Chapter 1 C.T.
Chapter 1 C.T.
Chapter 1 C.T.
Chapter 1
Current Transformers
Introduction
Practically all electrical measurements and relaying
decisions are derived from current and voltage signals. Since relaying
hardware works with smaller range of current (in amperes and not kA)
and voltage (volts and not kV), real life signals (feeder or transmission
line currents) and bus voltages have to be scaled to lower levels and
then fed to the relays. This job is done by current and voltage
transformers (CTs and VTs). CTs and VTs also electrically isolate the
relaying system from the actual power apparatus. The electrical
isolation from the primary voltage also provides safety of both human
personnel and the equipment. Thus,
• CT and VTs are the sensors for the relay.
• CT and VT function like ‘ears' and the ‘eyes' of the protection
system. They listen to and observe all happening in the external
world. Relay itself is the brain which processes these signals and
issues decision commands implemented by circuit breakers, alarms
etc.
• Clearly, quality of the relaying decision depends upon ‘faithful'
reproduction on the secondary side of the transformer.
1
7/25/2018
Equivalent Circuit of CT
To begin with,
equivalent circuit of a CT is
not much different from that
of a regular transformer (fig
5.1). However, a fundamental
difference is that while
regular power transformers
are excited by a voltage
source, a current transformer
has current source excitation.
Primary winding of the CT is
connected in series with the
transmission line. The load on
the secondary side is the
relaying burden and the lead
wire resistance.
2
7/25/2018
3
7/25/2018
Classification of CTs
4
7/25/2018
5
7/25/2018
6
7/25/2018
Class C CT
Letter designation 'C' indicates that the leakage
flux is negligible. Class C CTs are the more accurate bar type
CTs. In such CTs, the leakage flux from the core is kept very
small. For such CTs, the performance can be evaluated from
the standard exciting curves. Also, the ratio error is
maintained within ± 10% for standard operating conditions.
For such CTs, voltage rating on the secondary is specified up to
which linear response is guaranteed. For example, a class C CT
specification could be as follows: 200:5 C 100. The labeling
scheme indicates that we are dealing with a 200:5 class C CT
which will provide linear response up to 20 times rated
current provided the burden on the secondary is kept below
(100/(5*20)=1) ohm. Similarly, a corresponding class T CT
may be labeled as 200:5 T 100. For class C CTs, standard chart
for E2 versus excitation current on the secondary side is
available. This provides the protection engineer data to do
more exact calculations (refer fig 5.7). e.g., in determining
relaying sensitivity
7
7/25/2018
8
7/25/2018
9
7/25/2018
10
7/25/2018
11
7/25/2018
12
7/25/2018
13
7/25/2018
14
7/25/2018
15
7/25/2018
16
7/25/2018
CT Oversizing Factor
Cautions in CT Selection
While choosing a CT for a particular application, it is
necessary to observe following precautions.
• The CT rating and continuous load current should match. For
example, if maximum load current is 90A, a 100:5 CT may be
acceptable but 50:5 is not acceptable.
• The maximum fault current should be less than 20 times the CT
rated current. For example, 100:5 CT can be used, so long as burden
on the CT is within the rated values and maximum primary fault
current is below 2000A.
• The voltage rating of CT should be compatible. For example, 100:5
C100 would give linear response, up to 20 times rated current
provided CT burden is kept below(100/20 x 5 = 1 ). With 2 burden,
this CT can be used only if maximum current is limited to 1000A.
• Paralleling of CT's e.g. in differential protection, or with SLG fault
can create significant errors in CT performance. One should
generally ascertain that magnetizing current is kept much below the
pick up value.
17
7/25/2018
18
7/25/2018
19
7/25/2018
Many relaying
applications like distance
relays, directional
overcurrent relays require
measurement of voltages at
a bus. This task is done by a
voltage transformer (VT).
The principle of a voltage
transformer is identical to
the conventional
transformer. Hence, its
equivalent circuit can be
represented as shown in fig
8.1.
20
7/25/2018
Typically, the
secondary voltage of the VT
is standardized to 110 V (ac).
Hence, as the primary
voltage increases, the turns
ratio N1:N2 increases and
transformer becomes bulky.
To cut down the VT
size and cost, a capacitance
potential divider is used (fig
8.2). Thus, a reduced
voltage is fed to primary of
the transformer. This
reduces the size of VT. This
leads to development of
coupling capacitor voltage
transformers (CCVT).
21
7/25/2018
22
7/25/2018
23
7/25/2018
24
7/25/2018
Classification of CCVTs
CCVTs can be classified into following two types:
• Class 1
• Class 2
Table 8.1 shows the maximum limit for the ratio and phase angle errors. It
can be seen that errors of Class 2 type are double than that of class 1 type.
25
7/25/2018
26
7/25/2018
27
7/25/2018
28
7/25/2018
29
7/25/2018
30
7/25/2018
31
7/25/2018
32
7/25/2018
33