ances constitute an essential part of the electrical supply erators fitted, which constitute the main source of elec-
system, the system is to be so arranged as to ensure the trical power required by [2.2.1]
same continuity of supply as stated in this sub-article. b) arrangements are fitted to automatically start one or
This may be achieved by arranging at least two three-phase or more of the generators, constituting the main source of
three single-phase transformers supplied, protected and electrical power required by [2.2.1], upon the frequency
installed as indicated in Fig 1, so that with any one trans- variations exceeding ± 10% of the limits specified below
Figure 1 :
Three-phase transformers Single-phase transformers
R R
'P' S 'P' S
T T
enclosure or separation
R R
S S
T T
c) within the declared operating range of the generators 2.3.7 If the services which are to be supplied by the transi-
and/or generator systems the specified limits for the volt- tional source receive power from an accumulator battery by
age variations and the frequency variations in Ch 2, Sec means of semiconductor convertors, means are to be pro-
2 can be met vided for supplying such services also in the event of failure
d) the short circuit current of the generator and/or genera- of the convertor (e.g. providing a bypass feeder or a dupli-
tor system is sufficient to trip the generator/generator cation of convertor).
system circuit-breaker taking into account the selectivity
2.3.8 Where electrical power is necessary to restore propul-
of the protective devices for the distribution system
sion, the capacity of the emergency source shall be suffi-
e) where considered appropriate, load shedding arrange- cient to restore propulsion to the ship in conjunction to
ments are to be fitted other machinery as appropriate, from a dead ship condition
f) on ships having remote control of the ship's propulsion within 30 min. after blackout.
machinery from the navigating bridge, means are provided, For the purpose of this requirement only, the dead ship con-
or procedures be in place, so as to ensure that supplies to dition and blackout are both understood to mean a condi-
essential services are maintained during manoeuvring con- tion under which the main propulsion plant, boilers and
ditions in order to avoid a blackout situation. auxiliaries are not in operation and in restoring the propul-
sion, no stored energy for starting the propulsion plant, the
2.3 Emergency source of electrical power main source of electrical power and other essential auxilia-
ries is to be assumed available. It is assumed that means are
2.3.1 A self-contained emergency source of electrical available to start the emergency generator at all times.
power shall be provided. The emergency generator and other means needed to
restore the propulsion are to have a capacity such that the
2.3.2 Provided that suitable measures are taken for safe- necessary propulsion starting energy is available within 30
guarding independent emergency operation under all cir- minutes of blackout/dead ship condition as defined above.
cumstances, the emergency generator may be used, Emergency generator stored starting energy is not to be
exceptionally, and for short periods, to supply non-emer- directly used for starting the propulsion plant, the main
gency circuits. source of electrical power and/or other essential auxiliaries
Exceptionally is understood to mean conditions, while the (emergency generator excluded).
vessel is at sea, such as: For steam ships, the 30 minute time limit given in SOLAS
a) blackout situation can be interpreted as time from blackout/dead ship condi-
b) dead ship situation tion defined above to light-off the first boiler.
c) routine use for testing 2.3.9 Where the emergency source of power is necessary
d) short-term parallel operation with the main source of to restore the main source of electrical power, provisions
electrical power for the purpose of load transfer. are to be made to allow a manual restart of a main generat-
ing set in case of failure of the emergency source.
Unless otherwise instructed by the Society, the emergency
generator may be used during lay time in port for the supply 2.3.10 Provision shall be made for the periodic testing of
of the ship mains, provided the requirements of [2.4] are the complete emergency system and shall include the test-
complied with. ing of automatic starting arrangements, where provided.
2.3.3 The electrical power available shall be sufficient to 2.3.11 For starting arrangements for emergency generating
supply all those services that are essential for safety in an sets, see Ch 1, Sec 2, [3.1].
emergency, due regard being paid to such services as may
have to be operated simultaneously. 2.3.12 The emergency source of electrical power may be
either a generator or an accumulator battery which shall
2.3.4 The emergency source of electrical power shall be comply with the requirements of [2.3.13] or [2.3.15],
capable, having regard to starting currents and the transi- respectively.
tory nature of certain loads, of supplying simultaneously at
least the services stated in [3.6.3] for the period specified, if 2.3.13 Where the emergency source of electrical power is a
they depend upon an electrical source for their operation. generator, it shall be:
a) driven by a suitable prime mover with an independent
2.3.5 The transitional source of emergency electrical
supply of fuel, having a flashpoint (closed cup test) of
power, where required, is to be of sufficient capacity to sup-
not less than 43°C
ply at least the services stated in [3.6.7] for half an hour, if
they depend upon an electrical source for their operation. b) started automatically upon failure of the main source of
electrical power supply to the emergency switchboard
2.3.6 An indicator shall be mounted in a suitable place on unless a transitional source of emergency electrical power
the main switchboard or in the machinery control room to in accordance with c) below is provided where the emer-
indicate when the batteries constituting either the emer- gency generator is automatically started, it shall be auto-
gency source of electrical power or the transitional source matically connected to the emergency switchboard those
of emergency electrical power referred to in [2.3.15] and services referred to in [3.6.7] shall then be connected
[2.3.16] are being discharged. automatically to the emergency generator, and
c) provided with a transitional source of emergency electri- 2.4 Use of emergency generator in port
cal power as specified in [2.3.16] unless an emergency
generator is provided capable both of supplying the 2.4.1 To prevent the generator or its prime mover from
services mentioned in that paragraph and of being auto- becoming overloaded when used in port, arrangements are
matically started and supplying the required load as to be provided to shed sufficient non-emergency loads to
quickly as is safe and practicable subject to a maximum ensure its continued safe operation.
of 45 s.
2.4.2 The prime mover is to be arranged with fuel oil filters
2.3.14 It is accepted to apply the total consumer load in and lubrication oil filters, monitoring equipment and pro-
steps providing that: tection devices as requested for the prime mover for main
• the total load is supplied within 45 seconds since power power generation and for unattended operation.
failure on the main switchboard
2.4.3 The fuel oil supply tank to the prime mover is to be
• the power distribution system is designed such that the provided with a low level alarm, arranged at a level ensur-
declared maximum step loading is not exceeded ing sufficient fuel oil capacity for the emergency services for
the period of time as required in [3.6].
• the compliance of time delays and loading sequence
with the above is demonstrated at ship’s trials.
2.4.4 The prime mover is to be designed and built for con-
2.3.15 Where the emergency source of electrical power is tinuous operation and should be subjected to a planned
an accumulator battery it shall be capable of: maintenance scheme ensuring that it is always available
and capable of fulfilling its role in the event of an emer-
a) carrying the emergency electrical load without recharg- gency at sea.
ing while maintaining the voltage of the battery through-
out the discharge period within 12% above or below its 2.4.5 Fire detectors are to be installed in the location where
nominal voltage the emergency generator set and emergency switchboard
b) automatically connecting to the emergency switchboard are installed.
in the event of failure of the main source of electrical
power, and 2.4.6 Means are to be provided to readily change over to
emergency operation.
c) immediately supplying at least those services specified
in [3.6.7]. 2.4.7 Control, monitoring and supply circuits for the pur-
pose of the use of the emergency generator in port are to be
2.3.16 The transitional source of emergency electrical
so arranged and protected that any electrical fault will not
power where required by [2.3.13] item c), shall consist of
influence the operation of the main and emergency services.
an accumulator battery which shall operate without
recharging while maintaining the voltage of the battery When necessary for safe operation, the emergency switch-
throughout the discharge period within 12% above or board is to be fitted with switches to isolate the circuits.
below its nominal voltage and be so arranged as to supply
automatically in the event of failure of either the main or the 2.4.8 Instructions are to be provided on board to ensure
emergency source of electrical power for half an hour at that, even when the vessel is underway, all control devices
least the services in [3.6.7] if they depend upon an electrical (e.g. valves, switches) are in a correct position for the inde-
source for their operation. pendent emergency operation of the emergency generator
set and emergency switchboard.
2.3.17 Where the emergency and/or transitional source of These instructions are also to contain information on the
power is an uninterruptible power system (UPS), it is to required fuel oil tank level, position of harbour/sea mode
comply with the requirement of Ch 2, Sec 6, [2]. switch, if fitted, ventilation openings, etc.
2.3.18 Where the emergency and/or transitional emer-
gency loads are supplied from a battery via an electronic 3 Distribution
converter or inverter, the maximum permitted d.c. voltage
variations are to be taken as those on the load side of the 3.1 Earthed distribution systems
converter or inverter.
Where the d.c. is converted into a.c. the maximum varia- 3.1.1 System earthing is to be effected by means independ-
tions are not exceed those given in Ch 2, Sec 2, Tab 6. ent of any earthing arrangements of the non-current-carry-
ing parts.
2.3.19 If the emergency generator is fitted with control,
alarm and safety systems based on electronic equipment, 3.1.2 Means of disconnection are to be fitted in the neutral
these systems are to be so arranged that, when in failure, earthing connection of each generator so that the generator
there is still a possibility to operate the emergency generator may be disconnected for maintenance or insulation resist-
manually. ance measurements.
A failure of the electronic governor is not considered.
3.1.3 Generator neutrals may be connected in common,
2.3.20 For the emergency source of electrical power in pas- provided that the third harmonic content of the voltage
senger ships, see Pt D, Ch 11, Sec 5. wave form of each generator does not exceed 5%.
3.1.4 Where a switchboard is split into sections operated 3.5 Main distribution of electrical power
independently or where there are separate switchboards, neu-
tral earthing is to be provided for each section or for each 3.5.1 Where the main source of electrical power is neces-
switchboard. Means are to be provided to ensure that the sary for propulsion of the ship, the main busbar is to be
earth connection is not removed when generators are isolated. divided into at least two parts which are normally to be
connected by circuit breakers or other approved means
3.1.5 Where for final sub-circuits it is necessary to locally such as circuit breakers without tripping mechanisms or dis-
connect a pole (or phase) of the sub-circuits to earth after connecting links or switches by means of which busbars
the protective devices (e.g. in automation systems or to can be split safely and easily.
avoid electromagnetic disturbances), provision (e.g. d.c./d.c.
convertors or transformers) is to be made such that current Bolted links, for example bolted bus bar sections, are not
unbalances do not occur in the individual poles or phases. accepted.
3) in all control stations, machinery control rooms, and 3.6.6 In a ship engaged regularly in voyages of short dura-
at each main and emergency switchboard tion, i.e. voyages where the route is no greater than 20 nau-
4) at all stowage positions for firemen’s outfits tical miles offshore or where the vessel has a class notation
"Coastal Navigation", the Society may, if satisfied that an
5) at the steering gear, and
adequate standard of safety would be attained, accept a
6) at the fire pump referred to in e) below, at the sprin- lesser period than the 18-hour period specified in [3.6.3],
kler pump, if any, at the emergency bilge pump, if items b) to e), but not less than 12 hours.
any, and at the starting positions of their motors Note 1: In ships for which Solas is not applicable, a reduced period
c) for a period of 18 hours: of time may be accepted.
Note 2: For passenger ships see Pt D, Ch 11, Sec 5.
1) the navigation lights and other lights required by the
International Regulations for Preventing Collisions at 3.6.7 The transitional source of emergency electrical
Sea in force power, where required, shall supply for half an hour at least
2) on ships constructed on or after 1 February 1995 the the following services if they depend upon an electrical
VHF radio installation required by Regulation source for their operation:
IV/7.1.1 and IV/7.1.2 of SOLAS Consolidated Edi- a) the lighting required by [3.6.3], items a), b) and c) 1) for
tion 1992, and, if applicable: this transitional phase, the required emergency electric
• the MF radio installation required by Regulations lighting, in respect of the machinery space and the
IV/9.1.1, IV/9.1.2, IV/10.1.2 and IV/10.1.3 accommodation and service spaces may be provided by
• the ship earth station required by Regulation permanently fixed, individual, automatically charged,
IV/10.1.1, and relay operated accumulator lamps, and
• the MF/HF radio installation required by Regula- b) all services required by [3.6.3], items d) 1), d) 3) and
tions IV/10.2.1, IV/10.2.2 and IV/11.1 d) 4), unless such services have an independent supply
for the period specified from an accumulator battery
d) for a period of 18 hours:
suitably located for use in an emergency.
1) all internal communication equipment as required in
an emergency [3.6.4] 3.7 Shore supply
2) the shipborne navigational equipment as required by
Regulation V/12 where such provision is unreasonable 3.7.1 Where arrangements are made for supplying the
or impracticable the Society may waive this require- electrical installation from a source on shore or elsewhere,
ment for ships of less than 5 000 tons gross tonnage a suitable connection box is to be installed on the ship in a
convenient location to receive the flexible cable from the
3) the fire detection and fire alarm systems, and
external source.
4) intermittent operation of the daylight signalling
lamp, the ship’s whistle, the manually operated call 3.7.2 Permanently fixed cables of adequate rating are to be
points and all internal signals (see [3.6.5]) that are provided for connecting the box to the main switchboard.
required in an emergency unless such services have
an independent supply for the period of 18 hours 3.7.3 Where necessary for systems with earthed neutrals,
from an accumulator battery suitably located for use the box is to be provided with an earthed terminal for con-
in an emergency nection between the shore’s and ship’s neutrals or for con-
nection of a protective conductor.
e) for a period of 18 hours: one of the fire pumps required
by the relevant provisions of Part C, Chapter 4, if 3.7.4 The connection box is to contain a circuit-breaker or
dependent upon the emergency generator for its source a switch-disconnector and fuses.
of power The shore connection is to be protected against short-circuit
f) for the period of time required in Ch 1, Sec 11, [2], the and overload however, the overload protection may be
steering gear where it is required to be so supplied. omitted in the connection box if provided on the main
switchboard.
3.6.4 Internal communication equipment required in an
emergency generally includes: 3.7.5 Means are to be provided for checking the phase
sequence of the incoming supply in relation to the ship’s
a) the means of communication between the navigating
system.
bridge and the steering gear compartment
b) the means of communication between the navigating 3.7.6 The cable connection to the box is to be provided
bridge and the position in the machinery space or control with at least one switch-disconnector on the main switch-
room from which the engines are normally controlled board.
3.7.7 The shore connection is to be provided with an indi- • pumps discharging overboard above the lightest water
cator at the main switchboard in order to show when the line and in way of the area of lifeboat and liferaft
cable is energised. launching: Ch 1, Sec 10, [5.2.4].
3.7.8 At the connection box a notice is to be provided giv- 3.9.2 All power circuits terminating in a bunker or cargo
ing full information on the nominal voltage and frequency space are to be provided with a multiple-pole switch out-
of the installation. side the space for disconnecting such circuits.
3.12.2 The distribution board in [3.12.1] is to be supplied 3.13.6 The system is to be capable of operation from the
from two alternative circuits, one from the main source of navigation bridge and, except for the ship’s whistle, also
power and one from the emergency source of power (see from other strategic points.
also [3.6]).
Note 1: Other strategic points are taken to mean those locations,
The transfer of supply is to be practicable from the bridge, other than the navigation bridge, from where emergency situations
are intended to be controlled and the general alarm system can be
for example by means of a switch.
activated. A fire control station or a cargo control station should
normally be regarded as strategic points.
3.12.3 Each navigation light is to be controlled and pro-
tected in each insulated pole by a double-pole switch and a 3.13.7 The alarm is to continue to function after it has been
fuse or, alternatively, by a double-pole circuit-breaker, fitted triggered until it is manually turned off or is temporarily
on the distribution board referred to in [3.12.1]. interrupted by a message on the public address system.
3.12.4 Where there are double navigation lights, i.e. lights 3.13.8 The alarm system is to be audible throughout all the
with two lamps or where for every navigation light a spare accommodation and normal crew working spaces.
is also fitted, the connections to such lights may run in a
single cable provided that means are foreseen in the distri- 3.13.9 The minimum sound pressure level for the emer-
bution board to ensure that only one lamp or light may be gency alarm tone in interior and exterior spaces is to be 80
supplied at any one time. dB (A) and at least 10 dB (A) above ambient noise levels
occurring during normal equipment operation with the ship
3.12.5 Each navigation light is to be provided with an auto- underway in moderate weather.
matic indicator giving audible and/or visual warning in the
event of failure of the light. If an audible device alone is fit- 3.13.10 In cabins without a loudspeaker installation, an
ted, it is to be connected to a separate source of supply from electronic alarm transducer, e.g. a buzzer or similar, is to be
that of the navigation lights, for example an accumulator installed.
(storage) battery.
3.13.11 The sound pressure level at the sleeping position in
If a visual signal is used connected in series with the naviga- cabins and in cabin bathrooms is to be at least 75 dB (A)
tion light, means are to be provided to prevent the extinc- and at least 10 dB (A) above ambient noise levels.
tion of the navigation light due to the failure of the visual
signal. 3.13.12 For cables used for the general emergency alarm
system, see [9.6.2].
A minimum level of visibility is to be assured in the case of
use of dimmer devices.
3.14 Public address system
3.13 General emergency alarm system 3.14.1 The public address system is to be a loudspeaker
installation enabling the broadcast of messages into all
3.13.1 An electrically operated bell or klaxon or other spaces where people on board are normally present.
equivalent warning system installed in addition to the ship's
In spaces such as under deck passageways, bosun’s locker,
whistle or siren, for sounding the general emergency alarm
hospital and pump rooms, the public address system is/may
signal, is to comply with the requirements of this sub-article.
not be required.
3.13.2 The general emergency alarm system is to be sup- 3.14.2 Where the public address system is used to supple-
plemented by either a public address system complying ment the general emergency alarm system as per [3.13.2], it
with the requirements in [3.14] or other suitable means of is to be continuously powered from the emergency source
communication. of electrical power required by [2.3] and [3.6].
3.13.3 Entertainment sound system is to be automatically 3.14.3 The system is to allow for the broadcast of messages
turned off when the general alarm system is activated. from the navigation bridge and from other places on board
the ship as deemed necessary.
3.13.4 The system is to be continuously powered and is to
have an automatic change-over to a standby power supply 3.14.4 The system is to be protected against unauthorised
in case of loss of normal power supply. use.
An alarm is to be given in the event of failure of the normal 3.14.5 The system is to be installed with regard to acousti-
power supply. cally marginal conditions and not require any action from
the addressee.
3.13.5 The system is to be powered by means of two cir-
cuits, one from the ship's main supply and the other from 3.14.6 Where an individual loudspeaker has a device for
the emergency source of electrical power required by [2.3] local silencing, an override arrangement from the control
and [3.6]. station(s), including the navigating bridge, is to be in place.
3.14.7 With the ship underway in normal conditions, the 3.17.2 Where more than one main propulsion engine is
minimum sound pressure level for broadcasting emergency foreseen, each speed control system is to be provided with
announcements is to be: an individual supply by means of separate wiring from the
a) in interior spaces, 75 dB (A) and at least 20 dB (A) above main switchboard or from two independent section boards.
the speech interference level Where the main busbars are divided into two sections, the
b) in exterior spaces, 80 dB (A) and at least 15 dB (A) governors are, as far as practicable, to be supplied equally
above the speech interference level. from the two sections.
With respect to cabin/state rooms, the sound pressure level
is to be attained as required inside such spaces during sea 3.17.3 In the case of propulsion engines which do not
trials. depend for their operation on electrical power, i.e. pumps
driven from the main engine, the speed control systems are
3.15 Combined general emergency alarm- to be fed both from the main source of electrical power and
public address system from an accumulator battery for at least 15 minutes or from
a similar supply source.
3.15.1 Where the public address system is the only means
Such battery may also be used for other services such as
for sounding the general emergency alarm signal and the
automation systems, where foreseen.
fire alarm, in addition to the requirements of [3.13] and
[3.14], the following are to be satisfied:
• the system automatically overrides any other non emer- 3.18 Power supply to the speed control sys-
gency input system when an emergency alarm is tems of generator sets
required
• the system automatically overrides any volume control 3.18.1 Each electrically operated control and/or speed con-
provided to give the required output for the emergency trol system of generator sets is to be provided with a sepa-
mode when an emergency alarm is required rate supply from the main source of electric power and from
• the system is arranged to prevent feedback or other an accumulator battery for at least 15 minutes or from a
interference similar supply source.
• the system is arranged to minimise the effect of a single
failure so that the alarm signal is still audible (above 3.18.2 The speed control system of generator sets is to be
ambient noise levels) also in the case of failure of any supplied from the main switchboard or from independent
one circuit or component, by means of the use of: section boards.
