LS Inverter Series: Variable Frequency Drive
LS Inverter Series: Variable Frequency Drive
LS Inverter Series: Variable Frequency Drive
LS Inverter Series
iE5 / iC5 / iG5A / iS5 / iS7 / iH / iP5A / iV5
Automation Equipment
• For your safety, please read user's manual thoroughly before operating.
• Contact the nearest authorized service facility for examination, repair, or adjustment.
• Please contact qualified service technician when you need maintenance.
Do not disassemble or repair by yourself!
Safety Instructions • Any maintenance and inspection shall be performed by the personnel having expertise concerned.
www.lsis.biz
iV5
iP5A
iS7
3 phase
iS5
iH
iG5A
iE5
kW
iG5A
1 phase
iC5
iE5
kW
0.1 0.4 0.75 1.5 2.2 5.5 22 30 75 160 220 375 450
Contents
•iE5 4 •iP5A 10
•iC5 5 •iV5 11
•iG5A 6 •Comparison 12
•iS5 7 •Option list 14
•iS7 8 •Brake unit list 15
•iH 9 •External resistor list 15
LS Inverter Series 3
Simplicity-Precision, Flexibility-Standardization and
Easy to use-Diversity are the spiritual foundations of
LS Inverter variable frequency drives.
As an one-stop drive solution provider
LS is ready to offer its own competitive solutions
into the general power transmission industry.
2
iE5 User friendly micro size slim inverter
1 phase 0.1 - 0.4kW, 200V
Variable Frequency Drive / Inverter 3 phase 0.1 - 0.4kW, 200V
● V/f control
● Compact size: 68×128×85mm
● 0.1 ~ 200Hz frequency output
● IP20 enclosure
● PI control
● Stall prevention
● Built-in potentiometer
LS inverter brand Motor rating Series name Symbol Input rating Symbol Communication
001: 0.1kW ~ 004: 0.4kW iE5 1 Single-phase, 200V class None Not available
2 Three-phase, 200V class C RS485/Modbus
General specification
Model number: SV iE5- 001-1 002-1 004-1 001-2 002-2 004-2
Protection Inverter trip Over voltage / Low voltage / Over current / Ground fault detection / Inverter overload / Overload trip /
Inverter overheat / Condenser overload / Output phase loss / Overload protection /
Frequency command loss / Hardware fault
Inverter alarm Stall prevention
Enclosure IP20
4
iC5 High torque micro inverter
1 phase 0.4 - 2.2kW, 200V
Variable Frequency Drive / Inverter
● IP20 enclosure
● Built-in potentiometer
● 8 programmable I/O
LS inverter brand Motor rating Series name Symbol Input rating Symbol RFI filter
001: 0.1kW ~ 004: 0.4kW iC5 1 Single-phase, 200V class None Not available
F RFI filter (Class A)
General specification
Model number: SV iC5- 004-1 008-1 015-1 022-1
Motor rating [HP] 0.5 1 2 3
[kW] 0.4 0.75 1.5 2.2
Output rating Capacity [kVA] 0.95 1.9 3 4.5
Current [A] 2.5 5 8 12
Voltage [V] Single-Phase 200 ~ 230V
Frequency [Hz] 0.1 ~ 400Hz
Input rating Voltage [V] Single-Phase 200 ~ 230V (±10%)
Frequency [Hz] 50 ~ 60Hz (±5%)
Current [A] 5.5 9.2 16 21.6
