Service Manual: Heat Pump Air To Air Split Air Conditioner Icy Ii
Service Manual: Heat Pump Air To Air Split Air Conditioner Icy Ii
Service Manual: Heat Pump Air To Air Split Air Conditioner Icy Ii
MODELS: CH-S09FTXTB2S-W
CH-S12FTXTB2S-W
CH-S18FTXTB2S-W
CH-S24FTXTB2S-W
For proper operation, please read and keep this manual carefully.
Designed by Cooper&Hunter International Corporation, Oregon, USA
www.cooperandhunter.com
Downloaded from www.Manualslib.com manuals search engine
Service Manual
Table of Contents
Table of Contents
Downloaded from www.Manualslib.com manuals search engine
Service Manual
9. Maintenance . ...........................................................................................................58
9.1 Troubleshooting for Normal Malfunction. ........................................................................58
9.2 Error Code List . ..............................................................................................................62
9.3 Troubleshooting for Main Malfunction . ...........................................................................67
10. Exploded View and Parts List ..............................................................80
10.1 Indoor Unit . ...................................................................................................................80
10.2 Outdoor Unit . ................................................................................................................82
11. Removal Procedure . ......................................................................................84
11.1 Removal Procedure of Indoor Unit . ..............................................................................84
11.2 Removal Procedure of Outdoor Unit . ...........................................................................91
Appendix: . .......................................................................................................................97
Appendix 1: Reference Sheet of Celsius and Fahrenheit . ...................................................97
Appendix 2: Configuration of Connection Pipe. ....................................................................97
Appendix 3: Pipe Expanding Method . ..................................................................................98
Appendix 4: List of Resistance for Temperature Sensor . .....................................................99
Table of Contents
Downloaded from www.Manualslib.com manuals search engine
Service Manual
Outdoor Unit:
Remote Controller:
Technical Information 1
Downloaded from www.Manualslib.com manuals search engine
Service Manual
2. Specifications
2.1 Specification Sheet
Model CH-S09FTXTB2S-W
2 Technical Information
Downloaded from www.Manualslib.com manuals search engine
Service Manual
The above data is subject to change without notice; please refer to the nameplate of the unit.
Technical Information 3
Downloaded from www.Manualslib.com manuals search engine
Service Manual
4 Technical Information
Downloaded from www.Manualslib.com manuals search engine
Service Manual
The above data is subject to change without notice; please refer to the nameplate of the unit.
Technical Information 5
Downloaded from www.Manualslib.com manuals search engine
Service Manual
6 Technical Information
Downloaded from www.Manualslib.com manuals search engine
Service Manual
The above data is subject to change without notice; please refer to the nameplate of the unit.
Technical Information 7
Downloaded from www.Manualslib.com manuals search engine
Service Manual
10 10
Condition Condition
Indoor:DB27°C WB19°C Indoor:DB20°C WB15°C
8 Indoor air flow: Super High 8 Indoor air flow:Super High
Pipe length: 5m Pipe length: 5m
Current (A)
Current (A)
6 6
4 09K 4 09K
Cooling Heating
12K 12K
2 200 2 200
180
0 160 0 160
Capacity ratio(%)
Capacity ratio(%)
0140 15 20 30 40 50 60 70 80 90 0
140 15 20 30 40 50 60 70 80 90
120 Compressor speed (rps) 120 Compressor speed (rps)
100 100
80 80 Condition
60 Condition Indoor:DB20°C WB15°C
60
Indoor:DB27°C WB19°C Indoor air flow:Super High
Cooling
40 40 Heating
Indoor air flow: Super High Pipe length: 5m
20 Pipe length: 5m 20
10 10
0 0
33
Condition 35 37 39 41 43 45 -6 Condition
-4 -2 0 2 4 6 8 10
Indoor:DB27°C WB19°C Indoor:DB20°C 12K
8
2.3 Capacity Variation Ratio According to Temperature
8
Outdoor:DB35°C Outdoor
WB24°Ctemp.(°C) Outdoor:DB7°C Outdoor temp.(°C)
Indoor air flow: Super High 12K Indoor air flow:Super High
Pipe length: 5m Pipe length: 5m
Current (A)
Current (A)
6 6
4
Cooling 09K Heating 09K
4
200 200
180
2 180 2
160 160
Capacity ratio(%)
Capacity ratio(%)
140 140
0 0
120
0 120 15 20 30 40 50 60 70 80 90 0 15 20 30 40 50 60 70 80 90
100 100
80
Compressor speed (rps) 80 Compressor speed (rps)
60 Condition 60 Condition
Indoor:DB27°C WB19°C Indoor:DB20°C WB15°C
40
Cooling Indoor air flow: Super High 40
Heating Indoor air flow:Super High
1120 Pipe length: 5m 2011 Pipe length: 5m
10 0 010
• Conditions
33 35 37 39 41 43 45 -20 -18 -14 -10 -6 -2 2 6 10
9 Indoor: DB27°C/WB19°C 9
Outdoor: DB35°C/WB24°C
8 Outdoor temp.(°C)
Indoor air flow: High 8 Outdoor temp.(°C)
24K
Pipe length: 5m
Current (A)
Current (A)
7 7
6 6
5
24K 5
4 4 18K
18K • Conditions
3 3 Indoor: DB20°C/WB15°C
2 2 Outdoor: DB7°C/WB6°C
Indoor air flow: High
1 1 Pipe length: 5m
0 0
0 10 20 30 40 50 60 70 80 90 0 10 20 30 40 50 60 70 80 90 100 110 120
Compressor speed (rps) Compressor speed (rps)
8 Technical Information
Downloaded from www.Manualslib.com manuals search engine
Service Manual
0 0
33 35 37 39 41 43 45 -6 -4 -2 0 2 4 6 8 10
2.3 Capacity Variation Ratio According to Temperature
Outdoor temp.(°C) Outdoor temp.(°C)
Capacity ratio(%)
140 140
120 120
100 100
80 80
60 60 Condition
Indoor:DB27°C WB19°C Indoor:DB20°C WB15°C
40 Indoor air flow: Super High 40
Indoor air flow:Super High
20 Pipe length: 5m 20 Pipe length: 5m
0 0
33 35 37 39 41 43 45 -20 -18 -14 -10 -6 -2 2 6 10
Cooling Heating
120 120
110 110
100
Capacity ratio(%)
100
Capacity ratio(%)
90
80 90
80
70
• Conditions • Conditions
Indoor: DB27°C/WB19°C 70 Indoor: DB20°C/WB15°C
60 Outdoor: DB35°C/WB24°C Outdoor: DB7°C/WB6°C
Indoor air flow: High Indoor air flow: High
60
50 Pipe length: 5m 50 Pipe length: 5m
40 40
32 35 38 42 48 -30 -20 -15 -8 0 7 10
Outdoor Temp.(°C) Outdoor Temp.(°C)
Technical Information 9
Downloaded from www.Manualslib.com manuals search engine
Service Manual
09K 09K
50 55
45
50
Noise/dB(A)
40
Noise/dB(A)
35 45
30
25 40
20
15 35
10
SL L ML M MH H SH 30
0 8 20 30 40 50 60 70 80 90
Indoor fan motor rotating speed (rps) Compressor speed (rps)
12K
Indoor Unit Outdoor Unit
55
45
12K 50 12K
40
Noise/dB(A)
35 45
Noise/dB(A)
30 40
25 35
20 30
Super High Middle Middle Middle Low Quiet
0 8 20 30 40 50 60 70 80 90
High High Low
Compressor speed (rps)
Indoor fan motor rotating speed (rps)
18K, 24К
Indoor side noise Outdoor side noise
50 60
24K 58
Heating
56
Noise/dB(A)
40
Noise dB(A)
18K 54
Cooling
52
30
50
48
20 46
SL L ML M MH H SH 20 30 40 50 60 70 80 90 100
10 Technical Information
Downloaded from www.Manualslib.com manuals search engine
Service Manual
2.5 Cooling and Heating Data Sheet in Rated Frequency
Cooling:
Heating:
Cooling:
Pressure of gas pipe Inlet and outlet pipe
Rated cooling Compressor
connecting indoor and temperature of heat Fan speed of Fan speed of
condition(°C) (DB/WB) Model outdoor unit exchanger revolution
indoor unit outdoor unit
(rps)
Indoor Outdoor P (MPa) T1 (°C) T2 (°C)
27/19 35/- 12K 0.9 ~ 1.2 12 to 14 39 to 43 TURBO High 54
Heating:
Heating:
Instruction:
T1: Inlet and outlet pipe temperature of evaporator
T2: Inlet and outlet pipe temperature of condenser
P: Pressure at the side of big valve
Connection pipe length: 5 m.