- multiple amplifiers Where the main busbars are divided into two sections, the
- segregated cable routes to public rooms, alleyways, governors are, as far as practicable, to be supplied from the
stairways and control stations sections to which the relevant generators are connected.
- more than one device for generating electronic
sound signal
3.19 Installation of water-based local application
- electrical protection for individual loudspeakers
fire-fighting systems (FWBLAFFS)
against short-circuits.
3.16.2 Control and indicating circuits relative to primary 3.19.3 The system and its components are to be designed
essential services are to be branched off from the main cir- to withstand ambient temperature changes, vibration,
cuit in which the relevant equipment is installed. Equivalent humidity, shock, impact, clogging and corrosion normally
arrangements may be accepted by the Society. encountered in machinery spaces. Components within the
protected spaces are to be designed to withstand the ele-
3.16.3 Control and indicating circuits relative to secondary
vated temperatures which could occur during a fire.
essential services and to non-essential services may be sup-
plied by distribution systems reserved for the purpose to the
satisfaction of the Society. 3.19.4 Degrees of protection are to be in accordance with
[4.2].
3.17 Power supply to the speed control sys-
tems of main propulsion engines 3.19.5 Systems requiring an external power source are to
be supplied by the main power source.
3.17.1 Electrically operated speed control systems of main
engines are to be fed from the main source of electrical 3.19.6 In case of activation of the system, an alarm in
power. accordance with Ch 4, Sec 6, [4.7.4] is to be activated.
4 Degrees of protection of the enclosures Note 1: The water pressure testing of the enclosures protected to
IP X8 is to be based on the pressure that may occur at the location
of the component during flooding for a period of 36 hours.
4.1 General
4.2 Installation of electrical and electronic
4.1.1 The minimum required degree of protection for elec-
trical equipment, in relation to the place of installation, is
equipment in engine rooms protected by
generally that specified in Tab 2. fixed water-based local application fire-
fighting systems (FWBLAFFS)
4.1.2 Equipment supplied at nominal voltages in excess of
500 V and accessible to non-authorised personnel (e.g. 4.2.1 Unless it is essential for safety or operational pur-
equipment not located in machinery spaces or in locked poses, electrical and electronic equipment is not to be
compartments under the responsibility of the ship’s officers) located within areas protected by FWBLAFFS and in adja-
is to have a degree of protection against touching live parts cent areas where water may extend.
of at least IP 4X. The electrical and electronic equipment located within
areas protected by FWBLAFFS and those within adjacent
4.1.3 In addition to the requirements of this paragraph, exposed to direct spray are to have a degree of protection
equipment installed in spaces with an explosion hazard is not less than IP44.
also subject to the provisions of Ch 2, Sec 2, [6].
Electrical and electronic equipment within adjacent areas
4.1.4 The enclosures of electrical equipment for the moni- not exposed to direct spray may have a lower degree of pro-
toring and control of watertight doors which are situated tection provided evidence of suitability for use in these
below the bulkhead deck are to provide suitable protection areas is submitted taking into account the design and equip-
against the ingress of water. ment layout, e.g. position of inlet ventilation openings, fil-
ters, baffles, etc. to prevent or restrict the ingress mist/spray
In particular, the minimum required degree of protection is into the equipment. The cooling airflow for the equipment
to be: is to be assured.
• IP X7 for electric motors, associated circuits and control Note 1: Definitions (see Fig 2):
components
• protected space is a machinery space where a FWBLAFFS is
• IP X8 for door position indicators and associated circuit installed
components • protected areas: areas within a protected space which is
• IP X6 for door movement warning signals. required to be protected by FWBLAFFS
• adjacent areas:
Figure 2 : Definitions of areas • areas other those protected areas, exposed
• areas other those defined above, where water may extend.
Note 2: Additional precautions may be required to be taken in
respect of:
• tracking as the result of water entering the equipment
• potential damage as the result of residual salts from sea water
systems
• high voltage installations
• personnel protection against electric shock
Equipment may require maintenance after being subjected to water
mist/spray.
5.1 General
5.1.1 The cables and protective devices of final sub-circuits
are to be rated in accordance with their connected load.
G Diesel engine
5.1.2 Circuits supplying two or more final sub-circuits are
to be rated in accordance with the total connected load
subject, where justifiable, to the application of a diversity
(demand) factor.
Switch- Accessories
Heat- Cook-
board, (e.g.
Condition in Example of Gener- Trans- Lumi- ing ing Socket
control gear, Motors switches,
location location ators formers naires appli- appli- outlets
motor connection
ances ances
starters boxes)
Danger of Dry accommoda-
touching live tion spaces, dry IP 20 X (1) IP 20 IP 20 IP 20 IP 20 IP 20 IP 20 IP 20
parts only control rooms
Danger of Control rooms,
dripping liquid wheel-house, IP 22 X IP 22 IP 22 IP 22 IP 22 IP 22 IP 22 IP 22
and/or radio room
moderate Engine and boiler
mechanical IP 22 IP 22 IP 22 IP 22 IP 22 IP 22 IP 22 IP 44 IP 44
rooms above floor
damage
Steering gear
IP 22 IP 22 IP 22 IP 22 IP 22 IP 22 X IP 44 IP 44
rooms
Emergency
IP 22 IP 22 IP 22 IP 22 IP 22 IP 22 X IP 44 IP 44
machinery rooms
General
IP 22 X IP 22 IP 22 IP 22 IP 22 X IP 22 IP 44
storerooms
Pantries IP 22 X IP 22 IP 22 IP 22 IP 22 IP 22 IP 44 IP 44
Provision rooms IP 22 X IP 22 IP 22 IP 22 IP 22 X IP 44 IP 44
Ventilation ducts X X IP 22 X X X X X X
Increased Bathrooms and/or
X X X X IP 34 IP 44 X IP 55 IP 55
danger of showers
liquid and/or Engine and boiler
mechanical X X IP 44 X IP 34 IP 44 X X IP 55
rooms below floor
damage
Closed fuel oil
IP 44 X IP 44 IP 44 IP 34 IP 44 X X IP 55
separator rooms
Closed
lubricating oil IP 44 X IP 44 IP 44 IP 34 IP 44 X X IP 55
separator rooms
Increased Ballast pump IP 44 IP 44
IP 44 X IP 34 IP 44 X IP 55 IP 55
danger of rooms (2) (2)
liquid and Refrigerated
mechanical X X IP 44 X IP 34 IP 44 X IP 55 IP 55
rooms
damage
Galleys and
IP 44 X IP 44 IP 44 IP 34 IP 44 IP 44 IP 44 IP 44
laundries
Public bathrooms
X X IP 44 IP 44 IP 34 IP 44 X IP 44 IP 44
and shower
Danger of Shaft or pipe
liquid spraying, tunnels in double IP 55 X IP 55 IP 55 IP 55 IP 55 X IP 56 IP 56
presence of bottom
cargo dust, Holds for general
serious mecha- X X IP 55 X IP 55 IP 55 X IP 56 IP 56
cargo
nical damage,
aggressive fumes Ventilation trunks X X IP 55 X X X X X X
Danger of liquid
in massive Open decks IP 56 X IP 56 X IP 55 IP 56 X IP 56 IP 56
quantities
(1) The symbol “X” denotes equipment which it is not advised to install.
(2) Electric motors and starting transformers for lateral thrust propellers located in spaces similar to ballast pump rooms may have
degree of protection IP 22.
7.1 General requirements for overcurrent 7.2.3 In the absence of precise data concerning the charac-
protection teristics of generators, accumulator batteries and motors,
the maximum short-circuit currents on the main busbars
7.1.1 Electrical installations are to be protected against may be calculated as follows:
accidental overcurrents including short-circuit.
• for alternating current systems:
The choice, arrangement and performance of the various
protective devices are to provide complete and coordinated Iac = 10 ITG + 3,5 ITM
automatic protection in order to ensure as far as possible: Ipk = 2,4 Iac
• continuity of service in the event of a fault, through • for direct current systems supplied by batteries:
coordinated and discriminative action of the protective
devices Ip = K C10 + 6 ITM
• elimination of the effects of faults to reduce damage to where:
the system and the hazard of fire as far as possible.
Ip : Maximum short-circuit current
Note 1: An overcurrent is a current exceeding the nominal current.
Iac : r.m.s. value of the symmetrical component (at
Note 2: A short-circuit is the accidental connection by a relatively
the instant T/2)
low resistance or impedance of two or more points in a circuit
which are normally at different voltages. Ipk : Maximum peak value
ITG : Rated current of all generators which can be
7.1.2 Devices provided for overcurrent protection are to be
connected simultaneously
chosen according to the requirements, especially with
regard to overload and short-circuit. C10 : Battery capacity in Ah for a discharge duration
Note 1: Overload is an operating condition in an electrically of 10 hours
undamaged circuit which causes an overcurrent. K : Ratio of the short-circuit current of the batteries
to C10 (see Note 1)
7.1.3 Systems are to be such as to withstand the thermal
and electrodynamic stresses caused by the possible overcur- ITM : Rated current of all motors which are normally
rent, including short-circuit, for the admissible duration. simultaneously connected in the system.
Note 1: For stationary batteries the following values may be 7.4.3 The rated short-circuit making capacity of every
assumed for guidance: mechanical switching device intended to be capable of
• vented lead-acid batteries: K = 8 being closed on short-circuit is to be not less than the maxi-
• vented alkaline type batteries intended for discharge at low mum value of the short-circuit current at the point of installa-
rates corresponding to a battery duration exceeding three tion. On alternating current this maximum value corresponds
hours: K = 15 to the peak value allowing for maximum asymmetry.
• sealed lead-acid batteries having a capacity of 100 Ah or more
7.4.4 Every protective device or contactor not intended for
or alkaline type batteries intended for discharge at high rates
corresponding to a battery duration not exceeding three hours: short-circuit interruption is to be adequate for the maximum
K = 30. short-circuit current liable to occur at the point of installa-
tion having regard to the time required for the short-circuit
to be removed.
7.3 Selection of equipment
7.4.5 The use of a protective device not having a short-cir-
7.3.1 Circuit-breakers of withdrawable type are required cuit breaking or making capacity at least equal to the maxi-
where they are not suitable for isolation. mum prospective short-circuit current at the point where it
is installed is permitted, provided that it is backed up on the
7.3.2 Equipment is to be chosen on the basis of its rated
generator side by a fuse or by a circuit-breaker having at
current and its making/breaking capacity.
least the necessary short-circuit rating and not being the
7.3.3 In the selection of circuit-breakers with intentional generator circuit-breaker.
short-time delay for short-circuit release, those of utilisation
7.4.6 The same fuse or circuit-breaker may back up more
category B are to be used and they are to be selected also
than one circuit-breaker where the circuits concerned do
taking into account their rated short-time withstand current
not involve essential services.
capacity (Icw).
For circuit-breakers without intentional short-time delay for 7.4.7 The short-circuit performance of the back-up arrange-
short-circuit release, circuit breakers of utilisation category ment is to be equal to the requirements of IEC Publication
A may be used and they are to be selected according to 60947-2 for a single circuit-breaker having the same short-
their rated service short-circuit breaking capacity (Ics). circuit performance category as the backed-up circuit-
Note 1: For the purpose of these Rules, utilisation categories A and breaker and rated for the maximum prospective short-cir-
B are defined as follows: cuit level at the supply terminals of the arrangement.
• utilisation category A: circuit-breakers not specifically intended
7.4.8 Circuit-breakers with fuses connected to the load side
for selectivity under short-circuit conditions with respect to
other short-circuit protective devices in series on the load side,
may be used, provided the back-up fuses and the circuit-
i.e. without an intentional short-time delay provided for selec- breakers are of coordinated design, in order to ensure that
tivity under short-circuit conditions the operation of the fuses takes place in due time so as to
prevent arcing between poles or against metal parts of the
• utilisation category B: circuit-breakers specifically intended for
selectivity under short-circuit conditions with respect to other circuit-breakers when they are submitted to overcurrents
short-circuit protective devices in series on the load side, i.e. involving the operation of the fuse.
with an intentional short-time delay (which may be adjustable)
provided for selectivity under short-circuit conditions. 7.4.9 When determining the performance requirements for
the above-mentioned back-up protection arrangement, it is
7.3.4 For duplicated essential services and non-essential permissible to take into account the impedance of the vari-
services, circuit-breakers may be selected according to their ous circuit elements of the arrangement, such as the imped-
ultimate short-circuit breaking capacity (Icu). ance of a cable connection when the backed-up circuit-
breaker is located away from the back-up breaker or fuse.
7.3.5 For switches, the making/breaking capacity is to be in
accordance with utilisation category AC-22 A or DC-22 A 7.5 Continuity of supply and continuity of service
(in compliance with IEC Publication 60947-3).
7.5.1 The protection of circuits is to be such that a fault in
7.3.6 For fuse-switch disconnectors or switch-disconnector one service does not cause the loss of any essential services.
fuse units, the making/breaking capacity is to be in accord-
ance with utilisation categories AC-23 A or DC-23 A (in 7.5.2 The protection of the emergency circuit is to be such
compliance with IEC Publication 60947-3). that a failure in one circuit does not cause a loss of other
emergency services.
7.4 Protection against short-circuit Note 1: The continuity of supply for the primary essential services
and the continuity of service for the secondary essential services
7.4.1 Protection against short-circuit currents is to be pro- are to be ensured.
vided by circuit- breakers or fuses. The continuity of supply is the condition for which during and after
a fault in a circuit, the supply to the healthy circuits (see circuit 3 in
7.4.2 The rated short-circuit breaking capacity of every pro- Fig 3) is permanently ensured.
tective device is to be not less than the maximum prospec- The continuity of service is the condition for which after a fault in a
tive value of the short-circuit current at the point of circuit has been cleared, the supply to the healthy circuits (see cir-
installation at the instant of contact separation. cuit 3 in Fig 3) is re-established.
1 1 1
2 3 2 3 2 3
Continuity of service
1 1 1
2 3 2 3 2 3
7.6 Protection against overload For generators not arranged to operate in parallel with a
rated output equal to or less than 50 kVA, a multipole
7.6.1 Devices provided for overload protection are to have switch with a fuse in each insulated phase on the generator
a tripping characteristic (overcurrent-trip time) adequate for side may be accepted.
the overload ability of the elements of the system to be pro-
tected and for any discrimination requirements. 7.8.2 When multipole switch and fuses are used, the fuse
rating is to be maximum 110% of the generator rated current.
7.6.2 The use of fuses up to 320 A for overload protection
is permitted. 7.8.3 Where a circuit-breaker is used:
a) the overload protection is to trip the generator circuit-
7.7 Localisation of overcurrent protection breaker at an overload between 10% and 50% for an
overload of 50% of the rated current of the generator the
7.7.1 Short-circuit protection is to be provided for every time delay is not to exceed 2 minutes however, the fig-
non-earthed conductor. ure of 50% or the time delay of 2 minutes may be
7.7.2 Overload protection is to be provided for every non- exceeded if the construction of the generator permits this
earthed conductor nevertheless, in insulated single-phase b) the setting of the short-circuit protection is to instantane-
circuits or insulated three-phase circuits having substan- ously trip the generator circuit-breaker at an overcurrent
tially balanced loads, the overload protection may be omit- less than the steady short-circuit current of the generator.
ted on one conductor. Short time delays (e.g. from 0,5 s to 1 s) may be intro-
duced for discrimination requirements in "instantaneous"
7.7.3 Short-circuit and overload protective devices are not tripping devices.
to interrupt earthed conductors, except in the case of multi-
ple disconnection devices which simultaneously interrupt 7.8.4 For emergency generators the overload protection may,
all the conductors, whether earthed or not. instead of disconnecting the generator automatically, give a
visual and audible alarm in a permanently attended space.
7.7.4 Electrical protection is to be located as close as possi-
ble to the origin of the protected circuit. 7.8.5 After disconnection of a generator due to overload,
the circuit-breaker is to be ready for immediate reclosure.
7.8 Protection of generators
7.8.6 Generator circuit-breakers are to be provided with a
7.8.1 Generators are to be protected against short-circuits reclosing inhibitor which prevents their automatic reclosure
and overloads by multipole circuit-breakers. after tripping due to a short-circuit.
7.8.7 Generators having a capacity of 1500 kVA or above 7.9.4 The protective devices of the circuits supplying
are to be equipped with a suitable protective device or sys- motors are to allow excess current to pass during transient
tem which, in the event of a short-circuit in the generator or starting of motors.
in the supply cable between the generator and its circuit-
breaker, will de-excite the generator and open the circuit- 7.9.5 Final sub-circuits which supply one consumer with
breaker (e.g. by means of differential protection). its own overload protection (for example motors), or con-
sumers which cannot be overloaded (for example perma-
7.8.8 Where the main source of electrical power is neces- nently wired heating circuits and lighting circuits), may be
sary for the propulsion of the ship, load shedding or other provided with short-circuit protection only.
equivalent arrangements are to be provided to protect the
generators against sustained overload. 7.9.6 Steering gear circuits are to be provided with short-
circuit protection only (see Ch 1, Sec 11, [2]).
7.8.9 Arrangements are to be made to disconnect or reduce
automatically the excess load when the generators are over- 7.10 Protection of motors
loaded in such a way as to prevent a sustained loss of speed
and/or voltage (see Ch 2, Sec 2, Tab 6). The operation of 7.10.1 Motors of rating exceeding 1 kW and all motors for
such device is to activate a visual and audible alarm. A time essential services are to be protected individually against
delay of 5-20 s is considered acceptable. overload and short-circuit. The short-circuit protection may
be provided by the same protective device for the motor
7.8.10 When an overload is detected the load shedding
and its supply cable (see [7.9.5]).
system is to disconnect automatically, after an appropriate
time delay, the circuits supplying the non-essential services 7.10.2 For motors intended for essential services, the over-
and, if necessary, the secondary essential services in a sec- load protection may be replaced by an overload alarm (for
ond stage. steering gear motors see Ch 1, Sec 11, [2]).
7.8.11 Alternating current generators arranged to operate in 7.10.3 The protective devices are to be designed so as to
parallel are to be provided with reverse-power protection. allow excess current to pass during the normal accelerating
The protection is to be selected in accordance with the period of motors according to the conditions corresponding
characteristics of the prime mover. to normal use.
The following values are recommended: If the current/time characteristic of the overload protection
device does not correspond to the starting conditions of a
• 2-6% of the rated power for turbogenerators
motor (e.g. for motors with extra-long starting period), pro-
• 8-15% of the rated power for diesel generators. vision may be made to suppress operation of the device
during the acceleration period on condition that the short-
The reverse-power protection may be replaced by other
circuit protection remains operative and the suppression of
devices ensuring adequate protection of the prime movers.
overload protection is only temporary.
7.8.12 Generators are to be provided with an undervoltage
7.10.4 For continuous duty motors the protective gear is to
protection which trips the breaker if the voltage falls to
have a time delay characteristic which ensures reliable ther-
70%-35% of the rated voltage.
mal protection against overload.
The undervoltage release also prevents the closing of the
circuit-breaker if the generator voltage does not reach a 7.10.5 The protective devices are to be adjusted so as to
minimum of 85% of the rated voltage. limit the maximum continuous current to a value within the
The operation of the undervoltage release is to be instanta- range 105% - 120% of the motor’s rated full load current.
neous when preventing closure of the breaker, but it is to be
7.10.6 For intermittent duty motors the current setting and
delayed for selectivity purposes when tripping the breaker.
the delay (as a function of time) of the protective devices are
to be chosen in relation to the actual service conditions of
7.9 Protection of circuits the motor.
7.9.1 Each separate circuit shall be protected against short- 7.10.7 Where fuses are used to protect polyphase motor
circuit and against overload, unless otherwise specified in circuits, means are to be provided to protect the motor
these Rules or where the Society may exceptionally other- against unacceptable overload in the case of single phasing.
wise permit.
7.10.8 Motors rated above 1 kW are to be provided with:
7.9.2 Each circuit is to be protected by a multipole circuit-
• undervoltage protection, operative on the reduction or
breaker or switch and fuses against overloads and short-cir-
failure of voltage, to cause and maintain the interruption
cuits.
of power in the circuit until the motor is deliberately
7.9.3 Circuits for lighting are to be disconnected on both restarted or
non-earthed conductors single-pole disconnection of final • undervoltage release, operative on the reduction or fail-
sub-circuits with both poles insulated is permitted only in ure of voltage, so arranged that the motor restarts auto-
accommodation spaces. matically when power is restored after a power failure.