Weight [kg] 0.87 0.89 1.79 1.85
Protection Inverter trip Over voltage / Low voltage / Over current / Ground fault detection / Inverter overload / Overload trip /
Inverter overheat / Condenser overload / Output phase loss / Overload protection /
Frequency command loss / Hardware fault
Inverter alarm Stall prevention, Overload
Enclosure IP20
Option Communication Modbus RTU
LS Inverter Series 5
iG5A Powerful & compact sensorless vector control inverter
1 phase 0.4 - 1.5kW, 200V
Variable Frequency Drive / Inverter 3 phase 0.4 - 22kW, 200/400V
● Selectable V/f, sensorless vector control ● -10 - +10 volt analog input
● Motor parameter auto-tuning ● Built-in braking circuit
● Powerful torque at overall speed range ● Enhanced process PID control
● -15% - +10% input voltage margin ● Remote control using external keypad * RJ45 cable(Optional)
● Ground fault protection during operation KEB (Kinetic Energy Buffering) protection
● IP20 enclosure, NEMA1(Optional) Low leakage PWM
● Selectable manual/automatic torque boost ●Monitoring & commissioning software (DriveView)
General specification
Model number: SV iG5A-1 004 008 015
Motor rating [HP] 0.5 1 2
[kW] 0.4 0.75 1.5
Output rating Capacity [kVA] 0.95 1.9 3.0
Current [A] 2.5 5 8
Voltage [V] Three-Phase 200 ~ 230V
Frequency [Hz] 0.1 ~ 400Hz
Input rating Voltage [V] Single-Phase 200 ~ 230V (+10%, -15%)
Frequency [Hz] 50 ~ 60Hz (±5%)
Weight [kg] 0.77 1.12 1.84
Model number: SV iG5A-2 004 008 015 022 037 040 055 075 110 150 185 220
Motor rating [HP] 0.5 1 2 3 5 5.4 7.5 10 15 20 25 30
[kW] 0.4 0.75 1.5 2.2 3.7 4.0 5.5 7.5 11 15 18.5 22
Output rating Capacity [kVA] 0.95 1.9 3 4.5 6.1 6.5 9.1 12.2 17.5 22.9 28.2 33.5
Current [A] 2.5 5 8 12 16 17 24 32 46 60 74 88
Voltage [V] Three-Phase 200 ~ 230V
Frequency [Hz] 0.1 ~ 400Hz
Input rating Voltage [V] Three-Phase 200 ~ 230V (+10%, -15%)
Frequency [Hz] 50 ~ 60Hz (±5%)
Weight [kg] 0.76 0.77 1.12 1.84 1.89 1.89 3.66 3.66 9.00 9.00 13.3 13.3
Model number: SV iG5A-4 004 008 015 022 037 040 055 075 110 150 185 220
Motor rating [HP] 0.5 1 2 3 5 5.4 7.5 10 15 20 25 30
[kW] 0.4 0.75 1.5 2.2 3.7 4.0 5.5 7.5 11 15 18.5 22
Output rating Capacity [kVA] 0.95 1.9 3 4.5 6.1 6.5 9.1 12.2 18.3 22.9 29.7 34.3
Current [A] 1.25 2.5 4 6 8 9 12 16 24 30 39 45
Voltage [V] Three-Phase 380 ~ 480V
Frequency [Hz] 0.1 ~ 400Hz
Input rating Voltage [V] Three-Phase 380 ~ 480V (+10%, -15%)
Frequency [Hz] 50 ~ 60Hz (±5%)
Weight [kg] 0.76 0.77 1.12 1.84 1.89 1.89 3.66 3.66 9.00 9.00 13.3 13.3
Control Spec Control method Sensorless vector, V/f
Speed reference resolution Digital command: 0.01Hz / Analog reference: 0.06Hz (Max freq., 60Hz)
Frequency accuracy Digital command: 0.01% of Max output freq. / Analog signal command of 0.1% of Max output freq.
