0% found this document useful (0 votes)
112 views104 pages

Karmaveer Bhaurao Patil Polytechnic, Satara: Control Actions

Download as pdf or txt
Download as pdf or txt
Download as pdf or txt
You are on page 1/ 104

Rayat Shikshan Sanstha’s

KARMAVEER BHAURAO PATIL


POLYTECHNIC,
SATARA

Control Actions
Department Of Electronics And Telecommunication Engineering
Control System and PLC
EJ5G Subject Code: 17536 Third Year Entc

Amit Nevase
Lecturer,
Department of Electronics & Telecommunication Engineering,
Karmaveer Bhaurao Patil Polytechnic, Satara

9/27/2016 Amit Nevase 2


Objectives

The student will be able to:

 Understand classifications of control system.

 Understand Steady state, time response, and frequency


response analysis.

 Analyze the Stability of control system using RH criteria.

 Understand the fundamentals and diff. Hardware parts of


PLC.

 Draw ladder diagrams to program PLC


9/27/2016 Amit Nevase 3
Teaching & Examination Scheme

Teaching Scheme Examination Scheme

PAPER
TH TU PR TH PR OR TW TOTAL
HRS

03 -- 02 03 100 50# --- 25@ 175

 Two tests each of 25 marks to be conducted as per the schedule


given by MSBTE.
 Total of tests marks for all theory subjects are to be converted
out of 50 and to be entered in mark sheet under the head
Sessional Work (SW).
9/27/2016 Amit Nevase 4
Module I – Introduction to Control System
 Introduction to Control systems (4 Marks)
 Control System – Definition and Practical Examples
 Classification of Control System : Open Loop and Closed Loop Systems –
Definitions, Block diagrams, practical examples, and Comparison, Linear and
Non-linear Control System, Time Varying and Time In-varying Systems
 Servo System : Definition, Block Diagram, Classification (AC and DC Servo
System), Block diagram of DC Servo System.
 Laplace Transform and Transfer Function (4 Marks)
 Laplace Transform : Signifiance in Control System
 Transfer Function : Definition, Derivation of transfer functions for Closed loop
Control System and Open Loop Control System, Differential Equations and
transfer functions of RC and RLC Circuit
 Block Diagram Algebra (8 Marks)
 Order of a System : Definition, 0,1,2 order system Standard equation, Practical
Examples
 Block Diagram Reduction Technique: Need, Reduction Rules, Problems
9/27/2016 Amit Nevase 5
Module II – Time Response Analysis
 Time Domain Analysis (4 Marks)
 Transient and Steady State Response
 Standard Test Inputs : Step, Ramp, Parabolic and Impulse, Need, Significance
and corresponding Laplace Representation
 Poles and Zeros : Definition, S-plane representation
 First and Second order Control System (8 Marks)
 First Order Control System : Analysis for step Input, Concept of Time Constant
 Second Order Control System : Analysis for step input, Concept, Definition and
effect of damping
 Time Response Specifications (8 Marks)
 Time Response Specifications ( no derivations )
 Tp, Ts, Tr, Td, Mp, ess – problems on time response specifications
 Steady State Analysis – Type 0, 1, 2 system, steady state error constants,
problems

9/27/2016 Amit Nevase 6


Module III – Stability

 Introduction to Stability (4 Marks)


 Definition of Stability, Analysis of stable, unstable, critically stable
and conditionally stable
 Relative Stability
 Root locations in S-plane for stable and unstable system

 Routh’s Stability Criterion (8 Marks)


 Routh’s Stability Criterion : Different cases and conditions
 Statement Method
 Numericals Problems

9/27/2016 Amit Nevase 7


Module IV – Control Actions

 Process Control System (4 Marks)


 Process Control System – Block diagram, explanation of each block

 Control Actions (8 Marks)


 Discontinuous Mode : On-Off Controller, Equation, Neutral Zone
 Continuous modes: Proportional Controller (offset, proportional
band), Integral Controllers, Derivative Controllers – output
equations, corresponding Laplace transforms, Response of P, I, D
controllers
 Composite Controllers : PI, PD, PID Controllers – output equations,
response, comparison

