Marriot Grand Ballroom Concrete Works: Project Title: Contract Package No. 02
Marriot Grand Ballroom Concrete Works: Project Title: Contract Package No. 02
Marriot Grand Ballroom Concrete Works: Project Title: Contract Package No. 02
Document Title:
REVISION HISTORY
A1 1st Submission
GENERAL CONTRACTOR
Prepared By: NGCB CQC
Project Manager
Approved By:
Sr. Project Manager
EELHI
MGB-MS-017-AR-001 Page 1
TABLE OF CONTENT
1. PURPOSE
2. SCOPE AND APPLICATON OF WORKS
3. REFERENCES
4. DEFINITIONS AND ABBREVIATIONS
5. SPECIFICATION CLAUSE
6. RESOURCES AND MOBILIZATION
7. CONSTRUCTION EQUIPMENT
8. PERSONNEL
9. MATERIALS
10. CONSTRUCTION PROCEDURE AND METHODOLOGY
11. TESTING AND INSPECTION
12. RESPONSIBILITY
13. DESIGN DRAWINGS
14. QUALITY ASSURANCE
15. HEALTH AND SAFETY
16. ORGANIZATIONAL CHART
17. INSPECTION
18. ATTACHEMENTS
___________________________________________________________________________
1. PURPOSE
This method of statement defines that the Masonry Works to be conducted in the site are in
compliance with the Architectural Works Technical Specification and approve Construction
Methodology. And the Materials to be used for specific works are in compliance with the approved
design and material approvals. And will ensure that work procedures are in compliance with the
Project Safety Plan. The inspection will be based from the Project Quality Plan. The inspection is
associated quality procedures and an approved Inspection and Test Plan for the concrete repair
works.
2. SCOPE OF WORK
The work method is summarized as follows:
3. REFERENCES
This method statement has been prepared with reference to the following documents:
MGB-MS-017-AR-001 Page 2
4. DEFINITIONS AND ABREVIATIONS
5. SPECIFICATION CLAUSE
The specification requirements for Rubbed Concrete works are described within Project Technical
Specification of Architectural Works and For Construction Design Drawings as follows:
5.1.2.Concrete Lintels
5.1.2.1. Concrete Lintels: Precast or Cast-in-Place concrete lintels complying with
requirements in Structural Specifications “Cast-in-Place Concrete”
5.1.3.Mortar Materials
5.1.3.1. Portland Cement: ASTM C 150, Type I or II. Provide natural color or white cement
as required to produce mortar indicated.
5.1.3.2. Hydrated Lime: ASTM C 207, Type S
5.1.3.3. Aggregate for Mortar: ASTM C 144
5.1.3.4. Water: Potable
5.1.4.Reinforcement
5.1.4.1. Uncoated Steel Reinforcing Bars: ASTM A 615/1 615M or ASTM A 996/A 996M,
Grade 420
5.1.4.2. Masonry Joint Reinforcement, General: ASTM 951/A 951M
5.1.4.2.1. Interior Walls: Mill-Galvanized, carbon steel.
5.1.4.2.2. Wire Size for Cross Rods: W1.7 or 3.8-mm diameter
5.1.4.2.3. Spacing of cross Rods, Tabs, Cross Tabs: Not more than 407mm o.c.
5.1.4.2.4. Provide in lengths of not less than 3m
MGB-MS-017-AR-001 Page 3
made from with dovetail tabs for inserting into dovetail slots in concrete and
sized to extend to within 25mm of masonry face.
5.1.5.5. Partition Top Anchors: 2.66mm thick metal plate with 9.5mm diameter metal rod
152mm long welded to plate and with closed-end plastic tube fitted over rod that
allows rod to move in and out of the. Fabricate from steel, hot-dip galvanized after
fabrication
5.1.5.6. Rigid Anchors: Fabricate from steel bars 38mm wide by thick by 610mm long, with
ends turned up 51mm or with cross pins unless otherwise indicated
5.1.5.6.1. Corrosion Protection: Hot-dip galvanized to comply ASTM A 153/A 153M
5.1.7.Mortar Mixes
5.1.7.1. General: Do not use admixtures, including pigments, air-entertaining agents,
accelerators, retarders, water-repellent agents, anti-freeze compounds, or other
admixtures unless otherwise indicated
5.1.7.1.1. Do not calcium chloride in mortar or grout
5.1.7.1.2. Use Portland cement-lime mortar unless otherwise indicated
5.1.7.2. Mortar for Unit Masonry: Comply with ASTM C 270, Property Specification. Provide
the following types of mortar for applications stated unless another type is indicated
or needed to provide required compressive strength of masonry.
5.1.7.2.1. For reinforced masonry, use Type S or Type N
5.1.7.2.2. For Interior non-load bearing partitions, Type O may be instead of Type N
5.1.8.Execution
5.1.8.1. Examination
5.1.8.1.1. Examine conditions, with the Installer present, for compliance with
requirements for installation tolerances and other conditions affecting
performance of the work.
5.1.8.1.2. For the record, prepare written report, endorsed by installer, listing conditions
detrimental to performance of work.