7.10.9 The automatic restart of a motor is not to produce a 7.13.4 Circuits whose failure could endanger operation,
starting current such as to cause excessive voltage drop. such as steering gear control feeder circuits, are to be pro-
In the case of several motors required to restart automati- tected only against short-circuit.
cally, the total starting current is not to cause an excessive
7.13.5 The protection is to be adequate for the minimum
voltage drop or sudden surge current to this end, it may be
cross-section of the protected circuits.
necessary to achieve a sequence start.
7.10.10 The undervoltage protective devices are to allow the 7.14 Protection of transformers
motor to be started when the voltage exceeds 85% of the
rated voltage and are to intervene without fail when the volt- 7.14.1 The primary winding side of power transformers is
age drops to less than approximately 20% of the rated volt- to be protected against short-circuit and overload by means
age, at the rated frequency and with a time delay as necessary. of multipole circuit-breakers or switches and fuses.
Overload protection on the primary side may be dispensed
7.11 Protection of storage batteries with where it is provided on the secondary side or when the
total possible load cannot reach the rated power of the
7.11.1 Batteries are to be protected against overload and transformer.
short-circuit by means of fuses or multipole circuit-breakers
at a position adjacent to the battery compartment. 7.14.2 The protection against short-circuit is to be such as
Overcurrent protection may be omitted for the circuit to the to ensure the selectivity between the circuits supplied by
starter motors when the current drawn is so large that is the secondary side of the transformer and the feeder circuit
impracticable to obtain short-circuit protection. of the transformer.
7.11.2 Emergency batteries supplying essential services are 7.14.3 When transformers are arranged to operate in paral-
to have short-circuit protection only. lel, means are to be provided so as to trip the switch on the
secondary winding side when the corresponding switch on
the primary side is open.
7.12 Protection of shore power connection
7.12.1 Permanently fixed cables connecting the shore con- 8 System components
nection box to the main switchboard are to be protected by
fuses or circuit-breakers (see [3.7.4]). 8.1 General
7.13 Protection of measuring instruments, 8.1.1 The components of the electrical system are to be
pilot lamps and control circuits dimensioned such as to withstand the currents that can pass
through them during normal service without their rating
7.13.1 Measuring circuits and devices (voltage transform- being exceeded.
ers, voltmeters, voltage coils of measuring instruments,
insulation monitoring devices etc.) and pilot lamps are to be 8.1.2 The components of the electrical system are to be
protected against short-circuit by means of multipole cir- designed and constructed so as to withstand for the admissi-
cuit-breakers or fuses. ble duration the thermal and electrodynamic stresses
caused by possible overcurrents, including short-circuit.
The protective devices are to be placed as near as possible
to the tapping from the supply.
The secondary side of current transformers is not to be pro-
9 Electrical cables
tected.
9.1 General
7.13.2 Control circuits and control transformers are to be
protected against overload and short-circuit by means of 9.1.1 All electrical cables and wiring external to equipment
multipole circuit-breakers or fuses on each pole not con- shall be at least of a flame-retardant type, in accordance
nected to earth. with IEC Publication 60332-1.
Overload protection may be omitted for transformers with a
rated current of less than 2 A on the secondary side. 9.1.2 In addition to the provisions of [9.1.1], when cables
are laid in bunches, cable types are to be chosen in compli-
The short-circuit protection on the secondary side may be ance with IEC Publication 60332-3 Category A, or other
omitted if the transformer is designed to sustain permanent means (see Ch 2, Sec 12) are to be provided such as not to
short-circuit current. impair their original flame-retarding properties.
7.13.3 Where a fault in a pilot lamp would impair the oper- 9.1.3 Where necessary for specific applications such as
ation of essential services, such lamps are to be protected radio frequency or digital communication systems, which
separately from other circuits such as control circuits. require the use of particular types of cables, the Society may
Note 1: Pilot lamps connected via short-circuit-proof transformers permit the use of cables which do not comply with the pro-
may be protected in common with control circuits. visions of [9.1.1] and [9.1.2].
9.1.4 Cables which are required to have fire-resisting char- 9.3.2 Where cables are provided with armour or metallic braid
acteristics are to comply with the requirements stipulated in (e.g. for cables installed in hazardous areas), an overall imper-
IEC Publication 60331. vious sheath or other means to protect the metallic elements
against corrosion is to be provided (see Ch 2, Sec 9, [1.5]).
9.2 Choice of insulation
9.3.3 An impervious sheath is not required for single-core
9.2.1 The maximum rated operating temperature of the cables installed in tubes or ducts inside accommodation
insulating material is to be at least 10°C higher than the spaces, in circuits with maximum system voltage 250 V.
maximum ambient temperature liable to occur or to be pro-
duced in the space where the cable is installed. 9.3.4 In choosing different types of protective coverings,
due consideration is to be given to the mechanical action to
9.2.2 The maximum rated conductor temperature for nor-
which each cable may be subjected during installation and
mal and short-circuit operation, for the type of insulating
in service.
compounds normally used for shipboard cables, is not to
exceed the values stated in Tab 4. Special consideration will If the mechanical strength of the protective covering is con-
be given to other insulating materials. sidered insufficient, the cables are to be mechanically pro-
tected (e.g. by an armour or by installation inside pipes or
9.2.3 PVC insulated cables are not to be used either in conduits).
refrigerated spaces, or on decks exposed to the weather of
ships classed for unrestricted service.
9.3.5 Single-core cables for a.c. circuits with rated current
9.2.4 Mineral insulated cables will be considered on a case exceeding 20 A are to be either non-armoured or armoured
by case basis. with non-magnetic material.
9.6 Cables in circuits required to be operable Other types of flame-retardant switchboard wiring may be
under fire condition accepted at the discretion of the Society.
9.6.2 Electrical services required to be operable under fire 9.9.4 When the actual ambient temperature obviously dif-
conditions include: fers from 45°C, the correction factors shown in Tab 10 may
• fire and general alarm system be applied to the current carrying capacity in Tab 5 to Tab 9.
• fire-extinguishing systems and fire-extinguishing medium
alarms
Table 5 : Current carrying capacity, in A,
• fire detection system in continuous service for cables based on maximum
• control and power systems to power operated fire doors conductor operating temperature of 60°C
and status indication for all fire doors (ambient temperature 45°C)
• control and power systems to power operated watertight
doors and their status indication Nominal section, Number of conductors
• emergency lighting in mm2 1 2 3 or 4
• public address system 1,5 10 9 7
• Low Location Lighting
2,5 17 14 12
• remote emergency stop/shutdown arrangements for sys-
tems which may support the propagation of fire and/or 4 23 20 16
explosion. 6 29 25 20
10 40 34 28
9.6.3 Cables for services required to be operable under fire
conditions, including their power supplies, are to be run as 16 54 46 38
directly as is practicable. 25 71 60 50
9.6.4 Cables connecting fire pumps to the emergency 35 88 75 62
switchboard shall be of a fire-resistant type where they pass 50 110 94 77
through high fire risk areas.
70 135 115 95
9.10.3 For the nominal cross-sectional area of: 9.11.2 The nominal cross-sectional area of each cable is to
• earthing conductors, see Ch 2, Sec 12, [2.3] be sufficient to satisfy the following conditions with refer-
• earthing connections for distribution systems, see Ch 2, ence to the maximum anticipated ambient temperature:
Sec 12, [2.5] • the current carrying capacity is to be not less than the
• neutral connections for three-phase systems, see Ch 2, highest continuous load carried by the cable
Sec 8, [1.2.4]. • the voltage drop in the circuit, by full load on this cir-
cuit, is not to exceed the specified limits
9.11 Choice of cables • the cross-sectional area calculated on the basis of the
above is to be such that the temperature increases
9.11.1 The rated voltage of any cable is to be not lower which may be caused by overcurrents or starting tran-
than the nominal voltage of the circuit for which it is used. sients do not damage the insulation.
10.1.2 Where electrical equipment of a safe type is permit- • tested specially for Zone 2 (e.g. type “n” protection)
ted in hazardous areas it is to be selected with due consid- • pressurised, and accepted by the appropriate authority
eration to the following:
• encapsulated, and accepted by the appropriate authority
a) risk of explosive dust concentration (see Ch 2, Sec 2,
• the type which ensures the absence of sparks and arcs
[6.2]):
and of “hot spots” during its normal operation (mini-
• degree of protection of the enclosure mum class of protection IP 55).
• maximum surface temperature
10.1.8 When apparatus incorporates a number of types of
b) risk of explosive gas atmosphere (see Ch 2, Sec 2, [6.1]):
protection, it is to be ensured that all are suitable for use in
• explosion group the zone in which it is located.
• temperature class.
10.1.6 For electrical equipment installed in Zone 1 hazard- 10.3 Electrical installations in battery rooms
ous areas, only the following types are permitted:
• any type that may be considered for Zone 0 10.3.1 Only lighting fittings may be installed in compart-
• certified intrinsically-safe apparatus Ex(ib) ments assigned solely to large vented storage batteries (see
Ch 2, Sec 11, [6.2.1]).
• simple electrical apparatus and components (e.g. ther-
mocouples, photocells, strain gauges, junction boxes, The associated switches are to be installed outside such
switching devices), included in intrinsically-safe circuits spaces.
of category “ib” not capable of storing or generating Electric ventilator motors are to be outside ventilation ducts
electrical power or energy in excess of limits stated in and, if within 3 m of the exhaust end of the duct, they are to
the relevant rules, and accepted by the appropriate be of an explosion-proof safe type. The impeller of the fan is
authority to be of the non-sparking type.
• certified flameproof Ex(d) Overcurrent protective devices are to be installed as close
• certified pressurised Ex(p) as possible to, but outside of, battery rooms.
• certified increased safety Ex(e) Electrical cables other than those pertaining to the equip-
• certified encapsulated Ex(m) ment arranged in battery rooms are not permitted.
• certified sand filled Ex(q)
10.3.2 Electrical equipment for use in battery rooms is to
• certified specially Ex(s) have minimum explosion group IIC and temperature class
• through runs of cable. T1.
10.1.7 For electrical equipment installed in Zone 2 hazard- 10.3.3 Standard marine electrical equipment may be
ous areas, only the following types are permitted: installed in compartments assigned solely to valve-regu-
• any type that may be considered for Zone 1 lated sealed storage batteries.
10.4 Electrical installations in paint stores or 10.4.5 Enclosed spaces giving access to paint stores may
enclosed spaces leading to paint stores be considered as non-hazardous, provided that:
• the door to the paint store is a gastight door with self-
10.4.1 Electrical equipment is to be installed in paint stores closing devices without holding back arrangements
and in ventilation ducts serving such spaces only when it is • the paint store is provided with an acceptable, inde-
essential for operational services. pendent, natural ventilation system ventilated from a
Certified safe type equipment of the following type is safe area
acceptable: • warning notices are fitted adjacent to the paint store
• certified intrinsically-safe apparatus Ex(i) entrance stating that the store contains flammable liq-
• certified flameproof Ex(d) uids.
• certified pressurised Ex(p) Note 1: The paint stores and inlet and exhaust ventilation ducts
• certified increased safety Ex(e) under [10.4.4] are classified as Zone 1 and areas on open deck
under [10.4.4] are classified as Zone 2 as defined in IEC standard
• certified specially Ex(s).
60092-502.
Cables (through runs or termination cables) of armoured Note 2: A watertight door may be considered as being gastight.
type or installed in metallic conduit are to be used.
10.5 Electrical installations in stores for
10.4.2 Switches, protective devices and motor control gear
of electrical equipment installed in a paint store are to inter-
welding gas (acetylene) bottles
rupt all poles or phases and are preferably to be located in a 10.5.1 The following equipment may be installed in stores
non hazardous space. for welding gas bottles provided that it is of a safe type
appropriate for Zone 1 area installation:
10.4.3 Electrical equipment for use in paint stores is to
have minimum explosion group IIB and temperature class • lighting fittings
T3. • ventilator motors where provided.
10.4.4 In the areas on open deck within 1 m of inlet and 10.5.2 Electrical cables other than those pertaining to the
exhaust ventilation openings of paint stores or 3 m of equipment arranged in stores for welding gas bottles are not
exhaust mechanical ventilation outlets of such spaces, fol- permitted.
lowing electrical equipment may be installed:
10.5.3 Electrical equipment for use in stores for welding
• electrical equipment with the type of protection as per-
gas bottles is to have minimum explosion group IIC and
mitted in paint stores, or
temperature class T2.
• equipment of protection class Exn, or
• appliances which do not generate arcs in service and 10.6 Special ships
whose surface does not reach unacceptably high tem-
perature, or 10.6.1 For installations in hazardous areas in:
• appliances with simplified pressurised enclosures or • oil tankers, chemical tankers and liquefied gas carriers,
vapour proof enclosures( minimum class of protection see Pt D, Ch 7, Sec 5, Pt D, Ch 8, Sec 10 or Pt D, Ch 9,
IP55) whose surface does not reach unacceptably high Sec 10
temperature • ships arranged with spaces for the carriage of vehicles,
• cables as specified in [10.4.1]. see Pt D, Ch 1, Sec 4 or Pt D, Ch 12, Sec 4.
1 Constructional and operational 1.2.3 Sliprings, commutators and brushgear are to be read-
ily accessible for inspection, repairs and maintenance.
requirements for generators and
motors
1.3 Terminal connectors
1.1 Mechanical construction 1.3.1 Suitable, fixed terminal connectors are to be pro-
vided in an accessible position for connection of the exter-
1.1.1 Materials and construction of electrical machines are nal cables.
to conform to the relevant requirements of Ch 2, Sec 2, [4]
and Ch 2, Sec 2, [5]. 1.3.2 All terminal connectors are to be clearly identified
with reference to a diagram.
1.1.2 Shafts are to be made of material complying with the
provisions of NR216 Materials and Welding, Ch 2, Sec 3 or, 1.3.3 The degree of protection of terminal boxes is to be
where rolled products are allowed in place of forgings, with adequate to that of the machine.
those of NR216 Materialsand Welding, Ch 2, Sec 1.
1.4 Electrical insulation
1.1.3 Where welded parts are foreseen on shafts and rotors,
the provisions of NR216 Materials and Welding, Chapter 5 1.4.1 Insulating materials for windings and other current
are to apply. carrying parts are to comply with the requirements of Ch 2,
Sec 2, [4.2] and Ch 2, Sec 2, [4.3].
1.1.4 Sleeve bearings are to be efficiently and automati-
cally lubricated at all running speeds. 2 Special requirements for generators
Provision is to be made for preventing the lubricant from
gaining access to windings or other insulated or bare cur- 2.1 Prime movers, speed governors and
rent carrying parts.
overspeed protection
1.1.5 Means are to be provided to prevent bearings from
2.1.1 Prime movers for generators are to comply with the
being damaged by the flow of currents circulating between
relevant requirements of Ch 1, Sec 2, [2.8].
them and the shaft. According to the manufacturer’s
requirements, electrical insulation of at least one bearing is 2.1.2 When generators are to operate in parallel, the char-
to be considered. acteristics of speed governors are to comply with the provi-
sions of [2.2].
1.1.6 For surface-cooled machines with an external fan
installed on the open deck, adequate protection of the fan
against icing is to be provided. 2.2 A.c. generators
1.2.1 Sliprings and commutators with their brushgear are to 2.2.3 Each alternator is to be provided with automatic
be so constructed that undue arcing is avoided under all means of voltage regulation.
normal load conditions.
2.2.4 For a.c. generating sets operating in parallel, the gov-
1.2.2 The working position of brushgear is to be clearly and erning characteristics regarding the load are to comply with
permanently marked. requirement of Ch 1, Sec 2, [2.8.5].
2.2.5 When a.c. generators are operated in parallel, the Note 1: An alternative inspection scheme may be agreed by the
reactive loads of the individual generating sets are not to Society with the manufacturer whereby the attendance of the Sur-
differ from their proportionate share of the total reactive veyor will not be required as indicated above.
load by more than 10% of the rated reactive power of the
largest machine, or 25% of that of the smallest machine, 3.2 Shaft material
whichever is the lesser.
3.2.1 Shaft material for electric propulsion motors and for
main engine driven generators where the shaft is part of the
3 Testing of rotating machines propulsion shafting is to be certified by the Society.
3.1.3 All tests are to be carried out according to IEC Publi- 4.1 Technical documentation and visual
cation 60092-301. inspection
3.1.4 All machines of 100 KW and over, intended for 4.1.1 Technical documentation of machines rated at 100
essential services are to be surveyed by the Society during kW (kVA) and over are to be available for examination by
testing and, if appropriate, during manufacturing. the Surveyor.
4.1.2 A visual inspection of the machine is to be made to 4.5 Rated load test and temperature rise
ensure, as far as practicable, that it complies with the tech- measurements
nical documentation.
4.5.1 The temperature rises are to be measured at the rated
4.2 Insulation resistance measurement out-put, voltage and frequency and for the duty for which
the machine is rated and marked in accordance with the
4.2.1 Immediately after the high voltage tests the insulation testing methods specified in IEC Publication 60034-1, or by
resistances are to be measured using a direct current insula- means of a combination of other tests.
tion tester between:
a) all current carrying parts connected together and earth 4.5.2 The limits of temperature rise above ambient air tem-
perature of 45°C for air-cooled machines are those given in
b) all current carrying parts of different polarity or phase, Tab 3 .
where both ends of each polarity or phase are individu-
ally accessible.
4.6 Overload/ overcurrent test
The minimum values of test voltages and corresponding
insulation resistances are given in Tab 2. The insulation 4.6.1 Overload test is to be carried out as a type test for
resistance is to be measured close to the operating tempera- generators as proof of overload capability of generators and
ture, or an appropriate method of calculation is to be used. the excitation system, for motors as proof of momentary
excess torque as required in IEC Publication 60034-1. The
Table 2 : Minimum insulation resistance over-load test can be replaced at a routine test by an over-
current test. The overcurrent test is to be proof of the current
Minimum Minimum insulation
Rated voltage Un V capability of the windings, wires, connections etc. of each
test voltage V resistance MΩ
machine. The overcurrent test can be performed at reduced
Un = 250 2 Un 1 speed (motors) or at short-circuit (generators).
250 < Un ≤ 1000 500 1
4.6.2 In the case of machines for special uses (e.g. for
1000 < Un ≤ 7200 1000 Un/1000 + 1 wind-lasses), overload values other than the above may be
7200 < Un ≤ 15000 5000 Un/1000 + 1 considered.
4.3 Winding resistance measurement 4.7 Verification of the steady short circuit
current
4.3.1 The resistances of the machine windings are to be
measured and recorded using an appropriate bridge 4.7.1 It is to be verified that under steady state short-circuit
method or voltage and current method. conditions, the generator with its voltage regulating system
is capable of maintaining, without sustaining any damage, a
4.4 Verification of the voltage regulation current of at least three times the rated current for a duration
of at least 2 s or, where precise data is available, for a dura-
4.4.1 The alternating current generator, together with its tion of any time delay which may be fitted in a tripping
voltage regulation system, is to be verified in such a way device for discrimination purposes.
that, at all loads from no load running to full load, the rated
voltage at the rated power factor is maintained under steady
conditions within ± 2,5%. These limits may be increased to 4.8 Overspeed test
± 3,5% for emergency sets.
4.8.1 Machines are to withstand the overspeed test as spec-
4.4.2 When the generator is driven at rated speed, giving its ified in IEC Publication 60034-1. This test is not applicable
rated voltage, and is subjected to a sudden change of sym- for squirrel cage motors.
metrical load within the limits of specified current and
power factor, the voltage is not to fall below 85% nor 4.9 Dielectric strength test
exceed 120% of the rated voltage.
4.9.1 New and completed rotating machines are to with-
4.4.3 The voltage of the generator is then to be restored to stand a dielectric test as specified in IEC Publication 60034-1.
within plus or minus 3% of the rated voltage for the main
generator sets in not more than 1.5 s. For emergency sets, 4.9.2 For high voltage machines an impulse test is to be
these values may be increased to plus or minus 4% in not carried out on the coils according to Ch 2, Sec 13.
more than 5 s, respectively.
