POWER SYSTEM DEVICES NUMBERS

These numbers are based on a system adopted as standard given by IEEE. These numbers are used in
connection diagram, technical manuals and also in specifications.
1 Master Element 51 AC Time Over current Relay
2 Time Delay Starting or Closing Relay 52 AC Circuit Breaker
3 Checking or Interlocking Relay 53 Exciter or DC Generator Relay
4 Master Contactor 54 High-Speed DC Circuit Breaker
5 Stopping Device 55 Power Factor Relay
6 Starting Circuit Breaker 56 Field Application Relay
7 Anode Circuit Breaker 57 Short-Circuiting or Grounding (Earthing)
Device
8 Control Power Disconnecting Device 58 Rectification Failure Relay
9 Reversing Device 59 Overvoltage Relay
10 Unit Sequence Switch 60 Voltage or Current Balance Relay
11 Reserved for future application 61 Machine Split Phase Current Balance
12 Overspeed Device 62 Time-Delay Stopping or Opening Relay
13 Synchronous-speed Device 63 Pressure Switch
14 Underspeed Device 64 Ground (Earth) Detector Relay
15 Speed - or Frequency, Matching Device 65 Governor
16 Reserved for future application 66 Notching or Jogging Device
17 Shunting or Discharge Switch 67 AC Directional Over current Relay
18 Accelerating or Decelerating Device 68 Blocking Relay
19 Starting to Running Transition Contactor 69 Permissive Control Device
20 Electrically Operated Valve 70 Rheostat
21 Distance Relay 71 Level Switch
22 Equalizer Circuit Breaker 72 DC Circuit Breaker
23 Temperature Control Device 73 Load-Resistor Contactor
24 Over-Excitation Relay (V/Hz) 74 Alarm Relay
25 Synchronizing or Synchronism-Check Device 75 Position Changing Mechanism
26 Apparatus Thermal Device 76 DC Over current Relay
27 Under voltage Relay 77 Pulse Transmitter
28 Flame Detector 78 Phase-Angle Measuring or Out-of-Step
Protective Relay
29 Isolating Contactor 79 AC Reclosing Relay
30 Annunciator Relay 80 Flow Switch
31 Separate Excitation Device 81 Frequency Relay
32 Directional Power Relay 82 DC Reclosing Relay
33 Position Switch 83 Automatic Selective Control or Transfer
Relay
34 Master Sequence Device 84 Operating Mechanism
35 Brush-Operating or Slip-Ring Short-Circuiting, 85 Carrier or Pilot-Wire Receiver Relay
Device
36 Polarity or Polarizing Voltage Devices 86 Lockout Relay (Master Trip)
37 Undercurrent or Underpower Relay 87 Differential Protective Relay
38 Bearing Protective Device 88 Auxiliary Motor or Motor Generator
39 Mechanical Conduction Monitor 89 Line Switch
40 Field Relay 90 Regulating Device
41 Field Circuit Breaker 91 Voltage Directional Relay
42 Running Circuit Breaker 92 Voltage and Power Directional Relay
43 Manual Transfer or Selector Device 93 Field Changing Contactor
44 Unit Sequence Starting Relay 94 Tripping or Trip-Free Relay
45 Atmospheric Condition Monitor
46 Reverse-phase or Phase-Balance Current Relay
47 Phase-Sequence Voltage Relay
48 Incomplete Sequence Relay
49 Machine or Transformer, Thermal Relay

CODE OF PRACTICE : PROTECTION

The leads should be identified by ferrules near terminals.

The wiring should be by copper leads for C.T secondary’s for all cores (i.e.) metering as well as protection.
(for P.T Sec also)

Wherever two batteries are available, the primary protection and back-up protection should be from

different batteries.

Where there is only one battery at a Power Substation, the primary and back-up protections should be
given D.C supply through two individual circuits with independent fuses run from D.C bus.

D.C and A.C supplies should not be taken through different cores of the same cable.

The lead numbers are also standardized as follows

J Series D.C Incoming J1, J2, etc.


K Series Control - Closing, Tripping, etc. K1, K2, K3 etc.
L Series Alarms, indications and annunciations L1, L2, L3, etc.
E Series Potential transformer secondary’s E1, E2, E3, etc.
H Series LT A.C Supply H1, H2, H3, etc.
A Series C.T secondary for special protection A1, A2, A3, etc.
B Series Bus bar protection B1, B2, B3, etc.
C Series Protection Circuits C1, C2, C3, etc.
D Series Metering Circuits D1, D2, D3, etc.
Wherever CT cores are not used “SHORTING LOOPS” should be provided near CT secondary terminals
and not in marshaling boxes or at panels.

Certain lead numbers are standardized as follows and should be compulsorily adopted with ferrules at

terminations of leads.

J1 - Positive J2 - Negative
TRANSFORMER PROTECTION