Unit-1-Protective Relaying OC and Earth Fault Protection
Unit-1-Protective Relaying OC and Earth Fault Protection
Protective Relaying
What is System Protection?
1. Short circuits
2. Abnormal conditions
3. Equipment failures
Why do we need Protection?
1. Generators
2. Transformers
3. Transmission Lines
4. Feeders
5. Motors
6. Capacitor Banks
7. Bus Bars
Types of Protection
Apparatus Protection
Transformer Protection
Generator Protection
Motor Protection
System Protection
Out-of-Step Protection
Islanding System
Causes of faults
• Natural calamities
• Equipment related
• line breaks,
• mechanical damage,
• wrong connections,
• Fire hazards.
Shunt faults
(short circuit)
Voltage, frequency
decreases and current
increases
11
Faults Statistics
Faults in Various Elements of power System
Element % of Total Faults
Overhead Lines 50
Underground Cables 9
Transformers 10
Generators 7
Switchgears 12
CTs. VTs, Relays Control Equipment, etc 12
(ii). Reliability
(iii) Sensitivity
(iv) Stability
F
Protective Relays
More flexible.
Maximum flexibility.
i. Remote Back-up
iii. No conclusion
c. Numerical relays
Relays…
II. Based on Speed of Operation
a. Instantaneous relays
b. Time-delay relays
c. Impedance relays
e. Directional relays
c. Multi-input comparator
Relays…
VI. Based on timing characteristics
Firstly, they step down the heavy power system currents to low values
that are suitable for the operation of the relays and other measuring
instruments (meters) connected to their secondary windings.
Secondly, they isolate the relays and meters circuits from the high
voltages of the power system.
The standard current ratings of the secondary windings of the CTs used
in practice are 5A or 1A.
• When the relay is set to operate at current different from the rated
secondary current of the CT, the effective burden of the relay can be
calculated as follows:
2
Is
Pe = Pr
Ir
where
Na = Actual ratio
= Ip/Is
Ip = Primary current
Is = secondary current
The ratio error is largely dependant upon the iron-loss component of the
exciting current.
Phase-Angle Error
Im
β=
NI s
1
Rcf =
1+ ε
N − Na
where ε=
Na
Voltage Transformers
Na = Actual ratio
= Vp/Vs
Vp = Primary voltage
Is = secondary voltage
Phase-Angle Error
f. Reed type
Attracted armature Relays
Introduction
All these relays use the same electromagnetic attraction principle for
their operation.
The attracted armature relays are fast relays. They have fast operation
and fast reset because of small length of travel and light moving parts.
They are described as instantaneous, But their operating time does
vary with current. Slow operating and resetting times can be obtained.
On the other hand, very high operating speeds are possible. One
modern relay has 0.5 millisecond of operating time. The current/time
characteristic is hyperbolic.
Ratio Rest to Pick-up can be as high as 90-95% for a.c. relays and
60-90% for d.c. relays, means of special design features.
These relays do not have directional feature unless they are provided
with additional polarized coil.
As they are fast and operate on d.c. and a.c., they are affected by
transients. The transients contain d.c. component in addition to a.c.
wave. Therefore, though the steady state value may be less than
relay's pick-up the relay may pick-up during transient state.
F = K1I 2 − K2
where
F = net force
K1 = a constant
2 1 2 2 2
F = KI = K (I max sin wt) = K (I max − I max cos2wt)
2
The relay is an instantaneous relay. The operating speed is very high (5
ms).
They are affected by transients as they are fast and operate on both dc
and ac.
It is also used for auxiliary relays, such as indicating flags, slave relays,
alarm relays, annunciators, semaphores, etc.
Attracted armature…
b. Plunger type relay
Attracted armature…
c. Balanced beam relay
Attracted armature…
Neglecting spring effect, the net torque is given by
T = K1I12 − K2 I 22
where
T = net torque
K1, K2 = constants
These relays are costlier than induction cup or moving iron type relays.
The VA burden of moving coil relays is very small. These are used as
slave relays with rectifier bridge comparators.
There are two types of moving coil relays:
i. rotary moving coil
The moving coil assembly carries an arm which closes the contact.
Damping is provided by an aluminum former.
