SQN3&4 Electromotoric Actuators

Download as pdf or txt
Download as pdf or txt
You are on page 1of 17

7 808

Actuators SQN3...
SQN4...
Electromotoric actuators for use with air dampers and control valves of oil or gas
burners of small to medium capacity.

The SQN3... / SQN4... and this Data Sheet are intended for use by OEMs which
integrate the actuators in their products!

Use / features
The SQN3... / SQN4... actuators are designed to drive gas and air dampers on small to
medium-capacity oil or gas burners or for the load-dependent control of fuel and
combustion air volume:
- In connection with P-PI or PID controllers, such as the RWF...
- Directly via the different types of burner controls, such as LOA..., LMO..., LMG... or
LFL...
- In connection with 1- or 2-wire control or 3-position controllers

 All types of actuators - Impact-proof and heat-resistant plastic housing


with: - Screw terminals for the electrical connections
- Maintenance-free gear train, which can be disengaged
- Internal and external position indication
- Easy-to-adjust end and auxiliary switches for setting the switching points

 Holding torque: - SQN3... 0.8...3 Nm


- SQN4... 6 Nm

 Running time: - SQN3... 4.5...30 s


- SQN4... 120 s

 Direction of rotation: - SQN30... counterclockwise


- SQN31... / SQN41... clockwise

CC1N7808en
Building Technologies Division
13.05.2016 Infrastructure & Cities Sector
Warning notes
To avoid injury to persons, damage to property or the environment, the following
warning notes must be observed!

Do not interfere with or modify the actuators!

 All activities (mounting, installation and service work, etc.) must be performed by
qualified staff
 Before making any wiring changes in the connection area of the actuators,
completely isolate the equipment from the mains supply (all-polar disconnection).
Ensure that the plant cannot be inadvertently switched on again and that it is
indeed dead. If not observed, there is a risk of electric shock hazard
 Ensure protection against electric shock hazard by providing adequate protection
for the connection terminals and by securing the housing cover
 Each time work has been carried out (mounting, installation, service work, etc.),
check to ensure that wiring is in an orderly state
 Fall or shock can adversely affect the safety functions. Such actuators must not be
put into operation, even if they do not exhibit any damage

Mounting notes
 Ensure that the relevant national safety regulations are complied with

Standards and certificates


Applied directives:
 Low-voltage directive 2014/35/EC
 Electromagnetic compatibility EMC (immunity) 2014/30/EC

Compliance with the regulations of the applied directives is verified by the adherence to
the following standards / regulations:
 Automatic electrical controls for household and similar use DIN EN 60730-1
Part 1: General requirements
 Automatic electrical controls for household and similar use DIN EN 60730-2-14
Part 2-14: Particular requirements for electric actuators

The relevant valid edition of the standards can be found in the declaration of
conformity!

EAC Conformity mark (Eurasian Conformity mark)

ISO 9001:2008
ISO 14001:2004
OHSAS 18001:2007

Disposal notes
The actuator contains electrical and electronic components and must not be disposed
of together with domestic waste.
Local and currently valid legislation must be observed.

2/17

Building Technologies Division CC1N7808en


Infrastructure & Cities Sector 13.05.2016
Mechanical design
Housing - Made of impact-proof and heat-resistant plastic
- The housing accommodates:
– The reversible synchronous motor with gear train, which can be disengaged
– The camshaft of the control section
– The relays (depending on the type of actuator)
– The switches, connected to the terminals via the printed circuit board

Color: Gear train housing light-grey, cover dark-grey

Drive motor - Reversible and locking-proof synchronous motor

Coupling - Shaft can be disengaged from gear train and motor


via manual operation of a couplerpressure pin «K»
- Automatic reengagement

7808p08e/0205
Pin "K"

Adjustment of - With adjustable cams


switching points - Scales beside the cams indicate the angle of the switching point
- The other cams can be adjusted manually or with the enclosed hook-spanner or
similar tool

Position indication - Internally: Scale on the gear train side of the camshaft
- Externally: Scale in viewing window (refer to «Dimensions»)

Electrical connections - Refer to «Technical data»

Gear train - Maintenance-free

Drive shaft - Made of black-finished steel.


