SQN3&4 Electromotoric Actuators
SQN3&4 Electromotoric Actuators
SQN3&4 Electromotoric Actuators
Actuators SQN3...
SQN4...
Electromotoric actuators for use with air dampers and control valves of oil or gas
burners of small to medium capacity.
The SQN3... / SQN4... and this Data Sheet are intended for use by OEMs which
integrate the actuators in their products!
Use / features
The SQN3... / SQN4... actuators are designed to drive gas and air dampers on small to
medium-capacity oil or gas burners or for the load-dependent control of fuel and
combustion air volume:
- In connection with P-PI or PID controllers, such as the RWF...
- Directly via the different types of burner controls, such as LOA..., LMO..., LMG... or
LFL...
- In connection with 1- or 2-wire control or 3-position controllers
CC1N7808en
Building Technologies Division
13.05.2016 Infrastructure & Cities Sector
Warning notes
To avoid injury to persons, damage to property or the environment, the following
warning notes must be observed!
All activities (mounting, installation and service work, etc.) must be performed by
qualified staff
Before making any wiring changes in the connection area of the actuators,
completely isolate the equipment from the mains supply (all-polar disconnection).
Ensure that the plant cannot be inadvertently switched on again and that it is
indeed dead. If not observed, there is a risk of electric shock hazard
Ensure protection against electric shock hazard by providing adequate protection
for the connection terminals and by securing the housing cover
Each time work has been carried out (mounting, installation, service work, etc.),
check to ensure that wiring is in an orderly state
Fall or shock can adversely affect the safety functions. Such actuators must not be
put into operation, even if they do not exhibit any damage
Mounting notes
Ensure that the relevant national safety regulations are complied with
Compliance with the regulations of the applied directives is verified by the adherence to
the following standards / regulations:
Automatic electrical controls for household and similar use DIN EN 60730-1
Part 1: General requirements
Automatic electrical controls for household and similar use DIN EN 60730-2-14
Part 2-14: Particular requirements for electric actuators
The relevant valid edition of the standards can be found in the declaration of
conformity!
ISO 9001:2008
ISO 14001:2004
OHSAS 18001:2007
Disposal notes
The actuator contains electrical and electronic components and must not be disposed
of together with domestic waste.
Local and currently valid legislation must be observed.
2/17
7808p08e/0205
Pin "K"
Position indication - Internally: Scale on the gear train side of the camshaft
- Externally: Scale in viewing window (refer to «Dimensions»)
Mounting and fixing - Front of the gear train is used as the mounting surface
- Actuator is secured via through-holes
3/17
Example:
SQN31.111A2700 basic type
SQN31.112A2700 version for fitting a potentiometer
Conversion by the user Users have the choice of converting a basic type of actuator to a version for fitting a
potentiometer. For that, a conversion kit type AGA32 is available (refer to «Ordering»).
Attention!
Conversion of the basic type reference must be noted by the user on the actuator’s
type field using a permanent felt-tip pen.
4/17
Diagram Drive Running Operating Holding HS Relay Housing Types for mains voltage / mains frequency
shaft ¹) time torque torque 7) length ¹) AC 220 V -15 % AC 100 V -15 %
