Product Data Sheet: Circuit Breaker Compact NS800L - Micrologic 2.0 - 800 A - 3 Poles 3t

This document provides product specifications for a Compact NS800L circuit breaker with a Micrologic 2.0 trip unit rated for 800 amps. Key details include it being a 3-pole, 3-time protected breaker for AC distribution networks rated up to 800 volts. It has adjustable overload and instantaneous short-circuit protection settings and can disconnect currents up to 150,000 amps. Environmental standards include IP40 protection and operating temperatures from -25 to 70 degrees Celsius.

Uploaded by

Benjie Callanta
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
116 views3 pages

Product Data Sheet: Circuit Breaker Compact NS800L - Micrologic 2.0 - 800 A - 3 Poles 3t

This document provides product specifications for a Compact NS800L circuit breaker with a Micrologic 2.0 trip unit rated for 800 amps. Key details include it being a 3-pole, 3-time protected breaker for AC distribution networks rated up to 800 volts. It has adjustable overload and instantaneous short-circuit protection settings and can disconnect currents up to 150,000 amps. Environmental standards include IP40 protection and operating temperatures from -25 to 70 degrees Celsius.

Uploaded by

Benjie Callanta
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Product data sheet 33468

Characteristics circuit breaker Compact NS800L - Micrologic 2.0 -


800 A - 3 poles 3t

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range Compact
Range of product NS630b...1600
Product or component type Circuit breaker
Device short name Compact NS800L
Device application Distribution
Poles description 3P
Protected poles description 3t
Network type AC
Breaking capacity code L
Suitability for isolation Yes conforming to IEC 60947-2
Utilisation category Category A
Trip unit name Micrologic 2.0
Trip unit technology Electronic
Trip unit rating 800 A at 50 °C

Complementary
Network frequency 50/60 Hz
Control type Rotary handle
Toggle
Mounting mode Fixed
Mounting support Backplate
Upside connection Front
Downside connection Front
(In) rated current up to 65 °C 800 A at 50 °C
[Ui] rated insulation voltage 800 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 8 kV conforming to IEC 60947-2
[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2

May 8, 2020
1
Circuit breaker CT rating 800 A
Breaking capacity 130 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
150 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
150 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity 100 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
130 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
150 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
150 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
Auxiliary contact composition 1 NO/NC
Mechanical durability 10000 cycles
Electrical durability 2000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2
3000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2
3000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2
4000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
Local signalling Positive contact indication
Trip unit protection functions LI
Protection type Overload protection (long time)
Instantaneous short-circuit protection
Long time pick-up adjustment type Ir Adjustable
Long time pick-up adjustment range 0.4...1 x In
Long time delay adjustment type Adjustable 9 settings
[Tr] long-time delay adjustment range 0.7…16.6 s 7.2 x Ir
12.5…600 s 1.5 x Ir
0.5…24 s 6 x Ir
Thermal memory 20 mn
Instantaneous pick-up adjustment type Adjustable
Ii
Instantaneous pick-up adjustment 1.5...10 x Ir
range
Height 327 mm
Width 210 mm
Depth 147 mm

Environment
Standards IEC 60947-2
Product certifications ASEFA
ASTA
Power losses 20 W
IP degree of protection IP40 conforming to IEC 60529
IK degree of protection IK07 conforming to EN 50102
Pollution degree 3 conforming to IEC 60947
Ambient air temperature for operation -25…70 °C
Ambient air temperature for storage -50…85 °C

Offer Sustainability
Sustainable offer status Green Premium product
REACh Regulation REACh Declaration
EU RoHS Directive Compliant
EU RoHS Declaration
Mercury free Yes
RoHS exemption information Yes
China RoHS Regulation China RoHS declaration
Product out of China RoHS scope. Substance declaration for your information
Environmental Disclosure Product Environmental Profile
WEEE The product must be disposed on European Union markets following specific waste collection and
never end up in rubbish bins

2
Contractual warranty
Warranty 18 months