V/f curve Linear, Squared, User custom V/f
Overload capacity 150% for 1 minute
Torque boost Auto & manual torque boost
Keypad Display 4 digit, 7 segment LED
Operation method Keypad / Terminal / Communication operation
Frequency setting Analog: 0 to 10V / -10 to 10V / 0 to 20mA / Potentiometer / Digital: Keypad/ Modbus
Operation function PID control / Up-Down operation / 3-Wire operation
Input signal Multi-function terminal PNP / NPN selectable
(P1 ~ P8) 8 points (programmable)
Output signal Multi-function relay Fault output & inverter status output (N.O., N.C.) Less than AC 250V, 0.3A / Less than DC 30V 1A
Multi-function open collector DC24V (less than 50mA)
Analog output 0 to 10Vdc (less than 10mA): frequency / current / voltage / DC voltage selectable
Protection Inverter trip Over voltage / Low voltage / Over current / Ground fault detection / Inverter overload / Overload trip / Inverter overheat / Output phase loss /
Overload protection / Frequency command loss / Hardware fault/ Brake fault
Inverter alarm Stall prevention, Overload
Enclosure IP20, NEMA1 (Optional)
Others Built-in Dynamic brake circuit, Modbus-RTU, LS Bus, Remote cable(2M/3M/5M) plus external keypad
6
iS5 Precise vector control standard inverter
3 phase 0.75 - 55kW, 200V
Variable Frequency Drive / Inverter 3 phase 0.75 - 75kW, 400V
LS inverter brand Motor rating Series name Symbol Input rating Symbol Loader Symbol UL certification Symbol Rated voltage
008: 0.75kW ~ 750: 75kW iS5 2 Three-phase, 200 ~ 230V None Loader O Open type None 200~230V or 380~480V
4 Three-phase, 380 ~ 480V N Non Loader E Enclosed type 1 **** 380V, 440V, 460V, 480V
General specification
Model number: SV iS5-2 008 015 022 037 055 075 110 150 185 220 300 370 450 550
Motor rating [HP] 1 2 3 5 7.5 10 15 20 25 30 40 50 60 75
[kW] 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55
Output rating Capacity [kVA] 1.9 3 4.5 6.1 9.1 12.2 17.5 22.9 28.5 33.5 46 55 68 84
Current [A] 5 8 12 16 24 32 46 60 74 88 122 146 180 220
Voltage [V] Three-Phase 200 ~ 230V
Frequency [Hz] 0.1 ~ 400Hz (Sensorless vector control: ~ 300Hz, Sensored vector control: 0 ~ 120Hz)
Input rating Voltage [V] Three-Phase 200 ~ 230V (±10%)
Frequency [Hz] 50 ~ 60Hz (±5%)
Weight [kg] 4.6 4.6 4.8 4.9 7.5 7.7 13.8 14.3 19.4 20.0 42.0 42.0 61 61
Model number: SV iS5-4 008 015 022 037 055 075 110 150 185 220 300 370 450 550 750
Motor rating [HP] 1 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100
[kW] 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75
Output rating Capacity [kVA] 1.9 3 4.5 6.1 9.1 12.2 17.5 22.9 29.7 34.3 45 56 68 82 100
Current [A] 2.5 4 6 8 12 16 24 30 39 45 61 75 91 110 152
Voltage [V] Three-Phase 380 ~ 480V 380V, 440V, 460V, 480V
Frequency [Hz] 0.1 ~ 400Hz
Input rating Voltage [V] Three-Phase 380 ~ 480V (±10%) 380V, 440V, 460V, 480V
Frequency [Hz] 50 ~ 60Hz (±5%)
Weight [kg] 4.7 4.7 4.8 4.9 7.7 7.7 13.9 14.4 20 20 45 45 63 63 68
Control Spec Control method Sensorless vector, Sensored vector, V/f
Speed reference resolution Digital command: 0.01Hz (less than 100Hz),0.1Hz (greater than 100Hz) / Analog reference: 0.03Hz (Max freq., 60Hz)
Frequency accuracy Digital command: 0.01% of Max output freq. / Analog signal command of 0.1% of Max output freq.
V/f curve Linear, Squared, User custom V/f
Overload capacity 150% for 1 minute, 200% for 0.5 second
Torque boost Auto & manual(0 ~ 15%) torque boost
Keypad Display LCD keypad / 4 digit, 7 segment LED
Operation method Keypad / Terminal / Communication operation
Frequency setting Analog: 0 to 10V / 4 to 20mA / Potentiometer / Digital: Keypad/ Modbus-RTU / Fnet / DeviceNet / Profibus
Operation function PID control / Up-Down operation / 3-Wire operation
Input signal Multi-function terminal PNP / NPN selectable