at 50 Hz ²) (max.) AC 240 V +10 % AC 110 V +10 %
no. no. for 90° Nm Nm pcs. pcs. mm 50...60 Hz 4) 50...60 Hz 3)
s
0 0 4.5 1 0.8 3 --- 125 SQN30.102A2700 5) ---
1 0 4.5 1 0.8 2 1 110 SQN30.111A2700 SQN30.111A1700
1 0 4.5 1.5 0.8 2 1 110 SQN30.111A3500 ) ---
2 0 4.5 1 0.8 1 2 110 SQN30.121A2700 SQN30.121A1700
2 0 4.5 1.5 0.8 1 2 110 SQN30.121A3500 ) ---
3 0 4.5 1 0.8 1 2 110 SQN30.131A2700 SQN30.131A1700
5 0 4.5 1 0.8 1 2 110 SQN30.151A2700 SQN30.151A1700
5 0 12 1.8 1.8 1 2 110 SQN30.251A2700 SQN30.251A1700
0 0 30 3 3 3 --- 110 SQN30.401A2700 ---
0 3 30 3 3 3 --- 110 SQN30.401A2730 ---
0 0 30 3 3 3 --- 125 SQN30.402A2700 5) SQN30.402A1700 5)
0 3 30 3 3 3 --- 125 SQN30.402A2730 5) ---
1 0 30 3 3 2 1 110 SQN30.411A2700 ---
3 0 30 3 3 1 2 110 SQN30.431A2700 ---
5 0 30 3 3 1 2 110 SQN30.451A2700 ---
Diagram Drive Running Operating Holding HS Relay Housing Types for mains voltage / mains frequency
shaft ¹) time torque torque 7) length ¹) AC 220 V -15 % AC 100 V -15 %
at 50 Hz ²) (max.) AC 240 V +10 % AC 110 V +10 %
no. no. for 90° Nm Nm pcs. pcs. mm 50...60 Hz 4) 50...60 Hz 3)
0 0 4.5 1 0.8 3 --- 110 SQN31.101A2700 SQN31.101A1700
0 0 4.5 1 0.8 3 --- 125 SQN31.102A2700 5) SQN31.102A1700 5)
1 0 4.5 1 0.8 2 1 110 SQN31.111A2700 ---
1 6 4.5 1 0.8 2 1 110 SQN31.111A2760 ---
2 0 4.5 1 0.8 1 2 110 SQN31.121A2700 ---
2 3 4.5 1 0.8 1 2 110 SQN31.121A2730 ---
2 6 4.5 1 0.8 1 2 110 SQN31.121A2760 ---
5 0 4.5 1 0.8 1 2 110 SQN31.151A2700 SQN31.151A1700
5 3 4.5 1 0.8 1 2 110 SQN31.151A2730 ---
2 0 12 1.8 1.8 1 2 110 SQN31.221A2700 ---
2 3 12 1.8 1.8 1 2 110 SQN31.221A2730 ---
5 0 12 1.8 1.8 1 2 110 SQN31.251A2700 SQN31.251A1700
5 3 12 1.8 1.8 1 2 110 SQN31.251A2730 ---
0 0 12 1,8 1,8 3 --- 125 SQN31.202A2700 5) ---
5 0 12 1.8 1.8 1 2 125 SQN31.252A2700 5) SQN31.252A1700 5)
5 0 15 2 1.8 1 2 110 SQN31.351A2700 ---
0 0 30 3 3 3 --- 110 SQN31.401A2700 SQN31.401A1700
0 3 30 3 3 3 --- 110 SQN31.401A2730 ---
0 6 30 3 3 3 --- 110 SQN31.401A2760 ---
0 0 30 3 3 3 --- 125 SQN31.402A2700 5) SQN31.402A1700 5)
1 0 30 3 3 2 1 110 SQN31.411A2700 ---
1 3 30 3 3 2 1 110 SQN31.411A2730 ---
6 0 23 2.5 2.5 --- 2 125 SQN31.762A2700 5) ---
4 0 120 6 6 2 1 110 SQN31.941A2700 ---
5/17
Ordering
Actuator refer to «Type summary»
6/17
Attention!
Condensation, formation of ice and ingress of water are not permitted!
7/17
8/17
Note!
The following connection diagrams show the actuator’s start position as supplied:
- End switch position II (CLOSED)
- Dead
BV1
HS
N 3 1 2 4 10 8 9 13 11 12 7 5 6 **) In case of modulating operation, fuel
I 0 valve «BV2» is replaced by a gas
Si
N L
control valve «RV»
I II III IV V
M
LK
~ 1)
RV
0
SQN3x.x0xAxxxx 7808a11/1004
A B C D
Program sequence diagram shows
R
modulating operation
M1
M2
BV1
LR *)
RV
FS
t1
LKP
SA M
I NL I I
7808d05/1004
LK **
III KL III III
RV** II ZU II
t
9/17
*)
LR
BV1 *) Thermostat or similar with NO
SB
contact (1-wire control)
HS BV2
I 0 N 7 3 1 6 5 2 4 10 8 9 13 11 12
Si
N L
I II III IV
M
~ LK
1
7808a12/1004
SQN3x.x1xAxxxx
A B C D
R
M1
M2
BV1
LR
BV2
FS
t1
LKP
7808d07/1004
I NL I I
SA M IV IV IV IV
KL III IV
III
LK ZU II III
II
t
10/17
R
Z *) Thermostat or similar with NO contact
OH
AL M
BV1
(1-wire control)
*)
LR
BV2
SB
HS
N 1 2 6 7 5 4 3
7808a09/1204
I 0
Si
b1 b2 B
3) Cams III and IV are rigidly connected
N L
III 3)
IV
a b a b
A
a3 a2
II I V
MS
a b a b a b
2 LK
SQN3x.x2xAxxxx
SB A B C D
R
W
OH
t4
OW
tw t1
M
LR
BV1
BV2
TSA
FS
entspr. 6°
7808d01/1204
LKP
NL I I
I
SA M 3) Vb
IV
KL IV Va Vb
III
LK ZU III BV2 III
II
II t
11/17
LMG21.../LMG25.../LGB21...
12 2 10 8 3 6 11 9 7 4 5 1
ION
EK2
LP
AL M Z
BV1
GP
R/W LR
BV2
SB
HS N 1 2 6 7 5 4 3
7808a13/0304
b1 b2 B
0 I
3) Cams III and IV are rigidly
Si
III 3)
IV connected
N L
a b a b
A
a3 a2
II I V
MS
a b a b a b
2 LK
SQN3x.x2xAxxxx
SB A B C D
R
W
tw t1 t4
M
LR
BV1
7808d10/1204
BV2
TSA
FS
entspr. 6°
LKP
NL I I
I 3)
SA M IV Vb Va Vb
KL IV
III
LK III III
II ZU
II t
12/17
ION
*) Thermostat or similar with changeover
GP EK2 LP Z
AL LR *) contact (2-wire control) or 3-position
controller for «on / off» positioning pulses
R/W M BV1
and neutral position
7808a15/1004
HS
R3
R1
0 I
Si
B b1 b2
N L
A a1 a2
M LK
I II III V 1)
5
RV
SQN3x.x5xAxxxx
SB A B C D
R/W
GP
tw t1
M
Program sequence diagram shows
LP
modulating operation
BV1
LR *)
7808d14/1204
FS
SA LKP
M I I
I NL
LK **
III KL III III
RV** II ZU II
t
13/17
ION 2)
GP EK2
LP The cams of switches III and V are
AL LR *)
rigidly connected. This ensures that
R/W M BV1 ignition takes place at the low-fire
position «KL»
7808a14/1004
HS position
R1 R3
0 I
Si
B b1 b2
N L
A a1 a2
2)
M LK
I II III V 1)
6
RV
SQN3x.x6xAxxxx
SB A B C D
R/W
GP
tw t1
Program sequence diagram shows
M modulating operation
LP
BV1
LR *)
7808d12/1004
FS
9
entspr. 5°
SA LKP
M
NL I I
I
LK V
III KL
RV III III
ZU
II
II
t
Attention!
If the contacts of switch V welded in position 4 9, supervision of the ignition load position would be negated and
not be detected in operation. This means that the circuit is not safety-related but only used for supervision
purposes. The user must ensure that in the event of failure (should the burner ignite at nominal load «NL»), no
damage will occur.
14/17
I II III IV
M
~ LK
7808d04/1004
SQN4x.x4xAxxxx
TMG740 / TMO720
2)
21
8 13 14 9 15 4 6 12
N 7 1 6 5 2 3 4 8
7808a10/1004
B b1
b a
a1 A a2
1)
I II III IV V
M LK
b a b a
1
SQN3x.x3xAxxxx
LKP
I I
TMG... and TMO... are devices of other
NL
manufacture, neither made nor supplied by
entspr. 5° 1)
15/17
16/17
20 24 32 27.5 36 24
10
M,R M,R
7808m01e/0205
24
3
16
Viewing window 5.5
16
83
(96)
M,R 10
72
3) 3)
Pg9 Pg11
16.5 22 14
110 (125)1) > 85 44 32
76
14h10
25 8h9
17
45°
7
-0
.0
5
12.5 14h10 5 -0.05
10h9
2
6.5 5 +0.05
14h10
10h9
3 2)
-0.03
-0.09
10h9
25
8
14h10
All drive shafts are shown in end switch position II (CLOSED, as supplied).
2016 Siemens AG Building Technologies Division, Berliner Ring 23, D-76437 Rastatt
Subject to change!
17/17