China MAde AC DC Inverter Multi Split SM
China MAde AC DC Inverter Multi Split SM
China MAde AC DC Inverter Multi Split SM
TAS-09MVH
TAS-12MVH
TAS-18MVH/O
TAS-24MVH/O
TAS-09EH TAS-09EH/O
TAS-12EH TAS-12EH/O
TAS-18EH TAS-18EH/O
TAS-24EH TAS-24EH/O
REFRIGERENT
HEAT PUMP
R410A
7. ELECTRICAL DATA.............................................................................................7-1
14. APPENDIX A
1.1 General
The new CMV and CS is a high efficiency DC inverter technology outdoor unit,
since it’s a lego concept unit, it can be matched to several inverter indoor units such as wall
mounted type with a capacity range of 9000 – 12000 BTU for each single indoor unit.
DC Inverter
R410a
sine wave form and 120 degree rectangular wave form in compressor driver
sensor less inverter compressor driver
high speed calculation for accurate sine wave form vector control
smart PFC control
fuzzy logic control
High SEER
Lego Concept
Pre-Charged.
Cooling operation at outdoor temperature down to 500F
Heating operation at outdoor temperature down to 50F.
Variable Speed outdoor fan.
Low noise level
EEV for each indoor unit
TAS-18MVH/O TAS-24MVH/O
Function Heat Pump Heat Pump
Rated Voltage 208-230 VAC 208-230 VAC
Rated Frequency 60 Hz 60 Hz
Circuit Breaker Size 20A 30A
Op Range Cool °F 5~131 5~131
Op Range Heat °F minus 4 ~ 109 minus 4 ~ 109
Rated Current (RLA) (Heating/Cooling) 6 / 6.7 A 8 / 8.7 A
Refrigerant (lbs) R410A / 3.88 R410A / 6.61
Rated Capacity (Btu) 18,000 24,000
Capacity Invert Range (W) 5000(1650-7100) 6400(1750-8300)
Input / Actual Input (W) 1380/1450 1830/1882
Cooling
Max. Power (W) 2420 2990
Max Current (A) 10.5 13
SEER 14.8 15.6*
Rated Capacity (Btu) 22,000 25,000
Capacity Invert Range (W) 5800(1790-7800) 7200(2000-8400)
Input / Actual Input (W) 1,550 / 1,580 2,000 / 2,060
Heating Max. Power (W) 2579 3,200
Max Current (A) 11.3 13.9
Declared COP / Actual COP
3.75 / 3.65 3.5 / 3.4
(w/w.h.)
Model YDK-60A-6C YDK-60A-6C
Input (W) 196 196
Fan Motor Capacitor (UFD) 4 / 450 VAC 4/ 450 VAC
Fan Motor FLA (A) 0.98 0.98
Fan Speed (RPM) 900/750/500 900/750/500
Fan Type Axial Axial
Outdoor Fan Blade Diameter (in) 18.1 18.5
Fan Air Flow Volume of Outdoor Unit
2800 3200
(CFM)(M^3/h)
Model C-6RZ146H1A C-7VRN153HOW
outdoor
TYPE DC DC
Compressor Brand Sanyo Sanyo
Capacity (W) 6420 7110
Input (W) 1635 1770
Number of Rows 2-26 2-26
Tube Pitch x Row Pitch 1 x .866 in 1 x .866 in
Fin spacing 0.0708 in 0.0708 in
Fin Type Louvered Fin Louvered Fin
Condenser
Tube Outside Dia. and Type 0.375" Rifled Tube 0.375" Rifled tube
28.66 x 25.6 x .866 30.23 x 31.96 x .866
Coil Length x Height x Width
28.66 x 25.6 x .988 31.57 x 31.96 x .866
Number of circuits 4 4
Unit Dimensions (W x H x D) (in) 36.5 x 14.25 x 27.6 37.8x13.54x33.31
Packing dimensions (W x H x D)
39 x 16.14 x 30.32 41.73 x 18.5 x 36.41
Dimensions (in)
Net / Gross Weight (lb) 114.64 / 123.47 163.14 / 185.18
Design Length 16.4' 16.4'
Max Line Set Height 16.4' 16.4'
Max Line Set Length 49.21' 49.21'
Connection
Charge over Design Length 0.20 oz / Ft. 0.20 oz / Ft.