Technical Information 11
Downloaded from www.Manualslib.com manuals search engine
Service Manual
H
137 541 138
09K
Φ50 Φ50
35
132 60
Model W H D
09K 816 292 209
Unit:mm
12 Technical Information
Downloaded from www.Manualslib.com manuals search engine
Service Manual
2.5 Cooling and Heating Data Sheet in Rated Frequency
W D
H
Q R S
Φ55 Φ55
35
W1 W2 Unit:mm
Model W H D Q R S W1 W2
12K 866 292 209 162 541 163 160 80
Technical Information 13
Downloaded from www.Manualslib.com manuals search engine
Service Manual
W D
18K
Φ70 Φ70
55 13 55
119 44
24K
Φ70 Φ70
50
130 100
Unit:mm
Model W H D
18K 1018 319 230
24K 1178 326 264
14 Technical Information
Downloaded from www.Manualslib.com manuals search engine
Service Manual
596
378
899
596
Unit:mm
490
CH-S12FTXTB2S-W
378 899
550
354
Unit:mm
Technical Information 15
Downloaded from www.Manualslib.com manuals search engine
Service Manual
CH-S18FTXTB2S-W
963 340
700
890 396
560
364
Unit:mm
CH-S24FTXTB2S-W
920 370
790
1000 427
610
395
Unit:mm
16 Technical Information
Downloaded from www.Manualslib.com manuals search engine
Service Manual
Gas pipe
side
Valve
4-Way valve
Discharge
Heat Accumlator
exchanger Suction
Compressor
(evaporator)
Heat
exchanger
Liquid pipe (condenser)
side
Valve Strainer Electron Strainer
expansion
valve
COOLING
HEATING
GAS SIDE
3-WAY VALVE
4-Way valve
Discharge
HEAT
EXCHANGE
(EVAPORATOR) Suction Accumlator
COMPRESSOR
D
HEAT
EXCHANGE
(CONDENSER)
LIQUID SIDE Intercooler
COOLING
HEATING
Technical Information 17
Downloaded from www.Manualslib.com manuals search engine
Service Manual
5. Electrical Part
●Instruction
Symbol
Symbol Color Symbol Symbol Color Symbol Name
WH White GN Green CAP Jumper cap
YE Yellow BN Brown COMP Compressor
RD Red BU Blue Grounding wire
YEGN Yellow/Green BK Black / /
VT Violet OG Orange / /
Note: Jumper cap is used to determine fan speed and the swing angle of horizontal lover for this model.
● Indoor Unit
09K
BK BK
COM-OUT 2
BN
AP2 AC-L BN 3
CAP YEGN
XT C0NNECTING
PRINTED CIRCUIT BOARD YEGN YEGN
CABLE
JUMP PE PE
EVAPORATOR
BK SWITCH
SWING-LR SWING-UD1 SWING-UD2 DC-MOTOR C.
CLEAN
X10 SA
CONNECTOR NO.
X1 WH
X2
M2 M3 M4
M1 ELECTROSTATIC
LEFT-RIGHT UP-DOWN UP-DOWN DEDUSTING
STEPPING STEPPING STEPPING FAN MOTOR 6361268408
MOTOR MOTOR MOTOR
18 Technical Information
Downloaded from www.Manualslib.com manuals search engine
Service Manual
12К
287'22581,7
%. %.
&20287
%1
%1
&$3 $3 $&/
;7
<(*1
&11(&7,1*
35,17('&,5&8,7%2$5' <(*1 <(*1
&$%/(
-803
3( 3(
(9$325$725
%. 6:,7&+
6:,1*/5 6:,1*8' 6:,1*8' '&02725 &
&/($1
; 6$
&211(&725 12
; :+
;
0 0 0
0 (/(&75267$7,&
/()75,*+7 83'2:1 83'2:1 '('867,1* 6361268408
67(33,1* 67(33,1* 67(33,1* )$102725
02725 02725 02725
18К, 24К
:$51,1*
3OHDVHGRQ
WWRXFKDQ\HOHFWURQLFFRPSRQHQWRUWHUPLQDO
ZKHQWKHPDFKLQHLVUXQQLQJVWRSSLQJRUKDVEHHQSRZHUHG
RIIIRUOHVVWKDQPLQXWHVWRSUHYHQWHOHFWULFVKRFN
%8 %8
1 1
6:,1*/5 '&02725 5220 78%( ',63 ',63 &20,11(5 %. %.
&20287
%1 %1
$&/
<(*1
&$3 $3 <(*1
;7
&211(&7,1*
<(*1 &$%/(
3(
-803 35,17('&,5&8,7%2$5' 3(
(9$325$725
; %.
; 12 &
6:,1*8' 6:,1*8' :,), :+
&/($1 &211(&725 6$
+($/7+/ +($/7+1 6:,7&+
&211(&725 ; 5' %8
,1'22581,7
0 0
&211(&725
83'2:1 83'2:1 $3 (/(&75267$7,& &2/'3/$60$
67(33,1* 67(33,1* :,),02'8/( '('867,1* *(1(5$725
02725 02725
6361000023204
Technical Information 19
Downloaded from www.Manualslib.com manuals search engine
Service Manual
● Outdoor Unit
09К
%. / / %.
%1
/ / %1
&208
$&/ $30DLQ%RDUG
/
<(*1
<(*1 &1
( 2)$1
+($71
+($71
&1 +33
;7
%1%.
+($7/
<(*1
<(*1
3( 3( :+ :+ %27720
%$1'
/ / 97 97 +($7(5
1 /
32:(5 (.9 :+ 2* <9
<(*1 0 / &2035(6625
3
(/(&7521,& 5($&725 %$1'+($7(5
)$1 (;3$16,21 :$<
3( 02725 9$/9( 9$/9( 35(6685(
6:,7&+
127( 0RWRU
JURXQGRQO\
63610000299 DSSOLHVWRWKH
LURQVKHOOPRWRU
These wiring diagrams are subject to change without notice; please refer to the one supplied with the unit.
12К
%8 / %8
N 1 N2
/ %. 1
%.
%1
/
/ %1 &208
$&/
$30DLQ%RDUG
N3
BU
<(*1
( &1
+($71
+($71
+($7/
%1%.
3( 3( :+ :+ %27720
<(*1 %$1'
97 97 / / +($7(5
1 /
(.9 <9 2* :+
32:(5 <(*1 0 3 / &2035(6625
(/(&7521,& %$1'+($7(5
3( )$1 (;3$16,21 :$< 35(6685( 5($&725
NOTE:Motor 02725 9$/9( 9$/9( 6:,7&+
ground only
applies to the
iron shell motor. 63610000231
These wiring diagrams are subject to change without notice; please refer to the one supplied with the unit.
20 Technical Information
Downloaded from www.Manualslib.com manuals search engine
Service Manual
18К, 24К
%8 / %8
N 1 N2
/ %. 1
%.
%1
/
/ %1 &208
$&/
$30DLQ%RDUG N3
BU
<(*1
( &1
+($71
+($71
;7 2)$1 &1 +33
<(*1
+($7/
%1%.
3( 3( :+ :+ %27720
%$1'
97 97 / / +($7(5
1 /
(.9 <9 2* :+
32:(5 <(*1 0 3 / &2035(6625
(/(&7521,& %$1'+($7(5
3( )$1 (;3$16,21 :$< 35(6685( 5($&725
NOTE:Motor 02725 9$/9( 9$/9( 6:,7&+
ground only
applies to the
iron shell motor. 63610000231
The above data is subject to change without notice. Please refer to the nameplate of the unit.