- Ready fitted to the front of the gear train
- Different versions available

Mounting and fixing - Front of the gear train is used as the mounting surface
- Actuator is secured via through-holes

3/17

Building Technologies Division CC1N7808en


Infrastructure & Cities Sector 13.05.2016
Special versions for fitting potentiometer
Fitting a Certain types of actuators are supplied ready prepared for fitting a potentiometer.
potentiometer These actuators differ from the basic type only in that the housing is higher and that
they are prepared for accommodating a potentiometer. Accessories are not required.
The required type of potentiometer is to be ordered as a separate item (refer to
«Ordering»). In that case, the third digit after the dot in the actuator’s type reference will
change from «1» to «2».

Example:
SQN31.111A2700  basic type
SQN31.112A2700  version for fitting a potentiometer

Conversion by the user Users have the choice of converting a basic type of actuator to a version for fitting a
potentiometer. For that, a conversion kit type AGA32 is available (refer to «Ordering»).

Attention!
Conversion of the basic type reference must be noted by the user on the actuator’s
type field using a permanent felt-tip pen.

4/17

Building Technologies Division CC1N7808en


Infrastructure & Cities Sector 13.05.2016
Type summary (others types of actuators are available on request)

Actuators SQN30... / counterclockwise rotation 8)

Diagram Drive Running Operating Holding HS Relay Housing Types for mains voltage / mains frequency
shaft ¹) time torque torque 7) length ¹) AC 220 V -15 % AC 100 V -15 %
at 50 Hz ²) (max.) AC 240 V +10 % AC 110 V +10 %
no. no. for 90° Nm Nm pcs. pcs. mm 50...60 Hz 4) 50...60 Hz 3)
s
0 0 4.5 1 0.8 3 --- 125 SQN30.102A2700 5) ---
1 0 4.5 1 0.8 2 1 110 SQN30.111A2700 SQN30.111A1700
1 0 4.5 1.5 0.8 2 1 110 SQN30.111A3500 ) ---
2 0 4.5 1 0.8 1 2 110 SQN30.121A2700 SQN30.121A1700
2 0 4.5 1.5 0.8 1 2 110 SQN30.121A3500 ) ---
3 0 4.5 1 0.8 1 2 110 SQN30.131A2700 SQN30.131A1700
5 0 4.5 1 0.8 1 2 110 SQN30.151A2700 SQN30.151A1700
5 0 12 1.8 1.8 1 2 110 SQN30.251A2700 SQN30.251A1700
0 0 30 3 3 3 --- 110 SQN30.401A2700 ---
0 3 30 3 3 3 --- 110 SQN30.401A2730 ---
0 0 30 3 3 3 --- 125 SQN30.402A2700 5) SQN30.402A1700 5)
0 3 30 3 3 3 --- 125 SQN30.402A2730 5) ---
1 0 30 3 3 2 1 110 SQN30.411A2700 ---
3 0 30 3 3 1 2 110 SQN30.431A2700 ---
5 0 30 3 3 1 2 110 SQN30.451A2700 ---

Actuators SQN31... / clockwise rotation 8)

Diagram Drive Running Operating Holding HS Relay Housing Types for mains voltage / mains frequency
shaft ¹) time torque torque 7) length ¹) AC 220 V -15 % AC 100 V -15 %
at 50 Hz ²) (max.) AC 240 V +10 % AC 110 V +10 %
no. no. for 90° Nm Nm pcs. pcs. mm 50...60 Hz 4) 50...60 Hz 3)
0 0 4.5 1 0.8 3 --- 110 SQN31.101A2700 SQN31.101A1700
0 0 4.5 1 0.8 3 --- 125 SQN31.102A2700 5) SQN31.102A1700 5)
1 0 4.5 1 0.8 2 1 110 SQN31.111A2700 ---
1 6 4.5 1 0.8 2 1 110 SQN31.111A2760 ---
2 0 4.5 1 0.8 1 2 110 SQN31.121A2700 ---
2 3 4.5 1 0.8 1 2 110 SQN31.121A2730 ---
2 6 4.5 1 0.8 1 2 110 SQN31.121A2760 ---
5 0 4.5 1 0.8 1 2 110 SQN31.151A2700 SQN31.151A1700
5 3 4.5 1 0.8 1 2 110 SQN31.151A2730 ---
2 0 12 1.8 1.8 1 2 110 SQN31.221A2700 ---
2 3 12 1.8 1.8 1 2 110 SQN31.221A2730 ---
5 0 12 1.8 1.8 1 2 110 SQN31.251A2700 SQN31.251A1700
5 3 12 1.8 1.8 1 2 110 SQN31.251A2730 ---
0 0 12 1,8 1,8 3 --- 125 SQN31.202A2700 5) ---
5 0 12 1.8 1.8 1 2 125 SQN31.252A2700 5) SQN31.252A1700 5)
5 0 15 2 1.8 1 2 110 SQN31.351A2700 ---
0 0 30 3 3 3 --- 110 SQN31.401A2700 SQN31.401A1700
0 3 30 3 3 3 --- 110 SQN31.401A2730 ---
0 6 30 3 3 3 --- 110 SQN31.401A2760 ---
0 0 30 3 3 3 --- 125 SQN31.402A2700 5) SQN31.402A1700 5)
1 0 30 3 3 2 1 110 SQN31.411A2700 ---
1 3 30 3 3 2 1 110 SQN31.411A2730 ---
6 0 23 2.5 2.5 --- 2 125 SQN31.762A2700 5) ---
4 0 120 6 6 2 1 110 SQN31.941A2700 ---

