EGCP-2 Engine Generator Control Package

Download as pdf or txt
Download as pdf or txt
You are on page 1of 64

EGCP-2 Communications Manual

EGCP-2
Engine Generator Control Package

Manual 26181 (Revision A)


WARNING—DANGER OF DEATH OR PERSONAL INJURY
WARNING—FOLLOW INSTRUCTIONS
Read this entire manual and all other publications pertaining to the work to be performed
before installing, operating, or servicing this equipment. Practice all plant and safety
instructions and precautions. Failure to follow instructions can cause personal injury and/or
property damage.
WARNING—OUT-OF-DATE PUBLICATION
This publication may have been revised or updated since this copy was produced. To verify
that you have the latest revision, be sure to check the Woodward website:
www.woodward.com/pubs/current.pdf
The revision level is shown at the bottom of the front cover after the publication number. The
latest version of most publications is available at:
www.woodward.com/publications
If your publication is not there, please contact your customer service representative to get
the latest copy.
WARNING—OVERSPEED PROTECTION
The engine, turbine, or other type of prime mover should be equipped with an overspeed
shutdown device to protect against runaway or damage to the prime mover with possible
personal injury, loss of life, or property damage.
The overspeed shutdown device must be totally independent of the prime mover control
system. An overtemperature or overpressure shutdown device may also be needed for
safety, as appropriate.
WARNING—PROPER USE
Any unauthorized modifications to or use of this equipment outside its specified
mechanical, electrical, or other operating limits may cause personal injury and/or property
damage, including damage to the equipment. Any such unauthorized modifications: (i)
constitute "misuse" and/or "negligence" within the meaning of the product warranty
thereby excluding warranty coverage for any resulting damage, and (ii) invalidate product
certifications or listings.

CAUTION—POSSIBLE DAMAGE TO EQUIPMENT OR PROPERTY


CAUTION—BATTERY CHARGING
To prevent damage to a control system that uses an alternator or battery-charging device, make
sure the charging device is turned off before disconnecting the battery from the system.
CAUTION—ELECTROSTATIC DISCHARGE
Electronic controls contain static-sensitive parts. Observe the following precautions to
prevent damage to these parts.
• Discharge body static before handling the control (with power to the control turned off,
contact a grounded surface and maintain contact while handling the control).
• Avoid all plastic, vinyl, and Styrofoam (except antistatic versions) around printed circuit
boards.
• Do not touch the components or conductors on a printed circuit board with your hands
or with conductive devices.

IMPORTANT DEFINITIONS
• A WARNING indicates a potentially hazardous situation which, if not avoided, could result in
death or serious injury.
• A CAUTION indicates a potentially hazardous situation which, if not avoided, could result in
damage to equipment or property.
• A NOTE provides other helpful information that does not fall under the warning or caution
categories.

Revisions—Text changes are indicated by a black line alongside the text.

Woodward Governor Company reserves the right to update any portion of this publication at any time. Information
provided by Woodward Governor Company is believed to be correct and reliable. However, no responsibility is
assumed by Woodward Governor Company unless otherwise expressly undertaken.
© Woodward 2002
All Rights Reserved
Manual 26181 EGCP-2 Communications

Contents

ELECTROSTATIC DISCHARGE AWARENESS .................................................. II 


CHAPTER 1. GENERAL INFORMATION ........................................................... 1 
Overview .................................................................................................................1 
ServLink Overview..................................................................................................2 
Specifications .........................................................................................................2 
CHAPTER 2. EGCP-2 HMI SOFTWARE INSTALLATION .................................. 3 
CHAPTER 3. HARDWARE CONNECTIONS....................................................... 5 
CHAPTER 4. MONITORING SERVLINK SOFTWARE OPERATION ...................... 6 
Operating EGCP-2 Monitoring Software ..............................................................11 
CHAPTER 5. SERVLINK AND WATCH WINDOW CONFIGURATION SOFTWARE 18 
ServLink Variable List ...........................................................................................21 
CHAPTER 6. MODBUS RTU COMMUNICATIONS FOR THE EGCP-2 PANEL .... 35 
Introduction ...........................................................................................................35 
Modbus Configuration Items ................................................................................35 
CHAPTER 7. DOWNLOAD.EXE SETPOINT UTILITY ........................................ 52 
Introduction ...........................................................................................................52 
Requirements .......................................................................................................52 
Instructions ...........................................................................................................52 
CHAPTER 8. SERVICE OPTIONS ................................................................. 55 
Product Service Options .......................................................................................55 
Woodward Factory Servicing Options ..................................................................56 
Returning Equipment for Repair ...........................................................................57 
Replacement Parts ...............................................................................................57 
Engineering Services ...........................................................................................58 
How to Contact Woodward ...................................................................................58 
Technical Assistance ............................................................................................59 

Illustrations and Tables


Table 5-1. ServLink Variable List <<no category>> Category............................22
Table 5-2. ServLink Variable List Control Overview Category...........................23
Table 5-3. ServLink Variable List Front Panel Category .....................................24
Table 5-4. ServLink Variable List Gen Overview Category ................................25
Table 5-5. ServLink Variable List SPt (SetPoint) Category ..................................26
Table 6-1. Common Modbus Error Numbers .......................................................37
Table 6-2. Modbus Addresses for the RTU Protocol ...........................................44

Woodward i
EGCP-2 Communications Manual 26181

Electrostatic Discharge Awareness


All electronic equipment is static-sensitive, some components more than others.
To protect these components from static damage, you must take special
precautions to minimize or eliminate electrostatic discharges.

Follow these precautions when working with or near the control.

1. Before doing maintenance on the electronic control, discharge the static


electricity on your body to ground by touching and holding a grounded metal
object (pipes, cabinets, equipment, etc.).

2. Avoid the build-up of static electricity on your body by not wearing clothing
made of synthetic materials. Wear cotton or cotton-blend materials as much
as possible because these do not store static electric charges as much as
synthetics.

3. Keep plastic, vinyl, and Styrofoam materials (such as plastic or Styrofoam


cups, cup holders, cigarette packages, cellophane wrappers, vinyl books or
folders, plastic bottles, and plastic ash trays) away from the control, the
modules, and the work area as much as possible.

4. Do not remove the printed circuit board (PCB) from the control cabinet
unless absolutely necessary. If you must remove the PCB from the control
cabinet, follow these precautions:

• Do not touch any part of the PCB except the edges.

• Do not touch the electrical conductors, the connectors, or the


components with conductive devices or with your hands.

• When replacing a PCB, keep the new PCB in the plastic antistatic
protective bag it comes in until you are ready to install it. Immediately
after removing the old PCB from the control cabinet, place it in the
antistatic protective bag.

CAUTION—ELECTROSTATIC DISCHARGE
To prevent damage to electronic components caused by improper handling,
read and observe the precautions in Woodward manual 82715, Guide for
Handling and Protection of Electronic Controls, Printed Circuit Boards, and
Modules.

ii Woodward
Manual 26181 EGCP-2 Communications

Chapter 1.
General Information

Overview
The EGCP-2 has two communication ports: the inter-control RS-485 port and
the configurable RS-422 port. EGCP-2 controls communicate with each other
over the RS-485 network. This network uses a proprietary protocol and is not
intended to be accessed for information. The configurable RS-422 port protocol
may be selected for one of three options: ServLink communications protocol,
which uses the Woodward PC Tools interface exclusively, Modbus® * RTU
protocol, which uses an open protocol used by many third party software
manufacturers, or Upload Setpoints, which is a Microsoft DOS based program
used to transfer setpoint files between the control and a PC.
*—Modbus is a registered trademark of Schneider Automation Inc.

To select which protocol will be used, enter the Sequencing and Comms
configuration menu of the EGCP-2 panel using the proper software password,
and scroll to the menu item labeled “422 Protocol”. The selections under this
menu item are:
1. ServLink
2. Modbus
3. Upload Setpoints

NOTE
Whenever the RS-422 protocol setpoint is changed, the EGCP-2 must be
powered down, then powered up again to reset to the new protocol.

If ServLink is chosen for the protocol selection, the EGCP-2 will communicate in
the ServLink protocol, which is used with the Woodward EGCP-2 HMI software
P/N 8928-364 (see Chapter 2, EGCP-2 HMI Software Installation) or with the
Woodward Watch Window Professional software P/N 8928-800 (see Chapter 5,
ServLink and Watch Window Configuration Software).

If Modbus is chosen, the EGCP-2 will communicate in MODBUS RTU protocol,


and make its information available according to the address list shown in Table
6-2, Modbus Addresses for the RTU Protocol. Also, when the RS-422 Protocol is
set to Modbus, the Modbus Address, Modbus Time-out, and Modbus Reset
menu items of the Sequencing and Communications menu become functional.

If Upload Setpoints is chosen, the EGCP-2 panel will switch to a communications


mode where it is waiting to see characters on the 422 serial port that set it to
transfer the contents of the setpoint file to the PC. This task is run on the PC
using the download.exe DOS program (see Chapter 7, Download.exe Setpoint
Utility for more information).

Woodward 1
EGCP-2 Communications Manual 26181

ServLink Overview
Woodward’s ServLink and EGCP-2 HMI monitoring software package are
located on a single Compact Disc which ships with every unit. These software
tools are used together to establish communications with, and serve as a
monitoring and configuration interface for, the EGCP-2 platform.

When installed on a computer, the ServLink and EGCP-2 HMI files will reside in
the same directory, typically on the hard drive of the computer they are installed
on. Icons associated with the executable files for both the ServLink and EGCP-2
HMI software will be automatically generated upon installation.

These icons are used to run the programs. Using the computer’s RS-232 serial
port, the ServLink software establishes a direct serial communication link
between the computer and the EGCP-2. The ServLink software may also be
configured to operate via a modem for remote communications to the EGCP-2
control(s).

The ServLink software must always be started before the EGCP-2 HMI software
can be run. The ServLink software provides a bridge between the control and the
computer making the data from the control available to the computer software
applications.

The EGCP-2 software duplicates the front panel of the EGCP-2 hardware
platform. All the monitoring information which can be obtained from the hardware
can also be accessed by the EGCP-2 software in a format which is identical to
that of the hardware. This makes the software very familiar to those accustomed
to the EGCP-2 control keypad functions and LCD readout displays.

Specifications
Communications:
• RS-422 protocol
• 9600 Baud (fixed maximum)
• No Parity
• 1 Stop Bit
Minimum Computer Requirements:
• Pentium® 133 MHz PC
• 32 MB of RAM
• Windows® 95, 98, NT 4.0, and 2000 or greater (Windows NT or 2000
preferred)
Modem Requirements:
• Transmitting Modem:
o 9600 Baud Capability (minimum)
o 8 Data Bits
o No Parity
o 1 Stop Bit
• Receiving Modem:
o 9600 Baud Capability (minimum)
o DTR :OFF
o Echo Offline Commands: OFF
o Auto Answer: ON
o Smart Mode (if applicable): ON
o Handshaking: OFF

2 Woodward
Manual 26181 EGCP-2 Communications

Chapter 2.
EGCP-2 HMI Software Installation

The EGCP-2 Monitoring Software is located on a single compact disc. This disc
contains self-installing software required for installation of the ServLink and
EGCP-2 Monitoring Software onto a computer hard-drive operating within a
32 bit environment.

To install the software on your computer’s hard drive, turn on your computer and
wait until the Windows desktop is displayed. Insert the compact disc (CD) into
the CD drive of the computer which the installation will take place.

Go to the task bar located at the bottom of the desktop screen, and click once on
the Windows Start button. Then click on the Run option.

A dialog box will pop up and display a prompt window asking for the program you
wish to run. If you know the drive letter allocated to your CD drive type this drive
letter, followed by a colon, and then a back slash followed by the word “setup”.
For example, if CD the drive designation for your computer is D, the following
would be typed into the dialog box:
D:\SETUP

If you are unsure of which drive on your computer is designated as the CD drive,
you can double-click on the Windows desktop icon labeled “My Computer” to
display the various drive and network connections for your computer. Look for
the icon showing the CD drive followed by the drive letter designation. This letter
is the letter which must be used when in the Run window dialog box prior to the
setup instruction.

Once you have typed the proper command in the dialog box for setup, press the
Enter (or Return) key on your computer. Windows will automatically begin
reading the CD drive for setup instructions from the EGCP-2 HMI CD setup file
located there.

The ServLink and EGCP-2 software installation will initially prompt the user if it
may automatically create a directory on the hard drive of the computer, and label
this directory “Woodward”. Press the OK button and this directory will be made.
All the ServLink and EGCP-2 software will be placed under this directory on the
computer’s hard drive.

NOTE
Items on the Windows toolbar and desktop may appear differently than is
shown in this manual, depending on active programs in windows at the time
of installation or operation.

The intent of this manual is to accurately depict the windows which are
directly associated with the installation and operation of the EGCP-2
monitoring software.

Woodward 3
EGCP-2 Communications Manual 26181
As the installation continues, the screen will momentarily show the ServLink and
EGCP-2 icons that are created during the setup process. These icons are
automatically inserted into the Program Files menu under the EGCP-2 label.

The installation process has made a new set of programs under the EGCP-2
HMI 1.00 program file. Click once on the desktop tool bar Start button, and select
the Programs option. Among the various programs on the computer hard drive
should now be one group called Woodward, then “EGCP-2 HMI 1.00”. Select this
group to display the ServLink Server, EGCP-2 HMI, and Uninstall EGCP-2 HMI
1.00 executables. These are the executables which were installed from the CD to
the computer hard drive.