4.9.3 When it is necessary to perform an additional high
4.4.4 In the absence of precise information concerning the voltage test, this is to be carried out after any further drying,
maximum values of the sudden loads, the following condi- with a test voltage of 80% of that specified in IEC Publica-
tions may be assumed: 60% of the rated current with a tion 60034-1.
power factor of between 0.4 lagging and zero to be sud-
denly switched on with the generator running at no load, 4.9.4 Completely rewound windings of used machines are
and then switched off after steady - state conditions have to be tested with the full test voltage applied in the case of
been reached. new machines.
Table 3 : Temperature rise limits for air-cooled machines based on an ambient temperature of 45°C
4.9.5 Partially rewound windings are to be tested at 75% of 4.10 No load test
the test voltage required for new machines. Prior to the test,
the old part of the winding is to be carefully cleaned and 4.10.1 Machines are to be operated at no load and rated
dried. speed whilst being supplied at rated voltage and frequency
as a motor while generators are to be driven by a suitable
4.9.6 Following cleaning and drying, overhauled machines means and excited to give rated terminal voltage.
are to be subjected to a test at a voltage equal to 1,5 times
During the running test, the vibration of the machine and
the rated voltage, with a minimum of 500 V if the rated volt-
operation of the bearing lubrication system, if appropriate,
age is less than 100 V, and with a minimum of 1000 V if the
are to be checked.
rated voltage is equal to or greater than 100 V.
4.9.7 A repetition of the high voltage test for groups of 4.11 Verification of degree of protection
machines and apparatus is to be avoided if possible, but if a
test on an assembled group of several pieces of new appara- 4.11.1 As specified in IEC Publication 60034-5.
tus, each of which has previously passed its high voltage
test, is per-formed, the test voltage to be applied to such 4.12 Verification of bearings
assembled group is 80% of the lowest test voltage appropri-
ate for any part of the group. 4.12.1 Upon completion of the above tests, machines
Note 1: For windings of one or more machines connected together which have sleeve bearings are to be opened upon request
electrically, the voltage to be considered is the maximum voltage for examination by the Surveyor, to establish that the shaft is
that occurs in relation to earth. correctly seated in the bearing shells.
SECTION 5 TRANSFORMERS
1 Constructional and operational For transformers with a power lower than 5 kVA per phase,
this voltage drop is not to exceed 5%.
requirements
An exception is made for special transformers, such as start-
ing and instrument transformers, for which a different volt-
1.1 Construction
age variation may be considered.
1.1.1 Transformers, except those for motor starting, are to
1.3.2 In determining the voltage ratio and the impedance
be double wound (two or more separate windings).
voltage of transformers, account is to be taken of the total
1.1.2 Transformers are normally to be of the dry, air-cooled permitted voltage drop from the main switchboard’s busbars
type. to the consumers (see Ch 2, Sec 3, [9.11.4]).
1.1.3 When a forced air cooling system is used, an alarm is 1.3.3 Transformers are to be constructed to withstand,
to be activated in the event of its failure. without damage, the thermal and mechanical effects of a
secondary terminal short-circuit for 2 s, with rated primary
1.1.4 Liquid-cooled transformers may be used provided voltage and frequency.
that: For transformers of 1 MVA and over, this is to be justified
• the liquid is non-toxic and of a type which does not with appropriate tests or documentation.
readily support combustion
1.3.4 When transformers are so arranged that their second-
• the construction is such that the liquid is not spilled in
ary windings may be connected in parallel, their winding
inclined position
connections are to be compatible, their rated voltage ratios
• temperature and pressure relief devices with an alarm are to be equal (with tolerances allowed) and their short-cir-
are installed cuit impedance values, expressed as a percentage, are to
• drip trays or other suitable arrangements for collecting have a ratio within 0,9 to 1,1.
the liquid from leakages are provided When transformers are intended for operation in parallel,
• a liquid gauge indicating the normal liquid level range the rated power of the smallest transformer in the group is to
is fitted. be not less than half of the rated power of the largest trans-
former in the group.
1.1.5 Transformers are to have enclosures with a degree of
protection in accordance with Ch 2, Sec 3, Tab 2.
1.4 Electrical insulation and temperature rise
1.2 Terminals 1.4.1 Insulating materials for windings and other current
carrying parts are to comply with the requirements of Ch 2,
1.2.1 Suitable fixed terminal connections are to be pro- Sec 2.
vided in an accessible position with sufficient space for
convenient connection of the external cables. 1.4.2 All windings of air-cooled transformers are to be suit-
ably treated to resist moisture, air salt mist and oil vapours.
1.2.2 Terminals are to be clearly identified.
1.4.3 The permissible limits of temperature rise with an
1.3 Voltage variation, short-circuit conditions ambient air temperature of 45°C for (natural or forced) air-
and parallel operation cooled transformers are given in Tab 1. The temperature
rises shown for windings refer to measurement by the resist-
1.3.1 Under resistive load (cos Φ = 1), the voltage drop ance method while those for the core refer to the thermom-
from no load to full load is not to exceed 2,5%. eter method.
1.1.1 Semiconductor convertors are generally to comply 1.2.3 Semiconductor convertors are not to cause distortion
with the requirements for switchgear assemblies (see Ch 2, in the voltage wave form of the power supply at levels
Sec 8).
exceeding the voltage wave form tolerances at the other
user input terminals (see Ch 2, Sec 2, [2.4]).
1.1.2 The monitoring and control circuits are generally to
comply with the requirements of Part C, Chapter 3.
1.2.4 An alarm is to be provided for tripping of protective
1.1.3 For liquid-cooled convertors the following provisions devices against overvoltages and overcurrents in electric
are to be satisfied: propulsion convertors and for convertors for the emergency
source of power.
• liquid is to be non-toxic and of low flammability
• drip trays or other suitable means are to be provided to
1.3 Parallel operation with other power
contain any liquid leakages
sources
• the resistivity of the cooling fluid in direct contact with
semiconductor or other current carrying parts is to be
1.3.1 For convertors arranged to operate in parallel with
monitored and an alarm initiated if the resistivity is out-
other power sources, load sharing is to be such that under
side the specified limits.
normal operating conditions overloading of any unit does
1.1.4 Where forced cooling is used, the temperature of the not occur and the combination of paralleled equipment is
heated cooling medium is to be monitored. stable.
1.1.5 Where forced (air or liquid) cooling is provided, it is 1.4.1 The permissible limit of temperature rise of the enclo-
to be so arranged that the convertor cannot be or remain sure of the semiconductors is to be assessed on the basis of
loaded unless effective cooling is maintained. an ambient air temperature of 45°C or sea water tempera-
Alternatively, other effective means of protection against ture of 32°C for water-cooled elements, taking into account
overtemperature may be provided. its specified maximum permissible temperature value.
1.1.6 Stacks of semiconductor elements, and other equip- 1.4.2 The value of the maximum permissible temperature
ment such as fuses, or control and firing circuit boards etc., of the elements at the point where this can be measured
are to be so arranged that they can be removed from equip- (point of reference) is to be stated by the manufacturer.
ment without dismantling the complete unit.
1.4.3 The value of the mean rated current of the semicon-
1.1.7 Semiconductor convertors are to be rated for the
ductor element is to be stated by the manufacturer.
required duty having regard to the peak loads, system tran-
sient and overvoltage and to be dimensioned so as to with-
stand the maximum short-circuit currents foreseen at the 1.5 Insulation test
point of installation for the time necessary to trip the protec-
tion of the circuits they supply.
1.5.1 The test procedure is that specified in IEC Publication
60146.
1.2 Protection
1.5.2 The effective value of the test voltage for the insula-
1.2.1 Semiconductor elements are to be protected against tion test is to be as shown in Tab 1.
short-circuit by means of devices suitable for the point of
installation in the network.
Table 1 : Test voltages for high voltage test 2.2.4 An external bypass is to be provided.
on static convertors
2.2.5 The UPS unit is to be monitored and audible and vis-
ual alarm is to be given in a normally attended location for:
Um
-------
-= U Test voltage
2 • power supply failure (voltage and frequency) to the con-
V nected load
in V (1)
• earth fault
U ≤ 60 600
• operation of battery protective device
60 < U ≤ 90 900
• when the battery is being discharged
2 U + 1000
90 < U • when the bypass is in operation for on-line UPS units.
(at least 2000)
(1) Um: highest crest value to be expected between any
pair of terminals. 2.3 Location
2.1.3 Line interactive UPS unit 2.4.4 On restoration of the input power, the rating of the
An off-line UPS unit where the bypass line switch to stored charge unit shall be sufficient to recharge the batteries while
energy power when the input power goes outside the preset maintaining the output supply to the load equipment.
voltage and frequency limits.
3 Testing
2.1.4 On line UPS unit
A UPS unit where under normal operation the output load 3.1 General
is powered from the inverter, and will therefore continue to
operate without break in the event of the supply input fail- 3.1.1 Convertors intended for essential services are to be
ing or going outside preset limits. subjected to the tests stated in [2.2].
2.2.3 The type of UPS unit employed, whether off-line, line 3.1.4 The tests and, if appropriate, manufacture of conver-
interactive or on-line, is to be appropriate to the power sup- tors of 50 kVA and over intended for essential services are
ply requirements of the connected load equipment. to be attended by a Surveyor of the Society.
3.2 Tests on convertors 3.3 Additional testing and survey for unin-
terruptible power system (UPS) units as
3.2.1 Convertors are to be subjected to tests in accordance alternative and/or transitional power
with Tab 2.
3.3.1 UPS units of 50 kVA and over are to be surveyed by
Type tests are the tests to be carried out on a prototype con- the Society during manufacturing and testing.
vertor or the first of a batch of convertors, and routine tests
3.3.2 Appropriate testing is to be carried out to demon-
are the tests to be carried out on subsequent convertors of a
strate that the UPS unit is suitable for its intended environ-
particular type.
ment. This is expected to include as a minimum the
following tests:
3.2.2 The electronic components of the convertors are to be
• functionality, including operation of alarms
constructed to withstand the tests required in Ch 3, Sec 6.
• ventilation rate
• battery capacity.
3.2.3 Final approval of convertors is to include complete
function tests after installation on board, performed with all 3.3.3 Where the supply is to be maintained without a break
ship’s systems in operation and in all characteristic load following a power input failure, this is to be verified after
conditions. installation by practical test.
1.2.4 It is to be possible to check the electrolyte level and 2.1.5 Trickle charging to neutralise internal losses is to be
the ph. provided. An indication is to be provided to indicate a
charging voltage being present at the charging unit.
1.3 Valve-regulated sealed batteries
2.1.6 Protection against reversal of the charging current is
to be provided.
1.3.1 Valve-regulated sealed batteries are batteries whose
cells are closed under normal conditions but which have an 2.1.7 Battery chargers are to be constructed to simplify
arrangement which allows the escape of gas if the internal maintenance operation. Indications are to be provided to
pressure exceeds a predetermined value. The cells cannot visualise the proper operation of the charger and for trou-
normally receive addition to the electrolyte. bleshooting.
Note 1: The cells of batteries which are marketed as “sealed” or
“maintenance free” are fitted with a pressure relief valve as a safety 2.2 Tests on chargers
precaution to enable uncombined gas to be vented to the atmos-
phere; they should more properly be referred to as valve-regulated
2.2.1 Battery chargers are to be subjected to tests in
sealed batteries. In some circumstances the quantity of gas vented
can be up to 25% of the equivalent vented design. The design is to
accordance with Tab 1.
take into consideration provision for proper ventilation. Type tests are the tests to be carried out on a prototype
charger or the first of a batch of chargers, and routine tests
1.3.2 Cell design is to minimise risks of release of gas under are the tests to be carried out on subsequent chargers of a
normal and abnormal conditions. particular type.
2.2.2 The electronic components of the battery chargers 2.2.3 The tests of battery chargers of 5 kW and over
are to be constructed to withstand the tests required in Ch intended for essential services are to be attended by a Sur-
3, Sec 6. veyor of the Society.
1 Constructional requirements for 1.1.9 All parts of the switchboard are to be readily accessi-
main and emergency switchboards ble for maintenance, repair or replacement. In particular,
fuses are to be able to be safely inserted and withdrawn
from their fuse-bases.
1.1 Construction
1.1.10 Hinged doors which are to be opened for operation
1.1.1 Construction is to be in accordance with IEC Publica-
tion 60092-302. of equipment on the door or inside are to be provided with
fixing devices for keeping them in open position.
1.1.2 Where the framework, panels and doors of the enclo-
sure are of steel, suitable measures are to be taken to prevent 1.1.11 Means of isolation of the circuit-breakers of genera-
overheating due to the possible circulation of eddy currents. tors and other important parts of the installation are to be
provided so as to permit safe maintenance while the main
1.1.3 Insulating material for panels and other elements of busbars are alive.
the switchboard is at least to be moisture-resistant and
flame-retardant.
1.1.12 Where components with voltage exceeding the
1.1.4 Switchboards are to be of dead front type, with safety voltage are mounted on hinged doors, the latter are to
enclosure protection according to Ch 2, Sec 3, Tab 2. be electrically connected to the switchboard by means of a
separate, flexible protective conductor.
1.1.5 Switchboards are to be provided with insulated hand-
rails or handles fitted in an appropriate position at the front 1.1.13 All measuring instruments and all monitoring and
of the switchboard. Where access to the rear is necessary control devices are to be clearly identified with indelible
for operational or maintenance purposes, an insulated labels of durable, flame-retardant material.
handrail or insulated handles are to be fitted.
1.1.6 Where the aggregate capacity of generators con- 1.1.14 The rating of each circuit, together with the rating of
nected to the main busbars exceeds 100 kVA, a separate the fuse or the appropriate setting of the overload protective
cubicle for each generator is to be arranged with flame- device (circuit-breaker, thermal relay etc.) for each circuit is
retardant partitions between the different cubicles. Similar to be permanently indicated at the location of the fuse or
partitions are to be provided between the generator cubi- protective device.
cles and outgoing circuits.
1.1.7 Instruments, handles or push-buttons for switchgear 1.2 Busbars and bare conductors
operation are to be placed on the front of the switchboard.
All other parts which require operation are to be accessible 1.2.1 Busbars are to be of copper or of copper-surrounded
and so placed that the risk of accidental touching of live aluminium alloy if suitable for use in the marine environment
parts, or accidental making of short-circuits and earthings, and if precautions are taken to avoid galvanic corrosion.
is reduced as far as practicable.
1.2.2 All connections are to be so made as to inhibit corrosion.
1.1.8 Where it is necessary to make provision for the open-
ing of the doors of the switchboard, this is to be in accord-
ance with one of the following requirements: 1.2.3 Busbars are to be dimensioned in accordance with
IEC Publication 60092-302.
a) opening is to necessitate the use of a key or tool (e.g.
when it is necessary to replace a lamp or a fuse-link) The mean temperature rise of busbars is not to exceed 45°C
b) all live parts which can be accidentally touched after under rated current condition with an ambient air tempera-
the door has been opened are to be disconnected before ture of 45°C (see Ch 2, Sec 2, [1.2.2]) and is not to have any
the door can be opened harmful effect on adjacent components. Higher values of
temperature rise may be accepted to the satisfaction of the
c) the switchboard is to include an internal barrier or shut-
Society.
ter with a degree of protection not less than IP2X shield-
ing all live parts such that they cannot accidentally be
touched when the door is open. It is not to be possible 1.2.4 The cross-section of neutral connection on an a.c.
to remove this barrier or shutter except by the use of a three-phase, four-wire system is to be at least 50% of the
key or tool. cross-section for the corresponding phases.
1.2.5 Bare main busbars, excluding the conductors 1.3.4 All conductors are to be secured to prevent vibration
between the main busbars and the supply side of outgoing and are to be kept away from sharp edges.
units, are to have the minimum clearances and creepage
distances given in Tab 1. The values shown apply to clear- 1.3.5 Connections leading to indicating and control instru-
ances and creepage distances between live parts as well as ments or apparatus mounted in doors are to be installed
between live parts and exposed conductive parts. such that they cannot be mechanically damaged due to
Note 1: Clearance is the distance between two conductive parts movement of the doors.
along a string stretched the shortest way between such parts.
Creepage distance is the shortest distance along the surface of an 1.3.6 Non-metallic trays for internal wiring of switchboards
insulating material between two conductive parts. are to be of flame-retardant material.
Table 1 : Clearance and creepage distances 1.3.7 Control circuits are to be installed and protected such
that they cannot be damaged by arcs from the protective
Rated insulation voltage Minimum Minimum creep- devices.
a.c. r.m.s. or d.c., clearance, age distance,
in V in mm in mm 1.3.8 Where foreseen, fixed terminal connectors for con-
≤ 250 15 20 nection of the external cables are to be arranged in readily
accessible positions.
> 250 to ≤ 690 20 25
> 690 25 35
1.4 Switchgear and controlgear
1.2.6 Reduced values as specified in IEC Publication
60092-302 may be accepted for type tested and partially 1.4.1 Switchgear and controlgear are to comply with IEC
type tested assemblies. Publication 60947 series and to be chosen from among that
The reference values for the evaluation of the minimum type approved by the Society.
clearances and creepage distances for these assemblies are
based on the following: 1.4.2 The characteristics of switchgear, controlgear and
• pollution degree 3 (conductive pollution occurs, or dry protective devices for the various consumers are to be in
non-conductive pollution occurs which becomes con- compliance with Ch 2, Sec 3, [7].
ductive due to condensation which is expected)
• overvoltage category III (distribution circuit level)
1.5 Auxiliary circuits
• unhomogenous field conditions (case A) 1.5.1 Auxiliary circuits are to be designed in such a manner
• rated operational voltage 1000 V a.c., 1500 V d.c. that, as far as practicable, faults in such circuits do not
• group of insulating material IIIa. impair the safety of the system. In particular, control circuits
are to be designed so as to limit the dangers resulting from a
Special consideration is to be given to equipment located in fault between the control circuit and earth (e.g. inadvertent
spaces where a pollution degree higher than 3 is applica- operation or malfunction of a component in the installa-
ble, e.g. in diesel engine rooms. tion), also taking account of the earthing system of their
supply.
1.2.7 Busbars and other bare conductors with their sup-
ports are to be mechanically dimensioned and fixed such
1.5.2 Auxiliary circuits of essential systems are to be inde-
that they can withstand the stresses caused by short-circuits.
pendent of other auxiliary circuits.
Where maximum symetrical short-circuit currents are
expected to exceed 50 kA, calculation is to be submitted to 1.5.3 Common auxiliary circuits for groups of consumers
the Society. are permitted only when the failure of one consumer jeop-
ardises the operation of the entire system to which it
1.2.8 Busbars and bare conductors are to be protected,
belongs.
where necessary, against falling objects (e.g. tools, fuses or
other objects).
1.5.4 Auxiliary circuits are to be branched off from the
main circuit in which the relevant switchgear is used.
1.3 Internal wiring
1.5.5 The supply of auxiliary circuits by specifically
1.3.1 Insulated conductors for internal wiring of auxiliary
arranged control distribution systems will be specially con-
circuits of switchboards are to be constructed in accord-
sidered by the Society.
ance with Ch 2, Sec 9, [1.1.5].
1.3.2 All insulated conductors provided for in [1.3.1] are to 1.5.6 Means are to be provided for isolating the auxiliary
be of flexible construction and of the stranded type. circuits as well when the main circuit is isolated (e.g. for
maintenance purposes).
1.3.3 Connections from busbars to protective devices are to
be as short as possible. They are to be laid and secured in 1.5.7 For the protection of auxiliary circuits see Ch 2, Sec 3,
such a way to minimise the risk of a short-circuit. [7.13].
1.6.11 For paralleling purposes the following are to be pro- 3.1.2 The manufacturer is to issue the relative test reports
vided: providing information concerning the construction, serial
number and technical data relevant to the switchboard, as
• 2 voltmeters well as the results of the tests required.
• 2 frequency meters
3.1.3 The tests are to be carried out prior to installation on
• 1 synchroscope and synchronising indicating lamps or board.
equivalent means.
3.1.4 The test procedures are as specified in IEC Publica-
A switch is to be provided to enable one voltmeter and one
tion 60092-302.
frequency meter to be connected to each generator before
the latter is connected to the busbars.
3.1.5 The tests of main switchboards, emergency switch-
The other voltmeter and frequency meter are to be perma- boards or switchboards rated above 100 kW are to be
nently connected to the busbars. attended by a surveyor of the Society.