5/17

Building Technologies Division CC1N7808en


Infrastructure & Cities Sector 13.05.2016
Type summary (others types of actuators are available on request) (cont’d)

Actuators SQN41... / clockwise rotation 8)


Diagram Drive Running Operating Holding HS Relay Housing Types for mains voltage / mains frequency
shaft ¹) time torque torque 7) length ¹) AC 220 V -15 % AC 100 V -15 %
at 50 Hz ²) (max.) AC 240 V +10 % AC 110 V +10 %
no. no. for 90° Nm Nm pcs. pcs. mm 50...60 Hz 4) 50...60 Hz 3)
4 0 120 6 6 2 1 110 SQN41.941A2700 ---

Legend ¹) Refer to «Dimensions»


²) At 60 Hz, running times are about 20 % shorter
3)
AC 100…110 V +10 % / -15 % possible, but in case of undervoltage torque is reduced by about 20 %
4)
AC 220…240 V +10 % / -15 % possible, but in case of undervoltage torque is reduced by about 20 %
5)
Suited for fitting a potentiometer (refer to «Fitting a potentiometer»)
6)
Under nominal conditions; under extreme conditions (e.g. +60 °C, AC 230 V –15 %) about –25 %
7)
Optional auxiliary switches (in addition to the 2 end switches)
8)
When facing the drive shaft and when control voltage is fed to end switch I
)
On time at: - AC 220 V -15 % / +10 % and 50 Hz – max. 50 %
- AC 240 V -15 % / +10 % and 50 Hz – max. 35 %

Ordering
Actuator refer to «Type summary»

Potentiometer ASZ.... refer to Data Sheet N7921

Conversion kit AGA32 refer to Data Sheet N7921


- For converting a basic type of actuator to a version for fitting a potentiometer

Example of conversion by the user:

SQN30.401A2730 - Actuator (refer to «Type summary»)

AGA32 - Conversion kit

ASZ8.703 - Coiled potentiometer 220  / 90°, 3-pole

Service kit AGA33 refer to Data Sheet N7921


- For replacing old potentiometers type ASZ...5... / ASZ...6... by new potentiometers
type ASZ...7... and ASZ...8...

6/17

Building Technologies Division CC1N7808en


Infrastructure & Cities Sector 13.05.2016
Technical data
General actuator data
Actuator Mains voltage AC 220…240 V –15 % +10 %
AC 100…110 V –15 % +10 %
Mains frequency 50...60 Hz ±6 %
Primary fuse (external) 6.3 AT (customer responsible for
installation)
Type of motor synchronous motor
Power consumption 6.5 VA
Angular position max. 160°
Mounting position optional
Degree of protection IP 40 to DIN 40050, provided adequate
cable entries and fixing screws are used
Safety class I to VDE 0631
Cable entry threaded cable gland holder for
1 x Pg9 and 1 x Pg11, no locknut required

cable strain relief to be provided by the user


(also refer to «Degree of protection»),
Pg glands for all types are included in the
delivery
Cable connections screw terminals for wires having a cross-
sectional area of 0.5 to 2.5 mm²
Ferrules matching the dia. of the stranded wire
Direction of rotation refer to «Type summary»
Torques and holding torques refer to «Type summary»
Running times refer to «Type summary»
Life cycle Cycles (CLOSED  OPEN  CLOSED)
at specified torque: typical 250,000
Weight (on average) approx. 800 g

End and auxiliary Number of end switches 2


switches Number of auxiliary switches refer to «Type summary»
Actuation via camshaft, color-coded cams (refer to
«Connection diagrams»
Switching voltage AC 24...250 V
Adjustment of cams in increments of 1°
Perm. terminal rating at cos = 0,9: Peak current Operating current
Electronic circuit
- under load ON, not under load OFF Max. 14 A 2A
- under load ON, under load OFF Max. 7 A 1A

Environmental Storage DIN EN 60 721-3-1


conditions Climatic conditions class 1K2
Mechanical conditions class 1M2
Temperature range -20...+60 °C
Humidity < 95 % r.h.
Transport DIN EN 60 721-3-2
Climatic conditions class 2K2
Mechanical conditions class 2M2
Temperature range -20...+60 °C
Humidity < 95 % r.h.
Operation DIN EN 60 721-3-3
Climatic conditions class 3K3
Mechanical conditions class 3M3
Temperature range -20...+60 °C
Humidity < 95 % r.h.

Attention!
Condensation, formation of ice and ingress of water are not permitted!
7/17

Building Technologies Division CC1N7808en


Infrastructure & Cities Sector 13.05.2016
Function
A synchronous motor drives the drive shaft and the camshaft via a gear train. The
attached camshaft actuates the end and auxiliary switches. The switching position of
each end and auxiliary switch can be adjusted within its working range via the
associated cam. Some of the actuator versions are equipped with electronic modules
for auxiliary functions in connection with the end and auxiliary switches or with external
devices, such as controllers (refer to «Connection diagrams»). The functions and
technical data of both lines of actuators SQN3... and SQN4... are nearly identical.

8/17

Building Technologies Division CC1N7808en


Infrastructure & Cities Sector 13.05.2016
Connection diagrams

 Note!
The following connection diagrams show the actuator’s start position as supplied:
- End switch position II (CLOSED)
- Dead

No. 0  LFL... / LGK16... / LAL... and LOK16...

2-stage or modulating operation  Prepurging at nominal load position «NL»

LFL... / LGK16... / LAL... / LOK16... 1) Diagram shows arrangement for


1 2 9 11 20 10 8 18 19
modulating operation
LR *)

BV1

*) Thermostat or similar with changeover


contact (2-wire control) or 3-position
**)
controller for «on / off» positioning
SB
BV2 pulses and neutral position

HS
N 3 1 2 4 10 8 9 13 11 12 7 5 6 **) In case of modulating operation, fuel
I 0 valve «BV2» is replaced by a gas
Si

N L
control valve «RV»

I II III IV V
M
LK
~ 1)

RV
0

SQN3x.x0xAxxxx 7808a11/1004

A B C D
Program sequence diagram shows
R
modulating operation
M1
M2

BV1

LR *)

RV

FS
t1
LKP
SA M
I NL I I
7808d05/1004

LK **
III KL III III
RV** II ZU II
t

9/17

Building Technologies Division CC1N7808en


Infrastructure & Cities Sector 13.05.2016
Connection diagrams (cont’d)

No.   LFL... / LGK16... / LAL... / LOK16...

2-stage operation  Prepurging at nominal load position «NL»

LFL... / LGK16... / LAL... / LOK16...


1 2 19 9 20 11 10 8 18

*)
LR
BV1 *) Thermostat or similar with NO
SB
contact (1-wire control)

HS BV2

I 0 N 7 3 1 6 5 2 4 10 8 9 13 11 12
Si

N L

I II III IV
M
~ LK

1
7808a12/1004
SQN3x.x1xAxxxx

A B C D
R
M1
M2

BV1

LR

BV2

FS
t1
LKP
7808d07/1004

I NL I I
SA M IV IV IV IV
KL III IV
III
LK ZU II III
II
t

10/17

Building Technologies Division CC1N7808en


Infrastructure & Cities Sector 13.05.2016
Connection diagrams (cont’d)

No.   LOA24... / LOA25... / LOA28... / LMO24... / LMO44...

