600kw PDF
600kw PDF
600kw PDF
PNY600
Perkins E18TAG3
HCI534E
145 x 183
14.5:1
/Enfriado por aire
654
2241
11
156
llame a fábrica.
llame a fábrica.
542
852
Ottomotores se reserva el derecho de hacer cambios sin previo aviso con el fin de mejorar nuestros productos 2010.
Radiator MODELS
153.60
Ø Out=00.00
Ø in=20.32
Turbocharger
PNY 600
Air Filter
Conection Box
175.04
205.50
Generator
DESCRIPTION
RADIATOR : CH11451
ENGINE: 2806C-E18TAG3
36.80
GENERATOR : HCI534E
AIR FILTER : MOD. 6584
BASE FRAME : BP-PRK18TAG3-STF
TOTAL WEIGHT : DRY-3935.59 Kgs.
WET-4043.59 Kgs.
AVMS SPRING : 6 PZS.
Ø Out=00.00 -THE GESENT DIMENSIONS ARE THE SAME BY FAMILY MODEL, THERE COULD BE ONLY DIFERENCES ON THE ALTERNATOR
TOP VIEW Ø in=20.32 LENGHT SEE SPECIFIC GENERAL ARRAGEMENT DRAWING OF CERTEIN MODEL
-TOTAL WEIGHT COULD VARY CHECK RATING CHART FOR EACH MODEL
Title: GENERAL ARRANGEMENT PERKINS 2806C-E18TAGE
Customer: S/O: STAMFORD ALTERNATOR
Draw: R.G.C. Revised: F.H.M. Certificated: F.H.M. Code: DP-PRK-01
Date: JUL 21th 2008 Date: JUL 21th 2008 Date: JUL 21th 2008 Dept.: Engineering
Marks:cms Draw:
n/a
Scale: s/e
Of:
n/a
Rev. Description Date Certificated
Reviews Ottomotores keeps the right to change the information with out prior notice
FO 023-0
2800 Series
2806A-E18TAG3
Diesel Engine – ElectropaK
565 kWm at 1500 rpm
652 kWm at 1800 rpm
Economic Power
Mechanically operated unit fuel injectors with electronic control combined with
carefully matched turbocharging give excellent fuel atomisation and combustion
with optimum economy
Low emissions result from electronic control of fuel injected
Reliable Power
Developed and tested using the latest engineering techniques and finite element
analysis for high reliability, low oil usage and low wear rates
High compression ratios also ensure clean rapid starting in all conditions
Perkins global product support is designed to enhance the customer experience
of owning a Perkins powered machine. We deliver this through the quality of our
The Perkins 2800 Series is a family of distribution network, extensive global coverage and a range of Perkins supported
well-proven 6 cylinder 16 and 18 litre OEM partnership options. So whether you are an end-user or an equipment
in-line diesel engines, designed to manufacturer our engine expertise is essential to your success
address today's uncompromising
demands within the power generation
Compact, Clean and Efficient Power
industry with particular aim at the
Exceptional power to weight ratio and compact size give optimum power density
standby market sector. Developed
with easier installation and cost effective transportation
from a proven heavy-duty industrial
Designed to provide excellent service access for ease of maintenance
base, the engine offers superior
performance and reliability.
The 2806A-E18TAG3 is a
turbocharged and air-to-air charge
cooled, 6 cylinder diesel engine of 18
litres capacity. Its premium features
provide economic and durable
operation, low gaseous emissions
and advanced overall performance
This engine does not comply with harmonized international regulated emissions limits.
and reliability.
The above ratings represent the engine performance capabilities to conditions specified in ISO 8528/1, ISO 3046/1:1986, BS 5514/1.
* Baseload ratings are under development and will be available later.
Derating may be required for conditions outside these; consult Perkins Engines Company Limited.
Generator powers are typical and are based on an average alternator efficiency and a power factor (cos. θ) of 0.8.
Fuel specification: BS 2869: Part 2 1998 Class A2 or ASTM D975 D2. Lubricating oil: 15W40 to API CG4.
Rating Definitions
Baseload Power: Power available for continuous full load operation. Overload of 10% permitted for 1 hour in every 12 hours' operation.
Prime Power: Power available at variable load with a load factor not exceeding 80% of the prime power rating. Overload of 10% is permitted for 1 hour in every 12 hours' operation.
Standby Power: Power available in the event of a main power network failure up to a maximum of 500 hours per year of which up to 300 hours may be run continuously. Load factor may be up to 100% of standby
power. No overload is permitted.
All information in this document is substantially correct at time of printing and may be altered subsequently Publication No. 1872/01/08 Produced in England ©2006 Perkins Engines Company Limited
2800 Series
2806A-E18TAG3
Standard ElectropaK Specification 2,545 mm 1,536 mm
Air inlet
Mounted air filter
1
Fuel system
Mechanically actuated electronically controlled unit fuel injectors with full
authority electronic control
Governing to ISO 8528-5 class G2 with isochronous capability 2,050 mm
Lubrication system
Fuel Consumption
Wet sump with filler and dipstick
1500 rev/min 1800 rev/min
Full-flow replaceable ‘Ecoplus’ filter Engine Speed
g/kWh l/hr g/kWh l/hr
Oil cooler integral with filter header
Standby 197 129 208 157
Cooling system
Prime power 198 120 209 144
Gear-driven circulating pump
Mounted belt-driven pusher fan Baseload power - - 203 114
Radiator incorporating air-to-air charge cooler, (supplied loose) 75% of prime 204 93 202 104
System designed for ambients up to 50ºC power
Low coolant level switch 50% of prime 204 62 210 72
power
Electrical equipment
24 volt starter motor and 24 volt 70 amp alternator with DC output
ECM mounted on engine with wiring looms and sensors General Data
3 level engine protection system Number of cylinders 6
Cylinder arrangement Vertical in-line
Flywheel and housing Cycle 4 stroke
High inertia flywheel to SAE J620 size 18 Induction system Turbocharged and
SAE ‘0’ flywheel housing air-to-air charge
cooled
Mountings Combustion system Direct injection
Front engine mounting bracket Cooling system Water-cooled
Bore and stroke 145 mm x 183 mm
Literature Displacement 18.1 litres
User’s Handbook Compression ratio 14.5:1
Direction of rotation Anti-clockwise,
Optional Equipment viewed on flywheel
110 volt/240 volt immersion heater Total lubrication system 62 litres
Additional speed sensor capacity
Temperature and pressure sensors for gauges Total coolant capacity 61 litres
Electric hours counter Total dry weight 2050 kg
Air filter rain hood Dimensions Length 2545 mm
Twin starters/facility for second starter Width 1536 mm
Tool kit Height 1807.5 mm
Parts manual/Workshop manual
All information in this document is substantially correct at time of printing and may be altered subsequently
Publication No. 1872/01/08 Produced in England ©2006 Perkins Engines Company Limited