(P1 ~ P8) 8 points (programmable)
Output signal Multi-function relay Fault output & inverter status output (N.O., N.C.) Less than AC 250V, 0.3A / Less than DC 30V 1A
Multi-function open collector DC24V (less than 50mA)
Analog output 0 to 10Vdc (less than 10mA): frequency / current / voltage / DC voltage selectable
Protection Inverter trip Over voltage / Low voltage / Over current / Ground fault detection / Inverter overload / Overload trip / Inverter overheat /
Output phase loss / Overload protection / Frequency command loss / Hardware fault/ Brake fault
Inverter alarm Stall prevention, Overload, Temperature sensor fault
Enclosure IP20 (0.75~7.5kW), IP00 (11~75kW)
Option Board, Cable LCD KEYPAD, REMOTE CABLE(2M/3M/5M), Expansion I/O, Multi-motor control card, Encoder card
Communication LS Bus, Modbus-RTU, DeviceNet, Profibus-DP, Fnet
Others Built-in Dynamic brake unit (up to 7.5kW)
LS Inverter Series 7
iS7 High Torque Performance and Precise Control
3 phase 0.75 - 22kW, 220V
Variable Frequency Drive / Inverter 3 phase 0.75 ~ 160kW, 400V
● Constant torque / Variable torque dual rating ● 2nd motor sensorless control and parameter setting- IP21
● Selectable V/f, V/f PG, sensorless vector, sensored vector (0.75~160kW) / IP54 (0.75~22kW - Optional)
● 150 MIPS(million instructions per second) high speed DSP ● Built-in LS Bus / Modbus-RTU communication
PMSM sensorless vector function Master-K platform - 14 max. inputs & 7 max. outputs
Power Bake & Flux Brake function ● Extension I/O boards (Optional) :
Static motor parameter Auto-tuning (available soon) 11 max. inputs & 6 max outputs
● Easy to control : Easy Start Mode, User & Macro group, ● Communication boards (Optional) :
LS inverter brand Motor rating Series name Symbol Input rating Symbol Loader Symbol UL Certification Symbol Filter Symbol DCR
0008: 0.75kW ~ 1600: 160kW iS7 2 Three-phase, 200 ~ 230V S Loader O Open type None Not available None Not available
4 Three-phase, 380 ~ 480V N Non Loader E Enclosed Type 1 F EMC filter D DC Reactor
General specification
Model number: SV iS7-2 008 015 022 037 055 075 110 150 185 220
Motor rating [HP] 1 2 3 5 7.5 10 15 20 25 30
[kW] 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22
Output rating Capacity [kVA] 1.9 3 4.5 6.1 9.1 12.2 17.5 22.9 28.5 33.5
Current [A]: CT 5 8 12 16 24 32 46 60 74 88
Current [A]: VT 8 12 16 24 32 46 60 74 88 124
Voltage [V] Three-Phase 200 ~ 230V
Frequency [Hz] 0.01 ~ 400Hz
Input rating Voltage [V] Three-Phase 200 ~ 230V (-15% ~ +10%)
Frequency [Hz] 50 ~ 60Hz (±5%)
Current [A]: CT 8.3 12.9 18.6 24 32.9 41.4 58 69 88 96
Current [A]: VT 7 10.6 14.8 21.8 28 42 52 60 75 107
Model number: SV iS7-4 008 015 022 037 055 075 110 150 185 220 300 370 450 550 750 900 1100 1320 1600
Motor rating [HP] 1 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 120 150 180 225
[kW] 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160
Output rating Capacity [kVA] 1.9 3 4.5 6.1 9.1 12.2 17.5 22.9 29.7 34.3 45 56 68 82 100 139 170 201 248
Current [A]: CT 2.5 4 6 8 12 16 24 30 39 45 61 75 91 110 152 183 223 264 325
Current [A]: VT 4 6 8 12 16 24 30 39 45 61 75 91 110 152 183 223 264 325 370
Voltage [V] Three-Phase 380 ~ 480V
Frequency [Hz] 0.01 ~ 400Hz
Input rating Voltage [V] Three-Phase 380 ~ 480V (-15% ~ +10%)
Frequency [Hz] 50 ~ 60Hz (±5%)
Current [A]: CT 4.3 7.2 10.6 15.4 21 25.8 39 44 57 57 57 69 83 113 154
Current [A]: VT 3.5 5.3 7.3 10.8 13.8 22.5 26 33 40 52.2 90 109 123 162 195
Control Spec Control method Sensorless vector1, Sensorless vector2, Vector, V/f , V/f PG
Speed reference resolution Digital command: 0.01Hz / Analog reference: 0.06Hz (Max freq., 60Hz)
Frequency accuracy Digital command: 0.01% of Max output freq. / Analog signal command of 0.1% of Max output freq.
V/f curve Linear, Squared, User custom V/f
Overload capacity CT(Heavy duty): 150% for 1 minute, VT(Normal duty): 110% for 1 minute
Torque boost Auto & manual(0 ~ 15%) torque boost
Keypad Display LCD keypad
Operation method Keypad / Terminal / Communication operation
Frequency setting Analog: 0 to 10V / -10 to 10V/ 0 to 20mA / Digital: Keypad/ Communication
Operation function PID control / Up-Down operation / 3-Wire operation / Slip compensation / Reverse rotation prevention /
Auto tune flying start / Energy buffering / Power braking / Flux braking / Leakage current reduction / MMC
Input signal Multi-function terminal PNP / NPN selectable
(P1 ~ P8) 8 points (programmable)
Output signal Multi-function relay Fault output & inverter status output (N.O., N.C.) Less than AC 250V, 1A / Less than DC 30V 1A
Multi-function open collector DC24V (less than 50mA)
Analog output 0 to 10Vdc (less than 10mA): frequency / current / voltage / DC voltage selectable
Protection Inverter trip Over voltage / Low voltage / Over current / Ground fault detection / Inverter overload / Overload trip /
Inverter overheat / Output phase loss / Overload protection / Frequency command loss / Hardware fault/
Brake fault /Pre-PID fault
Inverter alarm Stall prevention, Overload, Temperature sensor fault , Encoder error , Fan fault ,
Keypad command loss ,Speed command loss
Enclosure IP21, IP54 (Optional: available soon), UL type 1(Optional : available soon)
Option Keypad Graphic LCD display keypad for iS7 (128x64 COG, 11 Rubber Key, 3 LED, IP21)
Board, Cable Expansion I/O, Encoder card, PLC card, Remote cable (2M/3M)
Communication Modbus TCP, Profibus-DP, Rnet, BACnet, CANOpen, LorkWork, DeviceNet
Others Built-in Dynamic brake unit (Up to 22kW), Modbus-RTU, LS Bus
8
iH Robust dual rated high power inverter
3 phase 30 - 55kW, 200V
Variable Frequency Drive / Inverter 3 phase 30 - 220kW, 400V
● Slip compensation
LS inverter brand Motor rating Series name Symbol Input rating Symbol UL Certification Symbol Rated voltage
030:30kW ~ 220: 220kW iH 2 Three-phase, 200 ~ 230V U UL 508C **** 220V, 380V, 440V, 460V
4 Three-phase, 380 ~ 480V
General specification
Model number: SV iH- 030-2U 037-2U 045-2U 055-2U 030-4U 037-4U 045-4U 055-4U 075-4U 090-4U 110-4U 132-4U 160-4U 220-4U
Motor rating Constant Torque [HP] 40 50 60 75 40 50 60 75 100 125 150 175 215 300
Constant Torque [kW] 30 37 45 55 30 37 45 55 75 90 110 132 160 220
Variable Torque [HP] 50 60 75 100 125 150 175 215 250 350
Variable Torque [kW] 37 45 55 75 90 110 132 160 185 280
Output ratings Constant Torque FLA [A] 122 146 180 220 61 75 91 110 152 183 223 264 325 432
(380V based) Constant Torque [kVA] 46 55 68 83 40 50 60 70 100 120 145 170 200 280
Variable Torque FLA [A] 80 96 115 125 160 228 264 330 361 477
Variable Torque [kVA] 52 62 74 80 103 147 170 213 233 307
Voltage [V] Three phase, 200 ~ 230V Three phase, 380 ~ 460V
Frequency [Hz] 0.5 ~ 400Hz 0.5 ~ 400Hz
Input ratings Voltage [V] Three phase, 200 ~ 230V (±10%) Three phase, 380 ~ 460V (±10%)
Frequency [Hz] 50 ~ 60Hz (±5%) 50 ~ 60Hz (±5%)
Weight [kg] 42 42 56 56 45 45 63 63 68 98 98 122 122 175
Input signal Operation method 32 character LCD keypad / Terminals / Communication (RS-485: LS Bus)
Frequency setting Analog: 0 ~ 10V, 4 ~ 20mA, additional port for Sub-Board (0 ~ 10V) / Digital: Keypad / Communication
Start signal Forward / Reverse
Multi-step operation Setting up to 8 speeds (using multi-function terminal)
Multi-step Accel./Decel. time 0.1 ~ 6000 seconds. Maximum 8 pre-defined steps using multi-function terminals
Operation function DC braking / Frequency limit / Frequency jump / Slip compensation / PI control / Stall prevention
Emergency stop Interrupting output from inverter
JOG JOG operation
Fault reset Resets fault signal when protective function is active
Output signal Operational status Frequency detection / Overload alarm / Stall / Overvoltage / Undervoltage / Inverter overheat / Run / Stop
Constant speed / Speed search
Indicator Output frequency / Output current / Output voltage / rpm
Protective Trip Overvoltage / Undervoltage / Overcurrent / Inverter overheat / Motor overheat / Fuse open / Ground fault / Overload
functions Main CPU error
Alarm Stall / Overload
Others LS Bus, Remote cable(2M/3M/5M)
LS Inverter Series 9
iP5A Fan & Pump specialized inverter
3 phase 5.5 - 30kW, 200V
Variable Frequency Drive / Inverter 3 phase 5.5 - 450kW, 400V
● Specialized functions for Fan & Pump : Automatic carrier frequency change
Advanced PID control (Pre-PID, Dual PID) ● Selectable V/f, Sensorless vector control
MMC (Multi Motor Control) function ● Long-life condenser & Simple framework
SV 055 iP5A - 2 N O L
LS inverter brand Motor rating Series name Symbol Input rating Symbol Loader Symbol UL Certification Symbol DCR
055: 5.5kW ~ 4500: 450kW iP5A 2 Three-phase, 200 ~ 230V None Loader O Open type None Not available
4 Three-phase, 380 ~ 480V N Non Loader E Enclosed Type 1 L DC Reactor
General specification
Model number: SV iP5A-2 055 075 110 150 185 220 300
Motor rating [HP] 7.5 10 15 20 25 30 40
(Fan/Pump) [kW] 5.5 7.5 11 15 18.5 22 30
Current [A] 24 32 46 60 74 88 115
(110% overload) Normal duty: 110% for 1 minute
Motor rating [HP] 5 7.5 10 15 20 25 30
(Normal load) [kW] 3.7 5.5 7.5 11 15 18.5 22
Current [A] 17 23 33 44 54 68 84
(110% overload) Heavy duty: 150% for 1 minute
Output rating [kVA] 9.1 12.2 17.5 22.9 28.2 33.5 43.8
Voltage [V] Three-Phase 200 ~ 230V
Frequency [Hz] 0.01 ~ 120Hz
Input rating Voltage [V] Three-Phase 200 ~ 230V (-15% ~ +10%)
Frequency [Hz] 50 ~ 60Hz (±5%)
Enclosure IP00 / UL open
IP20 / UL type1 (IP20 / UL type1 option)
Weight Non DCR type [kg] 4.9 6 6 13 13.5 20 20
Model number: SV iP5A-4 055 075 110 150 185 220 300 370 450 550 750 900 1100 1320 1600 2200 2800 3150 3750 4500
Motor rating [HP] 7.5 10 15 20 25 30 40 50 60 75 100 125 150 175 215 300 350 400 500 600
(Fan/Pump) [kW] 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160 220 280 315 375 450
Current [A] 12 16 24 30 39 45 61 75 91 110 152 183 223 264 325 432 547 613 731 877
(110% overload) Normal duty: 110% for 1 minute
Motor rating [HP] 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 175 215 300 350 400 500
(Normal load) [kW] 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160 220 280 315 375
Current (Non DCR / DCR) [A] 8.8 12 16 22/24 28/30 34/39 44/45 61 75 91 110 152 183 223 264 325 432 547 613 731
(110% overload) Heavy duty: 150% for 1 minute
Output rating [kVA] 9.6 12.7 19.1 23.9 31.1 35.9 48.6 59.8 72.5 87.6 121.1 145.8 178 210 259 344 436 488 582 699
Voltage [V] Three-Phase 380 ~ 480V
Frequency [Hz] 0.01 ~ 120Hz
Input rating Voltage [V] Three-Phase 380 ~ 480V (-15% ~ +10%)
Frequency [Hz] 50 ~ 60Hz (±5%)
Enclosure IP20 / UL type1 IP00 / UL open (IP20/UL type1 option) IP00 / UL open
Weight Non DCR type [kg] 4.9 6 6 12.5 13 20 20 27 27 29 42 43 243 280 380
Built-in DCR type [kg] 19.5 19.5 26.5 26.5 39 40 42 67 68 101 101 114 200 200
Control Spec Control method V/f, Sensorless Vector, Slip compensation, Easy start
Speed reference resolution Digital command: 0.01Hz (less than 100Hz), 0.1Hz (greater than 100Hz) / Analog reference: 0.01Hz (Max freq., 60Hz)
Frequency accuracy Digital command: 0.01% of Max output freq. / Analog signal command of 0.1% of Max output freq.
