Final Report For HVAC2
Final Report For HVAC2
Final Report For HVAC2
Contents
Page
1. Introduction/Objectives
2. Background Information
3. Design Criteria
4. System Selection
5. Detailed Design
7. Reference
8. Appendix
1. Introduction/Objectives
This project aims to enable students to apply the knowledge learnt to solve simulated
real-life problems and to acquire the competency. To carry out the project, we have to
design for ceiling height, PAU& FCU services with detail calculation and installation
of work for an office building
2. Background Information
The office building consists of 30 stores with 18 rooms including 13 manager rooms, 3
conference rooms, 1 drawing room, 1 security room, administration office and passenger
lift lobby. 2 side of toilets including female and disable toilet (LHS) and male toilet (RHS)
and the pantry, switch room, cleaning room. The gross floor area is 981.4m^2, headroom
is 3.2m. According to ASHRAE Handbook HVAC Applications 1999, the occupancy is 137.
Base on the calculation, referring to the area of floor plan and given rules of thumbs. The
fresh air flow per person are almost 8l/s.
3. Design Criteria
Outdoor condition
Dry bulb 33℃
Wet bulb 27℃
Indoor condition
Dry bulb 24℃
Relative Humidity 50%
Off coil condition 13℃DB
Through making assumption on the summer design outdoor condition 33℃DB, 27℃
WB and the indoor condition would be 24℃DB, 50%RH. By referring the
psychometric chart, the enthalpy and specific volume of summer design outdoor
condition is 84.5kJ/kg and 0.895m³/kg. For indoor condition, they are 48.5kJ/kg and
0.854m³/kg respectively. The off-coil condition is 13℃DB. By referring the
psychometric chart, the enthalpy and specific volume of summer design off-coil
condition is 35.5kJ/kg and 0.822 m³/kg.
NC Level
The NC level of office is 40 for office. The NC level is 40-45 for pantry.
The NC are a common way to measure and specify background noise in unoccupied
buildings and spaces. Their purpose is to produce a single value representation of a
complete sound spectrum. International standards organizations recognize the need to
objectify judgements on the amount of ambient noise in enclosed spaces, and provide us
with definitions for various NC.
Background noise may have several undesirable effects. Noise can be an annoyance that
creates fatigue and negatively affects productivity, safety and the ability to communicate.
Therefore, standard methodologies for quantifying noise have been developed. Noise
curves reflect different standardized means of creating a single number rating for the
background noise spectrum in a space. Different rooms, locations, regulations and
applications may allow different acceptable noise ratings. In most cases, the goal is that
background noise should not interfere with the purpose of the room, e.g. the noise of an
office air-conditioning system and consistent noise of traffic outside the building should not
interfere with telephone calls or conversations. In other cases, special noise may also be
tolerated or even introduced at higher levels, for example to create acoustic "privacy", or to
help mask other more irritating noise sources. So that we use 40 NC level for office and
40-45 NC level for pantry.
For choosing a suitable PAU, the first priority is that it can fit the required cooling load
of our calculation. Also, the size of PAU is also considered as the A/C plant room is
limited. Maintenance free would be considered as well. Classifications of air
conditioning systems are shown as below.
Space ventilation fan coil system: There is no treatment of outdoor air in the
PAU. Outdoor air is admitted directly to the mixing plenum of the FCU where it
mixes with the recirculating air before being conditioned at the cooling/heating
coil. It is classified as an all-water system.
4. System Selection
For the system selection, some elements are significantly considered as follow:
Air quality
Thermal environmental control
Noise
Flexibility and reliability
Operation and maintenance
Plant and duct space
Initial and operating costs
Liquid leakage hazard
Fire protection and smoke control
Aesthetic reasons
Central Systems or Packaged Unitary Systems
Constant Air Volume(CAV) and Variable Air Volume (VAV) Systems
All-air, Air-water and All-water Systems
Single Zone or Multi-Zone Systems
Single Duct or Multiple Duct Systems
Fan Coil Unit Systems
For our final decision, we choose Primary air fan coil system for air conditioning of this
30-storey commercial buildings, Primary air (conditioned air) is treated in a PAU to the
mixing plenum of FCU and mixes with recirculating room air..
Primary air fan coil system is chosen because of some reasons:
• Guaranteed outdoor air
• Less condensate at FCU
• Less water leakage problem
• Less noise problem
Compare with air-water and all-air systems, we choose Air-water system for the
conditioned air.
Air-water system is chosen because of some reasons:
• Less ductwork
• Less power required for heat transport using water
• Greater flexibility in meeting requirements of various zones (two independent
sources
5. Detailed Design
∵ No A/C system in toilets
∴ exhaust fan should be added
Required air change rate of toilet: 6-10 ACH
Taking the median, the required exhausted air volume of female toilet is 280 m³/h
and
331.2 m³/h for male toilet
Male toilet & Female toilet, Switch room, Disable Toilet, Cleaning Room
Panasonic –
FV-20WUL107
Heating can be provide by the FCU through hot water heating coil or electric heater. It can
also be catered for by the warm PA. The actual system operation depends on the system
used for two-pipe systems.
7. Reference
Window Mount Type Ventilating Fan
http://www.panasonic.hk/english/products/living/ventilation-air-
conditioning/ventilating-fan/fv-20wul107.aspx
PAU model
http://www.yorkthai.com/upload/product/fie/fie97-911.pdf
Date of Last update: June 2015 Page 7 of 3
Building Services System Design A (BSE4303)
8. Appendix
Append I Psychometric chart
Append II EAF
Append III Check figure
Append IV environmental design air supply rate person
Append V Selection of PAU
Append VI Selection of FCU
Append VII reflected ceiling plan
Append VIIII rect. duct sizing
Append IX Psychometric Chart
Append X PAU selection
Append XI PAD sizing
Append XII FCU duct sizing
Append XIII Fan-coil Catalogue 2011
Append XIV Circular Equivalents of Rec. duct
Append XV Critical Path
Append XVI Duct Sizing (all paths)
Append XVII HVAC.dwg
Append XVIII AC Room calculation sheet
Append XIX Design for duct sizing (FCU)
Append XX Design of Air Diffuser
Append XXI section view
Append XXII reflected ceiling plan