Connection Pipes 1/4" / 3/8" 1/4" x 1/2"
Design Pressure (PSI) 623.66 623.66
TAS-09MVH
Model YDK-16-4C
Input (W) 54
Capacitor (UFD) 1.2/450VAC
FAN MOTOR
Fan Motor FLA (A) 0.25
Speed (Hi/Med/Low) (RPM) 1150 / 950 / 750
Number of rows 22
Tube pitch row / pitch (in) .69 / .50
Fin spacing (in) 0.0614
Evaporator
Fin Type Louvered Fin
Tube outside dia.(in) / Type 0.2756 Rifled Tube
Indoor
Coil Length x height x width (in) 25.39 x 11.06 x 1
Air Flow (Hi/Med/Low) (CFM) 353 / 306 / 194
Noise Level (dB(A) ≤42
Fan Type Cross Flow
Fan Diameter (in) 3.661
Fan Length (in) 24.921
Design Pressure (PSI) 551.14
Unit Dimensions (W x H x D) (in) 31.1 x 10.63 x 8.27
Packing Dimensions W x H x D) (in) 33.86 x 13.78 x 10.43
Net / Gross Wt (lbs) 26.45 / 30.86
Dehumidifying Volume (pt/hr) 1.8
Auto-restart YES
2.2.2 TAS-12MVH S p e c i f i c a t i o n s
TAS-12MVH
Model YDK-16-4C
Input (W) 54
FAN MOTOR Capacitor (UFD) 1.2/450VAC
Fan Motor FLA (A) 0.25
Speed (Hi/Med/Low) 1200 / 950 / 850 (Cooling) 1200 / 950 / 750
(RPM) (Heating)
Number of rows 22
Tube pitch row / pitch (in) .69 / .50
Fin spacing (in) 0.059
Evaporator Fin Type Louvered Fin
Tube outside dia.(in) /
0.2756 Rifled Tube
Type
Indoor
Coil Length x height x
30.98 x 11.06 x 1
width (in)
Air Flow (Hi/Med/Low) (CFM) 459 / 406 / 218
Noise Level (dB(A) ≤45
Fan Type Cross Flow
Fan Diameter (in) 3.818
Fan Length (in) 30.393
Design Pressure (PSI) 551.14
Unit Dimensions (W x H x D) (in) 36.61 x 10.83 x 8.27
Packing Dimensions W x H x D) (in) 39.96 x 13.97 x 12.79
Net / Gross Wt (lbs) 30.86 / 37.48
Dehumidifying Volume (pt/hr) 3.03
Auto-restart YES
Cooling:
Indoor: 80oFDB 67oF WB
Outdoor: 95oF DB 75oF WB
Heating:
Indoor: 70 oF DB 60 oF WB
Outdoor: 47 oF DB 43 oF WB
Outdoor
Cooling Upper limit (DB) 110 oF
Lower limit (DB) 5oF
Heating Upper limit (DB) 75 oF
Lower limit (DB) 5oF
2PH 198–264V/115V
Voltage
3PH N/A
4. OUTLINE DIMENSIONS
4.1 outdoor Unit: TAS-09EH/O
825
845
50
72
956
50
351
342
378
560
5. PERFORMANCE DATA
5.1 Indoor Units Data
5.1.1 Indoor Units Capacity For 9000BTU
Capacity Model
TAS-09MVH
9000BTU
TAS-09EH
OUTDOOR
ENTERING AIR DB DATA 72/59 75/63 81/66 84/70 90/73
TEMPERATURE[0F]
LEGEND
OD COILENTERING
AIR DB/WB TEM DATA 59 68 77
PERATU RE[0F]
1.4
1.2
Capacity Ratio
90/73
1
84/70
0.8
81/66
0.6
75/63
0.4
72/59
0.2
0
77 86 95 104 115
Outdoor Temp.(deg F)
1.4
1.2
Capacity Ratio
1
59
0.8
68
0.6
77
0.4
0.2
0
5 14 20 30 36 45 50 59
Outdoor Temp.(deg F)
Capacity Model