Technical Information 21
Downloaded from www.Manualslib.com manuals search engine
Service Manual
4 1 Grounding wire
Interface of health function
2
3 live wire
Interface of health function
3
10 neutral wire
2
4 Neutral wire
11 5 Interface of DC motor
Interface of electrostatuc
6
12 dedusting
7 Auto button
13
8 Up&down swing interface 1
9 eft&right swing interface
10 Up&down swing interface 2
11 Interface of DRED
1 12 Interface of IC-DOOR
13 Interface of WiFi
14 Display interface
Interface of ambient
15
temperature sensor
Interface of tube temperature
16
14 sensor
17 Jumper cap
18 Communication interface
19 Live wire interface
20 Fuse
20 19 18 17 16 15
● Bottom view
22 Technical Information
Downloaded from www.Manualslib.com manuals search engine
Service Manual
Outdoor unit
09К
● Top view
2 3 4 5 6 7 8
10
11
12
16 15 14 13
● Bottom view
Technical Information 23
Downloaded from www.Manualslib.com manuals search engine
Service Manual
12
● Top view
10 9 8 7 6 5
11
12
3
13 14 15
● Bottom view
24 Technical Information
Downloaded from www.Manualslib.com manuals search engine
Service Manual
18К, 24К
● Top view
1 2 3 4 5 6
Terminal of compressor
1
wire
Terminal of low pressure
2
protection
Terminal of compressor
3
overload protection
7 Te r m i n a l o f o u t d o o r
4
temperature sensor
5 Terminal of outdoor fan
6 Terminal of 4-way valve
Communication wire
7
with indoor unit
8 8 Power supply live wire
9 Earthing wire
9
Power supply neutral
10
wire
11 PFC induction wire
10
11
● Bottom view
Technical Information 25
Downloaded from www.Manualslib.com manuals search engine
Service Manual
)XQFWLRQDQG&RQWURO
5HPRWH&RQWUROOHU,QWURGXFWLRQ
Buttons on Remote Controller
1 ON/OFF button
2 FAN button
3 MODE button
+/- button
4
5 TURBO button
1 2
2 3
6 button
5 4
7 button
4 7
6
3 8 9 8 CLOCK button
1 10 12
11 16 9 TIMER ON/
13
TIMER OFF button
14 15
10 TEMP button
11 / button
(before opening cover) (after opening cover) 12 I FEEL button
1 ON/OFF button 13 LIGHT button
26 Technical Information
Downloaded from www.Manualslib.com manuals search engine
Service Manual
2. FAN button
Press this button, Auto, Low, Medium-low, Medium, Medium-high, High speed can be circularly selected. After powered on, Auto fan speed
is default. Under DRY mode, Low fan speed only can be set up.
ATUO
Note: It’s Low fan speed
under Dry mode.
Low fan Medium-low fan Medium fan Medium-high fan High fan
3. MODE button
Press this button, Auto, Cool, Dry, Fan, Heat mode can be selected circularly. Auto mode is default while power on. Under Auto mode, the
temperature will not be displayed;Under Heat mode, the initial value is 28°C( 82°F);Under other modes, the initial value is 25°C(77°F).
OFF
7. button
Press this button to set swing angle,which circularly changes as below:
OFF
This remote controller is universal. If it receives threes kinds of following status,the swing angle will remain origial.
If guide louver is stopped when it is swinging up and down,it will remain its present position.
8. CLOCK button
Press this button, the clock can be set up,signal blink and display.Within 5 seconds, the value can be adjusted by pressing + or -
button, if continuously press this button for 2 seconds above,in every 0.5 seconds, the value on ten place of Minute will be increased
1.During
After
powered on, 12:00 is defaulted to display and signal will be displayed. If there is signal be displayed that denotes the current
time value is Clock value, otherwise is Timer value.
9. TIMER ON/TIMER OFF button
● Timer On setting: Signal “ON”will blink and display,signal will conceal,the numerical section will become the timer on setting status.
During 5 seconds blink,by pressing + or - button to adjust the time value of numerical section,every press of that button,the value will
be increased or decreased 1 minute.Hold pressing + or - button,2 seconds later,it quickly change,the way of change is: During the initial
2.5 seconds,ten numbers change in the one place of minute,then the one place is constant,ten numbers change in the ten splace of
minute at
2.5 seconds speed and carry. During 5s blink,press the Timer button,the timer setting succeeds.The Timer On has been set up,repress
the timer button,theTimer On will be canceled. Before setting theTimer,please adjust the Clock to the current actual time.
Technical Information 27
Downloaded from www.Manualslib.com manuals search engine
6HUYLFH0DQXDO
TIMER ON.
10. TEMP button
Press this button,the following temperature can be setted circularly: the setting temperature, indoor ambient temperature and outdoor
to ,displaying the indoor ambient temperature. is the outdoor ambient temperature. 3s laterit will return to the setting temprature or it
depends on the other received signal within3s.
Note: Outdoor ambient temperatue display range is 0~60°C (32~99°F). As for the outdoor ambient temperature below 0it displays 0°C(32°F).
Warm tips: When operating buttons on the cover, please make sure the cover is closed completely.
11. / button(This function is only available for some models)
scavenging function;LCD displays“ ”.Press the button for the second time to start healthy and scavenging functions simultaneously;LCD
displays“ ”and “ ” .Press this button for the third time to quit healthy and scavenging functions simultaneously.Press the button for the
fourth time to start healthy function; LCD display“ ” .Press this button again to repeat the operation above.
12. I FEEL button
button, every 200ms to send I FEEL once, after this function started,the remote control will send temperature to the main un it in every 10
minutes.When repress this button, this function will be turned off.
13. LIGHT button
Press this button at unit On or Off status,Light On and Light Off can be set up.After powered on, Light On is defaulted.
14. X-FAN button
Pressing X-FAN button in COOL or DRY mode,the icon is displayed and the indoor fan will continue operation for 2 minutes in order
to dry the indoor unit even though you have turned off the unit.After energization, X-FAN OFF is defaulted.X-FAN is not available in
AUTO,FAN or HEAT mode.
15. QUIET button
Press this button,the Quiet status is under the Auto Quiet mode (display" " and “Auto”signal ) and Quiet mode(display " " singal) and
Quiet OFF(there is no signal of " " displayed),after powered on,the Quiet OFF is defaulted. Under the Quiet mode (Display " "signal),
the fan speed is not available.
16. SLEEP button
●Press this button, can select Sleep 1 ( ), Sleep 2 ( ),Sleep 3 ( ) and cancel the Sleep, circulate between these, after
●Sleep 1 is Sleep mode 1, in Cool, Dehumidify modes: sleep status after run for one hour, the main unit setting temperature will increase 1°C,
2 hours,setting temperature increased 2°C, the unit will run at this setting temperature; In Heat mode: sleep status after run for one hour,
the setting temperature will decrease 1°C, 2 hours, setting temperature will decrease 2°C, then the unit will run at this setting temperature.
●Sleep 2 is sleep mode 2, that is air conditioner will run according to the presetting a group of sleep temperature curve.
In Cool mode:
(1) When setting the initial temperature 16~23°C, after turned on Sleep function, the temperature will be increased 1°C in every hour,after
3°C the temperature will be maintained, after 7hours,the temperature will be decreased 1°C, after that the unit will keep on running under
this temperature;
(2) When setting the initial temperature 24~27°C, after turned on Sleep function, the temperature will be increased 1°C in every hour,after
2°C the temperature will be maintained, after 7hours,the temperature will be decreased 1°C, after that the unit will keep on running under
this temperature;
(3) When setting the initial temperature 28~29°C, after turned on Sleep function, the temperature will be increased 1°C in every hour, after
1°C the temperature will be maintained, after 7hours,the temperature will be decreased 1°C, after that the unit will keep on running under
this temperature;
(4) When setting the initial temperature 30°C, under this temperature setting, after 7hours, the temperature will be decreased 1°C, after
that the unit will keep on running under this temperature;
In Heat mode:
(1) Under the initial presetting temperature 16°C, it will run under this setting temperature all along.
(2) Under the initial presetting temperature17~20°C, after Sleep function started up, the temperature will decrease 1°C in every hour, after
1°C decreased, this temperature will be maintained.
(3) Under the initial presetting temperature 21~27°C, after Sleep function started up, the temperature will decrease 1°C in every hour,after
2°C decreased, this temperature will be maintained.
(4) Under the initial presetting temperature 28~30°C, after Sleep function started up, the temperature will decrease 1°C in every hour, after
3°C decreased, this temperature will be maintained
●Sleep 3- the sleep curve setting under Sleep mode by DIY:
(1) Under Sleep 3 mode, press "Turbo" button for a long time, remote control enters into user individuation sleep setting status, at this time,
the time of remote control will display "1hour ", the setting temperature "88" will display the corresponding temperature of last setting sleep
(3) At this time, 1hour will be automatically increased at the timer postion on the remote control, (that are "2hours" or "3hours" or "8hours "),
28 7HFKQLFDO,QIRUPDWLRQ
the place of setting temperature "88" will display the corresponding temperature of last setting sleep curve and blink;
control will resume the original timer display;temperature display will resume to original setting temperature.
●Sleep3- the sleep curve setting under Sleep mode by DIY could be inquired:
The user could accord to sleep curve setting method to inquire the presetting sleep curve, enter into user individuation sleep setting status,
Note: In the above presetting or enquiry procedure, if continuously within10s, there is no button pressed, the sleep curve setting status will
be automatically quit and resume to display the original displaying. In the presetting or enquiry procedure, press "ON/OFF" button, "Mode"
button, "Timer" button or "Sleep" button, the sleep curve setting or enquiry status will quit similarly.