9/27/2016 Amit Nevase 8


Module V – PLC Fundamentals
 Introduction (4 Marks)
 Evolution of PLC in automation, need and benefits of PLC in
automation
 Block Diagram of PLC (12 Marks)
 Block diagram and description of different parts of PLC -
 CPU Function, Scanning cycle, speed of execution, Power supply
function,
 Memory – function , organization of ROM and RAM
 Input modules – function, different input devices used with PLC
and their uses
 Output modules – function, different output devices used with
PLC and their uses
 Fixed and Modular PLCs
9/27/2016 Amit Nevase 9
Module VI – PLC Hardware and Programming
 PLC Hardware (8 Marks)
 Discrete Input Modules – Block diagram, typical wiring details, Specifications of
AC input modules and DC input modules. Sinking and sourcing concept in DC
input modules
 Discrete Output Modules – Block diagram, typical wiring details, Specifications
of AC output modules and DC output modules.
 Analog Input and output modules : Block diagram, typical wiring details and
specifications
 PLC Programming (16 Marks)
 I/O Addressing in PLC
 PLC Instruction Set : Relay instructions, timer instructions, counter instructions,
data handling instructions, logical and comparison instructions
 PLC programming examples based on above instruction using Ladder
programming

9/27/2016 Amit Nevase 10


Module-IV
Control Actions

9/27/2016 Amit Nevase 11


Specific Objectives

Explain the need of Control actions

Differentiate between different types of Control

actions Such as P, I & D

Explain composite controllers; PI, PD, PID

controllers
9/27/2016 Amit Nevase 12
Module IV – Control Actions

 Process Control System (4 Marks)


 Process Control System – Block diagram, explanation of each
block

 Control Actions (8 Marks)


 Discontinuous Mode : On-Off Controller, Equation, Neutral Zone
 Continuous modes: Proportional Controller (offset, proportional
band), Integral Controllers, Derivative Controllers – output
equations, corresponding Laplace transforms, Response of P, I, D
controllers
 Composite Controllers : PI, PD, PID Controllers – output equations,
response, comparison
9/27/2016 Amit Nevase 13
Block Diagram of Process Control System

9/27/2016 Nevase Amit 14


Module IV – Control Actions

 Process Control System (4 Marks)


 Process Control System – Block diagram, explanation of each
block

 Control Actions (8 Marks)


 Discontinuous Mode : On-Off Controller, Equation, Neutral Zone
 Continuous modes: Proportional Controller (offset, proportional
band), Integral Controllers, Derivative Controllers – output
equations, corresponding Laplace transforms, Response of P, I, D
controllers
 Composite Controllers : PI, PD, PID Controllers – output equations,
response, comparison
9/27/2016 Amit Nevase 15
Classification of Control Actions

Discontinuous Continuous

On-Off Controller
I Composite
Two Position P D
Controllers
Controller
Multi Position PI
Controller PD
Floating Mode
Controller PID
9/27/2016 Nevase Amit 16
Related Terms

 Continuous Controller: Controller that responds to


continuous input variables are called continuous controller.

 Discrete Controller: Controller that responds to discrete


signal are called discrete controllers.

 Process Equation: A process equation describes the


mathematical relationship among the input and output
variables.

9/27/2016 Nevase Amit 17


Related Terms
 Process Load: The term process load refers to a set of
parameters that influences or bring changes in the process
excluding the controlled variable.
 Nominal Load: All the parameters have their normal or nominal
value
 Transient : A temporary or sudden change or the variation of
one of the variable is called transient.
 Process Lag : A process control loop responds to ensure that
some finite time later, the variable returns to the set point value.
Part of this time is consumed by the process itself and that time
is called process lag.
9/27/2016 Nevase Amit 18
Related Terms
 Control Lag : Control lag refers to the time for the
process control loop to make necessary adjustment to
the final control element.
 Dead Time : Another time variable associated with
process control is a function of both process control
system and the process. This is the elapsed time
between the instant of deviation (error) occurs and
when the corrective action first occurs.
 Cycling : Oscillation of error about the zero value. This
means the dynamic variable cycling above and below
the set point. For cycling we are interested in
amplitude and period of oscillation.
9/27/2016 Nevase Amit 19
Module IV – Control Actions