12000BTU
TAS-12MVH
TAS-12EH
OUTDOOR
ENTERING AIR DB
TEMPERATURE[0F]
DATA 72/59 75/63 81/66 84/70 90/73
TC 80 - 110 % of nominal
14~68 SC 80 - 105 % of nominal
(protection range)
PI 25 - 50 % of nominal
TC 11616 12336 13104 13872 14640
77 SC 10421 10603 10845 11027 11269
PI 0.72 0.73 0.75 0.76 0.77
TC 11040 11808 12576 13296 14064
86 SC 10118 10361 10542 10785 10966
PI 0.81 0.82 0.83 0.85 0.86
TC 10464 11232 12000 12768 13536
95 SC 9876 10058 10300 10542 10724
PI 0.88 0.90 0.92 0.93 0.94
TC 9936 10704 11424 12192 12960
104 SC 9634 9815 10058 10239 10482
PI 0.97 0.98 0.99 1.01 1.02
TC 9264 10032 10752 11520 12288
115 SC 9270 9512 9694 9936 10118
PI 1.07 1.08 1.09 1.11 1.13
OD COILENTERING
AIR DB/WB TEM DATA 59 68 77
PERATU RE[0F]
1.4
1.2
Capacity Ratio
90/73
1
84/70
0.8
81/66
0.6
75/63
0.4
72/59
0.2
0
77 86 95 104 115
Outdoor Temp.(deg F)
1.4
1.2
Capacity Ratio 1
59
0.8
68
0.6
77
0.4
0.2
0
5 14 20 30 36 45 50 59
Outdoor Temp.(deg F)
Capacity Model
18000BTU TAS-18EH
OUTDOOR
ENTERING AIR DB
TEMPERATURE[0F]
DATA 72/59 75/63 81/66 84/70 90/73
TC 80 - 110 % of nominal
14~68
SC 80 - 105 % of nominal
(protection range)
PI 25 - 50 % of nominal
TC 17424 18504 19656 20808 21960
77 SC 15480 15750 16110 16380 16740
PI 1.19 1.21 1.23 1.25 1.27
TC 16560 17712 18864 19944 21096
86 SC 15030 15390 15660 16020 16290
PI 1.34 1.36 1.38 1.40 1.42
TC 15696 16848 18000 19152 20304
95 SC 14670 14940 15300 15660 15930
PI 1.46 1.48 1.52 1.54 1.56
TC 14904 16056 17136 18288 19440
104 SC 14310 14580 14940 15210 15570
PI 1.60 1.62 1.64 1.66 1.68
TC 13896 15048 16128 17280 18432
115 SC 13770 14130 14400 14760 15030
PI 1.77 1.79 1.81 1.83 1.87
OD COILENTERING
AIR DB/WB TEM DATA 59 68 77
PERATU RE[0F]
1.4
1.2
Capacity Ratio
90/73
1
84/70
0.8
81/66
0.6
75/63
0.4
72/59
0.2
0
77 86 95 104 115
Outdoor Temp.(deg F)
1.4
1.2
Capacity Ratio 1
59
0.8
68
0.6
77
0.4
0.2
0
5 14 20 30 36 45 50 59
Outdoor Temp.(deg F)
Capacity Model
24000BTU TAS-24EH
OUTDOOR
ENTERING AIR DB
TEMPERATURE[0F]
DATA 72/59 75/63 81/66 84/70 90/73
TC 80 - 110 % of nominal
14~68
SC 80 - 105 % of nominal
(protection range)
PI 25 - 50 % of nominal
TC 23232 24672 26208 27744 29280
77 SC 20640 21000 21480 21840 22320
PI 1.72 1.75 1.78 1.81 1.84
TC 22080 23616 25152 26592 28128
86 SC 20040 20520 20880 21360 21720
PI 1.93 1.96 1.99 2.02 2.05
TC 20928 22464 24000 25536 27072
95 SC 19560 19920 20400 20880 21240
PI 2.11 2.14 2.20 2.23 2.26
TC 19872 21408 22848 24384 25920
104 SC 19080 19440 19920 20280 20760
PI 2.32 2.35 2.38 2.41 2.44
TC 18528 20064 21504 23040 24576
115 SC 18360 18840 19200 19680 20040
PI 2.56 2.59 2.62 2.65 2.71
OD COILENTERING
AIR DB/WB TEM DATA 59 68 77
PERATU RE[0F]
1.4
1.2
Capacity Ratio
90/73
1
84/70
0.8
81/66
0.6
75/63
0.4
72/59
0.2
0
77 86 95 104 115
Outdoor Temp.(deg F)
1.4
1.2
Capacity Ratio 1
59
0.8
68
0.6
77
0.4
0.2
0
5 14 20 30 36 45 50 59
Outdoor Temp.(deg F)
5.3.1.1 Cooling
5.3.1.2 Heating
6.1 Model
TAS-09EH/O TAS-18MVH/O
TAS-12EH/O TAS-24MVH/O
TAS-18EH/O
TAS-24EH/O
Model TAS-09EH/O
Power Supply 1 PH, 115 VAC,60Hz
Connected to Outdoor
Maximum Current 9.3A
Inrush Current 40A
Starting Current 1A
Circuit breaker 30A
Power supply wiring - No. x cross section 1 X 3 X 2.5 mm2
Interconnecting cable - No. x cross section 2 X 4 X 1 mm2
Model TAS-12EH/O
Power Supply 1 PH, 115 VAC,60Hz
Connected to Outdoor
Maximum Current 10.8A
Inrush Current 40A
Starting Current 1A
Circuit breaker 30A
Power supply wiring - No. x cross section 1 X 3 X 2.5 mm2
Interconnecting cable - No. x cross section 2 X 4 X 1 mm2
Model TAS-18EH/O
Power Supply 1 PH, 230 VAC,60Hz
Connected to Outdoor
Maximum Current 10.1A
Inrush Current 40A
Starting Current 1A
Circuit breaker 30A
21 SERVICE MANUAL FOR AMERICA
Power supply wiring - No. x cross section 1 X 3 X 2.5 mm2
Interconnecting cable - No. x cross section 2 X 4 X 1 mm2
Model TAS-24EH/O
Power Supply 1 PH, 230 VAC,60Hz
Connected to Outdoor
Maximum Current 12.2A
Inrush Current 35A
Starting Current 1A
Circuit breaker 30A
Power supply wiring - No. x cross section 1 X 3 X 2.5 mm2
Interconnecting cable - No. x cross section 2 X 4 X 1 mm2
Model TAS-18MVH/O
Power Supply 1 PH, 230 VAC,60Hz
Connected to Outdoor
Maximum Current 10.5A
Inrush Current 40A
Starting Current 1A
Circuit breaker 20A
Power supply wiring - No. x cross section 1 X 3 X 2.5 mm2
Interconnecting cable - No. x cross section 2 X 4 X 1 mm2
Model TAS-24MVH/O
Power Supply 1 PH, 230 VAC,60Hz
Connected to Outdoor
Maximum Current 13A
Inrush Current 35A
Starting Current 1A
Circuit breaker 30A
Power supply wiring - No. x cross section 1 X 3 X 2.5 mm2
Interconnecting cable - No. x cross section 2 X 4 X 1 mm2
Note:
Inrush current is the current when power is up. (charging the DC capacitors at outdoor unit
controller).
Starting current is the current when starting the compressor
NOTE
Power wiring cord should comply with local lows and electrical
regulations requirements.