17. About X-FAN function
This function indicates that moisture on evaporator of indoor unit will be blowed after the unit is stopped to avoid mould.
(1)Having set X-FAN function on: After turning off the unit by pressing ON/OFF button indoor fan will continue running for about 2 min. at
low speed. In this period, press X-FAN button to stop indoor fan directly.
(2)Having set X-FAN function off: After turning off the unit by pressing ON/OFF button, the complete unit will be off directly.
18. About AUTO RUN
When AUTO RUN mode is selected, the setting temperature will not be displayed on the LCD, the unit will be in accordance with the room
temp. automatically to select the suitable running method and to make ambient comfortable.
19. About turbo function
If start this function, the unit will run at super-high fan speed to cool or heat quickly so that the ambient temp. approachs the preset temp.
as soon as possible.
20. About lock
Press + and - buttons simultaneously to lock or unlock the keyboard. If the remote controlleris locked, the icon will be displayed on it, in
.
21. About swing up and down
(1)Press swing up and down button continuously more than 2s,the main unit will swing back and forth from up to down, and then loosen
the button, the unit will stop swinging and present position of guide louver will be kept immediately.
(2)Under swing up and down mode, when the status is switched from off to , if press this button again 2s later,
status will switch to off status directly; if press this button again within 2s,the change of swing status will also depend on the circulation
sequence stated above.
22. About swing left and right(This function is only available for some models)
(1)Press swing left and right button continuously more than 2s,the main unit will swing back and forth from left to right, and then loosen the
button, the unit will stop swinging and present position of guide louver will be kept immediately.
(2)2. Under swing left and right mode, when the status is switched from off to , if press this button again 2s later,
status will switch to off status directly; if press this button again within 2s,the change of swing status will also depend on the circulation
sequence stated above.
23. About switch between Fahrenheit and Centigrade
Under status of unit off, press MODE and - buttons simultaneously to switch °C and °F.
24. Combination of " TEMP" and "CLOCK" buttons : About Energy-saving Function
Press “TEMP” and “CLOCK” simultaneously in COOL mode to start energy-saving function.Nixie tube on the remote controller displays “SE”.
Repeat the operation to quit the function.
25. Combination of " TEMP" and "CLOCK" buttons : About 8°C Heating Function7KLVIXQFWLRQLVRQO\DYDLODEOHIRUVRPHPRGHOV
Press “TEMP” and “CLOCK” simultaneously in HEAT mode to start 8°C Heating Function.Nixie tube on the remote controller displays"
"and a selected temperature of “8°C” (46°F if Fahrenheit is adopted). Repeat the operation to quit the function.
26. About Auto Quiet function
When auto quiet function is selected:
(1)Under cooling mode: indoor fan operates at notch 4 speed. 10 minutes later or when indoor ambient temperature≤28°C, indoor fan will
operate at notch 2 speed or quiet mode according to the comparison between indoor ambinet temperature and set temperature.
(2)Under heating mode: indoor fan operates at notch 3 speed or quiet mode according to the comparison between indoor ambient
temperature and set temperature.
(3)Under dry, fan mode: indoor fan operates at quiet mode.
(4)Under auto mode: the indoor fan operates at the auto quiet mode according to actual cooling, heating or fan mode.
27. About Sleep function
Under the Fan and Auto mode, the Sleep function cannot be set up, under Dehumidify mode, only Sleep 1 can be selected.Select and
enter into any kind of Sleep mode, the Quiet function will be attached and stared, different Quiet status could be optional and turned off.
28. About WiFi function8. bout WIFI Function
Press "MODE" and "TURBO" button simultaneously to turn on or turn off WIFI function. When WIFI function is turned on, the " "
icon will be displayed on remote controller; Long press "MODE" and "TURBO" buttons simultaneously for 10s, remote controller will
send WIFI reset code and then the WIFI function will be turned on. WIFI function is defaulted ON after energization of the remote
controller. (This function only applicable for some models. )
7HFKQLFDO,QIRUPDWLRQ 29
Operation Guide
4
1 2
1. General operation
3
(1)After powered on, press ON/OFF button, the unit will start to run. (Note: When it is powered on, the
guide louver of main unit will close automatically.) 5
(2)Press MODE button, select desired running mode.
(3)Pressing + or - button, to set the desired temperature (It is unnecessary to set the temp. at AUTO
mode.)
(4)Pressing FAN button, set fan speed, can select AUTO FAN,LOW, MEDIUM-LOW, MEDIUM, MEDIUM-
HIGH and HIGH.
(5)Pressing and button, to select the swing.
2. Optional operation
(1)Press SLEEP button, to set sleep.
4
(2)Press TIMER ON and TIMER OFF button, can set the scheduled timer on or timer off. 2
(3)Press LIGHT button, to control the on and off of the displaying part of the unit (This function may be not
3
available for some units). 1
(4)Press TURBO button, can realize the ON and OFF of TURBO function.
30 7HFKQLFDO,QIRUPDWLRQ
Tpreset
Tpreset–2
–2˚C
˚C Stop cooling
≥ 6 min. ≥ 3 min. ≥ 6 min.
Stop cooling
≥ 6 min. ≥ 3 min. ≥ 6 min.
30S 30S
Compressor
Compressor 30S 30S
Outdoorfan
Outdoor fan
Set fan spee d
Indoorfan
Indoor fan Set fan spee d
Run Stop
Run Stop
② When outdoor unit has malfunction or stops for protection, indoor unit will keep previous operation status and display malfunction
code.
(2)Dry Mode
When Tamb.>Tpreset, the unit operates in cooling mode. Meanwhile, compressor and outdoor fan operate, and indoor fan operates at
set fan speed (low fan speed, quiet fan speed or auto quiet fan speed).
When Tpreset-2°C<Tamb. ≤Tpreset, the unit keeps previous operation status.
When Tamb.≤Tpreset-2°C, the compressor will stop, the outdoor fan will stop with a time lag of 30s and indoor fan operate at set fan
speed (low fan speed, quiet fan speed or auto quiet fan speed).
Under this mode, the temperature setting range is 16~30°C. Display displays operation icon, drying icon and set temperature.
Technical Information 55
Downloaded from www.Manualslib.com manuals search engine
Service Manual
Stop heating
Tpreset+5
Original operating status
Tpreset+2
Tamb.
6min. 3min. 6min. Start heating
Outdoor fan
60s 60s
Indoor fan <2 min. preset <2 min. preset
wind wind
Reversing valve
Run Stop
56 Technical Information
Downloaded from www.Manualslib.com manuals search engine
Service Manual
③ In this mode, TURBO can’t be set and fan speed can’t be adjusted.
④ In this mode, when compressor operates, fan speed will be adjusted as follows; when compressor stops operation, indoor unit will
operate at blowing residual heat.
When Tindoor amb. ≤9°C, indoor fan operates at high fan speed;
When 9°C < Tindoor amb. < 11°C, indoor fan operates at medium fan speed;
When Tindoor amb.≥11°C, indoor fan operates at low fan speed;
When changing among low high, medium, and low speeds, the minimum operation time is 210 seconds.
⑤ The unit with memory function can memorize 8°C heating mode.
Tamb.
11℃
9℃
Tamb. High
Fan speed Low Med.
11℃
(7)Energysaving Function 9℃
① In cooling mode, when receiving command of energysaving sent by remote control, the controller enters energysaving mode; If the
unit is under energysaving mode already, suchLow
command
Med.
willHigh
not be executed.
Fan speed
② When remote control is set to display set temperature, “dual 8”nixie tube displays “SE”.
③ In this mode, when compressor operates, fan speed will be adjusted according to auto fan mode under energysaving operation;
when compressor stops operation, indoor fan will operate at low speed.
a. When Tamb.≥31°C, indoor fan will operate at super high speed;
Tamb.
Tpreset + 1
④ In this mode, set temperature will be automatically adjusted according to actual operation conditions.
3.Other Control
(1)Clock Timer
Timer ON
If timer ON is set during operation of the unit, the unit will continue to operate. If timer ON is set at unit OFF, upon ON time reaches the
unit will start to operate according to previous setting status.
Timer OFF
If timer OFF is set at unit OFF, the system will keep standby status. If timer OFF is set at unit ON, upon OFF time reaches the unit will
stop operation.
Timer Change
Although timer has been set, the unit still can be turned on/off by pressing ON/OFF button of the remote controller. You can also set
the timer once again, and then the unit will operate according to the last setting.
If timer ON and timer OFF are set at the same time during operation of the unit, the unit will keep operating at current status till OFF
time reaches.
If timer ON and timer OFF are set at the same time at unit OFF, the unit will keep off status till ON time reaches.