2-stage operation  Prepurging at low-fire position «KL»

LOA24.../LOA25.../LOA28.../LMO24.../LMO44... 1) With oil preheater


1 2 10 8 3 7 6 4 5 11 12 2) Without oil preheater
2)
1)
W QRB...
OW

R
Z *) Thermostat or similar with NO contact
OH
AL M
BV1
(1-wire control)

*)
LR

BV2
SB

HS

N 1 2 6 7 5 4 3

7808a09/1204
I 0
Si

b1 b2 B
3) Cams III and IV are rigidly connected
N L

III 3)
IV
a b a b
A
a3 a2

II I V
MS
a b a b a b
2 LK

SQN3x.x2xAxxxx

SB A B C D
R
W

OH
t4
OW
tw t1
M

LR

BV1

BV2
TSA
FS
entspr. 6°

7808d01/1204

LKP
NL I I
I
SA M 3) Vb
IV
KL IV Va Vb
III
LK ZU III BV2 III
II
II t

11/17

Building Technologies Division CC1N7808en


Infrastructure & Cities Sector 13.05.2016
Connection diagrams (cont’d)

No.   LMG21... / LMG25... / LGB21...

2-stage operation  Prepurging at low-fire position «KL»

LMG21.../LMG25.../LGB21...
12 2 10 8 3 6 11 9 7 4 5 1

ION
EK2
LP
AL M Z
BV1
GP

R/W LR

BV2
SB

HS N 1 2 6 7 5 4 3

7808a13/0304
b1 b2 B

0 I
3) Cams III and IV are rigidly
Si

III 3)
IV connected
N L
a b a b
A
a3 a2

II I V
MS
a b a b a b
2 LK

SQN3x.x2xAxxxx

SB A B C D
R
W
tw t1 t4
M

LR

BV1
7808d10/1204

BV2
TSA
FS
entspr. 6°

LKP
NL I I
I 3)
SA M IV Vb Va Vb
KL IV
III
LK III III
II ZU
II t

12/17

Building Technologies Division CC1N7808en


Infrastructure & Cities Sector 13.05.2016
Connection diagrams (cont’d)

No.   LMG22... / LGB22... / LGB32...

2-stage or modulating operation  Prepurging at nominal load position «NL»

LMG22... / LGB22... / LGB32... 1) Diagram shows arrangement for


12 2 10 8 3 6 11 9 5 7 4 1 modulating operation

ION
*) Thermostat or similar with changeover
GP EK2 LP Z
AL LR *) contact (2-wire control) or 3-position
controller for «on / off» positioning pulses
R/W M BV1
and neutral position

**) In case of 2-stage modulating burners


SB **) **) (with gas damper «RV»), «BV2» and the
BV2 connection between the terminals
(shown as a broken line) will not be
N 1 8 2 7 5 6 3 4 9 needed

7808a15/1004
HS
R3
R1

0 I
Si

B b1 b2
N L
A a1 a2

M LK
I II III V 1)
5
RV
SQN3x.x5xAxxxx

SB A B C D
R/W
GP
tw t1

M
Program sequence diagram shows
LP
modulating operation
BV1

LR *)
7808d14/1204

FS

SA LKP
M I I
I NL
LK **
III KL III III
RV** II ZU II
t

13/17

Building Technologies Division CC1N7808en


Infrastructure & Cities Sector 13.05.2016
Connection diagrams (cont’d)

No.   LMG22... / LGB22... / LGB32...

Modulating operation  Prepurging at nominal load position «NL»

LMG22... / LGB22... / LGB32... 1) Diagram shows arrangement for


12 2 10 8 3 6 11 9 5 7 4 1 modulating operation

ION 2)
GP EK2
LP The cams of switches III and V are
AL LR *)
rigidly connected. This ensures that
R/W M BV1 ignition takes place at the low-fire
position «KL»

Z 2) *) Thermostat or similar with


SB
changeover contact (2-wire control)
or 3-position controller for «on / off»
N 1 8 2 7 5 6 3 4 9 positioning pulses and neutral

7808a14/1004
HS position
R1 R3
0 I
Si

B b1 b2
N L
A a1 a2

2)
M LK
I II III V 1)
6
RV
SQN3x.x6xAxxxx

SB A B C D
R/W
GP
tw t1
Program sequence diagram shows
M modulating operation

LP

BV1

LR *)
7808d12/1004

FS

9
entspr. 5°

SA LKP
M
NL I I
I
LK V
III KL
RV III III
ZU
II
II
t

Attention!
If the contacts of switch V welded in position 4  9, supervision of the ignition load position would be negated and
not be detected in operation. This means that the circuit is not safety-related but only used for supervision
purposes. The user must ensure that in the event of failure (should the burner ignite at nominal load «NL»), no
damage will occur.