22 SERVICE MANUAL FOR AMERICA
8. WIRING DIAGRAMS
9. REFRIGERATION DIAGRAMS
26 SERVICE MANUAL FOR AMERICA
9.1 TAS-09EH/O Refrigeration Diagram
When the outdoor unit is installed above the indoor unit an oil trap is required every 5m along the suction line at the
lowest point of the riser. Incase the indoor unit is installed above the outdoor, no trap is required
18000BTU:
mode high middle low
Cooling
1230 1000 950
speed
Heating
1230 1000 950
speed
12000BTU:
mode high middle low
Cooling
1000 900 750
speed
Heating
1000 900 750
speed
9000BTU:
mode high middle low
Cooling 1300 1150 950
DC Inverter 1:2
PG motor speed:
12000BTU:
mode higher high middle low lower
Cooling
1250 1200 950 850 850
speed
Heating
1250 1200 950 850 750
speed
9000BTU:
mode higher high middle low lower
Cooling
1250 1150 950 750 750
speed
Heating
1250 1150 950 750 750
speed
四、operating mode
Air conditioner have four operating mode: auto, cooling, dehumidify, heating.
1.Cooling(ΔT=Troom temp.-Tset temp.)
range of set temp. 60 OF~90OF;
compressor running as below figure:
compressor
on
CONT 5 MIN
off
OO
F +2 F ΔT
-2
It require outdoor unit to reduce power if indoor room temp. continuous less than set
temp. for 5 minutes.
Air blow function:indoor blower fan continuous running 20 seconds at low speed after
air conditioner turn off in cooling mode. if the flap is swing, shutdown the flap after
turn off indoor blower fan.
Indoor blower fan can select one of four speed.
Fan speed is determined by the difference of room temp. and set temp. in auto wind.
speed
high
middle
low
O
O O
F 2 5 F 9 F ΔT
It have anti freeze protection of indoor coil ,fan motor fault protection, sensor
fault protection, unit abnormal protection in cooling mode.
2.Dehumidify:(ΔT=Troom temp.-Tset temp.)
range of set temp.: default is 77 OF and it can’t change.
The indoor blower fan is running at low speed for thirty seconds after air conditioner
shutdown in dehumidify mode.
compressor
on
CONT 5 MIN
off
O
F -4 OF ΔT-7
It require outdoor unit to reduce power if indoor room temp. continuous more than set
temp. for 5 minutes.
Indoor blower fan continuous running for 30 seconds at current speed after indoor unit
reduce power.
Indoor blower fan can select one of four speed.
Fan speed is determined by the difference of room temp. and set temp. in auto wind.(but
anti cold wind is prior)
speed
high
middle
low
O O O O
0 F 4 FF 6 ΔT F 9
Anti cold wind:
When air conditioner first power on or change mode, indoor blower fan didn’t running. When the
coil pipe temp. of indoor unit is more than 86 OF,start turnning on indoor blower
fan(lower speed).if the coil pipe temp. of indoor unit drop to less than or equal
O
to 77 F,it shutdown indoor blower fan.
Heat wind control:
If coil pipe temp. of indoor unit is more than or equal to 90 OF, indoor blower fan is running
at set speed.
O
If coil pipe temp. of indoor unit is less than 90 F, indoor blower fan is running as below
figure.
speed
set speed
lower
turn off
O O O
F 86 F
77 90 F coil pipe temp.
O
Note:①When Tp≤86 F,flap is open at 85°and is running at lower speed, when Tp
≥90 OF, it is running at set speed and flap revert to prior state.
②If Tp≤77 OF,turn off indoor blower fan.
Defrost control
Indoor blower fan turn off when it enter defrost.
Clear quantity of heat
34 SERVICE MANUAL FOR AMERICA
Turn off air conditioner in heating mode, if the coil pipe temp. of indoor unit is
more than 104 OF, indoor blower fan is running at low speed. If the coil pipe temp.
of indoor unit is less than or equal to 104 OF or turn off air conditioner over 2 minutes,
It shutdown indoor blower fan.
4. Auto mode
set temp. is 77 OF and it can’t change;
Press emergency key in waiting state or select auto mode by remote, air conditioner
enter auto mode and set temp. is 77 OF.
Indoor blower fan is running for 20 seconds at lower speed after select auto mode,
the running lamp is light, it select correspond running mode accord to room temp.:
room temp. >79 OF, select cooling mode.
O
room temp. <70 F, select heating mode.
O O
70 F≤room temp.≤79 F,select ventilation mode.
When the running mode has confirmed, it can’t change, if it reenter auto mode, it
select running mode again accord to room temp..