 Process Control System (4 Marks)


 Process Control System – Block diagram, explanation of each block

 Control Actions (8 Marks)


 Discontinuous Mode : On-Off Controller, Equation, Neutral Zone
 Continuous modes: Proportional Controller (offset, proportional
band), Integral Controllers, Derivative Controllers – output
equations, corresponding Laplace transforms, Response of P, I, D
controllers
 Composite Controllers : PI, PD, PID Controllers – output equations,
response, comparison

9/27/2016 Amit Nevase 20


ON-OFF Controller- 2 Position Controller

Synonyms:
“two-position” or “bang-bang” controllers.

e = error =
set point – measured variable

Controller output has two possible values.


9/27/2016 Nevase Amit 21
Neutral Zone

Practical case (dead band)

δ = tolerance

system never reaches steady-state

9/27/2016 Nevase Amit 22


ON-OFF Controller-Multi position Controller
Multimode/ Multi-position Controller: Multimode controller is a
logical extension of On/Off controller. It is used to provide
several intermediate, rather than two, setting of the
controller output. This discontinuous control is used in an
attempt to reduce the cycling behavior and overshoot and
undershoot inherent in the On/Off controller.

9/27/2016 Nevase Amit 23


Floating Control Mode

In a floating control, the specific output of the


controller is not uniquely determined by the
error. If the error is zero the output does not
change but remains (floats) at whatever setting
it was when the error went to zero. When the
error moves off zero, the controller output again
begins to change
9/27/2016 Nevase Amit 24
Floating Control Mode
Floating mode controller is of two types:

Single Speed: In the single-speed floating mode, the


output of the control element changes at a fixed
rate when the error exceeds the neutral zone.

Multi Speed: In the multi-speed floating mode, not


one but several possible speeds (rates) are changed
by controller output. Usually, the rate increases as
the deviation exceeds certain rate.

9/27/2016 Nevase Amit 25


Electronic ON-OFF Controller

9/27/2016 Nevase Amit 26


Electronic ON-OFF Controller

9/27/2016 Nevase Amit 27


Advantages of ON-OFF Controller

Only two output states i.e. ON and OFF.

Simple construction

Low cost

9/27/2016 Nevase Amit 28


Disadvantages of ON-OFF Controller

Response of ON-OFF controller is slow.

Not suitable for complex system

9/27/2016 Nevase Amit 29


Module IV – Control Actions

 Process Control System (4 Marks)


 Process Control System – Block diagram, explanation of each block

 Control Actions (8 Marks)


 Discontinuous Mode : On-Off Controller, Equation, Neutral Zone
 Continuous modes: Proportional Controller (offset, proportional
band), Integral Controllers, Derivative Controllers – output
equations, corresponding Laplace transforms, Response of P, I, D
controllers
 Composite Controllers : PI, PD, PID Controllers – output equations,
response, comparison

9/27/2016 Amit Nevase 30


Proportional- Integral- Derivative
Output Response for Step Input Signal for:

Proportional Integral Derivative

9/27/2016 Nevase Amit 31


Proportional Control Action

 In the case of the proportional controller, the actuation


signal is proportional to the system deviation.
 If the system deviation is large, the value of the
manipulated variable is large.
 If the system deviation is small, the value of the
manipulated variable is small.
 The time response of the P controller in the ideal state
is exactly the same as the input variable

9/27/2016 Nevase Amit 32


Proportional Control Action

9/27/2016 Nevase Amit 33


Proportional Control Action

In a proportional control mode, a smooth linear


relationship exists between the controller
output and the error. The range of error to cover
the 0% to 100% controller output is called the
proportional band, because the one-to-one
correspondence exists only for errors in this
range.

9/27/2016 Nevase Amit 34


Proportional Control Action

The output can be expressed as:

Where,
Kp = proportional gain between error and
controller output
p0 = controller output with no error.

9/27/2016 Nevase Amit 35


Proportional Control Action

In a proportional control mode, the


proportional band is dependent on the gain
and can be expressed as :

9/27/2016 Nevase Amit 36


The proportional band of a proportional controller depends
on the inverse of the gain.

