<<Contents>> <<Index>>
General YTA series
Specifications Fieldbus Communication
GS 01C50T02-00EN
Fieldbus is the digital communication line for the
field instruments, whose signal is internationally
standardized by Fieldbus Foundation.
The Fieldbus bi-directional digital communication
performance makes possible for the field instruments
and the control devices to be a complete on-line
system, superseding the existing analog transmission
lines. Also, the precise transmission of various
process data including the PV and MV of the field
instruments is well established by the Fieldbus
multisensing function. Thus, based on FOUNDATION
Fieldbus specifications, YTA320 Fieldbus model offers
more flexible instrumentation through a higher level
communication capability and proposes the cost
reduction by multi-drop wirings with less cables.
FEATURES STANDARD SPECIFICATIONS
● Interoperability For items other than those described below, refer to
FOUNDATION Fieldbus specifications grant the GS 01C50B02-00EN.
interoperability of the field instruments without Applicable Model:
preparing designated softwares for the instrument. YTA320
● Reduction of instrumentation cost Output Signal:
The multi-drop wiring on the Fieldbus communication Digital communication signal based on FOUNDATION
line contributes to the reduction of wiring cost. Fieldbus protocol.
● Four AI and DI function blocks Supply Voltage:
YTA320 Fieldbus model has four independent AI 9 to 32 V DC for general use, flameproof type,
function blocks whose input can be selected from Type n, or nonincendive
Sensor1 input, Sensor2 input, terminal temperature, 9 to 24 V DC for intrinsically safe type Entity model
differential temperature, average temperature, and 9 to 17.5 V DC for intrinsically safe type FISCO
back-uped input. Four DI function blocks can be used model
as a limit switch for those temperature.
Conditions of Communication Line:
● Alarm function Supply Voltage: 9 to 32 V DC
YTA Fieldbus models securely support various Supply Current: 16.6 mA (max)
alarm functions, such as high/low alarm, notice of
block error, etc. based on FOUNDATION Fieldbus Functional Specifications:
specifications. Functional specifications for Fieldbus communication
conform to the standard specifications (H1) of
● Self-diagnostic function FOUNDATION Fieldbus.
The reliable self-diagnostic function detects such Function Block:
failure as measuring range failure and abnormal Four AI function blocks
ambient temperature, as well as the hardware failure. Four DI function blocks
● PID function block (option) One/Two PID function blocks (option)
PID function block enables field devices to control Link Master function
processes. Up to two blocks can be specified.
Yokogawa Electric Corporation GS 01C50T02-00EN
2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan ©Copyright Sep. 2000
Tel.: 81-422-52-5690 Fax.: 81-422-52-2018 17th Edition Apr. 2016
<<Contents>> <<Index>> 2
MODEL AND SUFFIX CODE
YTA320-F/
└─ Output signal . . . Digital communication (FOUNDATION Fileldbus protocol)
OPTIONAL SPECIFICATIONS
Item Description Code
TIIS certification TIIS Flameproof Approval,
JF3
Ex ds IIC T6 X Amb. Temp.: –20 to 60°C
Attached flameproof Electrical connection: G1/2 female
2pc. G12
packing adapter*1 Applicable cable: O.D. 8.5 to 11 mm
ATEX ATEX Flameproof and Dust Ignition Proof Approval
Applicable Standard: EN 60079-0: 2012+A11: 2013, EN 60079-1: 2007, EN 60079-31:2009
Certificate: KEMA 07ATEX0130
II 2 G Ex d IIC T6/T5 Gb, II 2 D Ex tb IIIC T70°C, T90°C Db
KF2
Ambient Temperature for Gas Atmospheres: −40 to 75°C for T6, −40 to 80°C for T5
Ambient Temperature for Dust Atmospheres: −30 to 65°C for T70°C, −30 to 80°C for T90°C
Enclosure: IP66/IP67
Electrical Connection: 1/2 NPT female and M20 female*3
ATEX Intrinsically Safe ia Approval
Applicable Standard: EN 50014: 1997, EN 50020: 2002, EN 50284: 1999, EN 60529: 1999
Certificate: KEMA 02ATEX1324 X
[Entity model]
ll 1G EEx ia llC T4, Ambient Temperature: −40 to 60°C (−40 to 140°F)
Supply Circuit: Ui=24 V DC, Ii=250 mA, Pi=1.2 W, Ci=1.5 nF, Li=8 µH
[FISCO model] KS25*4