V/f curve Linear, Squared, User custom V/f
Overload capacity 150% for 1 minute, 110% for 1 minute
Torque boost Auto & manual(0 ~ 15%) torque boost
Keypad Display LCD keypad
Operation method Keypad / Terminal / Communication operation
Frequency setting Analog: 0 to 12V / -12 to 12V/ 0 to 20mA / 4 to 20mA / Digital: Keypad/ Communication
Operation function PID control / DC braking / MMC / Easy start / Dual-PID / Safety stop / Flux braking
Input signal Multi-function terminal PNP / NPN selectable
(P1 ~ P8) 8 points (programmable)
Output signal Multi-function relay Fault output & inverter status output (N.O., N.C.) Less than AC 250V, 1A / Less than DC 30V 1A
Analog output 0 to 12Vdc (less than 1mA)
Protection Inverter trip Over voltage / Low voltage / Over current / Ground fault detection / Inverter overload / Overload trip / Inverter overheat / Output phase loss /
Overload protection / Frequency command loss / Hardware fault
Inverter alarm Stall prevention, Overload, Temperature sensor fault
Option Keypad LCD keypad
Board, Cable Current output card, REMOTE CABLE(2M/3M/5M)
Communication LonWork, BACNet , LS Bus & Modbus RTU, DeviceNet, Profibus-DP
Others Built-in LS Bus
10
iV5 High duty full flux vector control inverter
3 phase 2.2 - 37kW, 200V
Variable Frequency Drive / Inverter 3 phase 2.2 - 375kW, 400V
● High duty full flux vector control inverter ● Built-in braking circuit (up to 22kW)
● Static motor parameter auto-tuning ● Plug-in type control terminals
without disconnecting / motor coupling ● Extended I/O boards (optional)
● Operating with encoder, line drive/open EL I/O (I/O Interface Card for Elevator Application)
collector type ENC_DIV (Encoder division board :Open Collector)
● high torque at zero speed SYNC I/O (Speed / positioning board for
● Position control by encoder feedback Synchronization operation)
● 1: 1000 speed control range Sincos encoder signal input
● 0.01% speed control accuracy ● Monitoring & commissioning software (DriveView)
LS inverter brand Motor rating Series name Symbol Input rating Symbol Dynamic Brake Symbol Mold type Symbol Rated voltage
022: 2.2kW ~ 3750: 370kW iV5 2 Three-phase, 200 ~ 230V None Not available None Metallic cover None 200~230V or 380~480V
4 Three-phase, 380 ~ 480V DB Brake unit (MD) Mold cover *Note) **** 380V, 460V
General specification
Model number: SV iV5-2 022 037 055 075 110 150 185 220 300 370
Motor rating [HP] 3 5 7.5 10 15 20 25 30 40 50
[kW] 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37
Output rating Capacity [kVA] 4.5 6.1 9.1 12.2 17.5 22.5 28.2 33.1 46 55
Current [A] 12 16 24 32 46 59 74 88 122 146
Voltage [V] Three-Phase 200 ~ 230V
RPM 0 ~ 3600 [RPM]
Input rating Voltage [V] Three-Phase 200 ~ 230V (+10%, -10%)
Frequency [Hz] 50 ~ 60Hz (±5%)
Weight Mold cover type [kg] 6 6 7.7 7.7 13.7 13.7 20.3 20.3
Metallic cover type [kg] 14 14 28 28 28 28 42 42
Model number: SV iV5-4 022 037 055 075 110 150 185 220 300 370 450 550 750 900 1100 1320 1600 2200 2800 3150 3750
Motor rating [HP] 3 5 7.5 10 15 20 25 30 40 50 60 75 100 120 150 175 215 300 373 420 500
[kW] 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160 220 280 315 375
Output rating Capacity [kVA] 4.5 6.1 9.1 12.2 18.3 22.9 29.7 34.3 46 57 70 85 116 140 170 200 250 329 416 468 557
Current [A] 6 8 12 16 24 30 39 45 61 75 91 110 152 183 223 264 325 432 546 614 731
Voltage [V] Three-Phase 380 ~ 480V 380V , 460V
RPM 0 ~ 3600 [RPM]
Input rating Voltage [V] Three-Phase 380 ~ 480V (+10%, -10%)
Frequency [Hz] 50 ~ 60Hz (±5%)
Weight Mold cover type [kg] 6 6 7.7 7.7 13.7 13.7 20.3 20.3
Metallic cover type [kg] 14 14 28 28 28 28 42 42 63 63 68 98 98 112 112 175 243 380 380
Control Spec Control method Vector
Speed reference resolution Digital command: ±0.2% (25±10°C) / Analog reference: ±0.01 (0 ~ 40°C)
Frequency accuracy Digital command: 0.01% of Max output freq. / Analog signal command: ±0.005% of Max output freq.
