Replacing Barber Colman Synchronisers and Load Sharing Units With The Unigen
Replacing Barber Colman Synchronisers and Load Sharing Units With The Unigen
Replacing Barber Colman Synchronisers and Load Sharing Units With The Unigen
The Unigen is a combined synchroniser and load sharing unit, any model is
capable of replacing the Barber Colman units listed below.
DYN2 80100
DYN2 80101
DYN2 80104
DYN2 80105
DYN2 80108
DYN2 80109.
It can also replace the DYN2 90100, DYN2 90200 and DYN2 90300
synchronisers.
Auto
Mains
Failure
DYN2-80100-DYN2 80105
Breaker 32 x
FP RLY
+Alim
control x NO
9 33 x
RP RLY
x 10 NC
5 breaker IN
5A
4 22 Gen I1+
P1 S1
P2 S2 5 23 Gen I1-
6 24 Gen I2+
P1 S1
N x 31 Gen N (optional)
PowRcon
Shield 48 x
L1 100 - 480 V
F 1 28 Gen L1
L2
F 2 29 Gen L2
Barber Colman
L3 F 3 30 Gen L3 DYN2-80109
Surge
diverter
G
UNIGEN ILS Woodward
2301A
x 19 Shield ...
analog
15 18 Speed Ref
Speed
governor
14 17 Speed out
x 14 Speed CW +5V
17 or 18 15 Speed setpoint
x 11 kW out +5V
x 13 kW out 5mA
+/- 5V or potentiometer
5kOhms 1 2
Chassis 21 13
isolated from F
power supply 5Amps
d
c N° DESSIN REV
Others connexions
remote speed CCW 16 16
remote speed CW 15 14
shield parallel lines/droop ground 13 48
shield speed out ground 13 19
Neutral voltage(optionnal) nc 31
d
c N° DESSIN REV
Auto
Mains
Failure
DYN2-80108-DYN2 80109
Breaker 32 20 FP RLY
+Alim
control NO
22 9 33 21
RP RLY
23 10 NC
16 5 breaker IN
5A
4 22 Gen I1+
P1 S1
P2 S2 5 23 Gen I1-
6 24 Gen I2+
P1 S1
N x 31 Gen N (optional)
PowRcon
Shield 48 x
L1 100 - 480 V
F 1 28 Gen L1
L2
F 2 29 Gen L2
Barber Colman
L3 F 3 30 Gen L3 DYN2-80109
Surge
diverter
G
UNIGEN ILS Woodward
2301A
x 19 Shield ...
analog
15 18 Speed Ref
Speed
governor
14 17 Speed out
x 14 Speed CW +5V
17 or 18 15 Speed setpoint
x 11 kW out +5V
19 13 kW out 5mA
+/- 5V or potentiometer
5kOhms 1 2
Chassis 24 13
isolated from F
power supply 5Amps
d
c N° DESSIN REV
S ig n a l D YN 2-8 0109 U n ig e n I L S 50 H z
V oltag e p has e A o r L1 1 28
V oltag e p has e B o r L2 2 29
V oltag e p has e C o r L3 3 30
C urrent phas e A or 1+ 4 22
C urrent phas e A or 1- 5 23
C urrent phas e B or 2+ 6 24
C urrent phas e B or 2- 7 25
C urrent phas e C or 3+ 8 26
C urrent phas e C or 3- 9 27
P arralel lines high 10 44
P arralel lines lo w 11 45
D roo p 12 43
pow er s upply - 13 2
govern or c on nex ion: s peed out 14 17
govern or c on nex ion: s peed re f 15 18
paral relay : break e r in 16 5
rem ot e s pee d: s pe ed s et point 17 15 C onn ec t t he pot ent iom et er of rem ot e s pee d
s y nc : s pee d s e tpo in t 18 or t he out put o f th e s y nc hroc o upler
pow er m on it or ou t 19 13 if y ou w ant to have 0 -5m A or 11 if y ou w ant to have 0-5 V D C
FP RLY 20 32
FP RLY 21 33
R P R LY 22 9
R P R LY 23 10
pow er s upply + 24 1
O th e rs co n n e x i o n s
pow er m on it or ou t - ground 13 12
rem ot e s pee d C C W ground 13 16
rem ot e s pee d C W s pee d ref 15 14
s hield p ara llel lines / droop ground 13 48
s hield s peed out ground 13 19
N eut ral volt age(opt io nnal) nc 31
d
c N° DESSIN REV