3.2 Inspection of equipment, check of wiring 3.3.3 The test voltage at the moment of application is not to
and electrical operation test exceed half of the prescribed value. It is then to be
increased steadily within a few seconds to its full value. The
3.2.1 It is to be verified that the switchboard: prescribed test voltage is to be maintained for 1 minute.
• complies with the approved drawings 3.3.4 The value of the test voltage for main and auxiliary
• maintains the prescribed degree of protection circuits is given in Tab 2 and Tab 3.
• is constructed in accordance with the relevant construc-
tional requirements, in particular as regards creepage Table 2 : Test voltages for main circuits
and clearance distances.
Rated insulation voltage Ui, Test voltage a.c. (r.m.s.),
in V in V
3.2.2 The connections, especially screwed or bolted con-
nections, are to be checked for adequate contact, possibly Ui ≤ 60 1000
by random tests. 60 < Ui ≤ 300 2000
3.2.3 Depending on the complexity of the switchboard it 300 < Ui ≤ 660 2500
may be necessary to carry out an electrical functioning test. 660 < Ui ≤ 800 3000
The test procedure and the number of tests depend on
800 < Ui ≤ 1000 3500
whether or not the switchboard includes complicated inter-
locks, sequence control facilities, etc. In some cases it may
be necessary to conduct or repeat this test following instal- Table 3 : Test voltage for auxiliary circuits
lation on board.
SECTION 9 CABLES
1.1 Construction 1.2.3 All conductors are to be stranded, except for cables
of nominal cross-sectional area 2,5 mm2 and less (provided
1.1.1 Cables and insulated wiring are generally to be con-
that adequate flexibility of the finished cable is assured).
structed in accordance with IEC Publications of the series
60092-3.., as well with the provisions of this Chapter.
1.2.4 For the minimum nominal cross-sectional areas per-
1.1.2 Mineral-insulated cables are to be constructed mitted, see Ch 2, Sec 3, [9.10].
according to IEC Publication 60702.
1.3 Insulating materials
1.1.3 Optical fibre cables are to be constructed in accord-
ance with IEC Publication 60794.
1.3.1 The materials used for insulation are to comply with
IEC Publication 60092-351 and to have the thicknesses
1.1.4 Flexible cables constructed according to national
specified for each type of cable in the relevant standard.
standards will be specially considered by the Society.
The maximum permissible rated temperature is specified for
the various materials.
1.1.5 Cables and insulated wires other than those specified
in IEC Publications are subject to special consideration by
the Society in each case. Those for general purposes are to 1.3.2 Materials and thicknesses other than those in [1.3.1]
be constructed of materials having characteristics which will be specially considered by the Society.
produce a cable at least equivalent to those constructed
from materials referred to in IEC Publications. 1.4 Inner covering, fillers and binders
1.1.6 Insulated wiring for auxiliary circuits of switchboards
1.4.1 The cores of a multicore cable are to be laid up. The
may be constituted by cables with a single conductor of the
spaces between the cores are to be filled so as to obtain an
stranded type for all sections, PVC- or rubber-insulated in
assembly having an essentially circular cross-section. The
accordance with the Publications cited in [1.1.1] and with-
filling may be omitted in multicore cables having a conduc-
out further protection.
tor cross-sectional area not exceeding 4 mm2.
The insulated wiring is to be at least of the flame-retardant
type according to IEC Publication 60332-1. Equivalent When a non-metallic sheath is applied directly over the
types of flame-retardant switchboard wires will be specially inner covering or the fillers, it may substitute partially for
considered by the Society. the inner covering or fillers.
1.1.7 Fire resistant cables are to be designed and tested in 1.4.2 The materials used, the binders and the thicknesses of
accordance with the relevant IEC Publication 60092-series the inner coverings are generally to be in accordance with
Standards and comply with the requirements of IEC 60331- IEC Publications of the series 60092-3.., in relation to the
31 for cables of greater than 20 mm overall diameter, other- type of cable.
wise IEC 60331-21.
Note 1:For installation methods refer to those specified in Ch 2, Sec 1.5 Protective coverings (armour and
12, [7.1.4]. sheath)
Note 2:Fire resistant type cables are to be easily distinguishable.
Note 3:For special cables, requirements in the following standards 1.5.1 Metallic armour, if not otherwise protected against
may be used : corrosion, is to be protected by means of a coating of pro-
tective paint (see Ch 2, Sec 3, [9.3]).
• IEC 60331-23: Procedures and requirements - Electric data cables
• IEC331-25: Procedures and requirements - Optical fiber cables 1.5.2 The paint is to be non-flammable and of adequate
viscosity. When dry, it is not to flake off.
1.2 Conductors
1.5.3 The materials and construction used for (metal)
1.2.1 Conductors are to be of annealed electrolytic copper armour are to be in accordance with IEC Publication
with a resistivity not exceeding 17.241 Ω mm2/km at 20°C 60092-350 and their dimensions are to be those specified
according to IEC 60228. for each type of cable in the relevant standard.
1.5.4 The materials used for sheaths are to be in accord- 2.2 Routine tests
ance with IEC Publication 60092-359 and are to have the
thicknesses specified for each type of cable in the relevant 2.2.1 Every length of finished cable is to be subjected to the
standard. tests specified in [2.2.2].
The quality of the materials is to be adequate to the service
temperature of the cable. 2.2.2 The following routine tests are to be carried out:
1.5.5 Materials other than those in [1.5.3] and [1.5.4] will a) visual inspection
be specially considered by the Society. b) check of conductor cross-sectional area by measuring
electrical resistance
1.6 Identification
c) high voltage test
1.6.1 Each cable is to have clear means of identification so
d) insulation resistance measurement
that the manufacturer can be determined.
e) dimensional checks (as necessary).
1.6.2 Fire non propagating cables are to be clearly labelled
with indication of the standard according to which this 2.2.3 The manufacturer is to issue a statement providing
characteristic has been verified and, if applicable, of the information on the type and characteristics of the cable, as
category to which they correspond. well as the results of the tests required and the Type
Approval Certificates.
2 Testing
2.2.4 The test procedure is as specified in IEC Publication
2.1 Type tests 60092-350.
2.1.1 Type tests are to be in accordance with the relevant 2.2.5 Where an alternative scheme, e.g. a certified quality
IEC 60092-3.. Series Publications and IEC 60332-1, IEC assurance system, is recognised by the Society, attendance
60332-3 Category A, and IEC 60331 where applicable. of the Surveyor may not be required.
1 Switchgear and controlgear, protec- 1.3.6 The reverse power protection device is to respond to
the active power regardless of the power factor, and is to
tive devices operate only in the event of reverse power.
4.1.1 Plug-and-socket connections are to comply with IEC 5.3.3 Space heaters are to be provided with a temperature
Publication 60092-306 and with the following additional limiting device without automatic reconnection which
standards in relation to their use: automatically trips all poles or phases not connected to
• in accommodation spaces, day rooms and service earth when the temperature exceeds the maximum permis-
rooms (up to 16 A, 250 V a.c.): IEC Publication 60083 sible value.
or 60320, as applicable
• for power circuits (up to 250 A, 690 V a.c.): IEC Publica-
5.4 Cooking appliances
tion 60309 5.4.1 Live parts of cooking appliances are to be protected
• for electronic switchgear: IEC Publications, e.g. 60130 such that any foods or liquids which boil over or spill do not
and 60603 cause short-circuits or loss of insulation.
• for refrigerated containers: ISO 1496-2.
5.5 Fuel oil and lube oil heaters
5 Heating and cooking appliances 5.5.1 In continuous-flow fuel oil and lube oil heaters, the
maximum temperature of the heating elements is to be
5.1 Applicable requirements below the boiling point of the oil.
SECTION 11 LOCATION
1.1.1 The degree of protection of the enclosures and the 2.2.6 Where essential services for steering and propulsion
environmental categories of the equipment are to be appro- are supplied from section boards, these and any transform-
priate to the spaces or areas in which they are located; see ers, convertors and similar appliances constituting an essen-
Ch 2, Sec 3, Tab 2, Ch 2, Sec 3, Tab 3 and Ch 2, Sec 2, tial part of the electrical supply system are also to satisfy the
[5.2.2]. above provisions.
3.2.2 The arrangement of the main electrical system is to 5.1.4 Cables are generally not to be installed across expan-
be such that a fire or other casualty in spaces containing the sion joints.
main source of electrical power, associated converting Where this is unavoidable, however, a loop of cable of
equipment, if any, the main switchboard and the main light- length proportional to the expansion of the joint is to be
ing switchboard will not render inoperative the emergency provided (see Ch 2, Sec 12, [7.2.2]).
electric lighting system and the other emergency services
other than those located within the spaces where the fire or 5.2 Location of cables in relation to the risk
casualty has occurred.
of fire and overheating
3.3 Emergency switchboard 5.2.1 Cables and wiring serving essential or emergency
power, lighting, internal communications or signals are, so
3.3.1 The emergency switchboard shall be installed as near far as is practicable, to be routed clear of galleys, laundries,
as is practicable to the emergency source of electrical machinery spaces of Category A and their casings and other
power. high fire risk areas, except for supplying equipment in those
spaces.
3.3.2 Where the emergency source of electrical power is a
generator, the emergency switchboard shall be located in 5.2.2 When it is essential that a circuit functions for some
the same space unless the operation of the emergency time during a fire and it is unavoidable to carry the cable for
switchboard would thereby be impaired. such a circuit through a high fire risk area (e.g. cables con-
necting fire pumps to the emergency switchboard), the
3.4 Emergency battery cable is to be of a fire-resistant type or adequately protected
against direct exposure to fire.
3.4.1 No accumulator battery fitted in accordance with the
provisions of Ch 2, Sec 3, [2.3] shall be installed in the same 5.2.3 Main cable runs (see Note 1) and cables for the sup-
space as the emergency switchboard. ply and control of essential services are, as far as is practica-
ble, to be kept away from machinery parts having an
3.4.2 For ships not subject to Solas, accumulator batteries increased fire risk (see Note 2) unless:
fitted in accordance with the provisions of Ch 2, Sec 3, • the cables have to be connected to the subject equipment
[2.3] and connected to a charging device of power of 2 kW
• the cables are protected by a steel bulkhead or deck, or
or less may be accepted in the same space as the emer-
gency switchboard but outside the emergency switchboard • the cables in that area are of the fire-resisting type.
to the satisfaction of the Society. Note 1: Main cable runs are for example:
• cable runs from generators and propulsion motors to main and
4 Distribution boards emergency switchboards
• cable runs directly above or below main and emergency switch-
boards, centralised motor starter panels, section boards and cen-
4.1 Distribution boards for cargo spaces
tralised control panels for propulsion and essential auxiliaries.
and similar spaces
Note 2: Machinery, machinery parts or equipment handling com-
bustibles are considered to present an increased fire risk.
4.1.1 Distribution boards containing multipole switches for
the control of power and lighting circuits in bunkers and 5.2.4 Cables and wiring serving essential or emergency
cargo spaces are to be situated outside such spaces. power, lighting, internal communications or signals are to be
arranged, as far as practicable, in such a manner as to pre-
4.2 Distribution board for navigation lights clude their being rendered unserviceable by heating of the
bulkheads that may be caused by a fire in an adjacent space.
4.2.1 The distribution board for navigation lights is to be
placed in an accessible position on the bridge. 5.2.5 Cables are to be arranged as remote as possible from
sources of heat such as hot pipes, resistors, etc. Where
5 Cable runs installation of cables near heat sources cannot be avoided,
and where there is consequently a risk of damage to the
cables by heat, suitable shields are to be installed, or other
5.1 General precautions to avoid overheating are to be taken, for exam-
ple use of ventilation, heat insulation materials or special
5.1.1 Cable runs are to be selected so as to be as far as
heat-resisting cables.
practicable accessible, with the exception of single cables,
situated behind walls or ceilings constructed of incombusti-
ble materials, supplying lighting fittings and socket-outlets 5.3 Location of cables in relation to electro-
in accommodation spaces, or cables enclosed in pipes or magnetic interference
conduits for installation purposes.
5.3.1 For the installation of cables in the vicinity of radio
5.1.2 Cable runs are to be selected so as to avoid action equipment or of cables belonging to electronic control and
from condensed moisture and from dripping of liquids. monitoring systems, steps are to be taken in order to limit
the effects of unwanted electromagnetic interference (see
5.1.3 Connection and draw boxes are to be accessible. Ch 3, Sec 5).
5.4 Services with a duplicate feeder 6.2.3 The provisions of [6.2.1] and [6.2.2] also apply to
several batteries connected to charging devices of total
5.4.1 In the case of essential services requiring a duplicate power exceeding 2 kW calculated for each one as stated in
supply (e.g. steering gear circuits), the supply and associ- [6.2.1].
ated control cables are to follow different routes which are
to be as far apart as practicable, separated both vertically
6.3 Moderate vented batteries
and horizontally.
6.3.1 Batteries connected to a charging device of power
5.5 Emergency circuits between 0,2 kW and 2 kW calculated as stated in [6.2.1]
(hereafter referred to as "moderate batteries") are to be
5.5.1 Cables supplying emergency circuits are not to run arranged in the same manner as large batteries or placed in
through spaces containing the main source of electrical a box or locker in suitable locations such as machinery
power, associated transforming equipment, if any, the main spaces, storerooms or similar spaces. In machinery spaces
switchboard and the main lighting switchboard, except for and similar well-ventilated compartments, these batteries
cables supplying emergency equipment located within such may be installed without a box or locker provided they are
spaces (see [3.2.2]). protected from falling objects, dripping water and conden-
sation where necessary.
5.6 Electrical distribution in passenger ships
6.3.2 Rooms, lockers or boxes assigned to moderate batter-
5.6.1 For the electrical distribution in passenger ships, see ies are to be provided with natural ventilation or mechani-
Pt D, Ch 11, Sec 5, [1.2]. cal exhaust ventilation, except for batteries installed
without a box or locker (located open) in well-ventilated
6 Storage batteries spaces.
6.1.3 Starter batteries are to be located as close as practica- 6.4.2 Boxes for small batteries may be ventilated only by
ble to the engine or engines served. means of openings near the top to permit escape of gas.
6.1.4 Accumulator batteries shall not be located in sleeping
quarters except where hermetically sealed to the satisfaction 6.5 Ventilation
of the Society.
6.5.1 The ventilation of battery compartments is to be inde-
6.1.5 Lead-acid batteries and alkaline batteries are not to pendent of ventilation systems for other spaces.
be installed in the same compartment (room, locker, box),
unless of valve-regulated sealed type. 6.5.2 The quantity of air expelled (by natural or forced ven-
tilation) for compartments containing vented type batteries
is to be at least equal to:
6.2 Large vented batteries
Q = 110 I n
6.2.1 Batteries connected to a charging device of power where:
exceeding 2 kW, calculated from the maximum obtainable
charging current and the nominal voltage of the battery Q : Quantity of air expelled, in litres per hour
(hereafter referred to as "large batteries") are to be installed I : Maximum current delivered by the charging
in a room assigned to batteries only. equipment during gas formation, but not less
Where this is not possible, they may be arranged in a suita- than one quarter of the maximum obtainable
ble locker on deck. charging current in amperes
n : Number of cells in series.
6.2.2 Rooms assigned to large batteries are to be provided
with mechanical exhaust ventilation. 6.5.3 The quantity of air expelled (by natural or forced ven-
Natural ventilation may be employed for boxes located on tilation) for compartments containing valve-regulated
open deck. sealed batteries is to be at least 25% of that given in [6.5.2].
6.5.4 Ducts are to be made of a corrosion-resisting material 6.5.7 In mechanical exhaust ventilation systems:
or their interior surfaces are to be painted with corrosion- a) electric motors are to be outside the exhaust ducts and
resistant paint. battery compartment and are to be of safe type if
installed within 3 m from the exhaust of the ventilation
6.5.5 Adequate air inlets (whether connected to ducts or duct
not) are to be provided near the floor of battery rooms or the
b) fans are to be so constructed and of a material such as to
bottom of lockers or boxes (except for that of small batter-
render sparking impossible in the event of the impeller
ies).
touching the fan casing
Air inlet may be from the open air or from another space c) steel or aluminium impellers are not to be used
(for example from machinery spaces). d) the system is to be interlocked with the charging device
so that the battery cannot be charged without ventila-
6.5.6 Exhaust ducts of natural ventilation systems: tion (trickle charge may be maintained)
a) are to be run directly from the top of the compartment e) a temperature sensor is to be located in the battery com-
to the open air above (they may terminate in the open or partment to monitor the correct behaviour of the battery
in well-ventilated spaces) in cases where the battery element is sensitive to tem-
perature.
b) are to terminate not less than 90 cm above the top of the
battery compartment 6.5.8 For natural ventilation systems for deck boxes:
a) holes for air inlet are to be provided on at least two
c) are to have no part more than 45° from the vertical
opposite sides of the box
d) are not to contain appliances (for example for barring b) the exhaust duct is to be of ample dimensions
flames) which may impede the free passage of air or gas c) the duct is to terminate at least 1,25 m above the box in
mixtures. a goose-neck or mushroom-head or the equivalent
Where natural ventilation is impracticable or insufficient, d) the degree of protection is to be in accordance with Ch 2,
mechanical exhaust ventilation is to be provided. Sec 3, Tab 2.
SECTION 12 INSTALLATION
1.1.4 Equipment is to be installed so as not to cause, or at 1.4.2 In accepting a lesser ambient temperature than 45°C,
least so as to reduce to a minimum, electromagnetic inter- it is to be ensured that electrical cables for their entire
ference. length are adequately rated for the maximum ambient tem-
perature to which they are exposed along their length.
1.2.3 Equipment is to be so mounted that its enclosing a) supplied at a voltage not exceeding 50 V direct current
arrangements and the functioning of the built-in equipment or 50 V, root mean square between conductors,
will not be affected by distortions, vibrations and movements achieved without the use of auto-transformers (safety
of the ship’s structure or by other damage liable to occur. voltage); or
b) supplied at a voltage not exceeding 250 V by safety iso-
1.2.4 If electrical fittings, not of aluminium, are attached to lating transformers supplying one consuming device
aluminium, suitable provision is to be made to prevent gal- only; or
vanic corrosion.
c) constructed in accordance with the principle of double
insulation.
1.3 Accessibility
2.1.2 To minimise shock from high frequency voltage
1.3.1 Equipment is to be so installed that sufficient space is induced by the radio transmitter, handles, handrails and
available for inspection and maintenance as required for all other metal elements on the bridge or upper decks are to be
its parts (see [6.1.3]). in electrical connection with the hull or superstructures.
2.2.2 For metal frames or enclosures which are not earthed 2.4 Connection to the ship’s structure
as specified in [2.2.1], earthing connections complying
with [2.3] and [2.4] are to be used. 2.4.1 Every connection of an earth-continuity conductor or
earthing lead to the ship’s structure is to be secured by
2.2.3 For requirements regarding the earthing of coverings means of a screw of brass or other corrosion-resistant mate-
of cables and the mechanical protection of cables, see rial of diameter not less than 6 mm.
[7.11] and [7.12].
2.4.2 Such earthing connection is not to be used for other
purposes.
2.3 Earthing connections
2.4.3 The connection described in [2.4.1] is to be located
2.3.1 Every earthing connection is to be of copper or other in an accessible position where it may readily be checked.
corrosion-resistant material and is to be securely installed
and protected, where necessary, against damage and elec-
trolytic corrosion. 2.5 Earthed distribution systems
2.3.2 The nominal cross-sectional area of each copper 2.5.1 The system earthing of earthed distribution systems is
earthing connection is to be not less than that required in to be effected by means independent of any earthing
Tab 1. arrangements of non-current carrying parts and is to be con-
nected to the hull at one point only.
Earthing connections of other metals are to have conduct-
ance at least equal to that specified for a copper earthing 2.5.2 In an earthed distribution system in which the earth-
connection. ing connection does not normally carry current, this con-
nection is to conform with the requirements of [2.3], except
2.3.3 Metal parts of portable appliances are to be earthed, that the lower limit of 70 mm2 does not apply (see Tab 1).
where required (see [2.1.1]), by means of an earth-continu-
ity conductor in the flexible supply cable or cord, which 2.5.3 In a distribution system with hull return, the system
has the cross-sectional area specified in Tab 1 and which is earthing connection is to have at least the same cross-sec-
earthed, for example, through the associated plug and tional area as the feeder lines.
socket.