9/27/2016 Nevase Amit 37


Characteristics of P Control mode

 If error is zero, the output is a constant equal to p0.

 If there is an error, for every 1% of error, a


correction of Kp percent is added to or subtracted
from p0 depending the sign of the error.

 There is a band of error about zero of magnitude


PB with which the output is not saturated at 0% or
100%.

9/27/2016 Nevase Amit 38


Why not “Proportional”?
Offset:

 An important characteristics of proportional


controller mode is that it produces a permanent
residual error in the operating point of the
controlled variable, when a change in load occurs.
This error is referred to as offset. It can be
minimized by a larger constant Kp which will also
reduce the proportion band.

9/27/2016 Nevase Amit 39


An offset error must occur if a proportional controller
requires a new zero-error output following a load change

9/27/2016 Nevase Amit 40


Proportional Controller

Setpoint

Car – steering analogy: Check distance from middle of the lane and
correct steering in proportion to distance from desired position

9/27/2016 Nevase Amit 41


Electronic Proportional Controller

9/27/2016 Nevase Amit 42


Electronic Proportional Controller

Vout  GpVe  Vo
where Vout= output voltage

R2
Gp   gain
R1

Ve= error voltage


Vo= output with zero error

9/27/2016 Nevase Amit 43


Advantages of Proportional Controller

Construction is simple

These controllers has high loop gain

It has steady state tracking accuracy

It improves the disturbances signal reduction

It stabilizes the gain and makes the system more


stable

9/27/2016 Nevase Amit 44


Disadvantages of Proportional Controller

It cannot accommodate load change without


sustained deviation.
It produces the constant steady state error.
For very large gain it leads to instability of the
system
It has a sluggish i.e. slow response for wide
proportional band.
It makes the system less sensitive to parameter
variation

9/27/2016 Nevase Amit 45


Module IV – Control Actions

 Process Control System (4 Marks)


 Process Control System – Block diagram, explanation of each block

 Control Actions (8 Marks)


 Discontinuous Mode : On-Off Controller, Equation, Neutral Zone
 Continuous modes: Proportional Controller (offset, proportional
band), Integral Controllers, Derivative Controllers – output
equations, corresponding Laplace transforms, Response of P, I, D
controllers
 Composite Controllers : PI, PD, PID Controllers – output equations,
response, comparison

9/27/2016 Amit Nevase 46


Integral Control Action

 The I controller adds the system deviation over time. It


integrates the system deviation.

 As a result, the rate of change (and not the value) of


the manipulated variable is proportional to the system
deviation.

 This is demonstrated by the step response of the I


controller: if the system deviation suddenly increases,
the manipulated variable increases continuously.
9/27/2016 Nevase Amit 47
Integral Control Action

9/27/2016 Nevase Amit 48


Integral Control Action

 The greater the system deviation, the steeper the increase


in the manipulated variable
 For this reason the I controller is not suitable for totally
compensating remaining system deviation.
 If the system deviation is large, the manipulated variable
changes quickly.
 As a result, the system deviation becomes smaller and the
manipulated variable changes more slowly until equilibrium
is reached.
9/27/2016 Nevase Amit 49
Integral Control Action

 A pure I controller is unsuitable for most controlled


systems, as it either causes oscillation of the closed
loop or it responds too slowly to system deviation in
systems with a long time response.

 In practice there are hardly any pure I controllers.

9/27/2016 Nevase Amit 50


Integral Control Action

In a integral control mode, the rate of change of


controller output is proportional to the error. So
the output can be expressed as:

9/27/2016 Nevase Amit 51


Characteristics Integral Control Action

If error is zero, the output is a constant equal to


p0.

If there is an error, for every 1% of error, a


correction of KI percent is added to or
subtracted from p0 depending the sign of the
error.
9/27/2016 Nevase Amit 52
Integral mode controller action: (a) The rate of output change
depends on error, and (b) an illustration of integral mode output and
error.

9/27/2016 Nevase Amit 53


Why not “Integral”?