The ServLink Server and the EGCP-2 HMI are both used in communicating with
and monitoring the EGCP-2 control system. The Remove EGCP-2 HMI 1.00 icon
will remove all files associated with the installation of this software from the
computer hard drive if it is selected. The Remove program prompts the user prior
to uninstalling the software to confirm this action, which greatly reduces the
chance of accidental removal of the installed software.

Here is a typical screen from the Windows desktop with the ServLink and EGCP-
2 software installed on the computer’s hard drive:

Once the software is successfully installed on the computer, it will remain


resident on the hard drive indefinitely, or until it is uninstalled.

4 Woodward
Manual 26181 EGCP-2 Communications

Chapter 3.
Hardware Connections

Once the software is installed on the computer hard drive, the hardware
connection between the computer and the EGCP-2 control must be made for
correct communication between the two devices. This hardware connection is
completed in one of two ways:
1. Direct cable connection between the computer and the EGCP-2 control(s)
RS-422 network.
2. Remote connection via modem between the computer and the EGCP-2
control(s).
Direct Cable connection between the computer and EGCP-2 control(s) will be
discussed first as it is the most straightforward of the two connection methods.

The laptop or desktop computer, which will be used with the EGCP-2 RS-422
port, will have a 9-pin serial port. This port is configured by the computer
hardware to use a serial communications protocol called RS-232. The details of
this protocol are not important to know for hardware connection to the EGCP-2
control(s), other than there is a need to convert the RS-232 protocol of the
computer port to RS-422 protocol used by the EGCP control network. This
conversion is accomplished by an external conversion module, which takes the
RS-232 serial port input from the computer, and changes it to a RS-422 protocol
for the EGCP-2. These converters can be found in most computer or electronics
stores, and are called RS-232 to RS-422 Converters. Consult the EGCP-2
Installation manual for wiring diagrams. A complete cable assembly can also be
purchased from Woodward. The part number is 5417-551.

In a system with multiple (maximum 8) EGCP-2 controls, each control is


interconnected to the others on the RS-422 network in a multidrop fashion.

Modem connections are very similar, but now a modem is required both at the
computer and at the EGCP-2 end of the network. The modem may be an internal
or external type at the computer, and must be an external type at the EGCP-2
control. The conversion from RS-232 to RS-422 communications is made at the
modem connection into the EGCP-2 control network.

For detailed wiring diagrams pertaining to the RS-422 network of the EGCP-2
controls, please consult the EGCP-2 Installation and Operation Manual, number
26174.

Woodward 5
EGCP-2 Communications Manual 26181

Chapter 4.
Monitoring ServLink Software Operation

Now that the software has been installed on the hard drive of the computer, and
the desired hardware connections are in place between the computer and the
EGCP-2 controls, the next step is to run the software and confirm operation of
the entire communications network.

To run the EGCP-2 software, first click on the Start toolbar button in Windows
desktop, then Programs, Woodward, EGCP-2 HMI 1.00, and then click on the
ServLink server as shown here.

When you click once on the Icon, this screen will appear on the desktop. This is
the Dialog Screen, where the type of communications you are using will be
established prior to operation of the EGCP-2 monitoring software.

6 Woodward
Manual 26181 EGCP-2 Communications

The first action inside the ServLink screen is to set up a new network definition
file. Click once on File, and then on New as shown. The new network definition
window will pop up on the computer screen.
This will open up the Network Options screen. This screen allows the user to
configure the ServLink connection for serial COM port, or modem. When a serial
port is selected, the left side menus will be active and the right side menus will be
grayed out.

The “Use This Port” box of this screen is used to select which communication
port (COM) or modem will be used to communicate using RS-232 protocol to the
EGCP-2 control. Clicking on the drop down box will tell the ServLink software to
scan the computer and list any communications ports which are not being used
by other applications, that may be used for serial communications. If the port that
is desired does not appear, most likely it is being used by some other application
on the computer. Another port should be selected, or the application that was
using the port should be stopped.

Woodward 7
EGCP-2 Communications Manual 26181
The next block down, “In this mode”, is used to select either multidrop or point-to-
point communications over the serial port. Point-to-point communications
assumes that the computer will be communicating with only one control at the
other end of the network. Point-to-point communications should be used only
when the communications between the computer and the EGCP-2 control are
made in a direct fashion (no secondary devices or other EGCP-2 controls can
reside on the same network). There must be only the computer and one EGCP-2
control on the network for point-to-point communications.

The advantage of using the point-to-point communications mode option is speed.


Since the communications are only between the PC and one EGCP-2 control,
the ServLink software will scan for only one unit on the network. This takes less
time than a multidrop communications mode, which scans for all eight units on
the network, regardless of how many units are actually connected to it.

Use the multidrop communications option any time there are two or more
EGCP-2 units that require monitoring from the computer on the same network.

The next box down is the “At this baud rate” box. Set this to 9600 Baud. The
EGCP-2 is only capable of communicating at 9600 baud. Any other number put
in this box will cause communication failure with the EGCP-2 control.

The boxes on the right hand side of the ServLink New File setup screen are
normally turned “off” when the “Use This Port” box is configured for the COM
ports of the computer. However, when the modem option is selected in the “Use
This Port” box, the boxes on the right hand side of the screen become active, as
shown below:

The box labeled “From this location” allows the user to set up various dialing
properties for the modem, and store them under a user-defined name. These
dialing properties include such functions as tone/pulse dialing, call waiting
override, and adding any dialing prefixes to access external lines, etc.

The next box down on the right hand side of the screen is the “Using this phone
number” box. Here information about the number of origin and the number to be
dialed are entered by the user.

8 Woodward
Manual 26181 EGCP-2 Communications
When all the various communications options are selected in the ServLink
screen, press the OK button. ServLink will automatically dial the modem (if
applicable) and scan the network for active controls. This may take several
minutes, depending on network configuration. Here is what the screen of the
computer looks like when it is scanning the network for active controls:

When communications are established with the EGCP-2 control network, the
scanning screen will change to show that the ServLink software is reading the
control information. That screen will look like this:

Once communications are established, and the data is read from the EGCP-2
control network, the ServLink software will show each control it is communicating
on the network by that control’s network address. Here is a typical ServLink
network definition screen for a three-unit EGCP-2 network:

Woodward 9
EGCP-2 Communications Manual 26181

If your network configuration is constant (neither the number of controls on the


network nor the PC attached to the network will change), you may want to save
the Network Definition File you have created for ServLink. To do this, click on the
File button in the upper left hand window of ServLink. Select “Save As”. A dialog
window will pop up and ask you to name the new network definition file you have
created. Typically, this file will be stored in the EGCP-2 directory on the hard
drive of the computer ServLink is operating from. The file name given to the
network definition file will be given a “.net” extension. Once you have selected a
file name, click on the OK button in the dialog box. This saves the network
definition file you created.

Once you have created and saved the network definition file for ServLink, all you
have to do in the future to run the definition file is open ServLink from the
Programs Menu, and select File, and then Open. When Open is selected, a list
will appear containing the network definition file you created. Select the desired
network definition file, and ServLink will automatically select the necessary
communications options defined by the file and establish a communications link
with the EGCP-2 control network.

Now that ServLink has established a network connection, you may want to
“minimize” the ServLink window by clicking on the Minimize button in the upper
right hand of the ServLink Window. When you minimize an application, the
software continues running, but the window is reduced to a button on the desktop
toolbar. You can restore the application window to full size at any time by clicking
on the reduced toolbar button for that software with the left mouse button.

NOTE
Terminating ServLink will result in loss of communications with the network.
The ServLink Network Definition file will have to be executed again to re-
establish this link.

10 Woodward
Manual 26181 EGCP-2 Communications

Operating EGCP-2 Monitoring Software


Now that the communications link is established between the computer and the
EGCP-2 controls, the EGCP-2 Monitoring Software Tool can be used to view the
various parameters of each control on the RS-422 network.

To open the EGCP-2 controls program, click once on the Start button in the
desktop toolbar. Select Programs, Woodward, EGCP-2 HMI 1.00, and EGCP-2
HMI. Click once on the EGCP-2 HMI icon to execute the monitoring program, as
shown below:

Provided that the ServLink software is currently connected to the control network,
clicking this icon will start the HMI program. The HMI program cannot be run
without being connected to a control.

When the control is linked to the EGCP-2 monitoring software, the LCD display
on the hardware units will display an asterisk (*) cursor instead of the usual solid
block cursor. This allows operators of the EGCP-2 to recognize the units are
being accessed by remote control simply by looking at the display screen of the
hardware units.

When the control is linked to the EGCP-2 monitoring software, the Master
Situation Monitor screen will appear. This screen will show all EGCP-2 controls
connected to the network, and their various status information, as shown here:

Woodward 11
EGCP-2 Communications Manual 26181

This Master Situation Monitor Screen is showing three EGCP-2’s. Unit one is
generating power with no alarms. Units two and three are not generating power,
and unit three has an active alarm.

To view a specific unit’s front panel display, highlight the unit you wish to observe
using a single click of your mouse on that unit’s display line in the Master
Situation Monitor, as shown here. Then click the Front Panel icon on the lower
section of the screen next to the Woodward logo or simply double-click the unit
that is to be observed.

12 Woodward
Manual 26181 EGCP-2 Communications
The Front Panel Display for that unit EGCP-2 (Unit 1 in this case) will pop up as
shown below:

Multiple units can be viewed on the Windows desktop simultaneously. Each unit
is “stacked” on top of the others. You can view any unit by clicking the left mouse
key once on any part of that unit’s Front Panel display window, or if the front
panel display has been minimized, by clicking on the minimized bar for that front
panel on the desktop. Here is a screen showing a two unit system with both front
panels on the desktop. Notice that the unit is identified on the upper left hand
side of the front panel display bar.

Woodward 13
EGCP-2 Communications Manual 26181
The front panel display of the EGCP-2 monitoring software allows access to any
monitoring information available on the actual unit. The buttons of the front panel
operate in the same manner as the EGCP-2 as well. The front panel display
operates in the same manner as most desktop windows, except that the size of
the front panel display cannot be changed or maximized. The front panel display
can be closed by clicking the X button in the upper right hand corner, or
minimized to toolbar buttons using the under bar [_] button in the upper right
hand corner. If a front panel display window is closed, it must be re-opened from
the Master Situation Monitor.

In the following example there is an alarm condition on Unit #1. Highlighting Unit
#1, and then clicking on the front panel display icon in the lower left corner of the
Master Situation Monitor displays the front panel display for Unit #1.

14 Woodward
Manual 26181 EGCP-2 Communications
The front panel display for Unit 1 indicates two alarms in the System Status
menu. Clicking the Alarm/Event button with the left mouse button displays the
Alarm / Event Log of the control to the right hand LCD display as shown below:

The alarm event list shows two alarms. The most recent is a Mains Frequency
Low Alarm logged on June 17 at 13:21, and the other is a Remote Fault 3
discrete input driven alarm logged on the same date at 13:19.

Pressing the Scroll Down key as shown below scrolls the alarm event list in the
right hand display to show the end of the alarm event log list, as shown below.

Woodward 15
EGCP-2 Communications Manual 26181
Pressing the Alarm Clear Button results in the logged alarm events being
removed from the alarm event list. When all alarms have been cleared, the list
displays “None Recorded” as shown.

Pressing the Status button on the front panel display will revert the EGCP-2
display back to the status mode. Now both left and right displays show the status
information for the item selected.

16 Woodward
Manual 26181 EGCP-2 Communications
Using the Status, Configuration and Alarm/Event keys on the Front Panel display
will provide access to any screen and function that is normally available to the
users operating the unit directly from the front panel of the EGCP-2. For more
information on how to navigate between the various menus and menu items in
the EGCP-2, see the EGCP-2 Operation and Installation Manual number 26174.

To shut down the Master Situation Monitor, click once on the “X” button in the
upper right hand corner of the Master Situation Monitor. A pop-up window will
ask the operator to confirm the choice to shut down the EGCP-2 Monitoring
Software.

Selecting Yes shuts down the monitoring software. If No is selected, the


Monitoring software continues to monitor the control network.

Once the Monitoring software is shut down, the ServLink software must also be
terminated to shut down the external communication link over the RS-232 port of
the computer.

This concludes a typical EGCP-2 monitoring session using the ServLink


Software and EGCP-2 monitoring tool software.

Woodward 17
EGCP-2 Communications Manual 26181

Chapter 5.
ServLink and Watch Window
Configuration Software

In addition to the EGCP-2 HMI software, the EGCP-2 can also be configured
using the Woodward Watch Window Professional software. The Watch Window
software adds the ability to monitor data from a computer. It also allows a user to
save the control set points to a tab-delimited text file. The text file can be printed,
edited, and transferred to an EGCP-2 unit.

Watch Window Professional software is not included with the EGCP-2 panel.
This software must be purchased separately (part number 8928-800). To
evaluate the product before purchase, the software can be downloaded from the
Woodward website (www.woodward.com/ic/software). After downloading the
software, it will be active for a five day trial period, after which time, the software
will require a license to run.

The Watch Window software works similarly to the HMI software. The first step is
to connect to the control with the ServLink Server (see Chapter, Monitoring
ServLink Software Operation for information on starting a ServLink session). The
Watch Window Software will not run unless the computer is communicating with
at least one EGCP-2. Once the ServLink communication has been established,
start the Watch Window Professional program from the Windows toolbar Start
button.