2.5.4 The earthing connection is to be in an accessible
2.3.4 In no circumstances is the lead sheathing or armour position where it may readily be inspected and discon-
of cables to be relied upon as the sole means of earthing. nected for insulation testing.
Cross-sectional area
Type of earthing connection of associated current Minimum cross-sectional area of copper earthing connection
carrying conductor
1 Earth-continuity any Same as current carrying conductor up to and including 16 mm2 and one half
conductor in flexible above 16 mm2 but at least 16 mm2
cable or flexible cord
2 Earth-continuity any a) for cables having an insulated earth-continuity conductor
conductor • a cross-section equal to the main conductors up to and including
incorporated in fixed 16 mm2, but minimum 1,5 mm2
cable
• a cross-section not less than 50% of the cross-section of the main
conductor when the latter is more than 16 mm2, but at least 16 mm2
b) for cables with a bare earth wire in direct contact with the lead sheath
Cross-section of main conductor, Earthing connection,
in mm2 in mm2
1 ÷ 2,5 1
4÷6 1,5
3 Separate fixed ≤ 2,5 mm2 Same as current carrying conductor subject to minimum of 1,5 mm2 for
earthing conductor stranded earthing connection or 2,5 mm2 for unstranded earthing connection
> 2,5 mm2 but One half the cross-sectional area of the current carrying conductor, subjected
≤ 120 mm2 to a minimum of 4 mm2
> 120 mm2 70 mm2
2.6 Aluminium superstructures 5.2.2 Interior surfaces of metal shelves for battery cells,
whether or not grouped in crates or trays, are to be pro-
2.6.1 When aluminium superstructures are insulated from tected by a lining of electrolyte-resistant material, watertight
the steel hull to prevent electrolytic corrosion, they are to and carried up to at least 75 mm on all sides. In particular,
be secured to the hull by means of a separate bonding con- linings are to have a minimum thickness of 1,5 mm, if of
nection. lead sheet for lead-acid batteries, and of 0,8 mm, if of steel
for alkaline batteries.
2.6.2 The connections are to be adequately close together
and are to have a resistance less than 0,1 Ω. Alternatively, the floor of the room or locker is to be lined as
specified above to a height of at least 150 mm.
2.6.3 The connections are to be located where they may
readily be inspected. 5.2.3 Battery boxes are to be lined in accordance with
[5.2.2] to a height of at least 75 mm.
3 Rotating machines
6 Switchgear and controlgear assemblies
3.1
6.1 Main switchboard
3.1.1 Every rotating machine is preferably to be installed
with the shaft in the fore-and-aft direction. Where a rotating 6.1.1 The main switchboard is to be so arranged as to give
machine of 100 kW and over is installed athwartship, or easy access as may be needed to apparatus and equipment,
vertically, it is to be ensured that the design of the bearings without danger to personnel.
and the arrangements for lubrication are satisfactory to
withstand the rolling specified in Ch 2, Sec 2, Tab 4. 6.1.2 An unobstructed space is to be left in front of the
switchboard wide enough to allow access for operation;
4 Semiconductor convertors such width is generally about 1 metre.
When withdrawable equipment is contained in the switch-
4.1 Semiconductor power convertors board, the width of the space is to be not less than 0,5 m
when the equipment is fully withdrawn.
4.1.1 Naturally air-cooled semiconductor convertors are to
Reduced widths may be considered for small ships.
be installed such that the circulation of air to and from the
stacks or enclosures is not impeded and that the tempera-
6.1.3 Where necessary, an unobstructed space is to be pro-
ture of the cooling inlet air to convertor stacks does not
vided at the rear of the switchboard ample to permit main-
exceed the ambient temperature for which the stacks are
tenance; in general, the width of this passage is to be not
specified.
less than 0,6 m, except that this may be reduced to 0,5 m in
way of stiffeners and frames, and the height sufficient for the
5 Vented type storage batteries operation foreseen.
5.1 General 6.1.4 Where the switchboard is open at the rear, the rear
space in [6.1.3] is to form a locked space provided at each
5.1.1 Batteries are to be arranged so that each cell or crate end with an access door. The required IP protection for the
of cells is accessible from the top and at least one side to corresponding location is to be fulfilled.
permit replacement and periodical maintenance.
6.1.5 If necessary, the clear height above the switchboard
5.1.2 Cells or crates are to be carried on insulating supports specified by the manufacturer is to be maintained for pres-
of material non-absorbent to the electrolyte (e.g. treated sure relief in the event of a short-circuit.
wood).
6.1.6 When the voltage exceeds the safety voltage, non-
5.1.3 Cells are to be securely chocked by means of insulat- conducting mats or gratings are to be provided at the front
ing material non-absorbent to the electrolyte, e.g. strips of and rear of the switchboard as necessary.
treated wood. Special mechanical precautions are to be
taken to prevent the emergency battery from being dam- 6.1.7 Piping and conduits are not to be installed directly
aged by the shock due to a collision. above or in the vicinity of switchboards.
5.1.4 Provision is to be made for the free circulation of air. Where this is unavoidable, pipes and conduits are to have
welded joints only or to be provided with protection against
spray from steam or pressurised liquids or dripping.
5.2 Protection against corrosion
5.2.1 The interior of battery compartments (rooms, lockers, 6.2 Emergency switchboard
boxes) including all metal parts subject to the electrolyte is
to be protected against the deteriorating effect of the latter 6.2.1 For the installation of the emergency switchboard, the
by electrolyte-resistant coating or other equivalent means, same requirements apply as given in [6.1] for the installa-
unless corrosion-resistant materials are used. tion of the main switchboard.
6.3 Section boards and distribution boards b) the use of fire stops having at least B0 penetrations fitted
as follows (see Fig 1, Fig 2, Fig 3 and Fig 4):
6.3.1 For the installation of section and distribution boards, • cable entries at the main and emergency switchboard
the same requirements apply, as far as applicable, as given
• where cables enter engine control rooms
in [6.1] for the installation of the main switchboard.
• cable entries at centralised control panels for pro-
pulsion machinery and essential auxiliaries
7 Cables
• at each end of totally enclosed cable trunks
• at every second deck or approximately 6 metres for
7.1 General verticals runs and every 14 metres for horizontal
runs in enclosed and semi-enclosed spaces
7.1.1 Cables having insulating materials with different
maximum permissible conductor temperatures are not to be • at the boundaries of the spaces in cargo areas.
bunched together.
Figure 1 : Totally enclosed trunks
Where this is not practicable, the cables are to be so
installed that no cable reaches a temperature higher than its
rating.
2a
a B
2a
2a
14 m
BO BO
Penetration Penetration
DECK DECK
a Steel plate
1a
c) the use of fire protection coating applied to at least 1 7.2.2 Where the installation of cables across expansion
metre in every 14 metres on horizontal cable runs and joints is unavoidable, the minimum internal radius of the
over the entire length of vertical cable runs for cables loop at the end of the travel of the expansion joint is to be
installed in enclosed and semi-enclosed spaces. not less than 12 times the external diameter of the cable.
The cable penetrations are to be installed in steel plates of
at least 3 mm thickness extending all around to twice the
7.3 Fixing of cables
largest dimension of the cable run for vertical runs and once
for horizontal runs, but need not extend through ceilings,
decks, bulkheads or solid sides of trunks. These precautions 7.3.1 Cables shall be installed and supported in such a
apply in particular to bunches of 5 or more cables in areas manner as to avoid chafing or other damage.
with a high fire risk (such as Category A machinery spaces,
galleys etc.) and to bunches of more than 10 cables in other 7.3.2 The supports (tray plates, separate support brackets or
areas. hanger ladders) and the corresponding accessories are to be
of robust construction and of corrosion-resistant material or
7.2 Radius of bend suitably treated before erection to resist corrosion.
Vertical
or
2a
2a 2a a 2a
FIRE STOP
FIRE STOP
Steel plate
BO Penetration
Horizontal
1a
14m
1m 1m
Coating Coating
7.3.3 With the exception of cables installed in pipes, con- 7.5.4 Where cables pass through bulkheads or decks sepa-
duits, trunkings or special casings, cables are to be fixed by rating areas with a risk of explosion, arrangements are to be
means of clips, saddles or straps of suitable material, in order such that hazardous gas or dust cannot penetrate through
to tighten the cables without their coverings being damaged. openings for the passage of cables into other areas.
7.3.4 Cable clips or straps made from a material other than 7.5.5 Where cables pass through a bulkhead or deck which
metal are to be manufactured of a flame-retardant material. is required to have some degree of fire integrity, penetration
is to be so effected as to ensure that the required degree of
7.3.5 The distances between fastenings and between sup- fire integrity is not impaired.
ports are to be suitably chosen according to the type and
number of cables and the probability of vibration.
7.6 Expansion joints
7.3.6 When cables are fixed by means of clips or straps
7.6.1 If there is reason to fear that a tray plate, pipe or con-
made from a material other than metal and these cables are
duit may break because of the motion of the ship, different
not laid on top of horizontal cable supports (e.g. in the case
load conditions and temperature variations, appropriate
of vertical installation), suitable metal clips or saddles
expansion joints are to be provided.
spaced not more than 1 metre apart are to be used in addi-
tion in order to prevent the release of cables during a fire. This may apply in particular in the case of cable runs on the
weather deck.
7.3.7 Suspended cables of fire-resisting type are to be fixed
by means of steel straps spaced not more than 500 mm apart. 7.7 Cables in closed pipes or conduits
7.4 Mechanical protection 7.7.1 Closed pipes or conduits are to have such internal
dimensions and radius of bend as will permit the easy draw-
7.4.1 Cables exposed to risk of mechanical damage are to ing in and out of the cables which they are to contain; the
be protected by metal casing, profiles or grids or enclosed in internal radius of bend is to be not less than that permitted
metal pipes or conduits, unless the cable covering (e.g. for cables and, for pipes exceeding 63 mm external diame-
armour or sheath) provides adequate mechanical protection. ter, not less than twice the external diameter of the pipe
where this value is greater.
7.4.2 In situations where there would be an exceptional
risk of mechanical damage, e.g. in holds, storage spaces, 7.7.2 Closed pipes and conduits are to be suitably smooth
cargo spaces, etc., cables are to be protected by metal cas- on the interior and are to have their ends shaped or bushed
ing, trunkings or conduits, even when armoured, if the in such a way as not to damage the cable covering.
ship’s structure or attached parts do not afford sufficient pro-
tection for the cables. 7.7.3 The space factor (ratio of the sum of the cross-sec-
tional areas corresponding to the external diameters of the
7.4.3 For the protection of cables passing through decks, cables to the internal cross-sectional areas of the pipe or
see [7.5.3]. conduit) is to be not greater than 0,4.
7.4.4 Metal casing used for mechanical protection of 7.7.4 If necessary, openings are to be provided at the high-
cables is to be effectively protected against corrosion. est and lowest points so as to permit air circulation and
ensure that the heat from the cables can be dissipated, and
to obviate the possibility of water accumulating at any part
7.5 Penetrations of bulkheads and decks of the pipe or conduit.
7.5.1 If cables have to pass without adequate support
7.7.5 Vertical trunking for electrical cables is to be so con-
through non-watertight bulkheads and generally through
structed as not to jeopardise the required passive fire pro-
holes drilled in sheets of structural steel, these holes are to
tection between the spaces.
be fitted with glands or bushings of suitable material.
7.7.6 Metal pipes or conduits are to be protected against
7.5.2 If cables have to pass through a watertight bulkhead
corrosion.
or deck, the penetration is to be effected in a watertight
manner. 7.7.7 Non-metallic pipes or conduits are to be flame-
Either suitable individual watertight glands for single cables retardant.
or boxes containing several cables and filled with a flame-
retardant packing may be used for this purpose. 7.8 Cables in casings or trunking and con-
Whichever type of penetration is used, the watertight integ- duits with removable covers
rity of the bulkheads or deck is to be maintained.
7.8.1 Covers are to be removable and when they are open,
7.5.3 Cables passing through decks and continuing verti- cables are to be accessible.
cally are to be protected against mechanical damage to a
height of at least 200 mm above the deck. 7.8.2 Materials used are to comply with [7.7.6] and [7.7.7].
7.8.3 If the fixing of covers is by means of screws, the latter 7.11.5 Metal coverings of single-core a.c. cables and spe-
are to be of non-rusting material and arranged so as not to cial d.c. cables with high "ripple" content (e.g. for thyristor
damage the cables. equipment) are to be earthed at one point only (e.g. at the
mid-point).
7.8.4 Means are to be provided to ensure that the heat from
the cables can be dissipated and water accumulation is 7.11.6 The electrical continuity of all metal coverings of
avoided (see [7.7.4]). cables throughout the length of the latter, particularly at
joints and tappings, is to be ensured.
7.9 Cable ends 7.11.7 The metal covering of cables may be earthed by
means of glands intended for the purpose and so designed
7.9.1 Terminations in all conductors are to be so made as
as to ensure an effective earth connection.
to retain the original electrical, mechanical, flame-retarding
The glands are to be firmly attached to, and in effective
properties of the cable.
electrical contact with, a metal structure earthed in accord-
7.9.2 Where mechanical clamps are not used, the ends of ance with these requirements.
all conductors having a cross-sectional area greater than 4
7.11.8 The metal covering of cables may also be earthed by
mm2 are to be fitted with soldering sockets or compression-
means of clamps or clips of corrosion-resistant material
type sockets of sufficient size to contain all the strands of
making effective contact with the covering and earthed
the conductor.
metal.
7.9.3 Cables not having a moisture-resistant insulation (e.g.
mineral-insulated) are to have their ends effectively sealed 7.12 Earthing and continuity of metal pipes,
against ingress of moisture. conduits and trunking or casings
7.12.1 Metal casings, pipes, conduits and trunking are to
7.10 Joints and tappings (branch circuit) be effectively earthed.
7.10.1 Cable runs are normally not to include joints. 7.12.2 Pipes or conduits may be earthed by being screwed
Where absolutely necessary, cable joints are to be carried into a metal enclosure, or by nuts on both sides of the wall
out by a junction method with rebuilding of the insulation of a metallic enclosure, provided the surfaces in contact are
and protective coverings. clean and free from rust, scale or paint and that the enclo-
sure is in accordance with these requirements on earthing.
7.10.2 Joints in all conductors are to be so made as to
The connection is to be painted immediately after assembly
retain the original electrical (continuity and isolation),
in order to inhibit corrosion.
mechanical (strength and protection), flame-retarding and,
where necessary, fire-resisting properties of the cable. 7.12.3 Pipes and conduits may be earthed by means of
clamps or clips of corrosion-resistant metal making effective
7.10.3 Tappings (branch circuits) are to be made via suita- contact with the earthed metal.
ble connections or in suitable boxes of such design that the
conductors remain adequately insulated and protected from 7.12.4 Pipes, conduits or trunking together with connec-
atmospheric action and are fitted with terminals or busbars tion boxes of metallic material are to be electrically contin-
of dimensions appropriate to the current rating. uous.
7.10.4 Cables for safety voltages are not to terminate in the 7.12.5 All joints in metal pipes and conduits used for earth
same connection boxes as cable for higher voltages unless continuity are to be soundly made and protected, where
separated by suitable means. necessary, against corrosion.
7.13.5 In the installation of two, three or four single-core 7.17 Cables in the vicinity of radio equipment
cables forming respectively single-phase circuits, three-
phase circuits, or three-phase and neutral circuits, the 7.17.1 All cables between antennas and transmitters are to
cables are to be in contact with one another, as far as possi- be routed separately of any other cable.
ble. In any event, the distance between the external cover-
ing of two adjacent cables is to be not greater than one 7.17.2 Where it is necessary to use single-core cables, the
diameter. arrangement of conductors is to be such as to avoid com-
plete or partial loops.
7.13.6 When single-core cables having a current rating
greater than 250 A are installed near a steel bulkhead, the 7.18 Cables for submerged bilge pumps
clearance between the cables and the bulkhead is to be at
least 50 mm, unless the cables belonging to the same circuit 7.18.1 See Ch 2, Sec 3, [9.7].
are installed in trefoil twisted formation.
7.19 Cable trays/protective casings made of
7.13.7 Magnetic material is not to be used between single- plastics materials
core cables of a group. Where cables pass through steel
plates, all the conductors of the same circuit are to pass 7.19.1 Cable trays or protective casings made of plastics
through a plate or gland, so made that there is no magnetic materials (thermoplastic or thermosetting plastic material)
material between the cables, and the clearance between the are to be type tested.
cables and the magnetic material is to be no less than
75 mm, unless the cables belonging to the same circuit are 7.19.2 Cable trays/protective casings are to be supple-
installed in trefoil twisted formation. mented by metallic fixing and straps such that in the event
of a fire they, and the cables affixed, are prevented from fall-
ing and causing injury to personnel and/or an obstruction to
7.14 Cables in refrigerated spaces any escape route.
When used on open deck, they are to be protected against
7.14.1 For the types of cables permitted in refrigerated U.V. light.
spaces, see Ch 2, Sec 3, [9.4].
7.19.3 The load on the cable trays/ protective casings is to
7.14.2 Power cables installed in refrigerated spaces are not be within the Safe Working Load (SWL). The support spac-
to be covered by thermal insulation. Moreover, such cables ing is not to be greater than the manufacturer recommenda-
are not to be placed directly on the face of the refrigerated tions nor in excess of spacing at SWL test. In general, the
space unless they have a thermoplastic or elastomeric spacing is not to exceed 2 meters.
extruded sheath.
7.19.4 The selection and spacing of cable tray/protective
casing supports are to take into account:
7.14.3 Power cables entering a refrigerated space are to
pass through the walls and thermal insulation at right • cable trays/protective casings’ dimensions
angles, in tubes sealed at each end and protected against • mechanical and physical properties of their material
oxidation. • mass of cable trays/protective casings
• loads due weight of cables, external forces, thrust forces
7.15 Cables in areas with a risk of explosion and vibrations
• maximum accelerations to which the system may be
7.15.1 For the types of cables permitted in areas with a risk subjected
of explosion, see Ch 2, Sec 3, [10.2]. • combination of loads.
7.15.2 For penetration of bulkheads or decks separating 7.19.5 The sum of the cables total cross-sectional area,
areas with a risk of explosion, see [7.5.4]. based on the cables external diameter is not to exceed 40%
of the protective casing internal cross-sectional area. This
does not apply to a single cable in a protective casing.
7.15.3 Cables of intrinsically safe circuits are to be sepa-
rated from the cables of all other circuits (minimum
50 mm). 8 Various appliances
7.16 Cables and apparatus for services requi- 8.1 Lighting fittings
red to be operable under fire conditions 8.1.1 Lighting fittings are to be so arranged as to prevent
temperature rises which could damage the cables and wiring.
7.16.1 Cables and apparatus for services required to be Note 1: Where the temperature of terminals of lighting fittings
operable under fire conditions including their power sup- exceeds the maximum conductor temperature permitted for the
plies are to be so arranged that the loss of these services is supplied cable (see Ch 2, Sec 3, [9.9] ), special installation arrange-
minimized due to a localized fire at any one area or zone ments, such as terminal boxes thermally insulated from the light
listed in Ch 2, Sec 1, [3.25]. source, are to be provided.
8.1.2 Lighting fittings are to be so arranged as to prevent 8.2.2 Space heaters are to be so installed that there is no
surrounding material from becoming excessively hot. risk of excessive heating of the bulkheads or decks on
which or next to which they are mounted.
8.1.3 Lighting fittings are to be secured in place such that
they cannot be displaced by the motion of the vessel.
8.2.3 Combustible materials in the vicinity of space heaters
8.1.4 Emergency lights are to be marked for easy identification. are to be protected by suitable incombustible and thermal-
insulating materials.
8.2 Heating appliances
8.2.1 Space heaters are to be so installed that clothing,
8.3 Heating cables and tapes or other heat-
bedding and other flammable material cannot come in con- ing elements
tact with them in such a manner as to cause risk of fire.
Note 1: To this end, for example, hooks or other devices for hang- 8.3.1 Heating cables and tapes or other heating elements
ing garments are not to be fitted above space heaters or, where are not to be installed in contact with combustible materials.
appropriate, a perforated plate of incombustible material is to be
mounted above each heater, slanted to prevent hanging anything Where they are installed close to such materials, they are to
on the heater itself. be separated by means of a non-flammable material.
