Industrial Instrumentation Lab
Industrial Instrumentation Lab
Industrial Instrumentation Lab
LABORATORY
Session:SP’20
DEPARTMENT
OF
ELECTRONICS AND COMMUNICATION ENGINEERING
LIST OF EXPERIMENTS:
COMPULSORY EXPERIMENTS:
11. Simulation of the PID Controller Scheme using LabVIEW for Step input
and observation of Controllers output response for different controller
constants setting
13. Measurement of the Phase and Frequency using Virtual CRO and Delay
Network (Implementation of Lissajous pattern)
15. Programming of Ladder Diagram using ABB PLC with Stepper Motor
Control Simulation Modules
18. Development of panel for Speed Measurement and Test on Real Time
19. Development of front panel for Pressure Measurement and Test on Real
Time
INDUSTRIAL INSTRUMENTATION
LABORATORY
ON
APPARATUS:
1. Power Supply
2. Signal Condition and Amplifying
3. Analog to digital converter
THEORY:
PROCEDURE:
1. Connect the Load cell to the instrument.
2. Connect the power supply card to 230v 50 Hz power.
3. Fill the source tank with approximately 25 liters (2 bucket) of water.
4. Close the drain valve connected at the bottom of the Accralic Tank.
5. Switch on the instrument and allow the instrument in ON position 10 minutes for
initial warm-up.
6. Switch on the MOTOR ON switch the pump start pumping the water. Stop the
MOTOR when the water level reaches 5 cm. (Minimum Level)
7. Adjust the zero pot on the instrument panel till the display reads “000”.
8. Switch on the MOTOR and switch OFF as soon as the water level reaches 50 cm.
9. Adjust the SPAN pot on the instrument panel so that the display reads 50 cm.
10. Release the water, till the minimum level 5 cm is reached. The instrument should
read “00”. If the display does not come to zero, repeat the procedure 7 to 10 or
two to three times.
11. Drain out the water till 5 cm. The display will be reading “000” switch on the
motor and take the readings in steps of 5 cm.
12. Tabulate the readings in tabular column the actual level read by scale and the
instrument reading.
13. Plot the graph Actual reading v/s instrument reading. Calculation can be made for
linearity, hysteresis and accuracy of the instrument.
OBSERVATIONS:
RESULT:
PRECAUTIONS:
DEPARTMENT
OF
ELECTRONICS AND COMMUNICATION ENGINEERING
INDUSTRIAL INSTRUMENTATION
LABORATORY
ON
APPARATUS:
1. Power Supply
2. Oscillator
3. Signal Conditioner
4. Mixer and
5. Counter
THEORY:
Principle and working of
i) Magnetic Pickup : The voltage is induced in the coil around to a magnetic subjected to
change in magnetic field, this is principle of electromagnetic induction. The arrangement
is shown in fig. As shaft rotates, the teeth pass in front of pick up and produce a change
in field resistance of magnetic circuit. The density of a magnetic field increases and
decreases as each tooth approaches and leaves away from the end of the bar magnet per
second. Let T be no. of teeth on the rotor, N be be the revolutions per second and P be the
no. of pulse per sec. Then,
Speed N = Pulses per sec./ No. of teeth = P/Tx 60 rpm
ii) Photoelectric pickup : The photoelectric pick up tachometer utilize a rotating shaft to
the intercept a beam of light flow on a photoelectric or photo-conductive cell. The shaft
has an intermittent reflecting (white) and non reflecting (blade) surface. When a beam of
light the reflecting surface on a rotating shaft, light pulses are obtained and reflected light
is focused on the photoelectric cell. The frequency of the light pulses is proportional to
shaft speed and so will be frequency of electrical o/p pulses from photoelectric. Another
similar method consist in mounting an opaque disc on shaft. The rotating component the
disc has a no. of evenly spaced peripheral. Holes. A light source on the side of disc and
there is light sensor on opaque portion of disc between the lights source & the light
sensor, no light falls on sensor and consequently on o/p results. But a pulse of voltage is
produced every time a hole appear between the two is light illuminates the sensor. The
frequency of pulse generations is determined by no. of holes in disc and its speed of
rotations. Since no of holes is fixed, pulse of repetitions, frequency of transducers o/p is
proportional to angular velocity of moving member.
PROCEDURE:
Before Switching ON the instrument ensure that the connections are made
properly:
1. Switch ON the instrument by pushing down the toggle switch provided at the rear
side of the box, LED display glows to indicate the instrument ON.
2. Allow the instrument for 10 minutes in ON position for initial warm-up.
3. Select the sensor with the help of toggle switch.
4. Switch ON the electronic regulator. The fan rotates which will rotate the tone
wheels. The display will start indicating exact RPM of the motor.
5. Reading can be tabulated for both the sensors. Comparison can be made between
two sensors.