The Watch Window Professional software comprises three separate windows,


each with a different function.

18 Woodward
Manual 26181 EGCP-2 Communications

2 3

The Application Control window (1) is the main window for the software. It is
used to manage the Explorer window (2) and the Inspector window (3). A tool bar
is provided with icons to open, close, and save Inspectors, and to upload and
download the tunable setpoints.

New Open Save Add Close Load Save I/O Lock


Inspector Inspector Inspector Sheet Sheet Settings Settings

The Explorer window uses a tree similar to the


Windows Explorer program used to manage files
on the computer. Under each folder are subfolders,
which hold the various data variables.

In this picture the A phase current is found in the


Amps folder in the Gen Overview folder. Notice
that the number of amps is not shown.
Only the variable names can be found in the
Explorer window. In order to see the values
associated with the variable, the variable needs to
be transported to the Inspector screen. The user
determines which values are to be placed on the
inspector screen by clicking on the item in the
Explorer Window and dragging it into the Inspector
window. Variables can be selected individually or a
folder can be selected which will include all of the
items in that folder.

Woodward 19
EGCP-2 Communications Manual 26181

In the inspector screen the variable name is shown in four parts. First the identity
of the control is listed under the Control column. Then the Category, Block, and
Field are listed. Each variable will have a unique Field name. The Block is the
folder that the variable was located in, and the Category is the top level folder.
This is followed by the real time Value of that variable, and a Description field,
which can be edited by the user to add any notes or comments with the
inspector. For example, the units for a particular variable could be added.

There are three variable types that can be seen in the inspector screen and they
are identified by the following icons:

A variable that is read-only is marked by a set of eyeglasses.

A variable, which is adjustable, is marked with a pencil.

A variable that is only adjustable while the engine is shutdown, is


marked by a shield and pencil.

On the screen above, the middle item LO OIL PRESS LMT has been selected
and, because it is adjustable, a pair of arrows appear to the right of the value.
These arrows can be used to adjust the value by a ±1 % or ±10 % increment. It
is also possible to click the mouse in the Value box and enter a number directly
from the computer keyboard. The adjustment range for this variable is shown at
the bottom of the window. When using the adjustment arrows the changed value
becomes active immediately (no other action is needed). When using direct entry
the adjust arrows are replaced by a button with an equal sign. After the correct
value has been entered, click the equal sign button to activate the entered value.

20 Woodward
Manual 26181 EGCP-2 Communications

ServLink Variable List


The ServLink variables are divided into
five Category folders. The first four folders
contain information to be read from the
control. The SPt, or Setpoint folder,
contains the setpoint menus, where
tunable setpoints can be adjusted.

<< No Category>> Information


Under the <<no category>> heading are
12 Blocks of variables. Some of these
folders will contain information which is
not useful, such as
Begin Programming Mode,
End Programming Mode,
Front Panel,
Reset,
Save Values,
Shutdown,
Write Program Memory.

Woodward 21
EGCP-2 Communications Manual 26181
Table 5-1. ServLink Variable List <<no category>> Category

Block Field Description


Application ID Software part number
Configuration ID Compile date
Control ID Control number 1 through 8
Control Status Should return 1
<<no block>>
Product ID Should return GCP
Protocol ID ServLink version information
Run Mode Not used
System ID Control software information
Alarm LED State Status of front panel LED
Alarms Number of active alarms
Bus in Spec Bus voltage and frequency OK
Gen in Spec Gen voltage and frequency OK
Last Alarm Message Not used
Control Overview
LC State Not used
Mains in Spec Mains voltage and frequency OK
Priority Unit priority number
PT Connect 1 = Mains 2 = Bus
Unit Unit Address
Battery Voltage DC volts
KWhrs Kilowatt hours accumulated
Oil Pres Oil pressure in PSI or Bar
Engine Overview
RPM Engine speed
Run Time Run hours accumulated
Water Temp Coolant temp in C or F
Gen Freq Generator Frequency
Gen Overview
PF Generator average Power Factor
Load % of rated load generating
Manual Volt Bias % Bias command from Master for
multi-unit sync to Mains
Synchroscope Master Sync Bias % Bias command from Master for
multi-unit sync to Mains
Speed Bias Speed Bias Output in %
Volt Bias Speed Bias Output in %

Control Overview Information


Under the Control Overview heading are
two blocks of information.

22 Woodward
Manual 26181 EGCP-2 Communications
Table 5-2. ServLink Variable List Control Overview Category

Block Field Description


Audible Alarm Relay 11 Status
Engine Crank Relay 5 Status
Engine Preglow Relay 3 Status
Fuel Solenoid Relay 4 Status
Gen Breaker Relay 2 Status
Gen Breaker Trip Relay 10 Status
Relays
Idle/Rated or KVA Relay 12 Status
Local Bus PT Connect Relay 7 Status
Mains Breaker Relay 1 Status
Mains Breaker Trip Relay 9 Status
Mains Bus PT Disconnect Relay 8 Status
Visual Alarm Relay 6 Status
01 Auto Manual Discrete input 1 Status
02 Test Engine Discrete input 2 Status
03 Run W/Load Discrete input 3 Status
04 Voltage Raise Discrete input 4 Status
05 Voltage Lower Discrete input 5 Status
Switch 06 Speed Raise Discrete input 6 Status
07 Speed Lower Discrete input 7 Status
08 Gen CB Aux Discrete input 8 Status
09 Main CB Aux Discrete input 9 Status
10 Process Discrete input 10 Status
Remote Fault 1 Discrete input 11 Status
Remote Fault 2 Discrete input 12 Status
Remote Fault 3 Discrete input 13 Status
Switch Remote Fault 4 Discrete input 14 Status
Remote Fault 5 Discrete input 15 Status
Remote Fault 6 Discrete input 16 Status

Front Panel Information


Under the Front Panel heading are two blocks of information.

These variables are used by the EGCP-2


HMI program that is described in Chapter
3 of this manual. The Button variables are
commands that operate just as if an
operator has pressed one of the buttons
on the front panel. The variable will briefly
show a True value and then revert to
False. The Lines show the text that is
currently being displayed on the two
screens. Some of this text may not be
displayed correctly by the Watch Window
software.

Woodward 23
EGCP-2 Communications Manual 26181
Table 5-3. ServLink Variable List Front Panel Category

Block Field Description


Alarm Acknowledge Same as Alarm Clear button
Alarm List Same as Alarm / Event button
ATS Same as ATS button
Commit Same as Enter button
Configure Same as Config button
Down Same as down arrow button
Escape Same as Esc button
Generator Same as Gen button
IO Status Same as I/O button
Button Left Same as left arrow button
Prime Mover Same as Engine button
Reactive Load Same as PF / KVAR button
Real Load Same as KW Load button
Right Same as right arrow button
Sequencing Same as Sequencing button
Status Same as Status button
Synchronizer Same as Sync button
System Same as System button
Up Same as up arrow button
0 Text Displayed on line 1, left
display
1 Text Displayed on line 2, left
display
2 Text Displayed on line 3 ,left
display
3 Text Displayed on line 4 ,left
display
Line
4 Text Displayed on line 5 , right
display
5 Text Displayed on line 6 , right
display
6 Text Displayed on line 7 , right
display
7 Text Displayed on line 8 , right
display

24 Woodward
Manual 26181 EGCP-2 Communications

Gen Overview Information


Under the Gen Overview heading are 5
Blocks of variables. All of the three phase
voltage, current, and power information is
contained in these folders.

Table 5-4. ServLink Variable List Gen Overview Category

Block Field Description


A Generator A phase Amps
Amps B Generator B phase Amps
C Generator C phase Amps
A Generator A phase Volt Amps
KVA B Generator B phase Volt Amps
C Generator C phase Volt Amps
A Generator A phase kVARS
KVAR B Generator B phase kVARS
C Generator C phase kVARS
A Generator A phase kW
KWatts B Generator B phase kW
C Generator C phase kW
A Generator A phase Volts
Volts B Generator B phase Volts
C Generator C phase Volts

Woodward 25
EGCP-2 Communications Manual 26181

SPt (SetPoint) Information


Under the SPt heading are 10 Blocks of
tunable setpoints. These Blocks match the
menu structure that is accessed by the
Config button of the EGCP-2. Values
changed in this menu are used
immediately and are saved to memory and
retained on loss of power to the control.
The function of these setpoints will not be
discussed here. This information can be
found in manual 26174.

When adjusting the Configuration items


be sure the engine is shut down. In
order to change these values the user will
need to first place the software in I/O Lock
by clicking on the Lock icon or through the
Control menu. Once the control goes into
I/O lock, it will not be possible to start the
engine. Then after the changes to the
Configuration items are complete, the
control must be reset. Cycling the control input power resets the control.
Because the control power must be reset, it might be better to change the
configuration settings at the front panel itself or remotely using the EGCP-2 HMI
program. These methods do not require a reboot.

Table 5-5. ServLink Variable List SPt (SetPoint) Category

Block Field Description


0 Security Code
1 Network Address
2 Network Priority Not adjustable from Watch Window
3 Number Poles
4 Number Teeth
5 System Frequency 0 = 50 Hz 1 = 60 Hz
6 Rated Speed
7 Rated KW
8 Rated KVA
9 Rated KVAR
10 CT Ratio _____:5
Configuration 11 PT Ratio :1
12 Voltage Input 0 = Line to Neutral (Wye)
1 = Line to Line (Delta)
13 Voltage Reference
14 Display Units 0 = American 1 = Metric
15 Set Date Not adjustable from Watch Window
16 Set Time Not adjustable from Watch Window
17 Start Sequencing 0 = Disabled 1 = Enabled
18 Relay #12 Function 0 = KVA Switch 1 = Idle/Rated
Switch
19 Speed Bias Type 0 = .5 to 4.5 V 1 = ±3 V
2 = 500 Hz PWM

26 Woodward
Manual 26181 EGCP-2 Communications

Block Field Description


20 Voltage Bias Type 0 = ±1 V 1 = ±3 V
2 = ±9 V
21 Ckt Breaker Control 0 = Breaker 1 = Contactor
22 Operating Mode 0 = No Parallel 1 = Mains Parallel
23 Number of Units 0 = Single Unit 1 = Multiple Units
0 Voltage Rng ALM 0 = Disabled 1 = Warning
2 = Visual Alarm 3 = Audible Alarm
1 Gen Volt Hi Lmt
2 Gen Volt Hi Alm 0 = Disabled 1 = Warning
2 = Visual Alarm 3 = Audible Alarm
4 = SoftShutdown 5 = HardShutdown
3 Gen Volt Lo Lmt
4 Gen Volt Lo Alm 0 = Disabled 1 = Warning
2 = Visual Alarm 3 = Audible Alarm
4 = SoftShutdown 5 = HardShutdown
5 Voltage Alm Dly
6 Gen Freq Hi Lmt
7 Gen Freq Hi Alm 0 = Disabled 1 = Warning
2 = Visual Alarm 3 = Audible Alarm
4 = SoftShutdown 5 = HardShutdown
8 Gen Freq Lo Lmt
9 Gen Freq Lo Alm 0 = Disabled 1 = Warning
2 = Visual Alarm 3 = Audible Alarm
4 = SoftShutdown 5 = HardShutdown
10 Spd Freq Mismatch 0 = Disabled 1 = Warning
2 = Visual Alarm 3 = Audible Alarm
4 = SoftShutdown 5 = HardShutdown
11 Overcurrent Lvl
12 Overcurrent Dly
13 Overcurrent Alm 0 = Disabled 1 = Warning
Shutdowns and
2 = Visual Alarm 3 = Audible Alarm
Alarms
4 = SoftShutdown 5 = HardShutdown
14 Reverse Pwr
15 Rev Pwr Delay
16 Min Reverse Pwr
17 Reverse Pwr alm 0 = Disabled 1 = Warning
2 = Visual Alarm 3 = Audible Alarm
4 = SoftShutdown 5 = HardShutdown
18 Reverse KVAR Limit
19 Reverse KVAR
Delay
20 Reverse KVAR 0 = Disabled 1 = Warning
Alarm 2 = Visual Alarm 3 = Audible Alarm
4 = SoftShutdown 5 = HardShutdown
21 Remote Fault 1 0 = Disabled 1 = Warning
2 = Visual Alarm 3 = Audible Alarm
4 = SoftShutdown 5 = HardShutdown
22 Fault 1 Timer
23 RemFlt 1 Stable Dly
24 Remote Fault 2 0 = Disabled 1 = Warning
2 = Visual Alarm 3 = Audible Alarm
4 = SoftShutdown 5 = HardShutdown
25 Fault 2 Timer
26 RemFlt 2 Stable Dly
27 Remote Fault 3 0 = Disabled 1 = Warning
2 = Visual Alarm 3 = Audible Alarm
4 = SoftShutdown 5 = HardShutdown
28 Fault 3 Timer
29 Remote Fault 4 0 = Disabled 1 = Warning
2 = Visual Alarm 3 = Audible Alarm
4 = SoftShutdown 5 = HardShutdown
Woodward 27
EGCP-2 Communications Manual 26181

Block Field Description


30 Fault 4 Timer
31 Remote Fault 5 0 = Disabled 1 = Warning
2 = Visual Alarm 3 = Audible Alarm
Shutdowns and 4 = SoftShutdown 5 = HardShutdown
Alarms 32 Fault 5 Timer
(continued) 33 Remote Fault 6 0 = Disabled 1 = Warning
2 = Visual Alarm 3 = Audible Alarm
4 = SoftShutdown 5 = HardShutdown
34 Fault 6 Timer
0 Preglow Time
1 Crank Time
2 Crank Cutout
3 Crank Delay
4 Crank Repeats
5 Crank Fail 1 = Warning 2 = Visual Alarm
3 = Audible Alarm
6 Idle Speed
7 Idle Time
8 Cooldown Time
9 Cooldown Limit
10Engine Run Time
11 MW Hours
12 Overspeed
13 Overspeed Alarm 0 = Disabled 1 = Warning
2 = Visual Alarm 3 = Audible Alarm
4 = SoftShutdown 5 = HardShutdown
14 Batt Volt Hi Lmt
15 Batt Volt Hi Alm 0 = Disabled 1 = Warning
2 = Visual Alarm 3 = Audible Alarm
4 = SoftShutdown 5 = HardShutdown
16 Batt Volt Lo Lmt
17 Batt Volt Lo Alm 0 = Disabled 1 = Warning
2 = Visual Alarm 3 = Audible Alarm
Engine Control 4 = SoftShutdown 5 = HardShutdown
18 Hi Oil Press Lmt
19 Hi Oil Press Alm 0 = Disabled 1 = Warning
2 = Visual Alarm 3 = Audible Alarm
4 = SoftShutdown 5 = HardShutdown
20 Lo Oil Press Pre-Lmt
21 Lo Oil Press Pre-Alm 0 = Disabled 1 = Warning
2 = Visual Alarm 3 = Audible Alarm
4 = SoftShutdown 5 = HardShutdown
22 Lo Oil Press Lmt
23 Lo Oil Press Alm 0 = Disabled 1 = Warning
2 = Visual Alarm 3 = Audible Alarm
4 = SoftShutdown 5 = HardShutdown
24 Hi H2O Temp Pre-
Lmt
25 Hi H2O Temp Pre- 0 = Disabled 1 = Warning
Alm 2 = Visual Alarm 3 = Audible Alarm
4 = SoftShutdown 5 = HardShutdown
26 High H2O Temp
27 Hi H2O Temp Alm 0 = Disabled 1 = Warning
2 = Visual Alarm 3 = Audible Alarm
4 = SoftShutdown 5 = HardShutdown
28 Low H2O Temp
29 Lo H2O Temp Alm 0 = Disabled 1 = Warning
2 = Visual Alarm 3 = Audible Alarm
4 = SoftShutdown 5 = HardShutdown

28 Woodward
Manual 26181 EGCP-2 Communications

Block Field Description


0 Sync Mode 0 = Check 1 = Permissive 2 = Run
1 Sync Gain
2 Sync Stability
3 Voltage Matching 0 = Disabled 1 = Enabled
4 Voltage Window
5 Max Phase Window
6 Dwell Time
7 C B Hold Time
Synchronizer
8 Close Attempts
9 Reclose Delay
10 Sync Reclose Alm 1 = Warning 2 = Visual Alarm
3 = Audible Alarm
11 Sync Timeout
12 Sync Timeout Alm 1 = Warning 2 = Visual Alarm
3 = Audible Alarm
13 Deadbus Closure 0 = Disabled 1 = Enabled
0 Load Ctrl Mode 0 = Normal 1 = Soft Transfer
2 = KW Droop
1 Load Ctrl Gain
2 Loadshare Gain
3 Load Stability
4 Load Derivative
5 Load Ctrl Filter
6 Baseload Reference
7 Unload Trip
8 Load Droop
Real Load 9 Load Time
Control 10 Unload Time
11 Raise Load Rate
12 Lower Load Rate
13 KW Load High Limit
14 KW High Limit Alarm 0 = Disabled 1 = Warning
2 = Visual Alarm 3 = Audible Alarm
15 KW Load Low Limit
16 KW Low Limit Alarm 0 = Disabled 1 = Warning
2 = Visual Alarm 3 = Audible Alarm
17 KVA Switch Low
18 KVA Switch High
0 VAR/PF Mode 0 = Disabled 1 = PF Control
2 = VAR Control
1 VAR/PF Gain
2 Volts Ramp Time
Reactive Load 3 VAR/PF Sharing Gain
Control 4 VAR/PF Stability
5 KVAR Reference
6 PF Reference 0 = 1.0 lag 0.1 = 0.9 lag
-0.1 = 0.9 lead 0.2 = 0.8 lag
7 PF Deadband

Woodward 29
EGCP-2 Communications Manual 26181

Block Field Description


0 Process Action 0 = Direct 1 = Indirect
1 Process Gain
2 Process Stability
3 Process Derivative
4 Process Deadband
5 Process Droop
6 Process Filter
7 Process Reference
8 Raise Rate
9 Lower Rate
10 Process High Lmt
Process 11 Proc Hi Lmt Alm 0 = Disabled 1 = Warning
Control 2 = Visual Alarm 3 = Audible Alarm
4 = SoftShutdown 5 = HardShutdown
12 Process Low Lmt
13 Proc Lo Lmt Alm 0 = Disabled 1 = Warning
2 = Visual Alarm 3 = Audible Alarm
4 = SoftShutdown 5 = HardShutdown
14 Process Units 0 = mA 1 = Volts 2 = kW 3 = MW
4 = KVA 5 = MVA 6 = KVAR
7 = MVAR 8 = PF 9 = degC
10 = degF 11 = PSI 12 = KPa
13 = bar
15 Process Low Value
16 Process High Value
0 Check Mains Breaker 0 = Disabled 1 = Enabled
1 Fast Xfer Delay
2 Mains Stable Delay
3 Gen Stable Delay
4 Load Surge
5 Load Surge Alarm 0 = Disabled 1 = Warning
2 = Loss of Mains3 = LOM W/Alarms
6 Main Volt Hi Lmt
7 Main Volt Hi Alm 0 = Disabled 1 = Warning
Transfer 2 = Loss of Mains 3 = LOM W/Alarms
Switch 8 Main Volt Lo Lmt
9 Main Volt Lo Alm 0 = Disabled 1 = Warning
2 = Loss of Mains 3 = LOM W/Alarms
10 Main Freq Hi Lmt
11 Main Freq Hi Alm 0 = Disabled 1 = Warning
2 = Loss of Mains 3 = LOM W/Alarms
12 Main Freq Lo Lmt
13 Main Freq Lo Alm 0 = Disabled 1 = Warning
2 = Loss of Mains 3 = LOM W/Alarms
14 LOM Action Delay
0 Auto Sequencing 0 = Disabled 1 = Enabled
1 Auto Sequencing Dly
2 Max Gen Load
3 Next Genset Dly
4 Rated Load Dly
Sequencing
5 Max Start Time
and
6 Min Gen Load
Communica-
7 Reduced Load Dly
tions
8 Max Stop Time
9 422 Protocol Not adjustable from Watch Window
10 Modbus Id
11 Modbus Timeout
12 Modbus Reset Not adjustable from Watch Window

30 Woodward
Manual 26181 EGCP-2 Communications

Block Field Description


0 Process In Scale
1 Speed Bias Offset
2 Volts Bias Offset
3 PT Phase A Scale
4 PT Phase B Scale
5 PT Phase C Scale
6 CT Phase A Offset
7 CT Phase A Scale
8 CT Phase B Offset
9 CT Phase B Scale
Calibration 10 CT Phase C Offset
11 CT Phase C Scale
12 Bus PT Scale
13 Synchronizer
14 Battery VCO Gain
15 Batt VCO Offset
16 Oil Press Gain
17 Oil Press Offset
18 Water Temp Gain
19 Water Temp Offset
20 Net Comm Dropouts

Hints for Using Watch Window


In order to maintain efficiency when using the Watch Window software, we
recommend limiting the number of variables viewed on one inspector. The Watch
Window software will refresh all data that is on the screen at about a 200 ms
rate. The more variables that are on the screen the more taxing this will be on
the EGCP-2 processor to provide this data. As more and more items are added,
the refresh rate of the control will slow. Do not open more than one Watch
Window session at a time. Use multiple sheets instead of multiple inspectors.
When dragging variables from the Explorer window to the Inspector window,
drag the entire folder if more than a few variables are needed. The Watch
Window software can ask for all of the data in a folder more efficiently than
individual items.

Uploading and Downloading Setpoint Files


After all of the setpoints have been entered, these settings can be saved to a file
using the Watch Window Professional software.

Click on the Save Application Settings icon in the Application


Control window. A Windows Explorer box will appear to name
the file and select a location for it. Then a status bar will appear
updating the file transfer progress.

The format of this file is tab de-limited. Using a program like Microsoft Excel®,
this setpoint file can be sorted and edited. Two columns will be formed, one with
the variable name and the other with the variable value.

Woodward 31
EGCP-2 Communications Manual 26181

This list can be sorted by clicking on the Data menu item; choose sort list by
Configuration ID in ascending order. The first two categories, Control Overview
and Front Panel, should be ignored and may be deleted. The next group will be
the SPT 0 values, which are configuration items. Now all of the setpoints should
be in the order they would appear from the front panel and it is possible to print
this list, for a hardcopy.

32 Woodward
Manual 26181 EGCP-2 Communications

It is also possible to edit this file and transmit the edited settings into a control.
When editing this file, only edit the second column of values. Do not change the
Configuration ID column. The items Network Priority, Set Date, and Set Time
cannot be changed from Watch Window, so their values cannot be used in this
way. All items are numeric values. See the ServLink Variable List in this manual
to understand the enumerated lists.

When saving the file, do not change the file extension, “.CFG”, or the file type,
“Tab-delimited text file”. If the file is saved in Excel format, it will not load properly
into the EGCP-2.

To load a setpoint file into a control, click on the Load


Application Settings icon in the Application Control window. A
Windows Explorer box appears to find the file that is to be
transferred. Then a status bar appears updating the file transfer
progress.

Setpoint files can only be transferred when the unit is shut down. After the
transfer is complete, verify that the correct values have been entered into the
control. The asterisk will appear by the configuration items, which will prevent the
engine from starting. The asterisks must be cleared by committing the values or
cycling power to the EGCP-2.

Woodward 33
EGCP-2 Communications Manual 26181

Watch Window Procedure Summaries


Here are a few summaries or check lists that can be used for quick reference
when performing certain tasks with the Watch Window software.

Saving Setpoints to a File on the Computer:


1. Connect RS-232 to RS-422 cable between EGCP-2 and computer.
2. In the Sequencing and Comms menu, the item “422 Protocol” must be set for
ServLink.
3. Open the ServLink program and build a new Network Definition File or use
an existing file already saved on the computer.
4. Establish communications with the EGCP-2.
5. Save the Network Definition File if a new file was built in step 3.
6. Open the Watch Window Professional program.
7. Click on the Save Application Settings icon, or use the menus Control, App
Settings, Save to File.
8. In the Explorer box select a name and location for the setpoint file.
9. Click the Save button and the file transfer will begin.

Printing a Setpoint List


1. Save the setpoint file on to the computer as described above.
2. Open this file using a program such as Microsoft Excel. The format is a tab-
delimited text file that should open into two columns.
3. Sort the items alphabetically by clicking on the Data, and Sort menus.
4. Delete the Control Overview and Front Panel items lines 2-36.
5. Print the file.

Loading Setpoints into a Control


1. Connect RS-232 to RS-422 cable between EGCP-2 and computer.
2. In the Sequencing and Comms menu, the item “422 Protocol” must be set for
ServLink.
3. Open the ServLink program and build a new Network Definition File or use
an existing file already saved on the computer.
4. Establish communications with the EGCP-2.
5. Save the Network Definition File if a new file was built in step 3.
6. Open the Watch Window Professional program.
7. Verify that the engine is not running or in Auto.
8. Click the Load Applications Settings icon or use the menus Control, App
Settings, Load from File.
9. Find and Select the setpoint file that is to be transferred.
10. Click on the Open button and the file transfer will begin.
11. Following the transfer click Yes to Reset the control.
12. The configuration items will be flagged with an Asterisk that will prevent the
unit from being started
13. Commit the configuration items by selecting each one manually or cycling
power to the control.
14. The control should now be configured and ready for testing.

34 Woodward
Manual 26181 EGCP-2 Communications

Chapter 6.
Modbus RTU Communications for the
EGCP-2 Panel

Introduction
This chapter describes the second of the three EGCP-2 communication protocol
options, Modbus RTU.

The Modbus communication used by the EGCP-2 panel operates at 9600 baud,
with 8 data bits, 1 stop bit, NO parity, and NO flow control. The protocol used is
Modbus RTU (Master/Slave).

Modbus Configuration Items


There are three configurable menu items associated with the Modbus
communications located in the Sequencing and Comms menu: Modbus ID,
Modbus Timeout, and Modbus Reset.

The Modbus ID configuration menu item is adjustable from 1 to 247. This


address identifies the Modbus Slave to the Modbus Master using this address.
The Modbus address chosen for any particular EGCP-2 panel should be different
from all other devices on the Modbus network.

NOTE
The Network Address of the EGCP-2 panel is not linked to the Modbus ID in
any way.

The Modbus Timeout setpoint is located in the Sequencing and Comms


configuration menu. This item is the time which the EGCP-2 panel will wait
before either receiving a valid message from the Modbus master or indicating a
Modbus failure. If a time-out occurs, the EGCP-2 will no longer update the data
to its Modbus variable table. It assumes that there is no master present and that
the port is not being used. If a Modbus master does send a request after a
timeout the EGCP-2 may send data that is no longer current on the first request.
Then it will update its Modbus list of values again every 200 msec, until the
Modbus timeout timer elapses again. In order to avoid accessing old data, the
Modbus timeout setpoint must be set longer than the poll time of the Modbus
master.

There are several items to note when determining the Timeout setting. The
EGCP-2 must use a baud rate of 9600 bps. At this speed a complete transfer of
all of the EGCP-2 Modbus addresses (approximately 270) would take about one
second. If the Modbus master were to only request 50 % of these addresses,
then this could be accomplished in less time, and the data could be transferred in
about 0.5 seconds. Another factor to consider is the quality of the
communications.

Woodward 35
EGCP-2 Communications Manual 26181
The EGCP-2 will transfer all data in one second assuming that there were no
missed messages. A factor of safety should be added, to allow the EGCP-2 to
retransmit some data more than once within the scan time. This time could
depend on a variety of things such as length of communication cables, location in
the switchgear, characteristics of the Modbus master, etc. If the Modbus master
is only reading, for example, 50% of the addresses, the time for this transmission
would be 0.5 seconds. Therefore setting the number of retries at 1, allow another
0.5 seconds for a retry, so the timeout would need to be at least 1.0 second for a
single unit. Some Modbus Masters will also include a delay time between retries.
This time must be also accounted for. For multiple units this time is increased by
the number of units in the system. If there are three EGCP-2’s in the system it
should be understood that each one would be allowed one second to completer
its transmission, so the Modbus timeout tunable should be set to 3.0 seconds on
each control.

Modbus timeout setting =


[(% of data being transferred) / 100 * (1 + number of retries) +
(number of retries) * (retry delay)] * (number of units)

Example: Using 75 % of the data in a 4-unit system with 2 retries and no


retry delay.

(0.75 * 3) * 4 = 9 seconds.

The EGCP-2 panel indicates a Modbus failure in the bottom two lines of the
Modbus Timeout and Modbus Reset menu items. This display shows Link failure
(failure to receive a valid message from the master) as true/false, Exception error
as true/false, and an error number, which is associated with the type of
Exception error. For example, LF-XF 0 is the indication of a healthy Modbus
connection with a Link Failure of False, an Exception Error of False, and a failure
number of 0.

Similarly a message of LF-XT 9, would indicate the Modbus is connected and


communicating, however the control detected a Checksum Error. The Link
Failure is a non-latching-type indication that will indicate whether or not the slave
unit has received a request for data within the Time-out time. The Exception error
is a latching type indication that will be set to true after any one error and will
remain true even if the error condition has been corrected. To reset the
Exception error, the Modbus Reset menu in the Sequencing and Comms menu
item should be toggled from False to True. Once the reset is accomplished, the
Modbus Reset should be returned to False again. Table 6-1 lists the error
numbers that are associated with the Exception error.

36 Woodward
Manual 26181 EGCP-2 Communications
Table 6-1. Common Modbus Error Numbers

Code Name Meaning


00 NO ERROR No Modbus communication faults detected.
01 Illegal Function The function received is not an allowable
action for the addressed slave.
02 Illegal Data Address The address referenced in the data field is
not an allowable address for the addressed
slave.
03 Illegal Data Value The amount of data requested from the
slave was too large for the slave to return in
a single response.
09 Checksum Error There was an error in the message
checksum. This can indicate link quality
problems and/or noise on the line.
10 Garbled Message The slave received data, however it is too
short to be a valid Modbus
message/command.
12 Buffer Overflow Input buffer overflow. This indicates that the
length of the received message from the
master has exceeded the input buffer
capacity of the EGCP-2. Reduce message
sizes to correct.
20 Unsolicited Response Unsolicited message received by the slave.

Modbus Master Settings


The Modbus master will also have timers associated with its operation. The Poll
time, Reply Timeout, Retry Delay, and Number of Retries for the Modbus Master
must be configured to meet the requirements of the entire Modbus network and
the devices communicating on that network. As mentioned in the previous
section, the Poll time is dependent on the fact that the EGCP-2 communicates at
only 9600 baud. Poll times of at least one second per unit would be
recommended. If the master requires data faster than that, it will be necessary to
limit the number of variables being polled.

When setting up the Modbus master it is recommended to use the largest size of
variable requests possible, to limit the transfer traffic. For example, if the
variables 30002, 30003, 30007, 30008, and 30025, were all to be read, the most
efficient way would be to send one request of all variables between 30002 and
30025. Even though the slave would send 19 pieces of information that were not
needed, this would take less time than if each of the five were requested
individually. This is because each Modbus address variable is only two bytes in
length, but data requests from the master to the slave require several characters
and an acknowledgment from the slave.

NOTE
Communications settings will vary based on the Modbus system
configuration. These settings are the recommended typical settings for a
multiple unit EGCP-2 system connected to Modbus master.

Woodward 37
EGCP-2 Communications Manual 26181

Modbus Address Information


Boolean Writes—Addresses 00001–00016, 00024, and 00037
The Boolean write variables can be used for remote control of the EGCP-2 over
Modbus. Fourteen variables are available to mimic the fourteen discrete input
switches. The Gen CB Aux input and Mains CB Aux input are not included in the
Modbus addresses. They must be hard wired to the control. Additionally, a
variable is provided to Enable and Disable the Auto Sequencing Feature, and a
variable to override the Engine Cooldown sequence.

The EGCP-2 is designed to use the Modbus control inputs, and the hardwired
discrete inputs at the same time. There is no configuration item that sets the
control to look only for Modbus input or discrete input. The voltage raise and
lower (00004, 00005), speed raise and lower (00006, 00007), process control
(00008), and remote fault inputs (00009-00014) will follow the last command. For
example, the Process Control Modbus variable could be set to true remotely, and
the local raise and lower speed hardwire inputs would still be active as well. For
added safety, the four momentary switch inputs, Voltage Raise/Lower and Speed
Raise/Lower, are internally timed to operate as a one-second one-shot
command. This means that if the EGCP-2 receives an ON command via Modbus
for any of these four switches, the unit will turn the switch ON for one second,
and then turn the input OFF. If the Modbus update for the ON command occurs
again within the one-second period, the EGCP-2 continues holding the switch
ON until one second after the last active Modbus On update is received. This
feature prevents the situation where a raise or lower command is sent, and then
the Modbus communications stops before the command is removed, which might
take the voltage or speed to an unwanted level.

The control inputs Auto, Test, and Run with Load (00001, 00002, 00003),
operate differently from the other control inputs. Again for added safety, these
three inputs must be set as a group. The user must either use hardware input for
these three or Modbus input. It is not possible to have one input set via hardwire
and one via Modbus. The EGCP-2 will use the three hardware inputs until control
has been taken by the Modbus inputs. To activate the Modbus control mode, all
three of the addresses 00001, 00002, and 00003 must be set. It is not required
that these Modbus inputs be different from the actual hardware inputs, but all
three must be set before any remote control can take place. For example, if the
Auto, Test, and Run With Load inputs were all open, the user could send a False
command to addresses 00001, 00002, and 00003, and the control would switch
from the Hardware control mode to Modbus control, but no action would take
place. The following examples help explain this.

38 Woodward
Manual 26181 EGCP-2 Communications

Modbus control mode examples


Example 1
Modbus commands match Hardware switches.

Hardware EGCP-2
Switches Modbus Commands I/O Display

Auto Off 00001 send False


Test Off 00002 send False
Run Off 00003 send False

Action—All three Modbus commands are sent a False, which matches the
switch position.

Result—This enables both the Modbus and Hardware inputs, so the control will
now follow the next command it sees from either the Modbus or the Hardware.
No change is made because the Modbus values match the Hardware inputs.

Example 2
Modbus commands are different from Hardware switches.

Hardware EGCP-2
Switches Modbus Commands I/O Display

Auto Off 00001 send True


Test Off 00002 send False
Run Off 00003 send False

Action—The user sends a True on address 00001, a False on address 00002,


and a False on address 00003

Result—Nothing happens until a value is sent to the third address. When the
False is sent to 00003, then all three have been sent by Modbus and the control
will go into Auto Mode.

Example 3
Modbus was in control, Hardware switch changes state.

Hardware EGCP-2 I/O Display


Switches Modbus Commands

Auto Off 00001 was True


Test Off 00002 was False
Run to On 00003 was False

Action—The Run input was switched from off to on.

Result—The control was in the Auto mode, following the commands of the
Modbus. Once the Hardware switch changes state, the control follows the
Hardware inputs, and it will no longer be in Auto mode. The control goes into
Run mode and starts the engine. In this situation the Hardware and Modbus are
different, and the control is following the hardware because it was the last one to
change.

Woodward 39
EGCP-2 Communications Manual 26181
Example 4
Continuing from the previous example, the Modbus was in control, then
Hardware took over. Now a new Modbus command is sent.

Hardware EGCP-2 I/O Display


Switches Modbus Commands

Auto Off 00001 send True


Test Off 00002 was False
Run On 00003 send True

Action—A True is sent to address 00001 and then to address 00003.

Result—After the value is sent to address 00001, no change is seen. After a


value is sent to address 00003, the control will now follow the Modbus inputs, it
will no longer be in the Manual Run mode. The control will go into the Auto Run
mode. Notice that in this situation, two of the Modbus commands were needed to
switch the control back to Modbus. Previously the Run input hardware switch had
been changed so now the Run Modbus address must be sent before it can go
into the Modbus control mode, even though the address 00003 matches the
position of the hardware input. The test input has not been changed since it was
last sent over Modbus so it does not need to be resent.

In order to simplify this process, we recommend sending all three of the Modbus
addresses each time Modbus control is desired. In this way, it is not necessary to
track which hardware inputs may have changed.

There is no indication on the EGCP-2 display or over the Modbus, to indicate that
the control is following Modbus or hardware commands. Both can be in control at
the same time. This is important because it gives a local operator the ability to
shut down the control if necessary.

Analog Write 00024 is used to enable and disable the Auto Sequencing Function
of the EGCP-2. When this address is set True, Auto Sequencing is Enabled.
Note that this change is not held in the non-volatile memory and could change if
power is lost to the control.

Analog Write 00037 is used to override the cooldown function. This address may
be set to True during a cooldown sequence, at which time the EGCP-2 will open
its Fuel Solenoid output immediately. This address operates as a one-shot that is
only effective if the control is in the cooldown sequence. If the address is set to
True before the engine goes into the cooldown sequence, this override has no
effect.

40 Woodward
Manual 26181 EGCP-2 Communications
Boolean Read—Addresses 10001–10075
The Boolean Read variables are True/False inputs that show the positions of the
hardware, the alarm status, and some system status readings.

Boolean Read 10001 is true whenever the control is switching between the
Mains and Bus PT’s via the PT disconnect relays.

For the engine and generator alarms, variables 10034 through 10062, 10073 and
10075, these only go true after the delay time has been satisfied and will remain
true until the alarm is cleared from the alarm log. If the corresponding alarm is
set to the Disable level, it will not be seen in the Modbus variable.

For the Loss Of Mains Alarms, variables 10063 through 10067, these variables
when configured for any state except for Disabled, will indicate a “True” state
when the alarm condition is true. The alarm states are considered to be true as
follows:
Load Surge—Any instantaneous change in generator load equal to or greater
than the Load Surge setpoint. No Time Delay.
Mains Voltage High/Low Limit—Any value of the Mains Voltage equal to or
greater than the high limit setpoint, or less than or equal to the low limit setpoint.
The alarm condition will register true only if the high/low limit is exceeded for at
least the LOM action delay time.
Mains Frequency High/Low Limit—Any value of the Mains Frequency equal to
or greater than the high limit setpoint, or less than or equal to the low limit
setpoint. The alarm condition will register true only if the high/low limit is
exceeded for at least the LOM action delay time.

Due to the asynchronous nature of the triggering of the alarm state, and the
Modbus polling time, a software latch on the alarm indication is used. This latch
does not affect the actual indication of the alarm condition on the EGCP-2 control
panel. The latch is active only on the Modbus messaging between the EGCP-2
panel and the Modbus communications. The latch is set by the occurrence of any
of the LOM Alarm actions, and is only reset if the alarm condition no longer
exists, and the pre-existing alarm condition has been actively read once by the
Modbus master. This means that short duration LOM alarm events, such as Load
Surge, always show true for one Modbus poll cycle after the occurrence of the
alarm. If the alarm condition no longer exists after this poll cycle, the Modbus
alarm indication will reset to false as the alarm condition is no longer true. If the
alarm situation clears, these variables will return to False even if the event is not
cleared from the alarm log.

Boolean Read 10070, Voltage Input, will be True if the control is configured for
Delta Line to Line voltage sensing and False for Wye Line to Neutral sensing.

Boolean Read 10071, PF indication will be True to indicate a leading power


factor and False to indicate a lagging power factor.

Woodward 41
EGCP-2 Communications Manual 26181
Analog Read—Addresses 30001–30073, 30215-30350
The Analog Read variables are numeric representations showing the measured
values of the control inputs, the alarm action, and the mode of operation for
certain functions of the control.

These values use a signed integer format that does not support decimal places.
In order to view the decimal places on certain variables the value is multiplied by
a scaling variable.

For analog reads 30020 through 30048, the engine and generator alarms, the
alarm action is defined as follows:
0 = Disabled
1 = Warning
2 = Visual Alarm
3 = Audible Alarm
4 = Soft Shutdown
5 = Hard Shutdown

For analog reads 30049 through 30053, the Loss Of Mains Alarms, the alarm
action is defined as follows:
0 = Disabled
1 = Warning
2 = Loss of Mains
3 = Loss of Mains with Alarms

For the analog read 30067, the Load Control Mode, the mode is defined as
follows:
0 = Off
1 = Droop (Generator frequency will decrease as load is increased)
2 = Isochronous (On load, not in parallel with the mains)
3 = Baseload (In parallel with the mains, at a fixed kW setpoint)
4 = Process (In parallel with the mains, controlling the process input)

For the analog read 30068, the Synchronizer Mode, the mode is defined as
follows:
0 = Off
1 = ATS (Auto Transfer State. Trying to open the mains breaker
2 = Parallel (Trying to close mains breaker)
3 = In Sync (Generator breaker or mains breaker was synchronized
successfully.)
4 = ATS Return (Trying to open generator breaker)
5 = Parallel Mains (Trying to close mains breaker)
6 = Gen Close Timer (Generator breaker close issued, waiting for feedback to
show closed)
7 = Mains Close Timer (Mains breaker close issued, waiting for feedback to
show closed)
8 = Gen Sync Timer (checking for successful synchronization of the generator)
9 = Mains Sync Timer (checking for successful synchronization of the Mains
breaker)

For the analog read 30071, the Address of the Master Unit, is only valid on
controls that are in the Auto mode. Units not in Auto are not communicating with
the master and cannot be relied upon.

42 Woodward
Manual 26181 EGCP-2 Communications
For the analog read 30072, the engine state is defined as follows:
1 = Off
2 = Preglow
3 = Crank
4 = Run
5 = Cooldown (engine has run above the Cooldown setpoint and will wait before
stopping)
6 = Spindown (fuel solenoid is open but engine speed is still sensed as the
engine coasts down)
7 = Restart (previous start attempt has failed, so trying again.)

Analog read 30073, the Synchroscope Phase Angle, will give a value between
-180 and 180 degrees. Zero degrees would be in phase, negative measurements
occur when in the right half of the synchroscope, and positive measurements
occur when in the left half of the synchroscope. For example, if the synchroscope
were showing a rotation in the clockwise direction for a generator that was
slightly faster than the bus the sequence of angles would be:
0, –30, –60, –90, –120, –150, 180, 150, 120, 90, 60, 30, 0…

Analog Reads 30215, 30216, 30229, and 30230 work in conjunction with the
Analog Writes 40002, 40003, 40005, and 40007. A control reference is written
into the Analog Write address and the feedback of this write is provided with
these Analog Reads. For example, to change the base load reference to 200 kW,
the value of 200 would be sent to address 40003. This change can be verified by
reading address 30215, which ramps from the old baseload reference to 200.

Analog Reads 30250 through 30350 work in conjunction with the Analog Writes
40250 through 40350. Certain control setpoints can be changed by writing to the
Analog Write addresses, and the feedback for these writes is provided with the
corresponding Analog Reads. For example the Cooldown Time could be
changed to 60 seconds. A value of 60 is written to address 40277, and this is
verified by reading address 30277, which will become 60. In some cases the
Analog Read value will not be the same as the Analog Write. If a user changes
one of these setpoints from the front panel of the EGCP-2 by hand, the Analog
Read value will show the new value of the setpoint, which may be different from
the last Analog Write that was sent. Another case where the Read and Write may
be different, can occur if a new setpoint is written to one of the Analog Writes,
which can only be changed when the engine is stopped. The Analog Read
shows the value that is currently being used while the engine is running, and
then when the engine stops it accepts the new value.

Analog Writes—Addresses 40001- 40007 and 40250 - 40350


The Analog Write variables are numeric commands sent to the control from the
Modbus master. The unit priority number, control references, and certain
setpoints can be changed with these Modbus addresses.

Analog Write 40001 can be used to change the priority of the EGCP-2 over
Modbus. To change the priority the unit must be in the AUTO mode. When
multiple units are in Auto the following rules apply to changing the priority.

When decreasing (incrementing value) a unit's priority, every active unit (in
multiple unit configuration and auto mode) on the same network with a higher
priority (lower value) than the unit, which is currently having its priority, changed,
will increase (decrement value) priority when the priority change is committed.

Woodward 43
EGCP-2 Communications Manual 26181
And inverse to this:
When increasing (decrementing value) a unit's priority, every active unit (in
multiple unit configuration and auto mode) on the same network with a lower
priority (higher value) than the unit, which is currently having its priority, changed,
will decrease (increment value) priority when the priority change is committed.

Four references, the process level, base load, power factor, and kVAR, can be
adjusted with the Analog Writes 40002, 40003, 40005, and 40007. These
addresses are intended to be used while the engine is running. When a new
reference value is sent to the control, the actual reference ramps from its current
value to the new value. For baseload the ramp is determined by the Raise and
Lower Load Rates. For process the ramp is determined by the Process Raise
and Process Lower Rates. The power factor and kVAR ramps are determined by
the Voltage Ramp Time. A change made to these references is a temporary
change and does not get saved in the control memory.

While the engine is shut down, it is also possible to change the reference
setpoints, with Analog Writes 40300, 40318, 40319, and 40328. The reference
setpoint determines the initial reference the control will go to when it is started or
when the load control mode is changed. For example, with the engine stopped a
value of 500 is written to address 40300, the base load reference setpoint. When
the engine is started and closed on-line, the load ramps to 500 kW. Then to
change the load level, the 40003 address would be used. A change made to the
reference setpoint is saved in the control memory and retained after a loss of
power.

Analog Writes 40250 – 40350 are provided to change certain control setpoints.
Some of these setpoints can be adjusted only when the engine is shutdown,
such as the Rated kW (see Table ). The actual value of the setpoint is provided
with Analog Reads 30250 – 30350. Once the setpoint is changed the control will
begin to use the new value; no additional steps are needed to make the new
value active. A changed setpoint from the Modbus is saved in the control
memory and retained after a loss of power.

Table 6-2. Modbus Addresses for the RTU Protocol

Boolean Writes
Modbus Type Item Semantics
Address
00001 BW Automatic See Boolean Write Address
information
0 = False, 1 = True
00002 BW Test 0 = False, 1 = True
00003 BW Run with Load 0 = False, 1 = True
00004 BW Voltage/PF/VAR Raise Command 0 = False, 1 = True
00005 BW Voltage/PF/VAR Lower Command 0 = False, 1 = True
00006 BW Load / Speed Raise Command 0 = False, 1 = True
00007 BW Load / Speed Lower Command 0 = False, 1 = True
00008 BW Process Control Switch 0 = False, 1 = True
00009 BW Remote Fault Input #1 0 = False, 1 = True
00010 BW Remote Fault Input #2 0 = False, 1 = True
00011 BW Remote Fault Input #3 0 = False, 1 = True
00012 BW Remote Fault Input #4 0 = False, 1 = True
00013 BW Remote Fault Input #5 0 = False, 1 = True
00014 BW Remote Fault Input #6 0 = False, 1 = True
00015 BW Not Used
00016 BW Reset All Alarms Resets control, but does not clear
alarm log
00024 BW Auto Sequence 0 = Disabled, 1 = Enabled
00036 BW Cooldown Override 0 = Disabled, 1 = Enabled

44 Woodward
Manual 26181 EGCP-2 Communications
Boolean Reads
Modbus Type Item Semantics
Address
10001 BR Bus/ Mains PT Switch in Transition 0 = Not Active, 1 = Active
10002 BR Mains Stable Indication 0 = Not stable (waiting for timeout),
1 = Stable
10003 BR Bus Stable Indication 0 = Not Stable (waiting for timeout),
1 = Stable
10004 BR Alarm Status 0 = No Alarms, 1 = Active Alarm
10005 BR Loss of Mains Alarm Status 0 = Mains OK, 1 = LOM detected
10006 BR Mains Breaker Close DO Status 0 = Open, 1 = Closed
10007 BR Gen Breaker Close DO Status 0 = Open, 1 = Closed
10008 BR Engine Preglow DO Status 0 = Open, 1 = Closed
10009 BR Fuel Solenoid DO Status 0 = Open, 1 = Closed
10010 BR Engine Crank DO Status (Starter) 0 = Open, 1 = Closed
10011 BR Visual Alarm DO Status 0 = Open, 1 = Closed
10012 BR Bus PT Connect DO Status 0 = Open, 1 = Closed
10013 BR Mains PT Disconnect DO Status 0 = Open, 1 = Closed
10014 BR Mains Breaker Shunt Trip DO Status 0 = Open, 1 = Closed
10015 BR Gen Breaker Shunt Trip DO Status 0 = Open, 1 = Closed
10016 BR Audible Alarm Status DO Status 0 = Open, 1 = Closed
10017 BR Relay #12 Idle/Rated - KVA Switch 0 = Open, 1 = Closed
DO Status
10018 BR Auto DI Status 0 = Open, 1 = Closed
10019 BR Test DI Status 0 = Open, 1 = Closed
10020 BR Run DI Status 0 = Open, 1 = Closed
10021 BR Voltage Raise DI Status 0 = Open, 1 = Closed
10022 BR Voltage Lower DI Status 0 = Open, 1 = Closed
10023 BR Speed Raise DI Status 0 = Open, 1 = Closed
10024 BR Speed Lower DI Status 0 = Open, 1 = Closed
10025 BR Gen Breaker Aux. DI Status 0 = Open, 1 = Closed
10026 BR Mains Breaker Aux. DI Status 0 = Open, 1 = Closed
10027 BR Process Control DI Status 0 = Open, 1 = Closed
10028 BR Remote Fault #1 DI Status 0 = Open, 1 = Closed
10029 BR Remote Fault #2 DI Status 0 = Open, 1 = Closed
10030 BR Remote Fault #3 DI Status 0 = Open, 1 = Closed
10031 BR Remote Fault #4 DI Status 0 = Open, 1 = Closed
10032 BR Remote Fault #5 DI Status 0 = Open, 1 = Closed
10033 BR Remote Fault #6 DI Status 0 = Open, 1 = Closed
10034 BR Sync Timeout Alarm Status 0 = No Alarm, 1 = Active Alarm
10035 BR Sync Reclose Alarm Status 0 = No Alarm, 1 = Active Alarm
10036 BR Crank Fail Alarm Status 0 = No Alarm, 1 = Active Alarm
10037 BR Voltage Range Alarm Status 0 = No Alarm, 1 = Active Alarm
10038 BR Over Speed Alarm Status 0 = No Alarm, 1 = Active Alarm
10039 BR Gen Phase Over Current Alarm 0 = No Alarm, 1 = Active Alarm
Status
10040 BR Gen Reverse Power Alarm Status 0 = No Alarm, 1 = Active Alarm
10041 BR Gen Reverse VAR Alarm Status 0 = No Alarm, 1 = Active Alarm
10042 BR Speed/Freq Mismatch Alarm Status 0 = No Alarm, 1 = Active Alarm
10043 BR Coolant Temp. High Alarm Status 0 = No Alarm, 1 = Active Alarm
10044 BR Coolant Temp. Low Alarm Status 0 = No Alarm, 1 = Active Alarm
10045 BR Rated Oil Press High Alarm Status 0 = No Alarm, 1 = Active Alarm
10046 BR Rated Oil Press Low Alarm Status 0 = No Alarm, 1 = Active Alarm
10047 BR Battery Volt Low Alarm Status 0 = No Alarm, 1 = Active Alarm
10048 BR Battery Volt High Alarm Status 0 = No Alarm, 1 = Active Alarm
10049 BR Gen Under Volt Alarm Status 0 = No Alarm, 1 = Active Alarm
10050 BR Gen Over Volt Alarm Status 0 = No Alarm, 1 = Active Alarm
10051 BR Gen Over Freq Alarm Status 0 = No Alarm, 1 = Active Alarm
10052 BR Gen Under Freq Alarm Status 0 = No Alarm, 1 = Active Alarm
10053 BR Load High Limit Alarm Status 0 = No Alarm, 1 = Active Alarm
10054 BR Load Low Limit Alarm Status 0 = No Alarm, 1 = Active Alarm

Woodward 45
EGCP-2 Communications Manual 26181
Modbus Type Item Semantics
Address
10055 BR Process High Limit Alarm Status 0 = No Alarm, 1 = Active Alarm
10056 BR Process Low Limit Alarm Status 0 = No Alarm, 1 = Active Alarm
10057 BR Remote Fault1 Alarm Status 0 = No Alarm, 1 = Active Alarm
10058 BR Remote Fault2 Alarm Status 0 = No Alarm, 1 = Active Alarm
10059 BR Remote Fault3 Alarm Status 0 = No Alarm, 1 = Active Alarm
10060 BR Remote Fault4 Alarm Status 0 = No Alarm, 1 = Active Alarm
10061 BR Remote Fault5 Alarm Status 0 = No Alarm, 1 = Active Alarm
10062 BR Remote Fault6 Alarm Status 0 = No Alarm, 1 = Active Alarm
10063 BR Load Surge Alarm Status 0 = No Alarm, 1 = Active Alarm
10064 BR Mains Under Volt Alarm Status 0 = No Alarm, 1 = Active Alarm
10065 BR Mains Over Volt Alarm Status 0 = No Alarm, 1 = Active Alarm
10066 BR Mains Over Freq Alarm Status 0 = No Alarm, 1 = Active Alarm
10067 BR Mains Under Freq Alarm Status 0 = No Alarm, 1 = Active Alarm
10068 BR Not Used
10069 BR Generator Stable Indication 0 = Not Stable (wait for timeout), 1 =
Stable
10070 BR Generator Sense Configuration 0 = Wye (L-N), 1 = Delta (L-L)
10071 BR PF Leading/Lagging Indicator 0 = Lag, 1 = Lead
10073 BR Coolant Temp High Pre-Alarm Status 0 = No Alarm, 1 = Active Alarm
10075 BR Low Oil Press Pre-Alarm Status 0 = No Alarm, 1 = Active Alarm