ll 1G EEx ia llC T4, Ambient Temperature: −40 to 60°C (−40 to 140°F)
Supply Circuit: Ui=17.5 V DC, Ii=360 mA, Pi=2.52 W, Ci=1.5 nF, Li=8 µH
ll 1G EEx ia llB T4, Ambient Temperature: −40 to 60°C (−40 to 140°F)
Supply Circuit: Ui=17.5 V DC, Ii=380 mA, Pi=5.32 W, Ci=1.5 nF, Li=8 µH
Sensor Circuit: Uo=7.7 V, Io=70 mA, Po=140 mW, Co=1.6 µF, Lo=7.2 mH
Electrical Connection: 1/2 NPT female and M20 female*3
ATEX Intrinsically safe ic
Applicable standard: EN 60079-0:2012, EN 60079-11:2012
II 3 G Ex ic IIC T4 Gc Ambient Temperature: −30 to 70°C
Enclosure: IP66/IP67 KN25
Supply/Output circuit: Ui=32 V, Ci=2.4 nF, Li=8 µH
Input circuit: Uo=7.7 V, Io=70 mA, Po=140 mW, Co=1.6 µF, Lo=7.2 mH
Electrical connection: 1/2 NPT female and M20 female*3
Factory Mutual (FM) FM Explosionproof Approval
Applicable Standard: FM 3600, FM 3615, FM 3810, ANSI/NEMA 250
Explosionproof Class I, Div.1, Groups A, B, C and D;
Dust-ignitionproof for Class II/III, Div. 1, Groups E, F and G. FF1
“FACTORY SEALED, CONDUIT SEAL NOT REQUIRED.” Enclosure Rating: TYPE 4X
Temperature Class : T6 Ambient Temperature: −40 to 60°C (−40 to 140°F)
Electrical Connection: 1/2 NPT female*2
FM Intrinsically Safe Approval
Applicable Standard: FM 3600, FM 3610, FM 3611, FM 3810, NEMA250, ANSI/ISA-60079-0,
ANSI/ISA-60079-11
IS-AIS/I, II, III/1/ABCDEFG/T4 Ta=60°C; Type 4X
I/0/AEx ia IIC T4 Ta=60°C
Nonincendive Approval
NI-ANI/I/2/ABCD/T4 Ta=60°C; Type 4X
I/2/IIC/T4 Ta=60°C; Type 4X
S-ANI/II/2FG/T4 Ta=60°C; Type 4X
Dust Approval
DIP/III/1/T4 Ta=60°C; Type 4X
Entity Parameters:
FS15
Groups A, B, C, D, E, F and G and Group IIC :
Vmax=24 V, Imax=250 mA, Pi=1.2 W, Ci=1.5 nF, Li=8 µH
Nonincendive Field Wiring Paremeters:
Groups A, B, C, D, F and G and Group IIC : Vmax=32 V, Ci=1.5 nF, Li=8 µH
FISCO Paremeters:
Groups A, B, C, D, E, F and G and Group IIC :
Vmax=17.5 V, Imax=360 mA, Pi=2.52 W, Ci=1.5 nF, Li=8 µH
Groups C, D, E, F and G and Group IIB :
Vmax=17.5 V, Imax=380 mA, Pi=5.32 W, Ci=1.5 nF, Li=8 µH
Maximum Entity and Nonincendive Field Wiring Parameters: Output Terminals
Vt=6.7 V, It=60 mA, Ca=10 µF, La=10 mH, Po=100 mW
Electrical Connection: 1/2 NPT female*2
All Rights Reserved. Copyright © 2000, Yokogawa Electric Corporation GS 01C50T02-00EN Apr. 15, 2016-00
<<Contents>> <<Index>> 3
Item Description Code
Canadian Standards CSA Explosionproof Approval
Association (CSA) Applicable Standard: C22.2 No0, C22.2 No0.4, C22.2 No25, C22.2 No30, C22.2 No94,
C22.2 No142, C22.2 No157, C22.2 No213, C22.2 No1010.1
Certificate: 1089576
Explosionproof Class I, Div.1, Groups B, C and D, Class II, Groups E, F and G, Class III. CF1
Enclosure TYPE 4X
Temperature Class: T4
Ambient Temperature: −40 to 60°C (−40 to 140°F)
Electrical Connection: 1/2 NPT female*2
IECEx IECEx Flameproof and Dust ignition proof Approval
Applicable Standard: IEC 60079-0: 2011, IEC 60079-1: 2007-04, IEC 60079-31:2008
Certificate: IECEx KEM 07.0044
Ex d IIC T6/T5 Gb, Ex tb IIIC T70°C, T90°C Db
Ambient Temperature for Gas Atmospheres: −40 to 75°C (−40 to 167°F) for T6,
SF2
−40 to 80°C (−40 to 176°F) for T5
Ambient Temperature for Dust Atmospheres: −30 to 65°C (−22 to 149°F) for T70°C,
−30 to 80°C (−22 to 176°F) for T90°C
Enclosure: IP66/IP67
Electrical Connection: 1/2 NPT female and M20 female
IECEx Intrinsically safe and type n
Applicable Standard: IEC 60079-0: 2000, IEC 60079-11: 1999, IEC 60079-15: 2001
Certificate: IECEx CSA 05.0014
Ex ia IIC T4, Ex ia IIB T4, Ex nL IIC T4 Enclosure: IP66, IP67
Amb. Temp.: –40 to 60°C (–40 to 140°F)
Electrical Parameters:
SS25
[Ex ia Entity model] Ui=24 V, Ii=250 mA, Pi=1.2 W, Ci=1.5 nF, Li=8 μH
[Ex ia IIC FISCO model] Ui=17.5 V, Ii=360 mA, Pi=2.52 W, Ci=1.5 nF, Li=8 μH
[Ex ia IIB FISCO model] Ui=17.5 V, Ii=380 mA, Pi=5.32 W, Ci=1.5 nF, Li=8 μH
[Ex nL] Ui=32 V, Ci=1.5 nF, Li=8 μH
[Sensor Output] Uo=7.7 V, Io=70 mA, Po=140 mW, Co=1.6 μF, Lo=7.2 mH
Electrical Connection: 1/2 NPT female or M20 female*3
PID function PID control function (one block) LC1
PID control function (2 blocks) LC2
*1: If cable wiring is to be used to a TIIS flameproof type transmitter, add the YOKOGAWA-assured flameproof packing
adapter.
