Qis 10
Qis 10
Qis 10
1/8
Technical specifications
Diesel Generator Set
QIS 10
Voltage: 400/230 V
Frequency: 50HZ
g
TECHNICAL INFORMATION
kVA 10,2
Standby Power (ESP)
kW 8,2
kVA 9
Prime Power (PRP)
kW 7,2
Fuel tank L 55
Notes:
PRIME POWER: Electrical power data available at a variable load without limits of hours per year. An overload of
10 % is allowed for 1 hour of every 12. In accordance with ISO 8528/1 (2005) – PRP
STANDBY POWER: Electrical power data at variable load in an emergency in accordance with standard ISO
8528/1 (2005) – ESP. Overloads of emergency power are not allowed.
The standard reference conditions are: 25 ºC, 100 kPa and 30% relative humidity. Gasoil density: 0.85 g/cm3.
Gasoline density: 0.68 g/cm3.
Email: [email protected] • www.gesan.com
QIS 10 | 400/230 V | 50HZ |
2/8
g
INDEX
General description
Engine
Alternator
Soundproofed canopy
Electric Panel
ATS
Performance class
Regulation
Annex: Drawings
Grupos Electrógenos Europa, S.A. is a certified company with ISO 9001, ISO 14001, OHSAS 18001 and PECAL
We reserves the right to modify any characteristic of their equipment without prior warning.
Photographs representing the product range, while able to include options.
Weight and dimensions of a standard generator set.
Non-contractual document
Central Offices:
Polígono Industrial Pitarco II; Parcela 20
50450 Muel (Zaragoza) Spain
Tel.: +34 976 14 54 32
Fax: +34 976 14 54 31
[email protected]
After-sales Department:
Customer service: +34 976 14 54 33
Spare parts: +34 976 14 54 34
3/8
g
GENERAL DESCRIPTION
Specifically developed for the industrial applications, this stationary soundproof generator set is easy to use and
straightforward to maintain. The available features & options are designed to fully meet the requirements of all
industrial applications. The generator set will automatically start on mains failure and cool down and stop as soon as
the mains come back. The generator set also controls the load transfer between mains (utility) and generator set. It
can also be start-up by means of an external signal.
It’s your solution for Predictable Power.
g
ENGINE
Cooling System
The cooling system consists of a radiator, expansion tank, water pump, engine-driven cooling fan and thermostat, all of
them original from the engine manufacturer.
It is cooling the engine block thanks to a pressurized forced-circulation of 50/50 mixture of Ethylene Glycol anti-freeze.
All the rotating parts are protected.
Lubrication System
D1105-BG2- D1703M-BG-V2403M-BG-V3300DI
The air intake system for combustion consists of heavy duty air filter (dual stage filter and safety cartridge) and air
restriction indicator, original from the engine manufacturer.
Exhaust System
The exhaust system consists of aluminized pipes, stainless steel flexible pipes, interior and exterior aluminized steel
exhaust silencer that is highly resistant to corrosion and rain cap. Hot part protections are available in option to
comply with CE certificate.
4/8
Start system
The starting system consists of electrical starter, lead acid battery and 12V battery charger alternator that is driven by
the engine itself. The starter and the battery charger alternator are originals from the engine manufacturer.
The system can be completed by an optional battery switch.
The fuel system consists of a fuel tank, feed pump, water separator fuel filter including 30 microns filtering element,
injection pump and injection nozzles.
The fuel tank is made from plastic to prevent rust and includes a filling connection with cap and key, a cleaning hatch
and draining plug for easier maintenance. The fuel level is controlled thanks to a fuel level sensor with an analogue
gauge mounted in the control cubicle.
25% 1,5 37
50% 1,6 34
75% 2,1 26
5/8
g
ALTERNATOR
Mecc Alte alternator with 4 poles, with a lifetime lasting greased bearing, H class insulation, without brushes, 2/3 coil and
AVR (Automatic Voltage Regulator)
Protection of all the windings by means of 2-part high quality polyester resin impregnation. The stator windings receive a
double impregnation.
Excitation system with MAUX auxiliary winding with overload capacity 3 times the nominal current for 20 s.
Regulations:
• CEI 2-3
• IEC 34-1
• EN 60034-1
• VDE 0530
• BS 4999-5000
• CAN/CSA-C22.2 No14-68-No100-95
• ISO 8528:3
• THC < 4%
• THD < 4%
• THF (IEC) < 2%
• TIF (NEMA) < 45
Incorporates electromagnetic emissions suppressor in accordance with standard VDE 0875, class K.
6/8
g
SOUNDPROOFED CANOPY
Soundproof generator set by means of galvanized, phosphate steel, passivated and finish using polyester dust paint that
guarantees a resistance of at least 720 hours in a saline fog chamber in accordance with standard ASM B-117-09.
The canopy includes an external access to the lifting beam and push to close latches with key. The lifting beam is available
as an option.
It is lined inside with a noise-absorbing material of polyurethane foam with a 30 mm thick waterproof protector veil with a
density of 25 kg/m3.
It also has an emergency shutdown pushbutton that is accessible from the outside.
g
ELECTRIC PANEL
Easily accessed control cubicle integrated in the generator set with digital controller providing advanced engine
monitoring and protection features. Performance and maintenance requirements can also be observed. The cubicle
includes multi-poles thermal-magnetic protection circuit breaker against overloads and short-circuits.
Easily accessed control cubicle integrated in the generator set with digital controller providing advanced engine
monitoring and protection features. Performance and maintenance requirements can also be observed. The cubicle
includes multi-poles thermal-magnetic protection circuit breaker against overloads and short-circuits.
7/8
Control Card
DEEP SEA control plate, DSE 4620 with grid monitor that starts-up the generator set when it detects a failure in the
electrical power supply from the grid and sends a signal to the switching panel to switch from the grid position to the
group position . Once the power supply has been re-established, it sends an order to the switching panel to transfer
the generator set power to the grid and shuts-down the generator set once it has cooled down. It also starts-up the
generator set using an external signal.
Also, control plate DSE 4620 checks a large number of parameters of the generator set which allows it to display
information, statuses and alarms. If required, it will shutdown the generator set: Due to high coolant fluid
temperature, low oil pressure, low coolant fluid level, etc.
Includes a LCD screen with lighting, 2 navigation menubuttons, independent operational mode buttons, and alarms
and status indicating LEDs.
Communications via USB, and Completely configurable using a PC in Windows environment and free Scada type
software in real time.
Includes reading and displaying of parameters with RMS values, real time clock, events history log up to 15 events
and programming of alarms, events, start-ups and shutdowns.
Operating modes: START-UP, SHUTDOWN, AUTO, MANUAL AND TEST.
Generator
• Generator voltage (L-N)
• Generator voltage (L-L)
• Generator frequency
• Generator current
• kW
• kVA
• kWh
• kVAh
• Power factor
Grid
• Grid voltage (L-N)
• Grid voltage (L-L)
• Grid frequency
Engine
• Turn speed
• Cooling fluid temperature
• Oil pressure
• Hour meter
• Battery voltage
• No. of start-ups
• Fuel level
Protections
• Start-up fault (generator set shutdown)
• High coolant temperature (alarm and generato r set
shutdown)
• Low oil pressure (alarm and generator set shutdown)
• Low fuel level (alarm)
• Low cooling fluid level (generator set shutdown)
• Overload (alarm and generator set shutdown)
• Battery voltage high (alarm)
• Battery voltage low (alarm)
• Battery charge alternator failure (alarm)
• Generator low frequency (alarm and shutdown)
• Generator high frequency (alarm and shutdown)
• Generator low voltage (alarm and shutdown)
• Generator high voltage (alarm and shutdown)
• External emergency shutdown (shutdown)
• Engine overspeed (shutdown)
• Maintenance interval (alarm)
8/8
g
ATS
Optional Cabinet for switching between the grid and the generator set by means of Schneider brand contactors with an
integrated mechanical and electrical interlocking device.
High dynamic resistance against short-circuits. Stable positions not affected by the changes in voltage and mechanical
vibrations. IP66 protection. Connections: Lower/lower.
g
DIMENSIONS AND WEIGHT
g
PERFORMANCE CLASS
Execution class in accordance with ISO 8528/5 (2005) taking into account the behaviour of the generator set in a
permanent mode of operation with different load levels, as well as in a temporary mode of operation due to shocks in the
load.
Performance class G2
g
REGULATION
The generator set has a CE Marking that includes the following directives:
• ISO 8528
• ISO 3046
• BS 5000
• IEC 60034
95
650
95 A
94 n 16 (x4) B
100
254
786
735
240
1152
C
1105
734
167 211
Fuel tank drain
452
250
62
163
250 156 188 652 188 279 730 Entry for
69
MAINTENANCE SPACE ( 1 : 15 )
353
55
211 35
R670
260
R669
420
E
1200
320
800
715
685
1000
185
131
697 250 804
20
1000
788
This document is our property and shall not without our pur permission be altered,
copied, used for manufacturing or communicated to any other person or company
Note:
1200
Treatment
Thickness: INV
CONFIDENTIAL:
422
355
1098
1077
1053
892
C
571
156 188 652 188 279
D
1510
130
copied, used for manufacturing or communicated to any other person or company.
This document is our property and shall not without our permission be altered,
n 64
1053
Tolerances, if not indicated, according to:
Ed
Posi-
tion
Gewijzigd van
Modified from
Datum
Date
Ingev./Goedg.
Intr./Appd.
Parent 3D model Ed . Version 3D Approved
Des checked. Prod checked. Approved. Date
17/09/2014 1636005784