Each day in future, the system will operate according to preset mode till OFF time reaches and stop operation till ON time reaches. If
ON time and OFF time are the same, OFF command will prevail.
(2)Auto Button
If this button is pressed, the unit will operate in AUTO mode and indoor fan will operate at auto speed; meanwhile, the swing motor
operates. Press this button again to turn off the unit.
(3)Buzzer
Technical Information 57
Downloaded from www.Manualslib.com manuals search engine
Service Manual
Upon energization or availably operating the unit or remote controller, the buzzer will give out a beep.
(4)Sleep Function
Cooling mode、Dry mode: Basing on the set temperature of remote controller, after turning on the sleep function for a few hours, set
temperature will increase properly and automatically according to human body’s comfort.
Heating mode: Basing on the set temperature of remote controller, after turning on the sleep function for a few hours, set temperature
will decrease properly and automatically according to human body’s comfort.
(5)Turbo Function
This function can be set in cooling or heating mode to quickly cool or heat the room.
(6)X-FAN Function
① When the unit is operating at COOL or DRY mode( it is not available under AUTO, HEAT, FAN modes), the X-FAN function can be
turned on/off. When it is turned on,once pressing ON/OFF button to turn off the unit, indoor fan will continue operation at low speed
for 2 minutes. Within the 2 minutes, horizontal louver will keep its previous status while cold plasma and static dedusting will be forced
to be turned on and other loads will be turned off. Then the complete unit will be turned off; When X-FAN function is set to be off,once
pressing ON./OFF button, the complete unit will be turned on immediately.
② During X-FAN operation, press X-FAN button, the indoor fan, horizontal louver, cold plasma and static-dedusting will be turned off
immediately.
(7)Control of Indoor Fan
Indoor fan can be set by remote control within the range of Mute, Fan speed 1, Fan speed 2, Fan speed 3, Fan speed 4, Fan speed
5 and Turbo and Fan will operate at low, med. high or super high speed accordingly. And also, auto fan speed can be set. Under auto
fan speed mode, indoor fan will automatically select high, med., low or mute speed according to change of ambient temperature.
① Under Auto Heat mode or regular Heat mode, auto fan speed will be as follows:
When Tamb.<Tpreset-3°C, indoor fan will operate at high speed;
When Tpreset-3°C≤Tamb.<Tpreset+2°C indoor fan will operate at med. speed;
When Tpreset+2°C≤Tamb.<Tpreset+4°C, indoor fan will operate at low fan speed;
When Tamb≥Tpreset+4°C indoor fan will operate at mute.
Control Diagram of Auto Fan Speed under HEAT Mode
Tamb.
Tpreset +4ć
Tpreset +2ć
Tpreset -3ć
② Under FAN or COOL mode: if it is auto cooling mode or regular cooling mode, auto fan speed will be as follows:
When Tamb.≥Tpreset+3°C, indoor fan will operate at high speed;
When Tpreset<Tamb.<Tpreset+3°C indoor fan will operate at med. speed;
When Tpreset-2°C<Tamb.≤Tpreset, indoor fan will operate at low speed;
When Tamb.≤Tpreset-2°C indoor fan will operate at mute;
③ There is no auto fan speed under DRY mode
Note: Fan speed “High”, “Med.” and “Low” are respectively corresponding to “Fan speed 5”, “Fan speed 3” and “Fan speed 1”. There
is 210 seconds delay for fan speed switchover of auto fan.
Tamb.
Tpreset +3 ć
Tpreset
Tpreset -2 ć
(8)Vertical Swing
① Small Horizontal Louver
After energization, vertical swing motor will firstly have the horizontal louver rotate anticlockwise to position O to close air outlet. If
swing function has not been set after startup of the unit, horizontal louver will turn clockwise to position D1 in HEAT mode. If swing
function is set when starting up the unit, the horizontal louver will swing between O and D1.There are 7 swing status of horizontal
louver: Positions O, A1, B1, C1 and D1, swing between O and D1 and stop at any position between L and D (angles between O and
D1 are equiangular). Upon turning off the unit, the horizontal louver will close at position O. Swing function is available only when
(0 degree)
58 Technical Information
Downloaded from www.Manualslib.com manuals search engine
Service Manual
(0 degree)
(0 degree)
(0 degree)
(0 degree)
(9)Horizontal Swing
Upon energization, the vertical louver will be reset to the start position firstly and then stop in the middle position. When setting
horizontal swing, there are 7 status: Position ① , Position ② , Position ③ , Positon ④ , Position ⑤ , swing between ① and ⑤ and
stop at any position between ① and ⑤ . If setting horizontal swing during operation of the unit, the horizontal swing motor will drive
the louver to swing horizontally. When cancelling horizontal swing or it is not set when turning on the unit, the louver will stop in the
current.
(10)Display
① Operation and Mode Icons
Upon energization, the unit will display all icons within 3 seconds. Under standby state, LED lamp of standby is on. If the unit is turned
on by remote controller, LED lamp of operation is on; meanwhile, the mark of current running mode will be displayed. If the light button
is turned off, no mark will be displayed.
② Display of Nixie Tube on Indoor Unit
When energized & started for the first time, the indoor unit defaults to displaying current set temperature (16~30°C). When set
temperature display is set by remote controller, it will display set temperature; when room temperature display is set, it will display
room or outdoor temperature. After that, when operating the remote controller for other settings, the temperature display method
will keep original. When operating the remote controller during room temperature display, the set temperature will be displayed for 5
seconds firstly and then room temperature display returns. If there is malfunction, corresponding malfunction code will be displayed.
For example, if ambient temperature sensor has malfunction, “F1” will be displayed; if indoor pipe temperature has malfunction, “F2”
Technical Information 59
Downloaded from www.Manualslib.com manuals search engine
Service Manual
60 Technical Information
Downloaded from www.Manualslib.com manuals search engine
Service Manual
● Outdoor Unit
1. Compensation function of input parameters
According to the structure of wall-mounting unit, considering the comfortability for operation, indoor ambient temperature when the
compressor is at OFF status is higher than set temperature under heating mode.
2. Control of detecting the availability of parameters
For ensuring the safety and reliability of operation, please insert the outdoor discharge temperature sensor into the corresponding
temperature sensor bushing to make sure that the control system can detect system discharge temperature accurately. Otherwise, the
unit will stop operation and it displays malfunction of discharge temperature sensor (discharge temperature sensor hasn’t been
inserted
well), which can only be resumed by pressing ON/OFF button on remote controller. Basic functions:
3. Cooling mode
3.1 Working condition and process for cooling
3.1.1 If compressor is at OFF status, and Tpreset-(Tindoor amb.- Tindoor amb. compensation of cooling) ≤0°C, the unit operates in cooling mode;
3.1.2 During cooling operation, if 0°C ≤ Tpreset-(Tindoor amb.- Tindoor amb. compensation of cooling) <3°C, the unit still operates in cooling mode;
3.1.3 During cooling operation, if 3°C ≤ Tpreset-(Tindoor amb.- Tindoor amb. compensation of cooling) , the unit stops operation when reaching the
temperature point in cooling.
3.2 under the mode,the temperature setting range is 16~30°C.
4. Dry mode
4.1 Working conditioner and process for drying is same as that for cooling mode;
4.2 Temperature setting range is 16~30°C;
5. Fan mode
5.1 Compressor, outdoor fan and 4-way valve are all turned off;
5.2 Temperature setting range is 16~30°C.
6. Heating mode
6.1 Working conditioner and process of heating(Tindoor amb. is the actual temperature detected by indoor ambient temperature sensor;
△ Tindoor amb. compensation of heating is indoor ambient temperature compensation during heating operation).
6.1.1 If compressor is at OFF status, and Tindoor amb. - Tindoor amb. compensation of heating -Tpreset ≤-1°C, the unit operates in heating mode.
6.1.2 During heating operation, if 0°C≤ (Tindoor amb.- Tindoor amb. compensation of heating)-Tpreset <2°C, the unit still operates in heating mode.
6.1.3 During heating mode, if 2°C≤ (Tindoor amb. - Tindoor amb. compensation of heating)-Tpreset , the unit stops operation when reaching the temperature
point in heating.
6.2 Under this mode, the temperature setting range is 16~30°C.
7. Defrosting control heating mode
7.1 If it turns to defrosting time and it detected that the defrosting temperature is satisfied for 3mins successively, the unit turns into
defrosting process.