*2: Applicable for Electrical connection code 2.
*3: Applicable for Electrical connection code 2 and 4.
*4: Because the examination of conformity to the updated standards is under the way, intrinsically safe type EX ia (option:
KS25 for Fieldbus communication type) is pending the sale to EEA market.
All Rights Reserved. Copyright © 2000, Yokogawa Electric Corporation GS 01C50T02-00EN Apr. 15, 2016-00
<<Contents>> <<Index>> 4
< Settings When Shipped >
Sensor type ‘Pt100, 3 wire system’(for both inputs), or as specified in order.
Tag Number (PD tag) ‘TT1001’ unless otherwise specified in order.
(Not engraved on tag plate in such case.) *1
Output Mode (L_TYPE) ‘Direct’ unless otherwise specified in order
Calibration Range (XD_SCALE) Lower/Higher Range Value ‘0 to 100’, or as specified in order
Unit of Calibration Range Selected from °C and Kelvin. (Only one unit can be specified.)
When optional code /D2 is specified, °F and °R can also be specified.
Output Scale (OUT_SCALE) Lower/Higher Range Value ‘0 to 100%’
Node Address (in hexadecimal) ‘0xF3’ unless otherwise specified in order
Operation functional Class ‘BASIC’, or as specified
Sensor back up*2 ‘DISABLE’, or as specified
*1: Specified Tag Number is entered in the amplifier memory and also engraved on the stainless steel plate.
Restrictions: Up to 16 letters using any of alphanumerics and symbols of [–] and [ . ].
*2: Channel settings of AI function blocks depend on sensor back up setting.
Sensor Back up AI1 Channel AI2 Channel
DISABLE ‘Sensor1’ ‘Sensor2’
(Terminal board temperature.’ when Sensor2
type is ‘Non-connection’)
ENABLE Backup temperature ‘Terminal board temperature.’
(Sensor1 under normal condition, Sensor2 when
Sensor1 is in burn out mode)
Explanation of Fieldbus parameters:
(1) XD_SCALE: Set the input value from Transducer block (input range of sensor) which corresponds to 0% value
and 100% value of the calculation in the AI function block. In the case of YTA320, the value set as calibration
range should be entered to this parameter.
(2) OUT_SCALE: Output scaling parameter. Set the output value which corresponds to 0% value and 100%
value of the calculation in the AI function block. In the case of YTA320, the value set as output scale should
be entered to this parameter and set as ‘ 0 to 100 %’ upon shipment . When integral indicator is required, this
output is shown on LCD.
(3) L_TYPE: Determines if the values passed by the tranducer block to the AI block may be used directly (Direct)
or if the value is in different units and must be converted linearly (Indirect) or with square root (Indirect SQRT),
using the input range defined by XD_SCALE and the associated output range (OUT_SCALE).
< Ordering Information > Example; When 0 to 200 °C for calibration range is
Model, suffix codes, and optional codes Specify required, specify the values as follows:
followings if necessary.
Calibration range: Lower value 0
1. Sensor type for both two inputs. For RTD and Upper value 200
resistance input, specify the number of wire as well. Calibration unit: °C
(Example; Pt200 3-wire system)
2. Calibration range (XD_SCALE) < Related Instruments >
3. Units of calibration range: The customer should prepare instrument maintenance
Specify only one unit from the table, ‘Settings when tool, terminator, fieldbus power supply etc.
shipped.’
4. Output mode (L_TYPE) Supplier Type Model
Select ‘Direct’ or ‘Indirect Linear.’ P+F Isolator KLD2-PR-Ex1. IEC1 (FISCO)
5. Tag Number (PD tag)
Specify software tag (up to 30 letters) to be written < Reference >
on the amplifier memory and Tag number (up to 16 FOUNDATION; Trademark of Fieldbus Foundation.
letters) to be engraved on the tag plate separately.
6. Node Address
7. Operation Functional Class
Select ‘BASIC’ or ‘LINK MASTER’.
8. Sensor back up