Analog Reads
Modbus
Type Item Semantics Min Max Scale
Address
30001 AR Battery Voltage Vdc 0 500 10
30002 AR Engine Oil Pressure Units per configuration 0 1000 10
bar or psi
30003 AR Engine Coolant Units per configuration -100 300
Temperature deg C or deg F
30004 AR Engine Run Time Hours 0 32767
30005 AR Generator MW-Hours Mega Watt hours 0 32767
30006 AR Engine RPM RPM 0 5000
30007 AR Gen Phase A L-L Volts Volts 0 32767
30008 AR Gen Phase B L-L Volts Volts 0 32767
30009 AR Gen Phase C L-L Volts Volts 0 32767
30010 AR Gen Total KW kW -32768 32767
30011 AR Gen Total KVA kVA -32768 32767
30012 AR Generator Power Factor Always a positive 0 100 100
number (see BR
10071 for Leading or
Lagging status)
30013 AR Gen Phase A kVAR kVAR -32768 32767
30014 AR Gen Phase B kVAR kVAR -32768 32767
30015 AR Gen Phase C kVAR kVAR -32768 32767
30016 AR Gen Total kVAR kVAR -32768 32767
30017 AR Bus Frequency Hz 0 700 10
30018 AR Generator Frequency Hz 0 700 10
30019 AR Network Address 1 8
30020 AR Sync Timeout Action See Analog Read 1 3
Address information
30021 AR Sync Reclose Action See Analog Read 1 3
Address information
30022 AR Crank Fail Action See Analog Read 1 3
Address information
30023 AR Voltage Range Action See Analog Read 0 3
Address information
30024 AR Overspeed Action See Analog Read 0 5
Address information

46 Woodward
Manual 26181 EGCP-2 Communications
Modbus
Type Item Semantics Min Max Scale
Address
30025 AR Overcurrent Action See Analog Read 0 5
Address information
30026 AR Gen Reverse Power Alarm See Analog Read 0 5
Action Address information
30027 AR Gen Reverse VAR Alarm See Analog Read 0 5
Action Address information
30028 AR Speed Freq Mismatch See Analog Read 0 5
Action Address information
30029 AR Coolant Temp. High Alarm See Analog Read 0 5
Action Address information
30030 AR Coolant Temp. Low Alarm See Analog Read 0 5
Action Address information
30031 AR Oil Press High Alarm Action See Analog Read 0 5
Address information
30032 AR Oil Press Low Alarm Action See Analog Read 0 5
Address information
30033 AR Battery Volt Low Alarm See Analog Read 0 5
Action Address information
30034 AR Battery Volt High Alarm See Analog Read 0 5
Action Address information
30035 AR Gen Under Volt Alarm See Analog Read 0 5
Action Address information
30036 AR Gen Over Volt Alarm Action See Analog Read 0 5
Address information
30037 AR Gen Over Freq Alarm See Analog Read 0 5
Action Address information
30038 AR Gen Under Freq Alarm See Analog Read 0 5
Action Address information
30039 AR Load High Limit Action See Analog Read 0 5
Address information
30040 AR Load Low Limit Action See Analog Read 0 5
Address information
30041 AR Process High Limit Action See Analog Read 0 5
Address information
30042 AR Process Low Limit Action See Analog Read 0 5
Address information
30043 AR Remote Fault 1 Action See Analog Read 0 7
Address information
30044 AR Remote Fault 2 Action See Analog Read 0 7
Address information
30045 AR Remote Fault 3 Action See Analog Read 0 7
Address information
30046 AR Remote Fault 4 Action See Analog Read 0 7
Address information
30047 AR Remote Fault 5 Action See Analog Read 0 7
Address information
30048 AR Remote Fault 6 Action See Analog Read 0 7
Address information
30049 AR Load Surge Action See Analog Read 0 3
Address information
30050 AR Mains Under Volt Alarm See Analog Read 0 3
Action Address information
30051 AR Mains Over Volt Alarm See Analog Read 0 3
Action Address information
30052 AR Mains Over Freq Alarm See Analog Read 0 3
Action Address information
30053 AR Mains Under Freq Alarm See Analog Read 0 3
Action Address information
30054 AR Not Used
30055 AR Generator Phase A-N Volts Always Line-Neutral 0 32767
30056 AR Generator Phase B-N Volts Always Line-Neutral 0 32767

Woodward 47
EGCP-2 Communications Manual 26181
Modbus
Type Item Semantics Min Max Scale
Address
30057 AR Generator Phase C-N Volts Always Line-Neutral 0 32767
30058 AR Mains Phase A-N Volts Always Line-Neutral 0 32767
30059 AR Gen Phase A current Amps -32768 32767
30060 AR Gen Phase B current Amps -32768 32767
30061 AR Gen Phase C current Amps -32768 32767
30062 AR Gen Phase A KVA KVA -32768 32767
30063 AR Gen Phase B KVA KVA -32768 32767
30064 AR Gen Phase C KVA KVA -32768 32767
30065 AR Voltage Bias Analog Output % output: 0 100
0 = 0 bias
100 = 100% raise
-100 = 100% lower
30066 AR Speed Bias Analog Output % output 0 100
0 = 0 bias
100 = 100% raise
-100 = 100% lower
30067 AR Load Control State See Analog Read 0 4
Address information
30068 AR Synchronizer State See Analog Read 0 9
Address information
30069 AR Number of 0 99
Unacknowledged Alarms
30070 AR Unit Network Priority 1 8
30071 AR Address of Master Unit 1 8
30072 AR Engine State See Analog Read 0 7
Address information
30073 AR Synchroscope See Analog Read -180 180
Address information
30215 AR Actual Baseload Reference See Analog Read 0 30000
Address information
30216 AR Actual Process Reference See Analog Read -32767 32767
Address information
30229 AR Actual PF Reference –800 = 0.8 Lag -1000 to 500 to 1000
800 = 0.8 Lead -500 1000
1000 = unity PF
30230 AR Actual VAR Reference See Analog Read -20000 20000
Address information
30250 AR Network Address * 1 8
AR AC Frequency 0 = 50Hz 0 1
30253 1 = 60Hz *
30254 AR Rated RPM RPM * 100 5000
30255 AR Rated Power * 1 30,000
30256 AR Rated Volt-Amps * 1 30,000
30257 AR Rated Volt-Amps Reactive * 1 30,000
AR Operating Mode 0 = No Parallel 0 1
30267 1 = Mains Parallel *
AR Number of Units 0 = Single 0 1
30268 1 = Multiple *
30269 AR Preglow Time seconds 0 1200
30270 AR Crank Time seconds 0 240
30271 AR Crank Cutout RPM 5 1000
30272 AR Crank Delay seconds 1 240
30273 AR Crank Repeats 0 20
30276 AR Idle Time seconds 1 240
30277 AR Cooldown Time seconds 0 2400
AR Sync Mode 0 = Check 0 2
1 = Permissive
30280 2 = Run
30291 AR Sync Timeout seconds 0 1200

48 Woodward
Manual 26181 EGCP-2 Communications
Modbus
Type Item Semantics Min Max Scale
Address
AR Load Control Mode 0 = Normal 0 2
1 = Soft Transfer
30294 2 = kW Droop *
AR Base Load Reference 0 30,000
30300 Setpoint *
30303 AR Load Time seconds 1 7,200
30304 AR Unload Time seconds 1 7,200
30305 AR Raise Load Rate % / sec X 100 0.01 100.00 100
30306 AR Lower Load Rate % / sec X 100 0.01 100.00 100
30311 AR KVA Switch Low 0 30,000
30312 AR KVA Switch High 0 30,000
30315 AR Voltage Ramp Time seconds 0 1,000
30318 AR KVAR Reference Setpoint * -20,000 20,000
AR PF Reference Setpoint –800 = 0.8 Lag -1000 to 500 to 1000
800 = 0.8 Lead –500 1000
30319 1000 = unity PF *
AR Process Action 0 = Direct 0 1
30321 1 = Indirect *
30328 AR Process Reference -32,768 32767
30329 AR Process Raise Rate % / sec X 10 0.0 100.0 10
30330 AR Process Lower Rate % / sec X 10 0.0 100.0 10
30334 AR Fast Transfer Delay Seconds X 10 0.1 30.0 10
30335 AR Mains Stable Delay seconds 1 30,000
30336 AR Gen Stable Delay seconds 1 30,000
30342 AR LOM Action Delay seconds X 10 0.1 30.0 10
30344 AR Min Gen Load % of rated load 1 100
30345 AR Next Genset Delay seconds 1 1200
30346 AR Rated Load Delay seconds 1 1200
30347 AR Max Start Time seconds 1 1200
30348 AR Max Gen Load % of rated load 1 100
30349 AR Reduced Load Delay seconds 1 1200
30350 AR Max Stop Time seconds 1 1200

NOTE
Items marked with an asterisk can only be changed when the engine is not
running.

Analog Writes
Modbus Type Function Semantics Min Max Scale
Address
40001 AW Priority Change 1 8
Address
40002 AW Process Control See Analog Write -32767 32767
Actual Reference Address information
40003 AW Base Load Actual See Analog Write 0 30,000
Reference Address information
40004 AW Not Used
40005 AW PF Actual –500 = 0.5 Lag -1000 to- 500 500 to 1000 1000
Reference 500 = 0.5 Lead
1000 = unity PF
40006 AW Not Used
40007 AW Remote VAR See Analog Write -20000 20,000
Actual Reference Address information
40250 AW Network Address * 1 8
40253 AW AC Frequency 0 = 50Hz 0 1
1 = 60Hz *
40254 AW Rated RPM RPM * 100 5000
Woodward 49
EGCP-2 Communications Manual 26181
Modbus Type Function Semantics Min Max Scale
Address
40255 AW Rated Power * 1 30,000
40256 AW Rated Volt-Amps * 1 30,000
40257 AW Rated Volt-Amps 1 30,000
Reactive *
40267 AW Operating Mode 0 = No Parallel 0 1
1 = Mains Parallel *
40268 AW Number of Units 0 = Single 0 1
1 = Multiple *
40269 AW Preglow Time Seconds 0 1200
40270 AW Crank Time Seconds 0 240
40271 AW Crank Cutout RPM 5 1000
40272 AW Crank Delay Seconds 1 240
40273 AW Crank Repeats 0 20
40276 AW Idle Time Seconds 1 240
40277 AW Cooldown Time Seconds 0 2400
40280 AW Sync Mode 0 = Check 0 2
1 = Permissive
2 = Run
40291 AW Sync Timeout Seconds 0 1200
40294 AW Load Control 0 = Normal 0 2
Mode 1 = Soft Transfer
2 = kW Droop *
40300 AW Base Load 0 30,000
Reference
Setpoint *
40303 AW Load Time seconds 1 7,200
40304 AW Unload Time seconds 1 7,200
40305 AW Raise Load Rate % / sec X 100 0.01 100.00 100
40306 AW Lower Load Rate % / sec X 100 0.01 100.00 100
40311 AW KVA Switch Low 0 30,000
40312 AW KVA Switch High 0 30,000
40315 AW Voltage Ramp 0 1,000
Time Seconds
40318 AW KVAR Reference -20,000 20,000
Setpoint *
40319 AW PF Reference –800 = 0.8 Lag -1000 to –500 500 to 1000 1000
Setpoint 800 = 0.8 Lead
1000 = unity PF *
40321 AW Process Action 0 = Direct 0 1
1 = Indirect *
40328 AW Process -32,768 32767
Reference
Setpoint In configured units *
40329 AW Process Raise 0.0 100.0 10
Rate % / sec X 10
40330 AW Process Lower 0.0 100.0 10
Rate % / sec X 10
40334 AW Fast Transfer 0.1 30.0 10
Delay Seconds X 10
40335 AW Mains Stable 1 30,000
Delay Seconds
40336 AW Gen Stable Delay Seconds 1 30,000
40342 AW LOM Action 0.1 30.0 10
Delay Seconds X 10
40344 AW Min Gen Load % of rated load 1 100
40345 AW Next Genset 1 1200
Delay Seconds
40346 AW Rated Load 1 1200
Delay Seconds
40347 AW Max Start Time Seconds 1 1200

50 Woodward
Manual 26181 EGCP-2 Communications
Modbus Type Function Semantics Min Max Scale
Address
40348 AW Max Gen Load % of rated load 1 100
40349 AW Reduced Load 1 1200
Delay Seconds
40350 AW Max Stop Time Seconds 1 1200

NOTE
* Items marked with an Asterisk can only be changed when the engine is not
running.

Woodward 51
EGCP-2 Communications Manual 26181

Chapter 7.
Download.exe Setpoint Utility

Introduction
This chapter covers the third of the three EGCP-2 communication protocol
options, Upload Setpoints.

