The document calculates the battery size requirements for a fire alarm control panel based on its standby and alarm currents. It lists the equipment, standby and alarm currents, total current requirements, and recommended battery size as 11.8974 Amp-hours. The battery size is calculated using a formula that multiplies the standby and alarm currents by their durations and a derating factor of 1.2.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
232 views1 page
3X Battery Calculations
The document calculates the battery size requirements for a fire alarm control panel based on its standby and alarm currents. It lists the equipment, standby and alarm currents, total current requirements, and recommended battery size as 11.8974 Amp-hours. The battery size is calculated using a formula that multiplies the standby and alarm currents by their durations and a derating factor of 1.2.