7.2 Defrosting-starting: compressor stops operation and restart it up after 90s delayed,
7.3 Defrosting-ending: Compressor stops operation and it starts up after 90s delayed.
7.4 When any one of below defrosting-ending conditions is satisfied, the unit will quit from defrosting operation:
7.4.1 Toutdoor tube≥Tquit temperature 1 for defrosting;
7.4.2 Defrosting operation time is reached Tmax.defrosting time.
8. Control of compressor
8.1 Frequecny of compressor intangibly controls the frequency according to the relation between ambient temperature and set
temperature, and the change speed of ambient temperature;
8.2 Under cooling, heating or drying mode, compressor will be started up after outdoor fan is started for 5s.
8.3 At the OFF status, stop operation because of protection and switchover to fan mode, the compressor stops operation immediately.
8.4 Under each mode: Once the compressor is started up, it can be stopped only after operation.
8.5 Under each mode, one the compressor is stopped, it can be restarted up only after 3min delayed
9. Control of outdoor fan
9.1 When turn off the unit by remote controller, stop operation because of protection or stop operation after reaching the temperature
point, outdoor can stop operation only after the compressor is stopped for 1min;
9.2 Under fan mode: outdoor fan stops operation.
9.3 defrosting-starting: enter into defrosting. Outdoor fan stops operation after compressor stops for 50s.
9.4 Defrosting-ending: quit defrosting. When the compressor stops operation, the outdoor fan operates.
10. Control of 4-way valve
10.1 4-way valve status under cooling, drying and fan modes: OFF;
10.2 When the unit turned on and operated in heating mode, the 4-way valve is energized immediately.
10.3 If turn off unit or switch to other mode in heating mode, the 4-way valve is de-energized after the compressor stops for 2min;
10.4 When the unit is turned off because of each protection, the 4-way valve is de-energized after 4 mins delayed.
10.5 Defrosting-starting: enter into defrosting. After the compressor stops for 50s, the 4-way valve will be de-energized.
10.6 Defrosting-ending: quit defrosting. After the compressor stops for 50s, the 4-way valve is energized.
11. Freeze protection
11.1 Under cooling or drying mode, After compressor is turned on in 6 min later, if Tinner tube≤Tlimit temperature of freeze protection,operation frequency
of compressor will stop rising;If Tinner tube≤Tdecrease frequency temperature of freeze protection, operation frequency of compressor may decrease;
11.2 Under cooling or drying mode, if it’s detected that Tinner tube≤Tstop operation temperature of freeze protection for 3min successively, the unit will stop
Technical Information 61
Downloaded from www.Manualslib.com manuals search engine
Service Manual
operation due to freeze protection. If Tinner tube≥Ttemperature of freeze protection and the compressor has stopped for 3min, the complete unit can
resume operation.
11.3 If the unit is stopped because of freeze protection for 6 times successively, it can’t resume operation automatically and the
malfunction will be displayed continuously, which can only be resumed by pressing ON/OFF button. During operation, if operation
time of compressor is over, the times of stop operation because of freeze protection will be cleared. If turn off the unit or switch to fan/
heating mode, malfunction and times of malfunction is eliminated immediately.
12. Overload protection
12.1 Overload protection under cooling or drying mode: If Toverload stop operation temp. in cooling≤Toutdoor tube, the unit stops operation because of
overload in cooling; if Toutdoor tube< Toverload limit-frequecny temp in cooling and the compressor has stopped for 3min, the complete unit can resume
operation.
12.2 Under cooling or drying mode, if Toverload limit-frequecny temp. in cooling ≤Toutdoor tube, the frequency of compressor may decrease;
12.3 Overload protection under heating mode: If Toverload stop operation temp. in heating≤Tindoor tube, the unit stops operation because of overload in
heating; if Tindoor tube<Toverload limit-frequecny temp. in heating and the compressor has stopped for 3min, the complete unit can resume operation.
12.4 Under heating mode, if Toverload limit-frequecny temp. in heating ≤Tindoor tube, operation frequency of compressor may decrease;
12.5 If the unit is stopped because of overload protection for 6 times successively, it can’t resume operation automatically and the
malfunction will be displayed continuously, which can only be resumed by pressing ON/OFF button. During operation, if operation time
of compressor is over, the times of stop operation because of overload protection will be cleared. If turn off the unit, fan or switch to fan/
heating mode, malfunction and times of malfunction is eliminated immediately.
13. Discharge temperature protection of compressor
13.1 If Tstop operation temperature for discharge ≤Tdischarge, the unit stops operation because of discharge protection; If Tdischarge<Tnormal speed decreasefrequency for
discharge and compressor has stopped for 3min, the complete unit can resume operation;
13.2 If Tnormal speed decrease-frequency for discharge≤Tdischarge, operation frequency of compressor may decrease;
13.3 If the unit is stopped because of discharge protection of compressor for 6 times successively, it can’t resume operation
automatically,which can only be resumed by pressing ON/OFF button. During operation, if operation time of compressor is over, the
times of stop operation because of discharge protection will be cleared. If turn off the unit, or switch to fan/heating mode, malfunction
and times of malfunction is eliminated immediately.
14. Current protection function
14.1 If IAC current≥Ilimit frequency current for current protection,operation frequency of compressor will stop rising;
If IAC current≥Idecrease frequency current for current protection,operation frequency of compressor may decrease;
If IAC current≥Istop operation current for current protection,the unit will stop operation because of overcurrent protection.
14.2 If the unit is stopped because of overcurrent for 6 times successively, it can’t resume operation automatically, which can only be
resumed by pressing ON/OFF button. During operation, if operation time of compressor is over, the times of stop operation because of
overcurrent protection will be cleared.
15. Voltage drop protection
During operation of compressor, if the voltage is decreasing quickly, the system may stop operation and voltage drop malfunction is
caused. 3min later, the system will be restarted up automatically.
16. Communication malfunction
When it hasn’t received the correct signal from indoor unit for 3min, the unit will stop operation because if communication malfunction;
If communication malfunction is eliminated and compressor has stopped for 3min, the complete unit can resume operation.
17. IPM module protection
After compressor is turned on, if the overcurrent happens for IPM module, or control voltage is too low because of abnormal causes,
IPM will detect module protection signal immediately. Once it detected the module protection signal, the unit will stop operation
because of module protection. If module protection is resumed and compressor has stopped for 3min, the complete unit will resume
operation.
If the unit is stopped because of module protection for 3 times successively, the unit can resume operation automatically unless press
ON/OFF button. If the operation time for compressor is over, the times of stop operation because of module protection will be cleared.
18. Overheat protection of module
18.1 If Tnormal speed frequency-decreasing temp. of module≤Tmodule, the operation frequency of compressor may decrease;
18.2 If Tstop operation temperature of module≤Tmodule, the syste will stop operation for protection. If Tmodule <Tfrequency-limiting temperature of module and compressor
has stopped for 3min, the complete unit will resume operation;
18.3 If the unit is stopped because of overheating of compressor module for 6 times successively, it can’t resume operation
automatically,which can only be resumed by pressing ON/OFF button. During operation, if operation time of compressor is over, the
times of stop operation because of compressor overheating protection will be cleared. If turn off the unit, or switch to fan mode, times of
malfunction is eliminated immediately.
19. Overload protection of compressor
19.1 If it detected that the overload switch for compressor is open for 3min successively, the complete unit will stop operation for
protection;
19.2 If overload protection is resumed and compressor has stopped for 3min, the complete unit can resume operation;
19.3 If the unit stops operation because of overload protection for compressor for 3times successively, it can’t resume operation
automatically, which can only be resumed by pressing ON/OFF button. After compressor has operated for 30min, overload protection
times for compressor will be eliminated.
62 Technical Information
Downloaded from www.Manualslib.com manuals search engine
Service Manual
10. Pipe pliers, pipe cutter 11. Pipe expander, pipe bender 12. Soldering appliance, refrigerant container
8. Installation
8.1 Installation Dimension Diagram
At least 15cm
Space to the wall
At least 15cm
At least 15cm
m
0c
Space to the floor
30
At least 250cm
st
lea on
At u cti
str
ob
he
t ot
e
ac
Sp
Space to the obstruction
he
t ot
e ion
At least 50cm
ac t
Sp truc
b s st
o
t lea
A cm
30
Space to th
e wall
n
tio At least 50cm
t r uc 00
cm
b s 2
o as
t Space to the ob
he struction
t ot A t le
e
ac
Sp
Installation procedures
Start installation
Finish installation
Note: this flow is only for reference; please find the more detailed installation steps in this section.
(4) Properly connect the live wire, neutral wire and grounding
8.3 Selection of Installation Location wire of power socket.
(5) Be sure to cut off the power supply before proceeding any
1. Basic Requirement:
work related to electricity and safety.