5.1.8.1.3. Verify that reinforcing dowels are properly placed
5.1.8.1.4. Before installation, examine the rough-in and built-in construction for piping
systems to verify actual locations of piping connections.
5.1.8.1.5. Proceed with installation only unsatisfactory conditions have been corrected
5.1.8.2. Tolerances
5.1.8.2.1. Lines and Levels
5.1.8.2.2. For Conspicuous horizontal lines, such as lintels, sills, parapets, and reveals,
do not vary from level by more than 3mm in 3m, 6mm in 6m, or 12mm
maximum
5.1.8.2.3. For conspicuous vertical lines, such as external corners, door jambs, reveals,
and expansion and control joints, do not vary from plumb by more than 3mm
in 3m, 6mm in 6m, or 12mm maximum
5.1.8.2.4. For vertical alignment of exposed head joints, do not vary from plumb by more
than 6mm in 3m, or 12mm maximum.
MGB-MS-017-AR-001 Page 4
joints, returns, and offsets. Avoid using less-than-half-size units, particularly at
corners, jambs, and, where, possible, at other locations.
5.1.8.3.2. Lay concealed masonry with all units in a Wythe in running bond or bonded by
lapping not less than 50mm. Bond and interlock each course of each Wythe at
corners. Do not use units with less than nominal 100mm horizontal face
dimensions at corners or jambs
5.1.8.3.3. Stopping and resuming work: Stop work by racking back units in each course
from those in course below; do not tooth. When resuming work, clean
masonry surfaces that are to receive mortar before laying fresh masonry
5.1.8.3.4. Built-in Work: As construction progresses, build in items specified in this and
other sections. Fill in solidly with masonry around built-in items.
5.1.8.3.5. Fill space between steel frames and masonry solidly with mortar unless
otherwise indicated
5.1.8.3.6. Where built-in items are to be embedded in cores of hollow masonry units,
place a layer of metal lath, wire mesh, or plastic mesh in joint below and rod
mortar or grout into core.
5.1.8.3.7. Build non-load-bearing interior partitions full height of story to underside of
side or roof structure above unless otherwise indicated.
5.1.8.3.7.1. Install compressible filler in joint between top of partition and underside
of structure above.
5.1.8.3.7.2. Fasten partition top anchors to structure above and build into top of
partition. Grout cells of CMUs solidly around plastic tubes of anchors and
push tubes down into grout to provide 13-mm clearance between end of
anchor rod and end of tube. Space anchors 1200mm o.c. unless
otherwise indicated.
5.1.8.3.7.3. Wedge non-load-bearing partitions against structure above with small
pieces of tile, slate, or metal. Fill joint with mortar after dead-load
deflection of structure above approaches final position.
MGB-MS-017-AR-001 Page 5
5.1.8.7. Control and Expansion joints
5.1.8.7.1. General: Install control and expansion joint materials in unit as masonry
progresses. Do not allow materials to span control and expansion joints
without provision to allow for in-plane wall or partition movement.
5.1.8.7.2. From control joints in concrete masonry using one of the following methods:
5.1.8.7.2.1. Fit bond-breaker strips into hollow contour in ends of CMUs on one side
of control joint. Fill resultant core with grout and rake out joints in exposed
faces for application of sealant.
5.1.8.7.2.2. Install performed control-joint gaskets designed to fit standard sash
block
5.1.8.7.2.3. Install temporary foam-plastic in head joints and remove when unit
masonry is complete for application of sealant
5.1.8.8. Lintels
5.1.8.8.1. Provide concrete lintels where shown and where openings of more than
305mm for brick-size units and 610 for block-size units are shown without
structural steel or other supporting lintels
5.1.8.8.2. Provide minimum bearing of 200mm at each jamb unless otherwise indicated
5.1.10. Final Cleaning: After mortar is thoroughly set and cured, clean exposed masonry as
follows:
5.1.10.1. Remove large mortar particles by hand with wooden paddles ad nonmetallic scrape
hoes or chisels
5.1.10.2. Test cleaning methods on sample wall panel; leave one-half of panel uncleaned for
comparison purposes. Obtain architect’s approval of sample cleaning before
proceeding with cleaning masonry.
5.1.10.3. Wet wall surfaces with water before applying cleaners; remove cleaners promptly
by rinsing surfaces thoroughly with clear water.
MGB-MS-017-AR-001 Page 6
5.1.12. Materials:
5.1.12.1.1. Cement
5.1.12.1.2. Aggregates (Sand)
5.1.12.1.3. Reinforcement Bars
5.1.12.1.4. Sono Band
5.1.12.1.5. Tie Wires
5.1.12.1.6. Skim Coats
5.1.12.1.7. Baufix
5.1.12.1.8. Leveling Materials
5.1.12.1.9. Nylon Cord
5.1.12.1.10. Styrofoam
5.1.12.1.11. Structural sealant
The Accessibility at the site will be planned and subject for approval. The Safety of the staff, workers
and material delivery also concentrate on the plan in order to mobilize in accordance from the project
requirements. All the materials to be used are subject for submittal and approval in accordance with
the Architectural Work Technical Specification.