Intermediate values may be accepted for nominal voltages, 2.4.5 Fuses are not to be used for overload protection.
provided that the next higher air clearance is observed.
2.4.6 Lower voltage systems supplied through transformers
In the case of smaller distances, an appropriate voltage
from high voltage systems are to be protected against over-
impulse test is to be applied.
voltages. This may be achieved by:
a) direct earthing of the lower voltage system
Table 1 : Minimum clearances
b) appropriate neutral voltage limiters
Rated voltage, in kV Minimum clearance, in mm c) earthed screen between the primary and secondary
3 - 3,3 55 windings of transformers.
6 - 6,6 90
10 - 11 120
3 Rotating machinery
2.3.2 Creepage distances between live parts and between 3.1 Stator windings of generators
live parts and earthed metal parts for standard components
are to be in accordance with relevant IEC Publications for 3.1.1 Generator stator windings are to have all phase ends
the nominal voltage of the system, the nature of the insula- brought out for the installation of the differential protection.
tion material and the transient overvoltage developed by
switch and fault conditions. 3.2 Temperature detectors
For non-standardised parts within the busbar section of a
3.2.1 Rotating machinery is to be provided with tempera-
switchgear assembly, the minimum creepage distance is to
ture detectors in its stator windings to actuate a visual and
be at least 25 mm/kV and behind current limiting devices,
audible alarm in a normally attended position whenever the
16 mm/kV.
temperature exceeds the permissible limit.
If embedded temperature detectors are used, means are to
2.4 Protection be provided to protect the circuit against overvoltage.
2.4.3 Power transformers are to be provided with overload • liquid temperature (High) - trip or load reduction
and short circuit protection. • gas pressure relay (High) - trip.
7.2.6 Before a new high voltage cable installation, or an The test voltage is to be maintained for a minimum of
addition to an existing installation, is put into service, a 15 minutes.
voltage withstand test is to be satisfactorily carried out on
each completed cable and its accessories. After completion of the test, the conductors are to be con-
nected to earth for a sufficient period in order to remove
The test is to be carried out after an insulation resistance test.
any trapped electric charge.
When a d.c. voltage withstand test is carried out, the volt-
age is to be not less than: An insultation resistance test is then repeated.
• 1,6 (2,5 Uo + 2 kV) for cables of rated voltage (Uo) up Alternatively, an a.c. voltage withstand test may be carried
to and including 3,6 kV, or out on the advice of the high voltage cable manufacturer at
• 4,2 Uo for higher rated voltages a voltage not less than the normal operating voltage of the
cable, to be maintained for a minimum of 24 hours.
where Uo is the rated power frequency voltage between
conductor and earth or metallic screen, for which the cable Note 1: Tests specified in IEC Publication 60502 will be considered
is designed. adequate.
1.2.5 The electric motors and shaftline are to be con- 2.2.3 The electric plant is to be so designed as to prevent the
structed and installed so that, at any speed reached in serv- harmful effects of electromagnetic interference generated by
ice, all the moving components are suitably balanced. semiconductor convertors, in accordance with Ch 2, Sec 3.
2.3 Auxiliary machinery 2.5.4 For the protection of field windings and cables,
means are to be provided for limiting the induced voltage
2.3.1 Propeller/thruster auxiliary plants are to be supplied when the field circuits are opened. Alternatively, the
directly from the main switchboard or from the main distri- induced voltage when the field circuits are opened is to be
bution board or from a distribution board reserved for such maintained at the nominal design voltage.
circuits, at the auxiliary rated voltage.
2.5.5 In excitation circuits, there is to be no overload pro-
2.3.2 When the installation has one or more lubrication tection causing the opening of the circuit, except for excita-
systems, devices are to be provided to ensure the monitor- tion circuits with semiconductor convertors.
ing of the lubricating oil return temperature.
2.5.6 Each exciter is to be supplied by a separate feeder.
2.3.3 Propelling machinery installations with a forced
lubrication system are to be provided with alarm devices
which will operate in the event of oil pressure loss.
3 Construction of rotating machines
and semiconductor convertors
2.4 Electrical Protection
3.1 Ventilation
2.4.1 Automatic disconnections of electric propulsion
plants which adversely affect the manoeuvrability of the 3.1.1 Where electrical machines are fitted with an inte-
ship are to be restricted to faults liable to cause severe dam- grated fan and are to be operated at speeds below the rated
age to the equipment. speed with full load torque, full load current, full load exci-
tation or the like, the design temperature rise is not to be
2.4.2 The following protection of convertors is to be pro- exceeded.
vided:
• protection against overvoltage in the supply systems to 3.1.2 Where electrical machines or convertors are force-
which convertors are connected ventilated, at least two fans, or other suitable arrangements,
are to be provided so that limited operation is possible in
• protection against overcurrents in semiconductor ele- the event of one fan failing.
ments during normal operation
• short-circuit protection.
3.2 Protection against moisture and con-
2.4.3 Overcurrent protective devices in the main circuits densate
are to be set sufficiently high so that there is no possibility of
activation due to the overcurrents caused in the course of 3.2.1 Machines and equipment which may be subject to
normal operation, e.g. during manoeuvring or in heavy seas. the accumulation of moisture and condensate are to be pro-
vided with effective means of heating. The latter is to be
2.4.4 Overcurrent protection may be replaced by auto- provided for motors above 500 kW, in order to maintain the
matic control systems ensuring that overcurrents do not temperature inside the machine at about 3°C above the
reach values which may endanger the plant, e.g. by selec- ambient temperature.
tive tripping or rapid reduction of the magnetic fluxes of the
generators and motors. 3.2.2 Provision is to be made to prevent the accumulation
of bilge water, which is likely to enter inside the machine.
2.4.5 In the case of propulsion plants supplied by genera-
tors in parallel, suitable controls are to ensure that, if one or 3.3 Rotating machines
more generators are disconnected, those remaining are not
overloaded by the propulsion motors. 3.3.1 Electrical machines are to be able to withstand the
excess speed which may occur during operation of the ship.
2.4.6 In three-phase systems, phase-balance protective
devices are to be provided for the motor circuit which de- 3.3.2 The design of rotating machines supplied by static
excite the generators and motors or disconnect the circuit convertors is to consider the effects of harmonics.
concerned.
3.3.3 The winding insulation of electrical machines is to be
2.5 Excitation of electric propulsion motor capable of withstanding the overvoltage which may occur
in manoeuvring conditions.
2.5.1 Each propulsion motor is to have its own exciter.
3.3.4 The design of a.c. machines is to be such that they
2.5.2 For plants where only one generator or only one can withstand without damage a sudden short-circuit at
motor is foreseen, each machine is to be provided with a their terminals under rated operating conditions.
standby exciter, which it is easy to switch over to.
3.3.5 The obtainable current and voltage of exciters and
2.5.3 In the case of multi-propeller propulsion ships, only their supply are to be suitable for the output required during
one standby exciter is to be provided. Switch-over opera- manoeuvring and overcurrent conditions, including short-
tion is to be easy. circuit in the transient period.
3.4 Semiconductor convertors • monitoring of the alarms: any event critical for the
proper operation of an essential auxiliary or a main ele-
3.4.1 The following limiting repetitive peak voltages U RM ment of the installation requiring immediate action to
are to be used as a base for each semiconductor valve: avoid a breakdown is to activate an alarm
• when connected to a supply specifically for propeller • speed or pitch control of the propeller
drives: • shutdown or slow down when necessary.
URM = 1,5 UP
4.2.7 Where the electric propulsion system is supplied by
• when connected to a common main supply: the main switchboard together with the ship’s services, load
URM = 1,8 UP shedding of the non-essential services and /or power limita-
tion of the electric propulsion is to be provided. An alarm is
where to be triggered in the event of power limitation or load
UP : Peak value of the rated voltage at the input of shedding.
the semiconductor convertor.
4.2.8 The risk of blackout due to electric propulsion opera-
3.4.2 For semiconductor convertor elements connected in tion is to be eliminated. At the request of the Society, a fail-
series, the values in [3.4.1] are to be increased by 10%. ure mode and effects analysis is to be carried out to
Equal voltage distribution is to be ensured. demonstrate the reliability of the system.
4.2.6 The control system is to include the following main 4.3.6 An ammeter is to be provided on the supply circuit
functions: for each propulsion semiconductor bridge.
• tripping of protection on filter circuits to limit the distur- 5.2.2 Where there is more than one propulsion motor, all
bances due to semiconductor convertors cables for any one machine are to be run as far as is practi-
• tripping of protective devices against overcurrents up to cable away from the cables of other machines.
and including short-circuit in semiconductor convertors
(critical alarm) 5.2.3 Cables which are connected to the sliprings of syn-
chronous motors are to be suitably insulated for the voltage
• voltage unbalance of three-phase a.c. systems supplied
to which they are subjected during manoeuvring.
by semiconductor frequency convertors
• earth fault for the main propulsion circuit (see Note 2)
6 Tests
• earth fault for excitation circuits of propulsion machines
(see Note 3).
6.1 Test of rotating machines
Note 1: As an alternative to the air temperature of convertors or to
the airflow, the supply of electrical energy to the ventilator or the 6.1.1 The test requirements are to comply with Ch 2, Sec 4.
temperature of the semiconductors may be monitored.
Note 2: In the case of star connected a.c. generators and motors 6.1.2 For rotating machines, such as synchronous genera-
with neutral points earthed, this device may not detect an earth tors and synchronous electric motors, of a power of more
fault in the entire winding of the machine. than 1 MW, a quality plan detailing the different controls
Note 3: This may be omitted in brushless excitation systems and in during the machine assembly is to be submitted to the Soci-
the excitation circuits of machines rated up to 500 kW. In such ety for approval.
cases, lamps, voltmeters or other means are to be provided to
detect the insulation status under operating conditions. 6.1.3 In relation to the evaluation of the temperature rise, it
is necessary to consider the supplementary thermal losses
4.5 Reduction of power induced by harmonic currents in the stator winding. To this
end, two methods may be used:
4.5.1 Power is to be automatically reduced in the following • direct test method, when the electric propulsion motor
cases: is being supplied by its own frequency convertor, and/or
• low lubricating oil pressure of bearings of propulsion back to back arrangement according to the supplier’s
generators and motors facility
• indirect test method as defined in Ch 2, App 1; in this sidered. The commutator may be submitted to cycles
case, a validation of the estimation of the temperature comprising full or partial rotation in relation to the use
excess due to harmonics is to be documented. A justifi- of the POD as steering gear. The voltage drops and cur-
cation based on a computer program calculation may rent are to be recorded.
be taken into consideration, provided that validation of
such program is demonstrated by previous experience. An overload test is to be carried out in accordance with
Ch 2, Sec 4 (minimum 150%, 15 seconds)
6.1.4 Rotating machines used for propulsion or manoeu- • check of the behaviour of the sliprings when subjected
vring are to be subjected to the tests stated in Ch 2, Sec 4, to the vibration defined in Ch 3, Sec 6
[5.1.1].
• check of the behaviour of the sliprings, after damp heat
test, as defined in Part C, Chapter 3, and possible corro-
7 Specific requirements for PODs sion of the moving parts and contacts.
After the damp heat test, the following are to be carried out:
7.1 General
• insulation measurement resistance test: the minimum
7.1.1 The requirements for the structural part of a POD are resistance is to be in accordance with Ch 2, Sec 4, Tab 2
specified in Pt B, Ch 10, Sec 1, [11]. • dielectric strength test as defined in Ch 2, Sec 4.
7.2.2 The rotating commutator is to be type approved. Type 7.3.2 Means to adjust the air cooler characteristics are to
tests are to be carried out, unless the manufacturer can pro- be provided on board, in order to obtain an acceptable tem-
duce evidence based on previous experience indicating the perature rise of the windings. Such means are to be set fol-
satisfactory performance of such equipment on board ships. lowing the dock and sea trials.
7.2.3 A test program is to be submitted to the Society for 7.3.3 Vibrations of the electric motor are to be monitored.
approval. It is to be to demonstrated that the power trans- The alarm set point is to be defined in accordance with the
mission and transmission of low level signals are not manufacturer recommendation.
affected by the environmental and operational conditions
prevailing on board. To this end, the following checks and
tests are to be considered: 7.4 Instrumentation and associated devices
• check of the protection index (IP), in accordance with
7.4.1 Means are to be provided to transmit the low level
the location of the rotating commutator
signals connected to the sensors located in the POD.
• check of the clearances and creepage distances
• check of insulation material (according to the test proce- 7.5 Additional tests and tests on board
dure described in IEC Publication 60112)
7.5.1 Tests of electric propulsion motors are to be carried
• endurance test: out in accordance with Ch 2, Sec 4, and other tests in
accordance with Ch 1, Sec 15.
After the contact pressure and rated current are set, the
commutator is subjected to a rotation test. The number
of rotations is evaluated taking into consideration the 7.5.2 Tests are to be performed to check the validation of
ship operation and speed rotation control system. The the temperature rise calculation.
possibility of turning the POD 180° to proceed astern
and 360° to return to the original position is to be con- 7.5.3 Tests on board are described in Ch 1, Sec 15, [3.7].
SECTION 15 TESTING
3.1 Lighting and power circuits 4.1.1 Tests are to be carried out, by visual inspection or by
means of a tester, to verify that all earth-continuity conduc-
3.1.1 The insulation resistance between all insulated poles tors and earthing leads are connected to the frames of appa-
(or phases) and earth and, where practicable, between poles ratus and to the hull, and that in socket-outlets having
(or phases), is to be at least 1 MΩ in ordinary conditions. earthing contacts, these are connected to earth.
5 Operational tests 5.2.2 Short-circuit tests may also be required at the discre-
tion of the Society in order to verify the selectivity charac-
5.1 Generating sets and their protective teristics of the installation.
devices
5.3 Consuming devices
5.1.1 Generating sets are to be run at full rated load to ver-
ify that the following are satisfactory: 5.3.1 Electrical equipment is to be operated under normal
• electrical characteristics service conditions (though not necessarily at full load or
simultaneously) to verify that it is suitable and satisfactory
• commutation (if any)
for its purpose.
• lubrication
• ventilation 5.3.2 Motors and their starters are to be tested under nor-
• noise and vibration level. mal operating conditions to verify that the following are sat-
isfactory:
5.1.2 Suitable load variations are to be applied to verify the • power
satisfactory operation under steady state and transient con-
ditions (see Ch 2, Sec 4, [2] ) of: • operating characteristics
• voltage regulators • commutation (if any)
• speed governors. • speed
For sets intended to operate in parallel, the correct opera- 5.5 Installations in areas with a risk of
tion of the following is also to be verified: explosion
• reverse-power protection for a.c. installations (or
reverse-current protection for d.c. installations) 5.5.1 Installations and the relevant safety certification are
• minimum voltage protection. to be examined to ensure that they are of a type permitted
in the various areas and that the integrity of the protection
Note 1:Simulated tests may be used to carry out this check where concept has not been impaired.
appropriate.
5.1.5 The satisfactory operation of the emergency source of 5.6 Voltage drop
power and of the transitional source of power, when
required, is to be tested. In particular, the automatic starting 5.6.1 Where it is deemed necessary by the attending Sur-
and the automatic connection to the emergency switch- veyor, the voltage drop is to be measured to verify that the
board, in case of failure of the main source of electrical permissible limits are not exceeded (see Ch 2, Sec 3,
power, are to be tested. [9.11.4]).
• ∆ts1 is the stator temperature rise The rotor temperature rise is obtained by calculation of
rotor resistance, Rrotor = U/Ir , where U and I are the volt-
• ∆tr1 is the rotor temperature rise. age and current in the magnetic field winding.
• Test N° 2: Rated stator winding current with the termi- The following parameters are recorded, every 1/2 hour:
nals short-circuited. The temperature of the stator wind-
• temperature sensors as well as the stator current and
ing depends on the thermal Joule losses and mechanical voltage
losses, as above, where:
• the main field voltage and current
• ∆ts2 is the stator temperature rise
• the bearing temperatures (embedded sensor or ther-
• ∆tr2 is the rotor temperature rise, which for test N° 2 mometer), and the condition of cooling of the bearings,
is negligible. which are to be compared to those expected on board.
Shaft
coupling
Driving motor
Exciter rotating machine
Rotating diods
1.1.3 The tests described above allow the determination of equal to 1), the temperature rise of the rotor is to be cor-
the final temperature rise of stator and rotor windings with rected as follows:
an acceptable degree of accuracy.
• The temperature rise of the stator winding is estimated ∆t rotor = (∆tr1 − ∆tr3) x (rated loading conditions Ir/ test
as follows: loading conditions Irt)2 + ∆tr3
∆t stator = ∆ts1 + ∆ts2 − ∆ts3
∆t stator winding is to be corrected by the supplemen- 1.1.4 In the indirect method, a possible mutual influence of
tary temperature rise due to current harmonics evalu- the temperature rise between the stator and the rotor is not
ated by the manufacturer taken into consideration. The test results may be representa-
• Considering that in test N° 1 the magnetic field winding tive of the temperature rise on board ship, but a margin of
current Irt is different from the manufacturer’s estimated 10 to 15°C is advisable compared with the permitted tem-
value Ir (due to the fact that the cos ϕ in operation is not perature of the Rules and the measure obtained during tests.
Chapter 3
AUTOMATION
SECTION 6 TESTING
They are to be approved on the basis of the applicable Society the documents (plans, diagrams, specifications and
requirements of these Rules and in particular those stated in calculations) requested in this Section.
this Chapter. The list of documents requested is to be intended as guid-
Case by case approval may also be granted at the discretion ance for the complete set of information to be submitted,
of the Society, based on submission of adequate documen- rather than an actual list of titles.
tation and subject to the satisfactory outcome of any The Society reserves the right to request the submission of
required tests. additional documents in the case of non-conventional
design or if it is deemed necessary for the evaluation of the
1.4.2 Main and auxiliary machinery essential for the pro-
system, equipment or components.
pulsion, control and safety of the ship shall be provided
with effective means for its operation and control. Plans are to include all the data necessary for their interpre-
tation, verification and approval.
1.4.3 Control, alarm and safety systems are to be based on
Unless otherwise agreed with the Society, documents for
the fail-to-safety principle.
approval are to be sent in triplicate if submitted by the Ship-
1.4.4 Failure of automation systems is to generate an alarm. yard and in four copies if submitted by the equipment sup-
plier. Documents requested for information are to be sent in
1.4.5 Detailed indication, alarm and safety requirements duplicate.
regarding automation systems for individual machinery and In any case, the Society reserves the rights to require addi-
installations are to be found in tables located in Part C, tional copies, when deemed necessary.
Chapter 1 and in Part E, Chapter 3.
Each row of these tables is to correspond to one independ- 2.2 Documents to be submitted
ant sensor.
2.2.1 The documents listed in Tab 1 are to be submitted.
2 Documentation
2.3 Documents for computer based system
2.1 General
2.3.1 General
2.1.1 Before the actual construction is commenced, the For computer based systems, the documents listed in Tab 2
Manufacturer, Designer or Shipbuilder is to submit to the are to be submitted.
2.3.2 System description, computer software 2.4 Documents for type approval of equip-
This documentation is to contain: ment
• a list of all main software modules installed per hard-
ware unit with names and version numbers 2.4.1 Documents to be submitted for type approval of
• a description of all main software which is to include at equipment are listed hereafter:
least: • a request for type approval from the manufacturer or his
- a description of basic software installed per hard- authorized representative
ware unit, including communication software, when • the technical specification and drawings depicting the
applicable system, its components, characteristics, working princi-
- a description of application software. ple, installation and conditions of use and, when there
is a computer based system, the documents listed in
2.3.3 Description of computer hardware Tab 2
The documentation to be submitted is to include:
• any test reports previously prepared by specialised labo-
• hardware information of importance for the application
ratories.
and a list of documents that apply to the system
• the supply circuit diagram 2.4.2 Documentation to be submitted for type approval of
• a description of hardware and software tools for equip- software is listed in Information Note “Software Assessment
ment configuration for Shipboard Computer Based System” (NI-425).
• the information to activate the system
• general information for trouble shooting and repair 3 Environmental and supply conditions
when the system is in operation.