OBSERVATIONS:
A B C D
Sl.No. Actual Speed of Magnetic Pick- ERROR
Motor Photo Up B-C
reflective (RPM) (RPM)
RESULT:
PRECAUTIONS:
1. Always start the motor with help of zero speed., operate dimmerstat slowly.
2. Connect motor to earthing wire.
3. When experiment is over disconnect the photoelectric and magnetic pick up.
DEPARTMENT
OF
ELECTRONICS AND COMMUNICATION ENGINEERING
INDUSTRIAL INSTRUMENTATION
LABORATORY
ON
APPARATUS:
1. Power Supply
2. Rotameter
3. Orifice
4. Pump
5. Manometer
THEORY:
PROCEDURE:
1. Connect the power chord to 230V supply.
2. Fill the source tank with water till the foot valve of the pump immersed in the
water (approx. 10Lts).
3. Switch on the motor using power ON switch. The motor starts pumping the water.
Rotate the control valve till float of the Rota meter reads zero.
4. Release the valve slowly so that the Rota meter float reads 25 LPM. Measure the
difference in monometer.
5. Note down the monometer reading in steps & 10 to 25 LPM increase in flow.
Tabular the reading in the given column.
FLOW CALCULATION
To calculate the rate using the orifice meter we have the formula
Q=A x CD x 3600 x 1000 x √(2 x g x H)/1000 LHP
Where, Q=Rate of flow in LPH
A=Area of orifice hole =(л x D2)/4
Where D is Diameter of the orifice in Mts.
A=л/4 x (0.0055)2 = 2.3758 x 10-5 m2
CD = Orifice Coefficient =0.7
g= Gravitational Constant =9.91
H= h x [Em/Ew-1]
Where, Em=Density of mercury = 13600kg/m2
Ew= Density of water in kg/m2=1000kg/m2
H=Level difference in manometer in mm.
H=(h/1000) x (13600/1000-1)
H=(h/1000) x 12.6
Where h in mm.
We multiply by 3600 to convert from minutes to Hrs and multiply by 1000 to convert
from m3/hrs to liters.
Hence the equation can be simplified by calculating
Q=2.3758 x 105 x 0.7 x 3600 x 1000 x (√2 x 9.81 x h x 12.6 x 1000) LPH
OBSERVATIONS:
RESULT:
PRECAUTIONS:
DEPARTMENT
OF
ELECTRONICS AND COMMUNICATION ENGINEERING
INDUSTRIAL INSTRUMENTATION
LABORATORY
ON
APPARATUS:
Pressure Gauge
Dead Weights
THEORY:
PROCEDURE:
1. Fill the Oil tank with sufficient Oil.
2. Release the AIR RELEASE VALVE provided at the bottom till the oil starts
dripping continuously about 10 to 12 drops and tighter the release valve.
3. Release the control valve and pump the oil so that the oil circulates through the
tubes. Pump for a while about a minute so that all the tubes will be filled with oil
and any air bubble inside the tube will be removed.
4. Now close the Control Valve, and pump the oil the plunger starts floating. Pump
till the line on the plunger is visible. Rotate the plunger gently. The pressure is
built inside the chamber proportion to the weight on the plunger. The Test Gauge
fixed will starts showing the pressure.
5. Add 1 Kg dead weight on the plunger and pump once again till the mark on the
plunger is visible. The pressure inside the chamber increases by 1 Kg/cm2.
6. Add the weights on the plunger and pump till the line on the plunger is clearly
visible.
7. The bourdon pressure gauge will read the pressure corresponding to the dead
weights on the plunger. Note down the readings on the pressure gauge and
tabulate the readings with the corresponding readings to the dead weight. Plot the
graphs for actual pressure (dead weights v/s pressure gauge reading. Calculate
the accuracy, linearity and hysteresis of the pressure gauge.
8. Release the control valve slowly and remove the dead weight from the plunger.
NOTE: -Rotate the plunger along with the weights while taking the
readings.
- Maintain sufficient quantity of oil in the oil tank.
- Do not pump when the AIR RELEASE VALVE is loosened.
OBSERVATION:
RESULT:
DEPARTMENT
OF
ELECTRONICS AND COMMUNICATION ENGINEERING
INDUSTRIAL INSTRUMENTATION
LABORATORY
ON
PLC TRAINER
To select different options for input and output and functional blocks use F2
to F9 icons. Use I?I icon to have a complimentary input.
3. Use the inputs and outputs of the PLC from the Input Panel and Output
Panel.
SEQUENCE:
1. Press the BELL ON button (SENSE), the buffer starts blowing.
There are three rooms, where the person enters ROOM –1 stays in
for a will on work, then enters ROOM –2 finishes work and enter
ROOM –3 finishes works and returns. Assume sensors are provided
to sense the person entry to the rooms.