Accel/Decel curve Linear, S-Curve
Accel/Decel torque accuracy 3%
Accel/Decel torque time 0.00 ~ 6000.0 (Second)
Keypad Display LCD keypad
Operation method Keypad / Terminal / Communication operation
Frequency setting Analog: 0 to 10V / -10 to 10V / 0 to 20mA / Potentiometer / Digital: Keypad/ Option
Operation function PID control / Up-Down operation / 3-Wire operation
Input signal Multi-function terminal PNP / NPN selectable *Note)
(P1 ~ P7) 7 points (programmable)
Output signal Multi-function relay Fault output & inverter status output (N.O., N.C.) Less than AC 250V, 0.3A / Less than DC 30V 1A
Multi-function open collector DC24V (less than 50mA)
Analog output -10 to 10Vdc (less than 10mA): frequency / current / voltage / DC voltage selectable
Protection Inverter trip Over voltage / Low voltage / Over current / Ground fault detection / Inverter overload / Overload trip / Inverter overheat /
Output phase loss / Overload protection / Frequency command loss / Hardware fault/ Brake fault
Inverter alarm Overload
Option Communication Profibus, Modbus-RTU, DeviceNet
Board Optional I/O Interface Card for Elevator Application, Encoder division card(open collector),
Speed / positioning card for Synchronization operation, Sin/Cos Encoder Card
*Note) Available soon
LS Inverter Series 11
Comparison
Variable Frequency Drive / Inverter
Single Phase
Dynamic
DC EMC RS485 Modbus Modbus
Model Name Input Power / Motor Rating Control Method Protection Degree Keypad Braking MMC
Reactor Filter (LS BUS) -RTU -TCP
Unit
(200V / 0.1 ~ 0.4kW) ● ■ ■
iE5 V/f IP20 × × × × ×
(200V / 0.13 ~ 0.5hp) All ranges All ranges All ranges
Three Phase
(200V / 0.1 ~ 0.4kW) ● ■ ■
iE5 V/f IP20 × × × × ×
(200V / 0.13 ~ 0.5hp) All ranges All ranges All ranges
(400V / 40 ~ 300hp)
(200V / 2.2 ~ 37kW) 2.2~22kW
(Mold cover): IP00
(200V / 3 ~ 50hp) Flux Vector 5.5~22kW ● ■
iV5 × × ○ ○ × ×
(400V / 2.2 ~ 375kW) Closed loop (Metalic cover): IP20 All ranges 2.2 ~ 22kW
12
●: Built-in / ■: Built-in Option / ○: Optional Board / ×: No Support)
× × × × × × × × × × × × × × × ×
× × × × × × × × × × × × × × × ×
× × × × × × × × × × × × × × × ×
× × × × × × × × × × × × × × × ×
× × × × × × × × × × × × × × × ×
○ ○ ○ ○ ○ × × × × × × × × × × ×
* Note1) * Note1)
○ ○ ○ ○ × ○ ○ ○ × ○ ○ ○ ○ × × ×
× × ○ ○ × × ○ × ○ × × × × × × ×
× × × × × × × × × × × × × × × ×
○
○
Extended ○
● Sync
I/O: 5 Ch ○ ○ × × × × × × × × × Elevator ○
All ranges Operation
Analog Option
Option
Input
LS Inverter Series 13
Option list
Variable Frequency Drive / Inverter
14
Brake unit list
Variable Frequency Drive / Inverter
LS Inverter Series 15