1.1.1 All control systems essential for the propulsion, con- 3 Control systems
trol and safety of the ship shall be independent or designed
such that failure of one system does not degrade the per-
formance of another system. 3.1 General
1.1.2 Controlled systems are to have manual operation. 3.1.1 In the case of failure, the control systems used for
Failure of any part of such systems shall not prevent the use essential services are to remain in their last position they
of the manual override. had before the failure.
1.1.3 Automation systems are to have constant perform- 3.2 Local control
ance.
3.2.1 Each system is to be able to be operated manually
1.1.4 Safety functions are to be independent of control and from a position located so as to enable visual control of
monitoring functions. As far as practicable, control and operation. For detailed instrumentation for each system,
monitoring functions are also to be independent. refer to Part C, Chapter 1and Part C, Chapter 2.
1.1.5 Control, monitoring and safety systems are to have It shall also be possible to control the auxiliary machinery,
self-check facilities. In the event of failure, an alarm is to be essential for the propulsion and safety of the ship, at or near
activated. the machinery concerned.
In particular, failure of the power supply of the automation
system is to generate an alarm. 3.3 Remote control systems
1.1.6 When a computer based system is used for control, 3.3.1 When several control stations are provided, control
alarm or safety systems, it is to comply with the require- of machinery is to be possible at one station at a time.
ments of Ch 3, Sec 3.
3.3.2 At each location there shall be an indicator showing
1.1.7 The automatic change-over switch is to operate inde- which location is in control of the propulsion machinery.
pendently of both systems. When change-over occurs, no
stop of the installation is necessary and the latter is not to 3.3.3 Remote control is to be provided with the necessary
enter undefined or critical states. instrumentation, in each control station, to allow effective
control (correct function of the system, indication of control
1.1.8 Emergency stops are to be hardwired and independ- station in operation, alarm display).
ent of any computer based system.
Note 1: Computerized systems may be admitted if evidence is 3.3.4 When transferring the control location, no significant
given demonstrating they provide a safety level equivalent to a alteration of the controlled equipment is to occur. Transfer
hardwired system. of control is to be protected by an audible warning and
acknowledged by the receiving control location. The main
2 Power supply of automation systems control location is to be able to take control without
acknowledgement.
2.1
3.4 Automatic control systems
2.1.1 Automation systems are to be arranged with an auto-
matic change-over to a continuously available stand-by 3.4.1 Automatic starting, operational and control systems
power supply in case of loss of normal power source. shall include provisions for manually overriding the auto-
matic controls.
2.1.2 The capacity of the stand-by power supply is to be
sufficient to allow the normal operation of the automation 3.4.2 Automatic control is to be stable in the range of the
systems for at least half an hour. controller in normal working conditions.
2.1.3 Failure of any power supply to an automation system 3.4.3 Automatic control is to have instrumentation to verify
is to generate an audible and visual alarm. the correct function of the system.
4 Control of propulsion machinery Note 1: Arrangements which are not in compliance with the provi-
sions of this Article may be considered for the following ships:
• ships less than 24 m in length
4.1 Remote control
• cargo ships less than 500 tons gross tonnage
4.1.1 The requirements mentioned in [3] are to be applied • ships to be assigned restricted navigation notations
for propulsion machinery. • non-propelled units.
4.1.2 The design of the remote control system shall be such 4.2.2 On board ships fitted with remote control, direct con-
that in case of its failure an alarm will be given. trol of the propulsion machinery is to be provided locally.
The local direct control is to be independent from the
4.1.3 Supply failure (voltage, fluid pressure, etc.) in propul- remote control circuits, and takes over any remote control
sion plant remote control is to activate an alarm at the con- when in use.
trol position. In the event of remote control system failure
and unless the Society considers it impracticable, the preset 4.2.3 Each local control position, including partial control
speed and direction of thrust are to be maintained until (e.g. local control of controllable pitch propellers or
local control is in operation. This applies in particular in the clutches) is to be provided with means of communication
case of loss of electric, pneumatic or hydraulic supply to the with the remote control position. The local control positions
system. are to be independent from remote control of propulsion
machinery and continue to operate in the event of a black-
4.1.4 Propulsion machinery orders from the navigation out (see Note 1 in [4.2.1]).
bridge shall be indicated in the main machinery control
room, and at the manoeuvring platform. 4.2.4 Remote control of the propulsion machinery shall be
possible only from one location at a time; at such locations
4.1.5 The control shall be performed by a single control interconnected control positions are permitted.
device for each independent propeller, with automatic per-
formance of all associated services, including, where neces- 4.2.5 The transfer of control between the navigating bridge
sary, means of preventing overload of the propulsion and machinery spaces shall be possible only in the main
machinery. Where multiple propellers are designed to oper- machinery space or the main machinery control room. The
ate simultaneously, they must be controlled by one control system shall include means to prevent the propelling thrust
device. from altering significantly, when transferring control from
one location to another (see Note 1 in [4.2.1]).
4.1.6 Indicators shall be fitted on the navigation bridge, in
the main machinery control room and at the manoeuvring 4.2.6 At the navigating bridge, the control of the routine
platform, for: manoeuvres for one line of shafting is to be performed by a
single control device: a lever, a handwheel or a push-button
• propeller speed and direction of rotation in the case of
board. However each mechanism contributing directly to
fixed pitch propellers; and
the propulsion, such as the engine, clutch, automatic brake
• propeller speed and pitch position in the case of con- or controllable pitch propeller, is to be able to be individu-
trollable pitch propellers. ally controlled, either locally or at a central monitoring and
control position in the engine room (see Note 1 in [4.2.1]).
4.1.7 The main propulsion machinery shall be provided
with an emergency stopping device on the navigation 4.2.7 Remote starting of the propulsion machinery is to be
bridge which shall be independent of the navigation bridge automatically inhibited if a condition exists which may
control system. damage the machinery, e.g. shaft turning gear engaged,
In the event that there is no reaction to an order to stop, drop of lubrication oil pressure or brake engaged.
provision is to be made for an alternative emergency stop.
4.2.8 As a general rule, the navigating bridge panels are not
This emergency stopping device may consist of a simple
to be overloaded by alarms and indications which are not
and clearly marked control device, for example a push-but-
required.
ton. This fitting is to be capable of suppressing the propeller
thrust, whatever the cause of the failure may be.
4.2.9 Automation systems shall be designed in a manner
which ensures that threshold warning of impending or
4.2 Remote control from navigating bridge imminent slowdown or shutdown of the propulsion system
is given to the officer in charge of the navigational watch in
4.2.1 Where propulsion machinery is controlled from the time to assess navigational circumstances in an emergency.
navigating bridge, the remote control is to include an auto- In particular, the systems shall control, monitor, report, alert
matic device such that the number of operations to be car- and take safety action to slowdown or stop propulsion
ried out is reduced and their nature is simplified and such while providing the officer in charge of the navigational
that control is possible in both the ahead and astern direc- watch an opportunity to manually intervene, except for
tions. Where necessary, means for preventing overload and those cases where manual intervention will result in total
running in critical speed ranges of the propulsion machin- failure of the engine and/or propulsion equipment within a
ery is to be provided. short time, for example in the case of overspeed.
Acknowledgement of visual signals is to be separate for • the operation of the machinery is temporarily adjusted
each signal or common to a limited group of signals. to the prevailing abnormal conditions (e.g. by reducing
Acknowledgement is only to be possible when the user has the output of the associated machinery), or
visual information on the alarm condition for the signal or
all signals in a group. • the machinery is protected, as far as possible, from criti-
cal conditions by shutting off the fuel or power supply,
thereby stopping the machinery (shutdown), or appro-
6.2.3 Locking of alarms
priate shutdown.
Manual locking of separate alarms may be accepted when
this is clearly indicated. 7.2.2 Safety indication
Locking of alarm and safety functions in certain operating When the safety system has been activated, it is to be possi-
modes (e.g. during start-up or trimming) is to be automati- ble to trace the cause of the safety action. This is to be
cally disabled in other modes. accomplished by means of a central or local indication.
7 Safety system 7.4.1 For the automatic starting system of the standby units,
the following requirements are to be applied:
7.1 Design • faults in the electrical or mechanical system of the run-
ning machinery are not to prevent the standby machin-
7.1.1 System failures ery from being automatically started
A safety system is to be designed so as to limit the conse- • when a machine is on standby, ready to be automati-
quence of failures. It is to be constructed on the fail-to- cally started, this is to be clearly indicated at its control
safety principle. position
The safety system is to be of the self-check type; as a rule, • the change-over to the standby unit is to be indicated by
failure within the safety system, including the outside con- a visual and audible alarm
nection, is to activate an alarm.
• means are to be provided close to the machine, to pre-
vent undesired automatic or remote starting (e.g. when
7.2 Function the machine is being repaired)
• normal operating conditions are restored (e.g. by the 7.5.1 The safety systems are to be tested in accordance
starting of the standby unit), or with the requirements in Ch 3, Sec 6.
1 General requirements 1.5.3 The failure and restarting of computer based systems
should not cause processes to enter undefined or critical
states.
1.1 General
1.1.1 The characteristics of the system are to be compatible 1.6 System redundancy
with the intended applications, under normal and abnormal
1.6.1 If it is demonstrated that the failure of the system,
process conditions. The response time for alarm function is
which includes the computer based system, leads to a dis-
to be less than 5 seconds.
ruption of the essential services, a secondary independent
1.1.2 When systems under control are required to be dupli- means, of appropriate diversity, is to be available to restore
cated and in separate compartments, this is also to apply to the adequate functionality of the service.
control elements within computer based systems.
2 Hardware
1.1.3 As a rule, computer based systems intended for
essential services are to be type approved.
2.1 General
1.2 System type approval 2.1.1 The construction of systems is to comply with the
requirements of Ch 3, Sec 4.
1.2.1 The type approval is to cover the hardware and basic
software of the system. The type approval requirements are 2.2 Housing
detailed in Ch 3, Sec 6. A list of the documents to be sub-
mitted is provided in Ch 3, Sec 1. 2.2.1 The housing of the system is to be designed to face
the environmental conditions, as defined in Ch 2, Sec 2,
1.3 System operation [1], in which it will be installed. The design will be such as
to protect the printed circuit board and associated compo-
1.3.1 The system is to be protected so that authorised per- nents from external aggression. When required, the cooling
sonnel only can modify any setting which could alter the system is to be monitored, and an alarm activated when the
system. normal temperature is exceeded.
1.3.2 Modification of the configuration, set points or 2.2.2 The mechanical construction is to be designed to
parameters is to be possible without complex operations withstand the vibration levels defined in Ch 2, Sec 2,
such as compilation or coded data insertion. depending on the applicable environmental condition.
When a computer based system is used with a non-essential 5.2.2 A visual and audible alarm is to be activated in the
system and connected to a network used for essential sys- event of malfunction of the system, or subsystem. This alarm
tems, the coupling device is to be of an approved type. is to be such that identification of the failure is simplified.
8.1.1 The system tests are to be carried out according to Ch 9.1.1 System maintenance is to be planned and docu-
3, Sec 6. mented.
8.1.2 All alterations of a system (hardware and software) 9.1.2 Remote software maintenance amy be considered on
are to be tested and the results of tests documented. case by case basis.
1.2.2 Connectors are to be able to withstand standard 2.1.6 The interface connection is to be so designed to
vibrations, mechanical constraints and corrosion conditions receive the cables required. The cables are to be chosen
as given in Ch 3, Sec 6. according to Ch 2, Sec 3.
2.1.2 A separation is to be done between any electrical 2.2.8 The programmable components are to be clearly
components and liquids, if they are in a same enclosure. tagged with the program date and reference.
Necessary drainage will be provided where liquids are Components are to be protected against outside alteration
likely to leak. when loaded.
2.1 General
3 Cables
2.1.1 The location and selection of the sensor is to be done
so as to measure the actual value of the parameter. Temper- 3.1 Installation
ature, vibration and EMI levels are to be taken into account.
3.1.1 Cables are to be installed according to the require-
When this is not possible, the sensor is to be designed to
ments in Ch 2, Sec 12, [7].
withstand the local environment.
3.1.2 Suitable installation features such as screening and/or
2.1.2 The enclosure of the sensor and the cable entry are to twisted pairs and/or separation between signal and other
be appropriate to the space in which they are located. cables are to be provided in order to avoid possible interfer-
ence on control and instrumentation cables.
2.1.3 Means are to be provided for testing, calibration and
replacement of automation components. Such means are to 3.1.3 Specific transmission cables (coaxial cables, twisted
be designed, as far as practicable, so as to avoid perturba- pairs, etc.) are to be routed in specific cable-ways and
tion of the normal operation of the system. mechanically protected to avoid loss of any important trans-
mitted data. Where there is a high risk of mechanical dam-
2.1.4 A tag number is to identify automation components age, the cables are to be protected with pipes or equivalent.
and is to be clearly marked and attached to the component.
These tag numbers are to be collected on the instrument list 3.1.4 The cable bend radius is to be in accordance with the
mentioned in Ch 3, Sec 1, Tab 1. requirements of Ch 2, Sec 12, [7.2].
For mineral insulated cables, coaxial cables or fibre optic
2.1.5 Electrical connections are to be arranged for easy cables, whose characteristics may be modified, special pre-
replacement and testing of sensors and components. They cautions are to be taken according to the manufacturer’s
are to be clearly marked. instructions.
2.1.6 Low level signal sensors are to be avoided. When 3.2 Cable terminations
installed they are to be located as close as possible to
amplifiers, so as to avoid external influences. Failing this, 3.2.1 Cable terminations are to be arranged according to
the wiring is to be provided with suitable EMI protection the requirements in Part C, Chapter 2. Particular attention is
and temperature correction. to be paid to the connections of cable shields. Shields are to
be connected only at the sensor end when the sensor is 4.1.2 As far as practicable, piping containing liquids is not to
earthed, and only at the processor end when the sensor is be installed in or adjacent to electrical enclosures (see Ch 3,
floating. Sec 4, [2.1.2]).
3.2.2 Cable terminations are to be able to withstand the 4.1.3 Hydraulic and pneumatic piping for automation sys-
identified environmental conditions (shocks, vibrations, salt tems is to be marked to indicate its function.
mist, humidity, etc.).
4.1.1 For installation of piping circuits used for automation 5.1.2 The location is to be such as to allow easy access for
purposes, see the requirements in Ch 1, Sec 10. maintenance operations.
SECTION 6 TESTING
1.1.1 Automation systems are to be tested for type 2.1.1 The following requirements are applicable, but not
approval, at works and on board, when required. Tests are confined, to all electrical, control and instrumentation sys-
to be carried out under the supervision of a Surveyor of the tems which are intended to be type approved for use in
Society. marine applications. In particular, they apply to control,
protection, safety devices and internal communication.
1.1.2 The type testing conditions for electrical, control and
instrumentation equipment, computers and peripherals are 2.1.2 The necessary documents to be submitted, prior to
described in [2]. type testing, are listed in Ch 3, Sec 1, [2.4.1]. The type
approval of automation systems refers to hardware type
1.1.3 Automation systems are to be inspected at works, approval or software type approval, as applicable.
according to the requirements of [3], in order to check that
the construction complies with the Rules. 2.2 Hardware type approval
1.1.4 Automation systems are to be tested when installed 2.2.1 Hardware type approval of automation systems is
on board and prior to sea trials, to verify their performance obtained subject to the successful outcome of the tests
and adaptation on site, according to [4]. described in Tab 1.
6 Damp heat IEC Publication 60068- Temperature: 55°C • measurement of insulation resistance
2-30 Test Db Humidity: 95% before test
Duration: 2 cycles (12 + 12 hours) • equipment operating during the complete
first cycle and switched off during second
cycle except for functional test
• functional test during the first 2 hours of
the first cycle at the test temperature and
during the last 2 hours of the second cycle
at the test temperature
• recovery at standard atmosphere condi-
tions
• insulation resistance measurements and
performance test
14 Radiated Radio IEC 61000-4-3 Frequency range: • to simulate electromagnetic fields radiated
Frequency 80 MHz to 2 GHz by different transmitters
Modulation**: 80% AM at 1000Hz • the test is to be confined to the appliances
Field strength: 10V/m exposed to direct radiation by transmitters
Frequency sweep rate: at their place of installation
≤ 1,5.10-3 decades/s (or 1% / 3 sec) • performance criterion A (see (5))
According to level 3 severity standard ** If, for tests of equipment, an input signal
with a modulation frequency of 1000 Hz is
necessary, a modulation frequency of 400 Hz
should be chosen
15 Conducted A.C.: • to simulate distortions in the power supply
Audio • Frequency range: rated frequency system generated, for instance, by elec-
Frequency to 200th harmonic tronic consumers and coupled in as har-
• Test voltage (rms): 10% of supply monics
to 15th harmonic reducing to 1% • see figure “Test set-up” (see (8))
at 100th harmonic and maintain • performance criterion A (see (5))
this level to the 200th harmonic,
min 3 V r.m.s, max. 2 W
D.C.:
• Frequency range: 50 Hz - 10 kHz
• Test voltage (rms) :10% of supply,
max. 2 W
Generator
Power supply
AC DC
L1 (+)
V Volmeter *)
EUT N (÷)
PE
*) Decoupling (optional)
Vibration and salt mist testing may be performed on differ- 3 Acceptance testing
ent specimens, where applicable.
Reset of the automation system is accepted between each 3.1 General
test, where necessary.
3.1.1 Acceptance tests are generally to be carried out at the
2.2.2 The following additional tests may be required, depend- manufacturer’s facilities before the shipment of the equip-
ing on particular manufacturing or operational conditions: ment, when requested.
• mechanical endurance test Acceptance tests refer to hardware and software tests as
applicable.
• temperature shock test (e.g. 12 shocks on exhaust gas
temperature sensors from 20°C ± 5°C to maximum tem-
3.2 Hardware testing
perature of the range)
• immersion test 3.2.1 Hardware acceptance tests include, where applicable:
• oil resistance test • visual inspection
• operational tests and, in particular:
• shock test.
- tests of all alarm and safety functions
The test procedure is to be defined with the Society in each - verification of the required performance (range, cali-
case. bration, repeatability, etc.) for analogue sensors
- verification of the required performance (range, set
2.3 Software type approval points, etc.) for on/off sensors
- verification of the required performance (range,
2.3.1 Software of computer based systems are to be response time, etc.) for actuators
approved in accordance with Information Note “Software
Assessment for Shipboard Computer Based System” (NI- - verification of the required performance (full scale,
425). etc.) for indicating instruments
• endurance test (burn-in test or equivalent)
Type approval consists of an assessment of the development
quality and verification of test results. • high voltage test
• hydrostatic tests.
Assessment certificate may be issued at the request of the
manufacturer when approval is granted. Additional tests may be required by the Society.
2.3.2 Software are to be approved in association with hard- 3.2.2 Final acceptance will be granted subject to:
ware. Reference of software and hardware should be speci- • the results of the tests listed in [3.2.1]
fied in type approval certificate.
• the type test report or type approval certificate.
2.3.3 Basic software of standard type used as tools for oper-
ation of a computer based system may be accepted without 3.3 Software testing
type approval at the discretion of the Society.
3.3.1 Software acceptance tests of computer based systems
are to be carried out to verify their adaptation to their use
2.4 Navigational and radio equipment on board, and concern mainly the application software.
2.4.1 The test conditions as specified in the IEC 60945 3.3.2 The software modules of the application software are
(marine navigational and radiocommunication equipment to be tested individually and subsequently subjected to an
and systems - general requirements, methods of testing and integration test. The test results are to be documented and to
required test results) may be applied. be part of the final file. It is to be checked that:
• the development work has been carried out in accord-
2.5 Loading instruments ance with the plan
• the documentation includes the proposed test, the
2.5.1 Loading instrument approval consists of: acceptance criteria and the result.
• approval of hardware according to [2.2], unless two Repetition tests may be required to verify the consistency of
computers are available on board for loading calcula- test results.
tions only
• approval of basic software according to [2.3] 3.3.3 Software acceptance will be granted subject to:
• examination of the available documentation
• approval of application software, consisting in data veri-
fication which results in the Endorsed Test Condition • a functional test of the whole system.
according to Part B
The Society may ask for additional tests of systems which are
• installation testing according to [4]. part of safety systems or which integrate several functions.
4 On board tests
Table 2 : On board tests
Upon completion of on board tests, test reports are to be Reading Checking of calibration, full scale and
made available to the Surveyor. instruments standard reference value