PROCEX User Manual
CONTENTS
3. PARAMETERS SETTINGS 4
PROCEX User Manual
Section 1
PANEL MOUNTING & ELECTRICAL CONNECTIONS
PANEL CUTOUTS
Figure 1.1
ProceX96
ProceX72 Panel Cutout
ProceX48 ProceX48H
Panel Cutout
Panel Cutout
92 X 92 mm Panel Cutout
68 X 68 mm -0, +0.5 mm
45 X 45 mm
-0, +0.5 mm 45 X 92 mm
-0, +0.5 mm
-0, +0.5 mm
ELECTRICAL CONNECTIONS
RELAY
SSR
C NO RELAY
SSR
OUTPUT-1 6 12
NO
OUTPUT-2 AC SUPPLY
85 ~ 265 V
OUTPUT-2 AC SUPPLY
DC INPUT OUTPUT-1
85 ~ 265 V
5 11
N
5 10
RELAY NO C NC L N
C
NC
4 9 4 10
L
3 48 x 48 8 72 x 72
DC INPUT
3 9
NC
2 7
mA
2 8
V
C
1 6
mA
V
NO
1 7
SSR
SSR
RELAY
open for V
AC SUPPLY
85 ~ 265 V
L N
OUTPUT-1
9 18 open for V
V SSR
8 17
C
mA
NC C NO RELAY
NC
7 16
1 2 3 4 5 6 7 8
6 15
5 96 x 96 14 48 x 96
4 13
9 10 11 12 13 14 15 16
NC
3 12
OUTPUT-2
RELAY NO C NC L N
DC INPUT
2 11
C
SSR 85 ~ 265 V
mA
V
NO
1 10 AC SUPPLY
OUTPUT-2
RELAY
SSR
1
PROCEX User Manual
Section 2
FRONT PANEL AND OPERATION
Proce
Process Value
Display
Alarm-1 Alarm-2
Indicator Indicator
PROCEX48H
Figure 2.1(b)
PROGRAM PRG
Key UP Key
DOWN Key
Table 2.1
KEY DEFINITIONS
Upon switching on the power to the Indicator, all displays and indicators are lit on for approximately 3 seconds. This is followed
by the indication of the Indicator model name for approximately 1 second. The Indicator now enters MAIN Mode
wherein the display shows the PV proportional to the Input DC signal within user set Range Low and Range High Limits.
2
PROCEX User Manual
PV ERROR INDICATION
Table 2.2
3
PROCEX User Manual
Section 3
PARAMETER SETTINGS
The Indicator offers various parameters for setting-up the configuration and operation modes. Each parameter has a unique
name and a settable value. For example, the parameter ‘Input Type’ is identified by its name and has the settable
values ‘0-20mA / 4-20mA / 0-5V / 0-10V’.
Further, the parameters are organized under different groups. Each group of parameters is called PAGE. Each page is
assigned a unique number for its identification and access. The various pages along with their parameters are described later.
Follow the steps below for setting / changing any parameter value.
1. Keep PRG key pressed (approximately 5 seconds) until display shows PAGE ( ). Release the key.
3. Press PRG key if page 0 is the desired page number (operator page) or use UP / DOWN keys to set the desired page
number and then press PRG key. The display now shows the name for the first parameter in the page.
9. For returning to Main Mode, keep PRG key pressed (approximately 3 seconds) until the display starts showing PV.
The following figures step-wise show an example of changing the value for the parameter ‘Resolution’ from ‘1’ to ‘0.1’. The
parameter ‘Resolution’ is available on PAGE-12 and is second in the list. Notice that from MAIN Mode the appropriate page
number is selected first and then the desired parameter name is selected for changing the value. Finally, PRG key is used to
return back to MAIN Mode.
Figure 3.1
or or PRG
PRG PRG PRG
MAIN Mode Set-up Mode Page Number Page Number First Parameter Second Parameter
Display Display on Page-12 on Page-12
Press PRG key Press PRG key. Use UP/DOWN Press PRG key Use UP/DOWN Press PRG
for approx. 5 sec. Display shows keys to set to open the keys to move to key to view
until display ‘Page Number’ 0 Page Number Page next parameter the Parameter
shows ‘PAGE’ Value
Figure 3.2
or PRG PRG
4
PROCEX User Manual
Table 3.1
PAGE - 0 : OPERATOR PARAMETERS
Parameter Description Settings
ALARM-1 SETPOINT
-1999 to 9999
Available only if selected ‘Alarm-1 type’ is either ‘Process High’ or (with selected
‘Process Low’. This parameter value sets the Upper (Process Resolution)
High) or Lower (Process Low) Alarm Limit.
ALARM-2 SETPOINT
-1999 to 9999
Available only if selected ‘Alarm-2 type’ is either ‘Process High’ or (with selected
‘Process Low’. This parameter value sets the Upper (Process Resolution)
High) or Lower (Process Low) Alarm Limit.
Table 3.2
PAGE - 1 : PV MIN / MAX PARAMETERS
Parameter Description Settings
MAXIMUM PROCESS VALUE
View Only
This gives the maximum PV recorded since Power-up or last reset
RESET PV MONITOR No
This command resets Maximum value and Minimum value to the Yes
instantaneous Process Value.
Table 3.3
PAGE - 12 : INPUT CONFIGURATION PARAMETERS
Parameter Description Settings
INPUT TYPE
Controller Version :
The Indicator is factory calibrated for DC Voltage (0-5V / 0-10V) 0 - 20 mA
and DC Current (0-20mA / 4-20mA). Select the appropriate input
type as per the type of Input Signal. 4 - 20 mA
Note : 0-5V
For DC Voltage Input, keep Terminals 2 & 3 open.
0 - 10 V
For DC Current Input, keep terminals 2 & 3 shorted.
RESOLUTION 1
0.01
0.001
5
PROCEX User Manual
Table 3.4
PAGE - 11 : ALARM PARAMETERS
Parameter Description Settings
ALARM-1 TYPE None
Type for Alarm-1. Process Low
Process High
ALARM-1 LOGIC
Normal : The alarm-1 output remains ON under alarm conditions; Normal
OFF otherwise. Reverse
Reverse : The alarm-1 output remains OFF under alarm
conditions; ON otherwise.
ALARM-1 INHIBIT
Yes : The alarm-1 is suppressed during start-up alarm conditions. No
No : The alarm-1 is not suppressed during start-up alarm
Yes
conditions.
1 to 999
ALARM-2 HYSTERESIS
(with selected
Same as Alarm-1 Hysteresis. Resolution)
ALARM-2 INHIBIT No
Same as Alarm-1 Inhibit. Yes
6
Process Precision Instruments
101, Diamond Industrial Estate, Navghar, Vasai Road (E),
Dist. Palghar - 401 210.Maharashtra, India
May 2017