Installing the unit in the following places may cause
(6) Do not put through the power before finishing installation.
malfunction. If it is unavoidable, please consult the local dealer:
(7) For appliances with type Y attachment,the instructions
(1) The place with strong heat sources, vapors, flammable or
shall contain the substance of thefollowing.If the supply cord is
explosive gas, or volatile objects spread in the air.
damaged,it must be replaced by the manufacturer,its service
(2) The place with high-frequency devices (such as welding
agent or similarly qualified persons in order to avoid a hazard.
machine, medical equipment).
(8) The temperature of refrigerant circuit will be high, please
(3) The place near coast area. 2. Grounding Requirement:
keep the interconnection cable away from the copper tube.
(4) The place with oil or fumes in the air. (1) The air conditioner is first class electric appliance. It must
(5) The place with sulfureted gas. be properly grounding with specialized grounding device
(6) Other places with special circumstances. by a professional. Please make sure it is always grounded
2. Indoor Unit: effectively, otherwise it may cause electric shock.
(1) There should be no obstruction near air inlet and air outlet. (2) The yellow-green wire in air conditioner is grounding wire,
(2) Select a location where the condensation water can be which cant be used for other purposes.
dispersed easily and wont affect other people. (3) The grounding resistance should comply with national
(3) Select a location which is convenient to connect the electric safety regulations.
outdoor unit and near the power socket. (4) The appliance must be positioned so that the plug is
(4) Select a location which is out of reach for children. accessible.
(5) The location should be able to withstand the weight of (5) An all-pole disconnection switch having a contact separation
indoor unit and wont increase noise and vibration. of at least 3mm in all poles should be connected in fixed wiring.
(6) The appliance must be installed 2.5m above floor. (6) Including an air switch with suitable capacity, please note
(7) Dont install the indoor unit right above the electric the following table. Air switch should be included magnet
appliance. buckle and heating buckle function, it can protect the circuit-
(8) The appliance shall not be installed in the laundry. short and overload. (Caution: please do not use the fuse only
for protect the circuit)
3. Outdoor Unit:
(1) Select a location where the noise and outflow air emitted by
the outdoor unit will not affect neighborhood. 8.5 Installation of Indoor Unit
(2) The location should be well ventilated and dry, in which 1. Choosing Installation Iocation
the outdoor unit wont be exposed directly to sunlight or strong Recommend the installation location to the client and then
wind. confirm it with the client.
(3) The location should be able to withstand the weight of 2. Install Wall-mounting Frame
outdoor unit. (1) Hang the wall-mounting frame on the wall; adjust it in
(4) Make sure that the installation follows the requirement of horizontal position with the level meter and then point out the
installation dimension diagram. screw fixing holes on the wall.
(5) Select a location which is out of reach for children and far (2) Drill the screw fixing holes on the wall with impact drill (the
away from animals or plants.If it is unavoidable, please add specification of drill head should be the same as the plastic
fence for safety purpose. expansion particle) and then fill the plastic expansion particles
in the holes.
(3) Fix the wall-mounting frame on the wall with tapping screws 5. Connect the Pipe of Indoor Unit
(ST4.2X25TA) and then check if the frame is firmly installed by (1) Aim the pipe joint at the corresponding bellmouth.(As show
pulling the frame. If the plastic expansion particle is loose, in Fig.5)
please drill another fixing hole nearby. (2) Pretightening the union nut with hand.
3. Install Wall-mounting Frame (3) Adjust the torque force by referring to the following sheet.
(1) Choose the position of piping hole according to the direction Place the open-end wrench on the pipe joint and place the
of outlet pipe. The position of piping hole should be a little torque wrench on the union nut. Tighten the union nut with
lower than the wall-mounted frame.(As show in Fig.1) torque wrench.(As show in Fig.6)
(4) Wrap the indoor pipe and joint of connection pipe with
Wall Wall insulating pipe, and then wrap it with tape.(As show in Fig.7)
Mark on the middle of it Gradienter
Space Space
to the to the
wall wall
Open-end
above above wrench
Union nut
Pipe joint Union nut Pipe
Left Right Torque wrench Pipe
Φ55mm Φ55mm
(Rear piping hole) (Rear piping hole)
Fig.5 Indoor pipe Fig.6
Fig.1
Note:
Left Rear left (1) Add insulating pipe in the indoor drain hose in order to
Rear right
prevent condensation.
Fig.3 Right (2) The plastic expansion particles are not provided.
(As show in Fig.10)
Cut off
Insulating pipe
the hole Fig.10
Fig.4
Cable-cross Liquid
hole Fig.14 Band pipe
Drain hose
8.6 Installation of Outdoor Unit Refer to the following table for wrench moment of force:
1. Fix the Support of Outdoor Unit(select it according to the Hex nut diameter(mm) Tightening torque(N.m)
actual installation situation) Φ6 15~20
(1) Select installation location according to the house structure. Φ9.52 30~40
(2) Fix the support of outdoor unit on the selected location with Φ12 45~55
expansion screws. Φ16 60~65
Φ19 70~75
Note:
(1) Take sufficient protective measures when installing the 5. Connect Outdoor Electric Wire
outdoor unit. (1) Remove the wire clip; connect the power connection wire
(2) Make sure the support can withstand at least four times the and power cord to the wiring terminal according to the color; fix
unit weight. them with screws.(As show in Fig.23)
(3) The outdoor unit should be installed at least 3cm above the
floor in order to install drain joint.(As show in Fig.18)
N(1) 2 3
(4) For the unit with cooling capacity of 2300W~5000W, 6
N L
expansion screws are needed; for the unit with cooling capacity
of 6000W~8000W, 8 expansion screws are needed; for the
yellow-
unit with cooling capacity of 10000W~16000W, 10 expansion blue black brown
yellow- blue brown green
green
screws are needed. N L
POWER
Indoor unit connection
Fig.25
Liquid pipe Pipe joint U-shaped curve
Fig.24
Liquid gas pipe
valve Drain hose
Note:
Union nut
gas valve
(1) The through-wall height of drain hose shouldnt be higher
Fig.22 than the outlet pipe hole of indoor unit.(As show in Fig.25)
(2) Slant the drain hose slightly downwards. The drain hose
(3) Pretightening the union nut with hand.
cant be curved, raised and fluctuant, etc.(As show in Fig.26)
(4) Tighten the union nut with torque wrench .
2. Leakage Detection
(1) With leakage detector:
Check if there is leakage with leakage detector.
(2) With soap water:
If leakage detector is not available, please use soap water for
leakage detection. Apply soap water at the suspected position
and keep the soap water for more than 3min. If there are air
bubbles coming out of this position, theres a leakage.
9. Maintenance
9.1 Troubleshooting for Normal Malfunction
The remote
First, press the manual switch
controller does
button AUTO,if there is no
not receive
Remote controller malfunction response,check based on the
signals (after it
above methods. If it runs nor-
is powered, the
mally after pressing the button,
buzzer will Receiver loose or poor connection check again whether the instal-
sound, unless it
lation position and the connec-
has
tion wire of the reception head
malfunction) Receiver is broken
is correct. If it is correct,then re-
place the receiver or the remote
controller.
Heat insulation for the connection Make sure that heat insulation for the thick and thin pipes
pipes of the indoor unit and the out-
is good. Heat insulation must also be provided for the
door unit is bad.
joint andthe exposed part of the copper pipe .
The installation position of the Good ventilation must be provided for the
outdoor unit is not appropriate. installation position of the outdoor unit.
In the cooling and The outdoor fan motor is damaged. Replace the fan motor
heating mode,
the compressor Wrong connection Make the correct connection based on the
runs, but the out- circuit drawing
door fan does not
run. The outdoor fan capacitor is damaged. Replace the fan capacitor
Abnormal sound
Touch of pipeline of outdoor unit Separate the touching pipeline.
and shake
9. Maintenance
9.1 Precautions before Maintenance
There are high-capacity electrolytic capacitors on the outdoor mainboard. Thus, even the power is cut off, there is high voltage inside
the capacitors and it needs more than 20min to reduce the voltage to safety value. Touching the electrolytic capacitor within 20min after
cutting the power will cause electric shock. If maintenance is needed, follow the steps below to discharge electricity of electrolytic ca-
pacitor after power off.
(1) Open the top cover of outdoor unit and then remove the cover of electric box.
outdoor mainboard
(2) As shown in the fig below, connect the plug of discharge resistance (about 100ohm, 20W) (if there is no discharge resistance, you
can use the plug of soldering iron) to point A and B of electrolytic capacitor. There will be sparks when touching them. Press them forc-
ibly for 30s to discharge electricity of electrolytic capacitor.
discharge resistance or
plug of soldering iron
B
outdoor mainboard A
B
A
(3) After finish discharging electricity, measure the voltage between point A and B with universal meter to make sure if electricity dis-
charging is completed, in order to prevent electric shock. If the voltage between the two points is below 20V, you can perform mainte-
nance safely.