Attracted armature…
The operating time is about 2 cycles.
As this type has only one air gap, it is more sensitive than the rotary
moving coil relay.
The axially moving coil relay is a delicate relay and since the contact
gap is small, it has to be handled carefully.
Attracted armature…
e. Polarized moving Iron relay
The coil surrounds the reed contact. When the coil is energized, a
magnetic field is produced which causes the reeds to come together
and close the contact.
They are used for control and other purposes. Also used as a protective
relays. They are completely bounce free and are more suitable for
normally-closed applications. Their speed is 1 or 2 msec.
Electromagnetic Relays
Advantages
High operating speed with operating time in few milliseconds also can
be achieved.
In the definite time lag over current and earth fault protection along with
definite time lag over current relay.
In both Induction disc and Induction cup relays, the moving element
(disc or cup) is equivalent to the rotor of the induction motor.
The flux Ф1 induces e.m.f. E1 is the disc at 90° to Ф1. The e.m.f. E1
produces currents I2 lagging behind E1 by small angle.
Induction…
The interaction between I1 and Ф2 produces torque, which is
proportional to Φ2 I1 cos α, where I1 cos α is component of I1 in phase
with Φ2. Greater the angle θ, greater is the torque.
where
T = Net torque
K1, K2 = constants
Induction…
where
Φ1 = flux in shaded portion of magnet
Inverse characteristics
Induction…
The construction of this relay is similar to the watt-hour meter
commonly used everywhere.
The relay coil is tapped at several points. The current setting is selected
by inserting a knob to take desired number of turns of the coil in the
circuit.
Induction…
Highlights
In these relays, there is a facility for selecting the plug setting and time
setting such that the same relay can be used for a wide range of
current, time and characteristics.
Induction…
Plug Setting bride is provided with induction disc relays and it provides
a wide range of current settings.
The plug setting refers to the magnitude of current at which the relay
starts to operate. The plug setting bridge comprises connections tapped
from relay coil. By inserting the plug, in a particular gap in the bridge, a
certain number of turns of the relay coil are brought into circuit.
Ratio of reset of pick-up is high because operation does not involve any
change in air gap. The ratio is above 95%.
The rotor consists of a hollow metallic cylindrical cup. The rotor is free
to rotate in the gap between the stationary iron and the electromagnets.
In this type of relay, the eddy currents are produced in the metallic cup.
These currents interact with the flux produced by the other
electromagnet and torque is produced. The theory is similar to that of
the disc type induction relay.
Modern induction cup relays have 4 or more poles. A control spring and
moving contacts are carried on an arm attached to the spindle of the
cup.
A modern induction cup relay may have an operating time of the order
of 0.010 second.
Over Current Protection
Introduction
The value of the preset current above which the relay operates is
known as its pick-up value.
Over current relays offer the cheapest and simplest form of protection.
These relays are used for the protection of distribution lines, large
motors, power equipment, industrial systems, etc.
Over current relays are also used on some sub transmission lines
which can not justify more expensive protection such as distance or
pilot relays.
Over Current…
Several protective devices are used for over current protection. These
include
- Fuses
relays.
1. Motor protection
2. Transformer protection
5. HRC fuses, drop out fuses, etc. are used in low voltage medium voltage
and high voltage distribution systems, generally up to 11 kV.
Depending upon the time of operation the relays are categorized as:
The desired definite operating time can be set with the help of an
intentional time-delay mechanism provided in the relaying unit.
2. Instantaneous over current relay
It operates in 0.1 s or less. Some times the term like “high set” or “high
speed” is used for very fast relays having operating times less than
0.1s.
3. Inverse – time over current relay
IDMT relays are widely used for the protection of distribution lines.
Such relays have a provision for current and time settings.
5. Very Inverse-time over current relay
The very inverse characteristic gives better selectivity than the IDMT
characteristic. Hence, it can be used where an IDMT relay fails to
achieve good selectivity.
When IDMT and very inverse relays fail in selectivity, extremely inverse
relays are employed. IDMT relays are not suitable to be graded with
fuses.
This type of relay is very suitable for the protection of machines against
overheating. (I2 t = K)
Extremely …
This type of relays are used for the protection of alternators, power
transformers, earthing transformers, expensive cables, railway trolley
wires, etc.