Download.exe is a DOS-based freeware program that can upload and download


configuration files through the EGCP-2's RS-422 serial port. This program is
available through the Internet from the Woodward website
(www.woodward.com/ic/software).

Requirements
• RS-232 to RS-422 converter
• PC capable of running DOS-based executables
• DOWNLOAD.EXE, part number 9926-113 Rev B or greater

Instructions
Set-up
Save the DOWNLOAD.EXE file:
Save the DOWNLOAD.EXE file to the computer. In the following example this file is
saved in a directory called EGCP2 on the C: drive. Open a DOS command window
and go to the directory where the download file is stored. Type DOWNLOAD –h (or
–?) for a complete list of the command-line options (see below).

Establishing a Connection:
Connect the RS-232 / RS-422 cable between the EGCP-2 and the computer.
See the Communication Ports section of the Operation and Installation manual
26175 for more information about this cable interface.

NOTE
Only one EGCP-2 can be connected to the RS-422 communication network
when uploading or downloading setpoints. If a multidrop network has been
setup linking more than one EGCP-2 on the RS-422 communication port
network, it will be necessary to separate the control from the network in
order to upload or download setpoints.

52 Woodward
Manual 26181 EGCP-2 Communications

Uploading Setpoints
This procedure saves the setpoints from the control to a file on the computer.
The following examples assume that COM1 is the available serial port on the PC,
and the download.exe program has been saved to the directory, c:\EGCP2.

On the EGCP-2, under the SEQUENCING AND COMMS menu, step to the “422 Protocol”
item. Select "Upload Setpoints" and press the Enter key. Cycle power to the EGCP-2. When
the EGCP-2 passes the self-tests, it will be ready to start uploading setpoints.

Using a DOS command prompt window, go to the directory where the


DOWNLOAD.EXE file is stored and type "download –u –o unit1.spt" at the DOS
command prompt (see below). The –u tells the program to wait for an upload
string from the control. The –o specifies that the information should be saved to a
file, and unit1.spt is the file which will be created in the same directory. The file
name can be any name up to eight characters long. This command assumes that
COM port 1 is the COM port being used on the computer. If another port is being
used add the number of this port to the end of the command (for example,
"download –u –o unit1.spt 2” for COM 2), add a 3 for COM 3, etc.

The program will begin uploading setpoints within a few seconds. After the
upload is completed the text “Done” appears on the screen.

When uploading more than one control be sure to use a different name for the
.spt files (i.e. Unit1, Unit2…) or the files will be overwritten.

Downloading Setpoints
This procedure loads an existing setpoint file from the computer to the control.

Using a DOS command prompt window, go to the directory where the


DOWNLOAD.EXE file is stored and type "download unit1.spt" at the DOS
command prompt (see below). The RS-422 protocol setting can be set to any of
the three choices: Upload Setpoints, Modbus, or ServLink.

Woodward 53
EGCP-2 Communications Manual 26181
Cycle power to the EGCP-2. When the power is restored to the control the
download will begin. A scroll bar appears on the computer screen showing the
progress of the download (see below).

On the EGCP-2 screen the text “SETPOINTS” is displayed.

After the download is complete, press the Config key and enter the proper
password. Every item in the Configuration menu will need to be verified by
viewing the setpoint and pressing the Enter key on the control. An “*” is displayed
after the setpoint until this value has been committed to the control by pressing
the Enter key.

This step forces the user to view each setpoint and verify that the value that has
just been downloaded is correct for this system’s configuration. This only applies
to the Configuration menu, the other menus do not need to be committed,
although it is recommended that every item is verified.

Uploading and Downloading of setpoints can only be done between units with
the same code revision level. The EGCP-2 will display a warning message and
reboot after the self-tests if the setpoints and labels are not compatible with the
internal code revision number. This revision number is displayed briefly after the
self-tests are complete on the last line of the lower LCD panel.

54 Woodward
Manual 26181 EGCP-2 Communications

Chapter 8.
Service Options

Product Service Options


If you are experiencing problems with the installation, or unsatisfactory
performance of a Woodward product, the following options are available:
• Consult the troubleshooting guide in the manual.
• Contact the manufacturer or packager of your system.
• Contact the Woodward Full Service Distributor serving your area.
• Contact Woodward technical assistance (see “How to Contact Woodward”
later in this chapter) and discuss your problem. In many cases, your problem
can be resolved over the phone. If not, you can select which course of action
to pursue based on the available services listed in this chapter.

OEM and Packager Support: Many Woodward controls and control devices are
installed into the equipment system and programmed by an Original Equipment
Manufacturer (OEM) or Equipment Packager at their factory. In some cases, the
programming is password-protected by the OEM or packager, and they are the best
source for product service and support. Warranty service for Woodward products
shipped with an equipment system should also be handled through the OEM or
Packager. Please review your equipment system documentation for details.

Woodward Business Partner Support: Woodward works with and supports a


global network of independent business partners whose mission is to serve the
users of Woodward controls, as described here:
• A Full Service Distributor has the primary responsibility for sales, service,
system integration solutions, technical desk support, and aftermarket
marketing of standard Woodward products within a specific geographic area
and market segment.
• An Authorized Independent Service Facility (AISF) provides authorized
service that includes repairs, repair parts, and warranty service on Woodward's
behalf. Service (not new unit sales) is an AISF's primary mission.
• A Recognized Engine Retrofitter (RER) is an independent company that
does retrofits and upgrades on reciprocating gas engines and dual-fuel
conversions, and can provide the full line of Woodward systems and
components for the retrofits and overhauls, emission compliance upgrades,
long term service contracts, emergency repairs, etc.
• A Recognized Turbine Retrofitter (RTR) is an independent company that
does both steam and gas turbine control retrofits and upgrades globally, and
can provide the full line of Woodward systems and components for the
retrofits and overhauls, long term service contracts, emergency repairs, etc.

A current list of Woodward Business Partners is available at


www.woodward.com/support.

Woodward 55
EGCP-2 Communications Manual 26181

Woodward Factory Servicing Options


The following factory options for servicing Woodward products are available
through your local Full-Service Distributor or the OEM or Packager of the
equipment system, based on the standard Woodward Product and Service
Warranty (5-01-1205) that is in effect at the time the product is originally shipped
from Woodward or a service is performed:
• Replacement/Exchange (24-hour service)
• Flat Rate Repair
• Flat Rate Remanufacture

Replacement/Exchange: Replacement/Exchange is a premium program


designed for the user who is in need of immediate service. It allows you to
request and receive a like-new replacement unit in minimum time (usually within
24 hours of the request), providing a suitable unit is available at the time of the
request, thereby minimizing costly downtime. This is a flat-rate program and
includes the full standard Woodward product warranty (Woodward Product and
Service Warranty 5-01-1205).

This option allows you to call your Full-Service Distributor in the event of an
unexpected outage, or in advance of a scheduled outage, to request a
replacement control unit. If the unit is available at the time of the call, it can
usually be shipped out within 24 hours. You replace your field control unit with
the like-new replacement and return the field unit to the Full-Service Distributor.

Charges for the Replacement/Exchange service are based on a flat rate plus
shipping expenses. You are invoiced the flat rate replacement/exchange charge
plus a core charge at the time the replacement unit is shipped. If the core (field
unit) is returned within 60 days, a credit for the core charge will be issued.

Flat Rate Repair: Flat Rate Repair is available for the majority of standard
products in the field. This program offers you repair service for your products with
the advantage of knowing in advance what the cost will be. All repair work carries
the standard Woodward service warranty (Woodward Product and Service
Warranty 5-01-1205) on replaced parts and labor.

Flat Rate Remanufacture: Flat Rate Remanufacture is very similar to the Flat
Rate Repair option with the exception that the unit will be returned to you in “like-
new” condition and carry with it the full standard Woodward product warranty
(Woodward Product and Service Warranty 5-01-1205). This option is applicable
to mechanical products only.

56 Woodward
Manual 26181 EGCP-2 Communications

Returning Equipment for Repair


If a control (or any part of an electronic control) is to be returned for repair,
please contact your Full-Service Distributor in advance to obtain Return
Authorization and shipping instructions.

When shipping the item(s), attach a tag with the following information:
• return number;
• name and location where the control is installed;
• name and phone number of contact person;
• complete Woodward part number(s) and serial number(s);
• description of the problem;
• instructions describing the desired type of repair.

Packing a Control
Use the following materials when returning a complete control:
• protective caps on any connectors;
• antistatic protective bags on all electronic modules;
• packing materials that will not damage the surface of the unit;
• at least 100 mm (4 inches) of tightly packed, industry-approved packing
material;
• a packing carton with double walls;
• a strong tape around the outside of the carton for increased strength.

CAUTION—ELECTROSTATIC DISCHARGE
To prevent damage to electronic components caused by improper handling,
read and observe the precautions in Woodward manual 82715, Guide for
Handling and Protection of Electronic Controls, Printed Circuit Boards, and
Modules.

Replacement Parts
When ordering replacement parts for controls, include the following information:
• the part number(s) (XXXX-XXXX) that is on the enclosure nameplate;
• the unit serial number, which is also on the nameplate.

Woodward 57
EGCP-2 Communications Manual 26181

Engineering Services
Woodward offers various Engineering Services for our products. For these services,
you can contact us by telephone, by email, or through the Woodward website.
• Technical Support
• Product Training
• Field Service

Technical Support is available from your equipment system supplier, your local
Full-Service Distributor, or from many of Woodward’s worldwide locations,
depending upon the product and application. This service can assist you with
technical questions or problem solving during the normal business hours of the
Woodward location you contact. Emergency assistance is also available during non-
business hours by phoning Woodward and stating the urgency of your problem.

Product Training is available as standard classes at many of our worldwide


locations. We also offer customized classes, which can be tailored to your needs
and can be held at one of our locations or at your site. This training, conducted
by experienced personnel, will assure that you will be able to maintain system
reliability and availability.

Field Service engineering on-site support is available, depending on the product


and location, from many of our worldwide locations or from one of our Full-
Service Distributors. The field engineers are experienced both on Woodward
products as well as on much of the non-Woodward equipment with which our
products interface.

For information on these services, please contact us via telephone, email us, or
use our website and reference www.woodward.com/support, and then
Customer Support.

How to Contact Woodward


For assistance, call one of the following Woodward facilities to obtain the
address and phone number of the facility nearest your location where you will be
able to get information and service.

Electrical Power Systems Engine Systems Turbine Systems


Facility --------------- Phone Number Facility --------------- Phone Number Facility --------------- Phone Number
Australia ----------- +61 (2) 9758 2322 Australia ----------- +61 (2) 9758 2322 Australia ----------- +61 (2) 9758 2322
Brazil ------------- +55 (19) 3708 4800 Brazil ------------- +55 (19) 3708 4800 Brazil ------------- +55 (19) 3708 4800
China ------------ +86 (512) 6762 6727 China ------------ +86 (512) 6762 6727 China ------------ +86 (512) 6762 6727
Germany: Germany:
Kempen --- +49 (0) 21 52 14 51
Stuttgart ----- +49 (711) 78954-0 Stuttgart ----- +49 (711) 78954-0
India --------------- +91 (129) 4097100 India --------------- +91 (129) 4097100 India --------------- +91 (129) 4097100
Japan -------------- +81 (43) 213-2191 Japan -------------- +81 (43) 213-2191 Japan -------------- +81 (43) 213-2191
Korea--------------- +82 (51) 636-7080 Korea--------------- +82 (51) 636-7080 Korea--------------- +82 (51) 636-7080
The Netherlands - +31 (23) 5661111 The Netherlands - +31 (23) 5661111
Poland -------------- +48 12 618 92 00
United States----- +1 (970) 482-5811 United States----- +1 (970) 482-5811 United States----- +1 (970) 482-5811

You can also contact the Woodward Customer Service Department or consult our
worldwide directory on Woodward’s website (www.woodward.com/support)
for the name of your nearest Woodward distributor or service facility.

For the most current product support and contact information, please refer to the
latest version of publication 51337 at www.woodward.com/publications.
58 Woodward
Manual 26181 EGCP-2 Communications

Technical Assistance
If you need to telephone for technical assistance, you will need to provide the following information.
Please write it down here before phoning:

General
Your Name
Site Location
Phone Number
Fax Number

Prime Mover Information


Engine/Turbine Model Number
Manufacturer
Number of Cylinders (if applicable)
Type of Fuel (gas, gaseous, steam, etc)
Rating
Application

Control/Governor Information
Please list all Woodward governors, actuators, and electronic controls in your system:

Woodward Part Number and Revision Letter

Control Description or Governor Type

Serial Number

Woodward Part Number and Revision Letter

Control Description or Governor Type

Serial Number

Woodward Part Number and Revision Letter

Control Description or Governor Type

Serial Number
If you have an electronic or programmable control, please have the adjustment setting positions or
the menu settings written down and with you at the time of the call.

Woodward 59
We appreciate your comments about the content of our publications.
Send comments to: [email protected]
Please include the manual number from the front cover of this publication.

PO Box 1519, Fort Collins CO 80522-1519, USA


1000 East Drake Road, Fort Collins CO 80525, USA
Phone +1 (970) 482-5811 • Fax +1 (970) 498-3058
Email and Website—www.woodward.com

Woodward has company-owned plants, subsidiaries, and branches,


as well as authorized distributors and other authorized service and sales facilities throughout the world.
Complete address / phone / fax / email information for all locations is available on our website.

2008/9/Fort Collins

You might also like