SEQUENCE:
1. Switch ON S-1 (SENSE) the person is in ROOM –1,
ROOM –1 Light glows
2. Switch ON S-2 (SENSE) the person enters ROOM –2,
ROOM –1 Light switches off and ROOM –2 light glows.
3. Switch ON S-3 (SENSE) the person enters ROOM –3,
ROOM –2 Light switches off and ROOM –3 light glows.
4. Switch OFF S-3 (SENSE) the person leaves ROOM –3 and enters
ROOM -2,
ROOM –3 Light switches off and ROOM –2 light glows.
5. Switch OFF S-2 (SENSE) the person leaving ROOM –2 and enters
ROOM –1,
ROOM –2 Light switches off and ROOM –1 light glows.
Switch OFF S-1 (SENSE) the person leaving ROOM –1.
2. U1 –PLC1 –3-4
SEQUENCE:
1. PRESS the MOTOR ON button.
LED glows indicating the Motor in running.
2. PRESS the MOTOR OFF button.
LED Switches off indicating the Motor is off.
(b) SILO CONTROL SIMULATION:
SEQUENCE:
1. Press Cycle Start button.
Run LED glows to indicate the conveyer is moving.
2. Switch ON SENS Bottle position. Switch Fill LED glows for a will to
indicate the bottle is filling and then FULL LED glows to indicate the
bottle is full.
3. U1 – PLC1 –5
SEQUENCE:
1. Press COUNT button.
LED 3 showing ZERO will increase in steps of 1 till NINE.
2. Press SHIFT LEFT button
LED 2 starts glowing the same value LED 3 is glowing the and
LED 1 will glow by pressing again.
3. Press SHIFT RIGHT button.
LED 2 Starts glowing and LED 1 will glow by pressing again.
4. U1 – PLC -6
Three motors has to run in sequence say the motors are connected to three
Conveyer where the Box moves from one conveyer to another in sequence.
Three LED’s are connected to indicate the status of Motor. Loading of Box
on to the conveyer is sensed by the sensors provided an toggle switch.
SEQUENCE:
1. Press CYCLE START button.
Say the box in loading on to the conveyer.
2. Switch ON “SENS BOX CONVEYER –1”
MOTOR 1 LED glows to indicate the conveyer –1 is moving.
3. Switch ON “SENS BOX CONVEYER –2”
MOTOR –2 LED glows to indicate the Conveyer –2 is moving and
the Conveyer –1 steps after leading BOX to Conveyer –2.
4. Switch ON “SENS BOX CONVEYER –3”
MOTOR -3 LED glows to indicate the Box is loaded from
conveyer 2 to conveyer 3 and conveyer 3 is moving, conveyer 2
stops.
The above sequences continue at constant interval till the “CYCLE STOP” button
is pressed.
5. U1 – PLC1 –7 -8
SEQUENCE:
1. Press MOTOR ON button.
MAIN RELAY LED glows to indicate the power to the Starter
along with the STAR RELAY LED will be on for a will for initial
motor starting and then DELTA RELAY LED Switches ON
Continuously to indicate the Motor is running in Delta mode.
2. Press MOTOR OFF button.
The DELTA RELAY LED Switches off indicating the Motor is
Switched OFF.
6. U1 – PLC1 –9
This module is simulated to control Water level in both overhead tank and Sump.
Switching of Water pump depends on Water levels in both the overhead tank and sump.
To sense the water level and to switch on the pump, toggle Switches are provided.
SEQUENCE:
1. Switch ON ‘SUMP SENS LO’ Switch.
SUMP LEVEL LOW LED glows to indicate the water level is low in the
sump.
2. Switch ON ‘TANK SENS LO’ Switch.
TANK LEVEL LOW LED glows to indicate the water level is low in the
tank.
3. Switch ON ‘PUMP ON’ Switch.
LED will not glow indicating the pump is not ON because the water level in
the sump is low.
4. Switch ON ‘SUMP SENS HI’ Switch.
The SUMP LEVEL HI LED will glow indicating the sump is filled with water
and simultaneously PUMP ON LED will also glow indicating the pump is
ON.
5. Switch ON the ‘TANK SENS HI’ Switch.
The TANK LEVEL HI LED will glow indicating the TANK in filled and
Simultaneously the PUMP ON LED Switches OFF indicating the pump is
OFF.
7. U1 – PLC1 –10
This SAP Module is a simulation of Automatic bottle filling plant. The bottle
moves on Conveyer 1, 2, and 3 during the bottle get filled and cap in screwed to it and
then unloaded.
SEQUENCE:
1. Press CYCLE START button.
‘CONVEYER 1 RN’ LED starts glowing to indicate the bottle in moving on
the conveyer.