Integral Windup:

The problem for integral controller is that, if


there is a zero change in slope, the controller
output holds to a constant value. This is called
integral windup. The only way to cut the wind
up is to put a negative error

9/27/2016 Nevase Amit 54


Integral Controller

Integration of a curve  area under the curve

Integrated input signal is multiplied by a factor, Ki

9/27/2016 Nevase Amit 55


Integral Controller

Setpoint

Car steering analogy:


Look out through the back window and keep track of
•how long the car has been out of desired position and
•by how much.
How long (sec) * how much (m) is the integral (sec*m).
The longer the car was positioned away from the set point the stronger
the signal Good to correct for long term and only slight deviation from set
point.

9/27/2016 Nevase Amit 56


Integral Controller

 A purely integrating controller is slow and

 Error takes long time to build up

 Action can become too strong  overshooting

 Int controller is unaware of current position  Generally


used combined with P control (looking at current position)
– PI control

9/27/2016 Nevase Amit 57


Electronic Integral Controller

9/27/2016 Nevase Amit 58


Electronic Integral Controller

t
Vout  GI  Vedt  Vout (0)
0

where Vout= output voltage


1
G   integration gain
I
RC
Ve= error voltage
Vout(0)= initial output voltage

9/27/2016 Nevase Amit 59


Advantages of Integral Controller

It reduces steady state error i.e. effect of offset.

It provides high controlled output at a particular


time after the error generated is for high value
of KI.

It responds to the continued existence of


deviation.

9/27/2016 Nevase Amit 60


Disadvantages of Integral Controller

It is never used alone.

It makes the system unstable for oscillatory


response.

It introduces hunting in the system response


about its steady state condition.

9/27/2016 Nevase Amit 61


Module IV – Control Actions

 Process Control System (4 Marks)


 Process Control System – Block diagram, explanation of each block

 Control Actions (8 Marks)


 Discontinuous Mode : On-Off Controller, Equation, Neutral Zone
 Continuous modes: Proportional Controller (offset, proportional
band), Integral Controllers, Derivative Controllers – output
equations, corresponding Laplace transforms, Response of P, I, D
controllers
 Composite Controllers : PI, PD, PID Controllers – output equations,
response, comparison

9/27/2016 Amit Nevase 62


Derivative Control Action

In a derivative control mode, the controller


output is proportional to the derivative of the
error. So the output can be expressed as:

9/27/2016 Nevase Amit 63


Derivative mode controller action changes depending
on the rate of error.

9/27/2016 Nevase Amit 64


Characteristics Derivative Control Action

 If error is zero or the error is constant in time, the


mode provides no output.

 If there is an error, for every 1% -per-second rate of


change of error, the mode contributes an output of
KD percent.

 For direct action, a positive rate of change of error


produces a positive derivative mode output.

9/27/2016 Nevase Amit 65


Why not “Derivative”?

Derivative Overrun:

 A step change in set point causes a false step error for the
derivative controller. This step change causes the derivative
part of the controller to saturate the overall controller
output. This ultimately forces the final control element to go
to hard Off mode. This is called derivative overrun. The
solution to this problem is to feed the derivative controller
with process variable (PV) instead of error

9/27/2016 Nevase Amit 66


Derivative Controller
 Examines the rate of change of the output of the
process
 The faster the change, the stronger the action
 The derivative of the output (slope) is multiplied by
a constant, Kd

9/27/2016 Nevase Amit 67


Derivative Controller

Setpoint

9/27/2016 Nevase Amit 68


Derivative Controller
 Differential control is insensitive to slow changes
 If the variable is parallel to the setpoint, no change
is made (slope = 0)

 Differential control is very useful when combined


with P and I control  PID control

9/27/2016 Nevase Amit 69


Electronic Derivative Controller

dVout dVe
Vout  R1C   R 2C
dt dt
9/27/2016 Nevase Amit 70
Advantages of Derivative Controller

It can overcome the overshoot and severe


cycling.
It has a rapid response to counter the effect of
rapidly changing errors.
It responds to the changes of the speed and
direction to the deviation.
It does not affect the steady state error directly,
but anticipates the error.
It increases the stability of the system by
initiating an early corrective action

9/27/2016 Nevase Amit 71


Disadvantages of Derivative Controller

 It cannot be used alone, since it cannot give any


output for zero or constant error.

 It is ineffective for slowly changing error and hence


causes the drift.

 It amplifies the noise signal and causes a saturation


effect on the system.

 It does not eliminate the steady state error. (offset)


9/27/2016 Nevase Amit 72
Module IV – Control Actions

 Process Control System (4 Marks)


 Process Control System – Block diagram, explanation of each block

 Control Actions (8 Marks)


 Discontinuous Mode : On-Off Controller, Equation, Neutral Zone
 Continuous modes: Proportional Controller (offset, proportional
band), Integral Controllers, Derivative Controllers – output
equations, corresponding Laplace transforms, Response of P, I, D
controllers
 Composite Controllers : PI, PD, PID Controllers – output
equations, response, comparison

9/27/2016 Amit Nevase 73


PI-Controller

 The PI controller combines the behaviour of the I


controller and P controller.
 This allows the advantages of both controller types to
be combined: fast reaction and compensation of
remaining system deviation.
 For this reason, the PI controller can be used for a large
number of controlled systems.
 In addition to proportional gain, the PI controller has a
further characteristic value that indicates the
behaviour of the I component: the reset time (integral-
action time).

9/27/2016 Nevase Amit 74


PI-Controller

9/27/2016 Nevase Amit 75


PI-Controller

This control mode results from a combination of


the proportional mode and the integral mode.
The output can be expressed as:

9/27/2016 Nevase Amit 76


Proportional-integral (PI) action showing the reset
action of the integral contribution

9/27/2016 Nevase Amit 77


Characteristics of PI-Controller

When error is zero, the controller output is fixed


at PI(0) .
If there is an error, the proportional term
contributes a correction, and the integral term
begins to increase/decrease the accumulated
value [ initially, pI (0)], depending on the sign of
the error and the direct or reverse action.

9/27/2016 Nevase Amit 78


Electronic PI Controller

t
R2 R2 1
Vout  ( )Ve  ( )
R1 
R1 R 2C 0
Vedt  Vout (0)
9/27/2016 Nevase Amit 79
Advantages of PI Controller

It provides better stability to the system.

It provides simplicity and directness.

It fully eliminates the steady state error i.e.


offset.

It has good transient response.

It stabilizes the controller gain.

9/27/2016 Nevase Amit 80


Disadvantages of PI Controller

 It takes the longer time to stabilize the controller


gain than proportional controller action.

 It suffers from only oscillation induced by the


integral overshoot.

 It requires excessive stabilization, when the process


has many energy elements or dead time.

9/27/2016 Nevase Amit 81


Module IV – Control Actions

 Process Control System (4 Marks)


 Process Control System – Block diagram, explanation of each block

 Control Actions (8 Marks)


 Discontinuous Mode : On-Off Controller, Equation, Neutral Zone
 Continuous modes: Proportional Controller (offset, proportional
band), Integral Controllers, Derivative Controllers – output
equations, corresponding Laplace transforms, Response of P, I, D
controllers
 Composite Controllers : PI, PD, PID Controllers – output
equations, response, comparison

9/27/2016 Amit Nevase 82


PD Controller

This control mode results from a combination of


the proportional mode and the derivative mode.
The output can be expressed as:

9/27/2016 Nevase Amit 83


PD- Controller

 The PD controller consists of a combination of


proportional action and differential action.
 The differential action describes the rate of change of
the system deviation.
 The greater this rate of change – that is the size of the
system deviation over a certain period – the greater
the differential component.
 In addition to the control response of the pure P
controller, large system deviations are met with very
short but large responses.
 This is expressed by the derivative-action time (rate
time).

9/27/2016 Nevase Amit 84


Proportional-derivative (PD) action showing the offset
error from the proportional mode

9/27/2016 Nevase Amit 85


Electronic PD Controller

R2 R2 dVe
Vout  ( )Ve  ( ) R3C  Vo
R1  R3 R1  R3 dt
9/27/2016 Nevase Amit 86
Advantages of PD Controller

It allows the rise of narrower proportional band


with its lesser offset.
It increases the controller gain during the error
change.
It can compensate the rapidly changing error.
It can handle the fast process load change.
It can compensate some of the lag in a process.
9/27/2016 Nevase Amit 87
Disadvantages of PD Controller

It cannot eliminate the offset of proportional


controller.