The General Contractor (NGCB) will notify the schedule one day before the actual mobilization of the
staff, workers, equipment.
It is understood that NGCB will be responsible for the provision of appropriate type of crane for the
transportation of materials and equipment to complete the works including temporary construction
water and power supplies and lighting system.
7. CONSTRUCTION EQUIPMENT
This Method of Statement for Masonry Works has been envisaged that no major equipment will be
required by this activity. The typical construction equipment requirements are as listed below and will
be used up to the completion of the activities.
8. PERSONNEL
For this Masonry Concrete works will be organized by both General Contractor and Nominated
Subcontractor. All the personnel shall be fully competent and trained to carry out all works
associated with the Masonry Works. They shall have attended the required contractor’s safety
induction and will abide by the Health and Safety Plan, policy and procedures as well as
environmental plan. It is envisaged that the installation will be conducted by the followings:
8.1. Site Engineer
8.2. Survey Team
8.3. Quality Control Engineer
8.4. Foreman
8.5. Mason
8.6. Labor
MGB-MS-017-AR-001 Page 7
9. MATERIALS
The Materials for the Masonry Works shall be prepared at the site fabrication area. Materials for
Masonry works shall be inspected at the fabrication area before the works starts. The work will be
done at site using a manual procedure provided by NGCB and as per specifications by
supplier/manufacturer.
All materials delivered to the site will be inspected by NGCB Engineers In-charge together with the
QA/QC Inspectors and EELHI Inspectors to check if the materials are in accordance with the site
requirement and conform to the approved design and material qualification. A sample of mix
materials shall be inspected at site and tested before the retouching works; rejected materials shall
not be accepted and shall be returned to supplier.
The inward inspection of materials will be carried out in accordance with the relevant QA/QC
procedures and or approved Project Quality Control Plan and manufacturer’s / specification of
suppliers.
Note: No materials shall be permitted to enter and/or installed inside the jobsite without inspection
and approval from CQC Engineers upon arrival at jobsite.
This Masonry Works construction procedures and methods define the Scope of Work summarized
in section two of this method statement.
Before the Masonry Works, the following are required to be carried out:
10.1.1. Securing Material submittal and ITP are with approved status.
10.1.2. Check if the materials have been inspected and ready for fabrication
10.1.3. Check that the site access to the work area available, clean and safe.
10.1.4. Check if the temporary services provisions are available.
10.2.1. All delivered materials shall be inspected upon arrival on site. The inspection shall be
advised, in advance, as required by the ITP and in accordance with the Project Quality
Plans
10.2.2. The delivered materials shall be in accordance with the approved design technical
specification and approved material submittal.
10.2.3. Material approvals in form of approved SRF and all applicable documentations and
certifications shall be available during incoming material inspection.
10.2.4. Any materials delivered in the site that are not complying with the approved material
submittals and structural technical specification or rejected by EELHI Engineer shall
either be returned to the supplier or stored in the site at a suitable quarantine area.
10.2.5. The materials shall be free from defects or damaged, and still workable.
10.3.1. Generally, prior to commencement of the delivery of materials for masonry works, the
setting out of the masonry works shall be conducted to determine the location and
elevation.
10.3.2. The setting out of the works shall be on the basis of an “approved for construction
drawings and or approved shop drawings”. Settings points shall be from the common
reference point established provided in the site by NGCB.
10.3.3. Any discrepancy between the common reference point on the approved for construction
drawings and the actual site provisions shall be notified to EEHLI and an NCR shall be
raised.
10.4.Installation Procedure
MGB-MS-017-AR-001 Page 8
10.4.1. General: Check the layout if correct
10.4.2. Clean and remove dirt from the concrete flooring
10.4.3. Align the dowel for masonry
10.4.4. Apply first sono bond on the base where to install the CHB wall, before the mortar
bedding
10.4.5. lay CHB, one by one
10.4.6. Check the alignment of the CHB
10.4.7. Fill all the hollow spaces on CHB before the laying of jointing mortar, repeatedly
10.4.8. Install horizontal reinforcements at every 600mm, drilled and epoxy applied at rebar
10.4.9. Install reinforcements for stiffener column @ every 3.0 meters and the same for
stiffener/lintel beams
10.4.10. Case to case basis, if the span or/and height of the area to CHB is greater than 3.0
meters and less than 6.0 meters, equally distribute the 3.0 meters of span from the
center line
10.4.11. If there’s a block-out needed, install the lintels on the top of block-out before the
proceeding on laying of CHB
10.4.12. Place Styrofoam at every end of CHB for material expansion purposes
12. RESPONSIBILITY
The Contractor (NGCB) will be supervising all activities in the site through Construction
Supervisors, Foreman and skilled workers at the site. The QA/QC Inspectors will be responsible
for arranging and controlling the inspection and testing activities with the EELHI Inspectors.
18. ATTACHEMENTS
Checklist for inspection of incoming material for concrete rehabilitation materials.
Checklist for installed of concrete reinforcement.
MGB-MS-017-AR-001 Page 9