2. Switch ON, ‘SENSE BOTTLE FILL’ switch
‘CONVEYER 1 RN’ LED stitches of indicating the conveyer stops moving
and the ‘BOTTLE FILL’ LED glows indicating the bottle is filling then
switches off BOTTLE FULL LED glows along with CONVEYER 2 RUN
LED And switches off as the bottle moves to the CONVEYER 2.
3. Switch ON ‘SENSE BOTTLE SCREEN’, and switch OFF ‘SENSE BOTTLE
FILL’.
SCREW CAP LED switches ON for few seconds indicating the cap is fitted to
the bottle and CONVEYER RUN LED glows to indicating the bottle is
moving.
4. Switch OFF ‘SENSE BOTTLE UNLOAD’ switch.
BOTTLE UNLOAD LED glows for few seconds indicating the bottle is
unloaded and the cycle stops.
8. UI – PLC1 – 11-12
9. UI – PLC1- 13
SEQUENCE:
1. Press SELECT button.
CAR –1 PARK LED stars blinking indicating the parking slot is selected.
2. Press CAR PARK button.
CAR –1 PARK LED stops blinking indicating the car is parked.
3. Press SELECT button twice.
CAR –1 PARK LED starts blinking and then CAR –2 PARK button starts
blinking.
4. Press CAR PARK button.
CAR –2 PARK LED stops blinking indicating the car is parked, in the same
way car can be parked for all the 6 parking slots. ALL CAR PARK LED will
be glowing indicating the cars are parked in all the slots, NO SPACE LED
starts glowing indicating there is no space to park another car.
5. Press SELECT button.
CAR –1 PARK LED stars blinking indicating the parking slot is selected.
6. Press CAR EXIT button
CAR –1 PARK LED switches off indicating the car is exited and the parking
slot is vacant. In the same way all the parking slots can be selected and cars
can be exited.
Now, assume all the parking slots are filled.
7. Press SELECT button.
CAR –1 PARK LED starts blinking indicating the parking slot is selected.
8. Press CAR PARK button.
CAR –1 PARK LED along with NO SPACE LED stats blinking indicating the
car is excited.
SEQUENCE:
11. UI – PLC1 - 15
ELEVATOR SIMULATION
This SAP module is a simulation of elevator for first, second and third floor. LED
shows the movement of the lift up and down. The lift reaching the floors is sensed
by toggle switches.
SEQUENCE:
12. UI – PLC1 – 16
SEQUENCE:
13. UI – PLC1 – 17
SEQUENCE:
14. UI - PLC1 – 18
SEQUENCE:
Input 1=0
Input 2=1 then output is 1 (Q)
Input 1=1
Input 2=1 then output is 0 ( )
4. In the same way logic can be tested for OR, AND, EX-OR also.
5. By switching the toggle switch to NOT position:
NOT – INU, NOT – OR, NOT – AND, NOT EX-OR status can also be
tested.
NOTE: Simulation can also be made for three inputs. This can be taken as an
assignment for students to program.
14. UI PLC1 – 19
SEQUENCE:
15. UI – PLC1 - 20
SEQUENCE:
INDUSTRIAL INSTRUMENTATION
LABORATORY
ON
APPARATUS:
1. Shaker
2. Control Unit
i) Power Oscillator
ii) Vibration Meter
3. Accelerometer
4. Threaded steel studs M5.
THEORY:
PROCEDURE:
1. Connect the sensor to the instrument through the BNC socket provided on the rear
mentioned SENSOR.
2. Connect the Vibration generator to the instrument through the cable provided at
the rear panel of the instrument marked EXCITER.
3. Connect the instrument to the 230 V 50 Hz. Supply through cable provided at the
rear panel.
4. Keep the FREQ. Pot and the VOLT pot in the minimum position.
5. Switch on the instrument, the display glows to indicate the power is on.
6. Turn the VOLT pot to the max position.
7. Now turn the FREQ pot in steps of 100 Hz. And note down the readings of
Acceleration, Velocity and Displacement by selecting the MODE through selector
switch.
8. Tabulate the readings in the tabular column. Experiment can be repeated for
different voltage levels settable through VOLT knob provided.
OBSERVATION:
RESULT:
PRECAUTIONS:
Acceleration
Velocity
Displacement
0,0 frequency
DEPARTMENT
OF
ELECTRONICS AND COMMUNICATION ENGINEERING
INDUSTRIAL INSTRUMENTATION
LABORATORY
ON
APPARATUS:
1. Compressor
2. Single Acting cylinder
3. Double Acting cylinder
4. Valves
5. Connecting Pipes
THEORY:
PROCEDURE:
1. Ensure the compressor is having sufficient pressure(8 kg Maxim).
2. Connect the Pipes properly according to the block Diagram
Realize AND and OR function.
OBSERVATION:
Observe the operation of the single acting and double acting cylinder according to the
valve position
RESULT:
PRECAUTIONS: