This document provides relay setting calculations for the Ittagi-Lingapur transmission line. It includes details of the transmission line such as the station names, line name, voltage level, and conductor details. It also lists the resistance and reactance values for the three protection zones along the transmission line. The recommended relay settings for phase-to-phase and phase-to-earth faults are provided for each zone in percentage and ohms. Forward and backward mho settings are also specified.

Uploaded by

Ravi Shankar V
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
148 views1 page

Karnataka Power Transmission Corporation Limited MRT Circle, Bangalore

This document provides relay setting calculations for the Ittagi-Lingapur transmission line. It includes details of the transmission line such as the station names, line name, voltage level, and conductor details. It also lists the resistance and reactance values for the three protection zones along the transmission line. The recommended relay settings for phase-to-phase and phase-to-earth faults are provided for each zone in percentage and ohms. Forward and backward mho settings are also specified.

Uploaded by

Ravi Shankar V
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 1

Karnataka Power Transmission Corporation Limited

MRT Circle, Bangalore


Date 23/12/05
Relay settings Calculations
Scheme:MDT-45 Conductor: Drake

Station Name Ittagi Zone 1 Reach APP


Line Name HKT Mining Res. Reach 2.5728
kV 66 Rea.Reach 12.7968
PTR 600 IMP 13.052869036
CTR 600 Zone 2 Reach APP
Line Length 40 Res. Reach 0.7236
Adj. Shortest Line Lingapur Rea.Reach 3.5991
Ad.Sh.Line Length 18 IMP 3.6711194165
Adj. Long. Line Lingapur Zone 3 Reach APP
Adj. Long. Line length 18 Res. Reach 1.4472
Conductor details Rea.Reach 7.1982
Protected line(+ve seq) Imp 7.3422388329
R1 0.0804 Zone I Resistance 2.5728
X1 0.3999 Zone 1 Reactacne 12.7968
Adj. Shortest Line Zone 1 IMP 13.052869036
R2 0.0804 Zone 2 Resistance 3.9396
X2 0.3999 Zone 2 Reactance 19.5951
Adj.Long Line Zone 2 IMP 19.987205712
R3 0.0804 Zone 3 Resistance 4.6632
X3 0.3999 Zone 3 Reactance 23.1942
Protected Line (Zero Seq) Zone 3 IMP 23.658325128
Ro 0.229 Zone 1Zero seq R 7.328
Xo 1.246 Zone 1Zero seq X 39.872
Protected line Z 0.407902157
Protected line Zo 1.266868975
Protected Line (Zom)
Rom 0.261
Xom 0.68774

Settings to be Adopted 145.4037863


0.374565801
Z
Ph - Ph Zone 1 Zone 2 Zone 3
% Settings 25.5 66.7 56.400
Ohms 1 4 4.000

Ph - E
% Settings 25.5 66.7 33.100
Ohms 1 4 4.000
Offset Mho Settings
Forward 46.9 %, 4 ohms
Backward 1 ohms
PSB : All plugs in off position
ZH plugs in H position
Zone 2 time = 0.5 sec
Zone 3 time = 1.0 sec