9/27/2016 Nevase Amit 88


Module IV – Control Actions

 Process Control System (4 Marks)


 Process Control System – Block diagram, explanation of each block

 Control Actions (8 Marks)


 Discontinuous Mode : On-Off Controller, Equation, Neutral Zone
 Continuous modes: Proportional Controller (offset, proportional
band), Integral Controllers, Derivative Controllers – output
equations, corresponding Laplace transforms, Response of P, I, D
controllers
 Composite Controllers : PI, PD, PID Controllers – output
equations, response, comparison

9/27/2016 Amit Nevase 89


PID- Controller
 In addition to the properties of the PI controller, the
PID controller is complemented by the D component.
 This takes the rate of change of the system deviation
into account.
 If the system deviation is large, the D component
ensures a momentary extremely high change in the
manipulated variable.
 While the influence of the D component falls of
immediately, the influence of the I component
increases slowly.
 If the change in system deviation is slight, the
behaviour of the D component is negligible

9/27/2016 Nevase Amit 90


PID- Controller

 This behavior has the advantage of faster response and


quicker compensation of system deviation in the event
of changes or disturbance variables.

 The disadvantage is that the control loop is much more


prone to oscillation and that setting is therefore more
difficult.

9/27/2016 Nevase Amit 91


PID- Controller

9/27/2016 Nevase Amit 92


PID Controller

This is one of the most powerful but complex


controller mode operations combines the
proportional, integral and derivative modes. The
output for this mode can be expressed as:

9/27/2016 Nevase Amit 93


The three-mode controller action exhibits proportional,
integral, and derivative action.

9/27/2016 Nevase Amit 94


Problems with Individual Element P, I, D

Setpoint

P: Alarm: strong left turn needed


I: No problem: Past Right and Left errors are about
equal
D: No problem: Direction is parallel to setpoint

9/27/2016 Nevase Amit 95


Time Analogy of PID Controller

 P: Present time. Only considers current position. Not


aware of current direction and of error history

 I: Past time. Only compiles an error sum of the past.


Not aware of current distance of signal from setpoint
and of current direction.

 D: Future time. Only considers current direction


(trend). Now aware of current distance of signal from
setpoint and of error history.

9/27/2016 Nevase Amit 96


PID Response

1. Output without
control Positive 1
deviation
2. Proportional
action
Controlled
3. Integral action variable 2

4. Proportional + Set-point 4
integral action
5, 6
5. Proportional + 3
derivative action Negative
deviation
6. Proportional +
integral +
derivative action Time

9/27/2016 Nevase Amit 97


Electronic PID Controller

R2 R2 1 R2 dVe
Vout  ( )Ve  ( )
R1 R1 RICI  Vedt ( ) RDCD
R1 dt
 Vout (0)
9/27/2016 Nevase Amit 98
Advantages of PID Controller

It reduces the overshoot which often occurs


when integral control action is added to
proportional control action.
It counteracts the lag characteristics introduced
by the integral control action.
It approaches the tendencies towards
oscillations.
It senses the rate of movement away from the
set point and gives corrective action earlier than
only with P or PI
9/27/2016 Nevase Amit 99
Advantages of PID Controller

It is more effective for control process with


many energy storage element than P+I control
action used alone.

It eliminates the offset i.e. steady state error


introduced by proportional control action.

It stabilizes the gain of the controller

9/27/2016 Nevase Amit 100


Car Steering Analogy
References

Process Control and


Instrumentation
Technology – C. D.
Johnson

9/27/2016 Amit Nevase 102


Online Tutorials

 http://www.electrical4u.com
/types-of-controllers-
proportional-integral-
derivative-controllers/
 http://elearning.vtu.ac.in/ne
wvtuelc/courses/06IT64.html
 https://www.facstaff.bucknell
.edu/mastascu/eControlHTM
L/Intro/Intro2.html
9/27/2016 Amit Nevase 103
Thank You
Amit Nevase
9/27/2016 Amit Nevase 104

You might also like