Start
Is the wiring
terminal between temperature
sensor and the controller loosened or yes
poor ly contacted?
no
Malfunction is
no eliminated.
no
no Malfunction is yes
eliminated.
Is the te mperature
sensor normal according to the
Resistance Table? no
Replace it with a
temperature sensor
of the same model
yes
yes
no Malfunction is
removed.
End
Start
Turn unit on
Yes to check whether the
No malfunction is
eliminated.
Turn unit on
No No to check whether the Yes
malfunction is
eliminated.
Connect power and restart the unit. It's the malfunction of main board.
Test whether the voltage between terminal 1 and terminal 2 No Replace a new main board that is
of motor interface is within 280~310VDC. of the same model.
Yes
Yes
Then check whether the voltage It's the malfunction of main board.
between terminal 2 and terminal 3 No Replace a new main board that is
of the same model.
of the motor interface is 15VDC.
Yes
Then check whether there is voltage It's the malfunction of main board.
between terminal 2 and terminal 4 No Replace a new main board that is
of the motor interface. of the same model.
Yes
Troubleshooting for C5
malfunction
yes
no Is malfunction
eliminated
Is
the jumper cap inserted no
correctly and
tightly ?
Insert the
jumper cap
tightly
yes
no Is malfunction yes
eliminated
yes
Is malfunction yes
eliminated
no
End
4. Communication malfunction E6
Start
No
Yes
Is there incorrect
match between the mainboard Match them
Malfunction is
and the display panel or between No according to Yes
eliminated
the indoor and outdoor the requirement
mainboards?
Yes No
No No
Replace indoor
mainboard
Yes
Yes
End
Start
Yes
Is malfunction
eliminated
The end
●Outdoor unit:
1.Key detection point
Test1
B
E
L
A
F G
D
J
K
I
Test11
S
M
Test12
T
N
●Outdoor unit:
(1) Capacitor charge fault (Fault with outdoor unit) (AP1 below refers to the outdoor control panel)
Main Check Points:
●Use AC voltmeter to check if the voltage between terminal L and N on the wiring board is within 210VAC~240VAC.
●Is the reactor (L) correctly connected? Is the connection loose or fallen? Is the reactor (L) damaged?
Fault diagnosis process:
Turn on the unit
and wait 1 minute
Use DC voltmeter
to measure the
voltage on the two
ends of electrolytic
capacitor
Check the
connection of reactor
(L in the Electrical
Wiring Diagram)
End
(2) IPM Protection, Out-of-step Fault, Compressor Phase Overcurrent (AP1 below refers to the outdoor control
panel)
Main check points:
●Is the connection between control panel AP1 and compressor COMP secure? Loose? Is the connection in correct order?
●Is the voltage input of the machine within normal range? (Use AC voltmeter to measure the voltage between terminal L and N on the
wiring board XT)
●Is the compressor coil resistance normal? Is the insulation of compressor coil against the copper tube in good condition?
●Is the working load of the machine too high? Is the radiation good?
●Is the charge volume of refrigerant correct?
Fault diagnosis process:
Energize and
switch on
Use ohmmeter to
measure the resistance
between the three If the Replace the
terminals on compressor resistance is compressor
COMP, and compare the normal? N
measurements with the COMP
compressor resistance on
Service Manual.
N
Use ohmmeter to
measure the resistance Resistance higher
between the two than 500MΩ?
terminals of compressor
COMP and copper tube.
Y
Replace the
control panel
AP1
END
(3) High temperature and overload protection diagnosis (AP1 hereinafter refers to the control board of the
outdoor unit)
Mainly detect:
●Is outdoor ambient temperature in normal range?
●Are the outdoor and indoor fans operating normally?
●Is the heat dissipation environment inside and outside the unit good?
Fault diagnosis process:
Replace the
outdoor fan
End
(4) Start-up failure (following AP1 for outdoor unit control board)
Mainly detect:
●Whether the compressor wiring is connected correct?
●Is compressor broken?
●Is time for compressor stopping enough?
Fault diagnosis process:
Replace the
compressor
End
(5) Out of step diagnosis for the compressor (AP1 hereinafter refers to the control board of the outdoor unit)
Mainly detect:
●Is the system pressure too high?
●Is the input voltage too low?
Fault diagnosis process:
Is stop time of the Check if the fan terminal Replace the fan
Is the outdoor fan working
compressor longer than OFAN is connected correctly capacitor C1
normally?
3 minutes?
Replace the
outdoor fan
Is the outdoor unit blocked Remove foreign objects
by foreign objects?
Are the wires for the compressor connected
correctly? Is connection sequence right?
Is the connection made in clockwise
direction?
Replace the
control panel AP1
Connect the
wires correctly
Replace the
compressor
Replace the
compressor
End
End
(6) Overload and air exhaust malfunction diagnosis (following AP1 for outdoor unit control board)
Mainly detect:
●Is the PMV connected well or not? Is PMV damaged?
●Is refrigerant leaked?
Fault diagnosis process:
20 minutes after the
complete unit is
powered off
Replace the
control panel
AP1
End
(7) Power factor correct or (PFC) fault (a fault of outdoor unit) (AP1 hereinafter refers to the control board of the
outdoor unit)
Mainly detect:
●Check if the reactor (L) of the outdoor unit and the PFC capacitor are broken
Fault diagnosis process:
Start
The capacitor is
Is the resistance around zero? Y short circuited and Restart the unit If the fault is eliminated? Y
the capacitor
should be repla-
ced
N
End
(8) Communication malfunction: (following AP1 for outdoor unit control board)
Mainly detect:
●Is there any damage for the indoor unit mainboard communication circuit? Is communication circuit damaged?
●Detect the indoor and outdoor units connection wire and indoor and outdoor units inside wiring is connect well or not, if is there any
damage?
Fault diagnosis process:
Start
N
If the fault is eliminated?
N
Replace the main board
of the indoor unit
Y
Y End
Appendix:
Appendix 1: Reference Sheet of Celsius and Fahrenheit
Conversion formula for Fahrenheit degree and Celsius degree: Tf=Tcx1.8+32
Set temperature
Fahrenheit Fahrenheit Fahrenheit
display Fahrenheit display Fahrenheit display Fahrenheit
Celsius(℃) Celsius(℃) Celsius(℃)
temperature (℉) temperature (℉) temperature (℉)
(℉) (℉) (℉)
61 60.8 16 69/70 69.8 21 78/79 78.8 26
62/63 62.6 17 71/72 71.6 22 80/81 80.6 27
64/65 64.4 18 73/74 73.4 23 82/83 82.4 28
66/67 66.2 19 75/76 75.2 24 84/85 84.2 29
68 68 20 77 77 25 86 86 30
Ambient temperature
Fahrenheit Fahrenheit Fahrenheit
display Fahrenheit display Fahrenheit display Fahrenheit
Celsius(℃) Celsius(℃) Celsius(℃)
temperature (℉) temperature (℉) temperature (℉)
(℉) (℉) (℉)
32/33 32 0 55/56 55.4 13 79/80 78.8 26
34/35 33.8 1 57/58 57.2 14 81 80.6 27
36 35.6 2 59/60 59 15 82/83 82.4 28
37/38 37.4 3 61/62 60.8 16 84/85 84.2 29
39/40 39.2 4 63 62.6 17 86/87 86 30
41/42 41 5 64/65 64.4 18 88/89 87.8 31
43/44 42.8 6 66/67 66.2 19 90 89.6 32
45 44.6 7 68/69 68 20 91/92 91.4 33
46/47 46.4 8 70/71 69.8 21 93/94 93.2 34
48/49 48.2 9 72 71.6 22 95/96 95 35
50/51 50 10 73/74 73.4 23 97/98 96.8 36
52/53 51.8 11 75/76 75.2 24 99 98.6 37
54 53.6 12 77/78 77 25
Improper pipe expanding is the main cause of refrigerant leakage.Please Pipe cutter
expand the pipe according to the following steps:
Leaning Uneven Burr
A:Cut the pip
● Confirm the pipe length according to the distance of indoor unit and outdoor unit.
● Cut the required pipe with pipe cutter.
● Remove the burrs with shaper and prevent the burrs from getting into the pipe. Shaper
Downwards
C:Put on suitable insulating pipe
Smooth surface
F:Inspection
● Check the quality of expanding port. If there is any blemish, expand the
Improper expanding
port again according to the steps above.
Resistance Table of Ambient Temperature Sensor for Indoor and Outdoor Units(15K)