This relay is also used for reclosing distribution circuits after a long
outage.
Extremely …
This relay is able to distinguish a fault current and inrush current due its
steep time-current characteristic. Therefore an extremely inverse relay
is quite suitable for the load restoration purpose.
Method of defining shape of time current characteristics
K
t=
I n −1
K
t=
In
0.14
i. IDMT : t=
I 0.02 − 1
13.5
ii. Very inverse : t=
I −1
80
iii. Extremely inverse : t=
I 2 −1
Current Setting
The current above which an over current relay should operate can be
set.
The operation of the relay requires a certain flux and ampere turns. The
current settings of the relay are chosen by altering the number of turns
of the current coil by means of a plug.
The relay which is used for protection against ground faults (earth-fault
relay) has settings 20% to 80% of the rated current in steps of 10%.
There are 10 steps in which time can be set. The term time multiplier
setting (TMS) is used for these steps of time settings.
The directional power relay operates when power in the circuit flows in
the specific direction.
The number of tapping's are provided to the current coil with which
desired current setting can be achieved. The restraining torque is
provided by the spiral spring.
The spindle of disc carries the moving contacts which make contact
with tripping circuit terminals when the disc rotates.
Directional…
The voltage coil provided on the upper magnet produces the flux Ф1.
this lags the voltage by 90o.
T αφ 1φ 2 sin α
but φ 1α V and φ 2α I
while α = 90 − φ
therefore T α VI sin( 90 − φ )
But, when there is a current reversal and hence the power reversal
then the driving torque acts in opposite direction to the restraining
torque in such a manner that the moving contacts close the tripping
circuit contacts. This opens the circuit breaker to isolate the faulty part.
The directional induction type over current relay uses two relay
elements mounted on a common case these elements are:
The trip contacts of this relay (1-1’) are connected in series with
secondary winding of non-directional element.
Directional…
Non-Directional Element
The trip contacts of this relay (1-1’) are connected in series with
secondary winding of non-directional element. So unless and until trip
contacts (1-1’) are closed by the movement of disc of directional
element, the non-directional element can not operate. Thus, the
movement of the non-directional element is controlled by the
directional element.
Directional…
Operation
When the fault takes place the current or power in the circuit has a
tendency to flow in reverse direction. The current flows through the
current coil of the directional element which produces the flux. The
voltage coil produces another flux.
The two fluxes interact to produce the torque due to which the disc
rotates. As disc rotates the trip contacts (1-1’) get closed. So
directional element must operate first to have the operation of the
non-directional element.
Directional…
The following conditions must be satisfied to have the operation of the
entire relay.
ii. the current value in the reverse direction must be greater than the
current setting.
iii. The high value of current must persist for a time period which is
greater than the time setting of the relay.
Directional…
Directional Characteristics
Tα Φv ΦI sin (θ+ Φ)
θ+ Φ = 90
The condition for the maximum torque is shown dotted in the figure
θ+ Φ = 0 or 180
Directional…
Protection of Parallel Feeders and Ring mains
At the sending end of the feeders (at A and B), non-directional relays
are required. At the end of other feeders (at C and D) directional over
current relays are required.
Here the directional relays can operate for fault current flowing in a
particular direction shown by arrow
Earth fault relays are more sensitive than the relays used for phase
faults. The plug setting for phase fault relays varies from 50% to 200%
of the CT secondary rating in steps of 25%.
Earth Fault…
Earth Fault Protective Schemes
Figure (b) and (c) shows earth fault relays used for the protection of
transformer and an alternator, respectively.
Earth Fault…
Earth Fault…
Phase Fault Protective Schemes
This scheme is mainly for the protection of the system against phase
faults.
Figure shows the connections of phase fault relay. Three over current
relays.
Earth Fault…
Combined Earth Fault and Phase Fault Protective Schemes
Figure shows the two over current relays (phase to phase fault relays)
and one earth fault relay.
For the protection against ground faults, only one directional over
current relay is required.
The directional element has two coils. One coil is energized by current
and the other by voltage.
A special five limbs VT which can energize both the earth fault relay as
well as the phase fault relays as shown in figure (c).