14/17

Building Technologies Division CC1N7808en


Infrastructure & Cities Sector 13.05.2016
Connection diagram (cont’d)

No.   Special application


N 7 3 1 6 5 2 4 10 8 9 13 11 12

I II III IV
M
~ LK

7808d04/1004
SQN4x.x4xAxxxx

No.   TMG740 / TMO720 (burner control of other manufacture)

2-stage operation  Prepurging at nominal load position «NL»

TMG740 / TMO720
2)
21
8 13 14 9 15 4 6 12

M 1) Cams of switches III and IV are rigidly connected


NL
2) TMO720 terminal no. 6
TMG740 terminal no. 21
BV1
L2

N 7 1 6 5 2 3 4 8
7808a10/1004

B b1

b a

a1 A a2

1)
I II III IV V
M LK
b a b a
1

SQN3x.x3xAxxxx

LKP
I I
 TMG... and TMO... are devices of other
NL
manufacture, neither made nor supplied by
entspr. 5° 1)

V V Siemens. Combination with the type of


IV
Siemens actuator proposed here must be
KL IV IV IV
III checked with the supplier of the TMG... or
III III III TMO... while taking into consideration safety
zu
7808d03/0104
t
aspects and the current burner control
II II
version.
The user assumes full responsibility for this
application.

15/17

Building Technologies Division CC1N7808en


Infrastructure & Cities Sector 13.05.2016
Legend No.  Number of internal diagram
(second position after the dot in the actuator’s type reference)
I / II End switch
III / IV / V Auxiliary switch
AL Remote indication of fault (alarm)
BV1 Fuel valve stage 1
BV2 Fuel valve stage 2
EK2 External remote reset button
ION Ionization probe
FS Flame signal amplifier
GL Gas / air ratio controller
GP Gas pressure switch
HS Main switch
KL Low-fire
L Live conductor
LK Air damper
LKP Air damper position
LP Air pressure switch
LR Load controller
M Burner or fan motor
M Actuator’s synchronous motor
M1 Without postpurging
M2 With postpurging
N Neutral conductor
NL Nominal load
OH Oil preheater
OW Oil preheater’s readiness contact
QRB... Photoresistive flame detector
R Temperature or pressure controller
Relay
RV Gas damper
SA Actuator
Si External primary fuse (as specified in the Data Sheet of the relevant burner control)
SB Safety limiter
ST... Stage
t... / T... Program times (refer to the Data Sheet of the relevant burner control)
TSA Safety time
R Resistance
Z Ignition transformer
ZU Damper fully closed
 Direction of rotation OPEN
 Direction of rotation CLOSE

Program sequence diagrams


A Burner ON
A–B Startup of burner
B–C Burner operation / load control operation (modulating or 2-stage)
C Burner OFF
C–D Overrun time
D End of program sequence, burner control ready for a new start

16/17

Building Technologies Division CC1N7808en


Infrastructure & Cities Sector 13.05.2016
Dimensions
Dimensions in mm

20 24 32 27.5 36 24
10

M,R M,R

7808m01e/0205

24
3

16
Viewing window 5.5

16
83

(96)
M,R 10

72
3) 3)
Pg9 Pg11
16.5 22 14
110 (125)1) > 85 44 32
76

Type of drive shaft Type of drive shaft Drive shaft no.


Side view according to
"Type summary"

14h10
25 8h9
17

45°

7
-0
.0
5
12.5 14h10 5 -0.05
10h9
2

6.5 5 +0.05
14h10
10h9

3 2)
-0.03
-0.09

10h9
25
8
14h10

All drive shafts are shown in end switch position II (CLOSED, as supplied).

1) Housing length depending on type of actuator R Fixing positions


(refer to «Type summary») M Through-hole 5.3 mm dia.
2) Center slot: 6.3 mm deep
Hole dia. 5.1 mm: 16.5 mm deep (incl. center slot
depth)
3) Not included in delivery

2016 Siemens AG Building Technologies Division, Berliner Ring 23, D-76437 Rastatt
Subject to change!
17/17

Building Technologies Division CC1N7808en