When the mode of auto select is clash with other indoor unit running mode:
If it auto select is cooling mode and other indoor unit is running heating mode, then it select
ventilation mode.
If it auto select is heating mode, but other indoor unit is running cooling mode, display error of mode
clash.
if it select is ventilation mode, then it running is ventilation.
5.Ventilation
1) Range of set temp.:60 OF -90 OF.
2) Indoor blower fan is operate same as cooling mode.
3) Flap is operate same as cooling mode.
4) Indoor unit no power require in ventilation mode.
Fixed
Full close
2、Heating
Condition Entering Method
O
label Capacity Pressing Tubro for 5 times+Setting temp.77 F
O
H01 Pressing Tubro for 5 times+Setting temp.79 F
O
H11 Pressing Tubro for 5 times+Setting temp.81 F
O
H12 Pressing Tubro for 5 times+Setting temp.83 F
O
H22 Pressing Tubro for 5 times+Setting temp.85 F
O
H32 Pressing Tubro for 5 times+Setting temp.87 F
O
H2V Pressing Tubro for 5 times+Setting temp.89 F
O
H01:Indoor temp. 62 F,Compressor min
O
H11:Indoor temp. 47 F,Compressor min
O
H12:Indoor temp. 47 F,Compressor max
O
H22:Indoor temp. 35 F,Compressor max
O
H32:Indoor temp. 17 F,Compressor max
O
H2V:Indoor temp. 35 F,Compressor mid
2. Inputs of five analogue inputs (the temperature measuring points distributing as Diagram 1, all the
analogues go through digital filter for disposal), and two switch signals and two communication
signals:
a) Signal input of outdoor ambient temperature
b) Signal input of median temperature of outdoor coil
c) Signal input of discharge temperature of compressor
d) Signal input of suction temperature of compressor
e) Signal input of power supply voltage
f) over-heat protection signal of compressor
g) communication signal of indoor unit 1
h) communication signal of indoor unit 2
i) protection signal of outdoor IPM module
2) Adjustment of Expansion Valve according to the difference in temperature between the inlet and
outlet of evaporator
During the first ten minutes of cooling mode, the expansion valve of the indoor unit at the request
of cooling shall be set to the basic step. Ten minutes later, the expansion valve step and its adjust
cycle shall be adjusted according to the difference in temperature between the inlet and outlet of
evaporator.
compressor
compressor
41 SERVICE MANUAL FOR AMERICA
outdoor FM
reverse valve
十.Protect function:
1. Delay protection of compressor
The compressor can’t run after it stop within 3 minutes.
2. Fault protection of module
The air conditioner stop running immediately and display error code if the module is
fault.
3. Protection of communicate fault
The control of outdoor unit can connect with all indoor units, when it power on, it
sent data to each indoor unit continuously, if it receive a correct data from correspond
indoor unit, then the indoor unit is exist. when the control of outdoor unit didn’t
receive communication data from indoor unit which is exist within 30 seconds, it will
display communication fault. If all communication channels are failure, air
conditioner will shutdown and display fault code.
43 SERVICE MANUAL FOR AMERICA
4. Leakage or reverse valve fault
The air conditioner shutdown immediately when meet one of below conditions.
1) Heating: coil pipe temp. of outdoor unit can’t decrease 3 degree within setting
time and coil pipe temp. of indoor unit can’t increase 3 degree all along.
2) Cooling: coil pipe temp. of outdoor unit can’t increase 3 degree within setting
time and coil pipe temp. of indoor unit can’t decrease 3 degree all along.
5. High temp. protection of compressor discharge
1) The protection don’t effect if the temp. sensor of compressor discharge fault.
2) The air conditioner stop running immediately and display error code when the temp.
of compressor discharge more than Tsd.
3) The compressor decrease frequency until the temp. of compressor discharge less
O O
than 210 F if the temp. of compressor discharge more than 203 F. The compressor resume
normal frequency when the temp. of compressor discharge less than 194 OF.
6. Temperature switch protection of compressor
The air conditioner will shutdown immediately and display fault code if the temp.
switch of compressor switch off.
7. High temp. protection of middle coil pipe of condenser
1) The protection don’t effect if the temp. sensor of middle coil pipe fault.
2) The compressor decrease frequency until the temp. of middle coil pipe less than
136 OF.if the temp. of middle coil pipe more than 134 OF..
3) It resume normal frequency when the temp. of middle coil pipe less than133 OF..
8. High temp. protection of indoor coil pipe
1) The compressor decrease frequency until the temp. of indoor coil pipe more than
(Tsce-2) if the temp. of indoor coil pipe less than (Tsce-2)in cooling mode.
The compressor decrease frequency until the temp. of indoor coil pipe less than
(Tsce+2) if the temp. of indoor coil pipe more than (Tsce+2) in heating mode.
2) It resume normal frequency when the temp. of indoor coil pipe less than Tsce(cooling mode) or
less than Tshe(heating mode).
9. Low temp. protection of compressor suction
1) The protection don’t effect if the temp. sensor of compressor suction fault or compressor don’t
run or in heating mode..
2) The compressor decrease frequency until the temp. of compress suction more than
Tss if the temp. of compressor suction less than Tss. It resume normal frequency when the
temp. of compressor suction more than (Tss+2).
10. Fault protection of outdoor sensor
The air conditioner is running at the frequency of less than (3/5)*Fmax and display fault code if
the temp. sensor of compressor discharge fault, or the temp. sensor of outdoor middle coil
pipe fault, or the temp. sensor of compressor suction fault, or the temp. sensor of outdoor
ambient fault.
11. High temp. of ambient
1) The protection don’t effect if the temp. sensor of outdoor ambient fault.
2) The air conditioner stop running immediately and display error code if outdoor
ambient temp. more than 131 OF or less than -4 OF.
12. Over current protection of compressor
44 SERVICE MANUAL FOR AMERICA
1) The air conditioner stop running immediately and display error code when input
current more than or equal to Imax.
2) The compressor decrease 2Hz per 3 seconds until input current less than or equal
to (Imax-13) when the input current more than (Imax-13).
2)The compressor decrease 1Hz per 3 seconds until input current less than or equal
to (Imax-16) when the input current more than (Imax-16).
3) It resume normal frequency when the input current less than or equal to (Imax-20).
13.DC voltage of wire protection
1) The air conditioner stop running and display DC voltage abnormal when it less than
260V.
2)The compressor decrease frequency and display FA6 when DC voltage less than 285V.
3) The air conditioner resume normal running when DC voltage more than 290V.
fault display
Transducer module protection P2
Over current P3
Discharge temperature of P4
compressor overheat, ambient
temperature overheat
DC voltage of outdoor unit abnormal P7
Leakage or reverse valve fault P8
Outdoor sensor fault F6
Compressor drive fault FC
WARNING!!!
When Power Up – the whole outdoor unit controller, including the wiring, is under HIGH
VOLTAGE!!!
Never open the Outdoor unit before turning off the Power!!!
When turned off, the system is still charged (400V)!!!
It takes about 3 Min. to discharge the system.
Touching the controller before discharging may cause an electrical shock!!!
For safe handling of the controller please refer to section 1.6 below.
F2:
1,Temp. sensor of indoor room short or cut off.---change sensor
F3:
1,Temp. sensor of indoor coil pipe outlet short or cut off.---change sensor.
2,Temp. sensor of indoor coil pipe entrance short or cut off.---change sensor.
3,Temp. sensor of indoor coil pipe middle short or cut off.---change sensor.
F4:
1,PG motor fault.---change motor. PG.
2,Fixed screw loose.---fix cross flow fan.
3,Communication interfere. (earth wire can’t with communicate wire in same cable)---check cable.
F6:
1,Temp. sensor of discharge short or cut off.---change sensor.
2,Temp. sensor of suction short or cut off.---change sensor.
3,Temp. sensor of condenser middle short or cut off.---change sensor.
P2:(auto-restart)
1,over current protection of inverter module.
2,over voltage protection of inverter module.
3,high temp. protection of inverter module.
P3:
1,over load (outdoor ambient temp. more high).
2,Voltage over low.
46 SERVICE MANUAL FOR AMERICA
P4:
1: discharge temp. too high.---maybe leak refrigerant, add refrigerant.
2:outdoor ambient temp. too high, if (T<-4 OF,T>131 OF), it will alarm.
3:temp. switch of compressor cut off.。
4:Communication interfere. (earth wire can’t with communicate wire in same cable)---check cable.
P7:
1,PFC board fault.---change PFC board.
2,Communication of main board and PFC board fault.---check wires of main board and PFC board.
P8:
1,Less refrigerant.---add refrigerant.
2,Coil pipe sensor can’t contact with coil pipe.
3,4-way valve fault.---change 4-way vavle fault.
四通阀组
1 前网罩 Front Grill 1 11 Four-way valve assembly 1
件
电子膨胀
2 面 板 Front Plate 1 12 Electronic expansion valve 1
阀
3 轴流风轮 Axial flow fan 1 13 右侧板 Right panel 1
4 电 机 Motor 1 14 电器盒盖 Top of the Electric Box 1
5 左侧板 Left panel 1 15 阀座板 Valve installation plate 1
6 电机支架 Motor support 1 16 低压阀 Low-pressure valve 1
7 冷凝器 Condenser 1 17 高压阀 High-pressure valve 1
8 顶盖板 Top panel 1 18 维修板 Maintenance plate 1
9 电器盒 Electric box 1 19 压缩机 Compressor 1
10 背网 Rear Grill 1 20 中隔板 Partition board 1
21 底盘 Base 1
APPENDIX A
INSTALLATION AND OPERATION MANUAL
Please read carefully the sections corresponding to the specific model you choose, and keep the
Manual properly so as to facilitate your reference at later time.
IMPORTANT!
Please Read Before Starting
This air conditioning system meets strict safety and operating standards.
As the installer or service person, it is an important part of your job to install or service the system so it
operates safely and efficiently.
For safe installation and trouble-free operation, you must:
? Carefully read this instruction booklet before beginning.
? Follow each installation or repair step exactly as shown.
? Observe all local, state, and national electrical codes.
? Pay close attention to all danger, warning, and caution notices given in this manual. WARNING:
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or
death.
CAUTION: This symbol refers to a hazard or unsafe practice which can result in personal injury and
the potential for product or property damage.
CONTENTS
LOCATION OF OUTDOOR UNIT 1
ELECTRICAL CONNECTION BETWEEN INDOOR AND OUTDOOR UNIT 3
INSTALLATION/SERVICE TOOLS (ONLY FOR R410A PRODUCT) 7
REFRIGERANT TUBING 9
FINAL TASKS
11
NOTE: This manual is for Multi split applications only.
For indoor units installation please refer to the
installation manual supplied
55 SERVICE MANUAL FOR AMERICA
within the indoor unit packa
Fig 2
Fig 1 Fig 2
CAUTION
Fig 11
1.INDOOR UNIT
2.Liquid tube(small dia.)
3.Suction tube(large dia.)
4. Plugs
5.Flare nuts
6.Tubing between units
7.Suction tube
8.Liquid tube
9.OUTDOOR UNIT
10.FIare nuts
11 .Suction valve(larger) 12.Liquid valve(smal)
NOTE:1.For unit use connectionsA,B and D
2.For large indoor unit of 5.0KW Use the lower
connection(unit D) and use the
3/8"-1/2"transition( supplied)
3.The electric control channel must match the
tube channel.
Caution!
When unscrewing the
valve caps, do not stand
in front of them or the
spindles at any time,as
the system is under
pressure.
Fig 14 1.Suction
Fig 13 To prevent refrigerant valve 2.Service port
3.Liquid valve
leakage,coat the flared
surface with
refrigeration oil
5 FINAL TASKS
1 .Check all valve caps and ensure that they had tightened properly.Close the valve cover.
2.Fill gaps on the wall between hole sides and tubing with sealer.
3.Attach wiring and tubing to the wall with clamps where necessary.
4.Operate the unit for no less than 5 minutes at heating or cooling mode.
5.Explain filter removal,cleaning and installation.
6.Operate the air conditioner together with the customer and explain all functions.
7.Give the operating and installation manuals to the customer