Data Sheet 6ES7212-1BE40-0XB0: General Information
Data Sheet 6ES7212-1BE40-0XB0: General Information
Data Sheet 6ES7212-1BE40-0XB0: General Information
General information
Product type designation CPU 1212C AC/DC/relay
Firmware version V4.2
Engineering with
● Programming package STEP 7 V14 or higher
Supply voltage
Rated value (AC)
● 120 V AC Yes
● 230 V AC Yes
permissible range, lower limit (AC) 85 V
permissible range, upper limit (AC) 264 V
Line frequency
● permissible range, lower limit 47 Hz
● permissible range, upper limit 63 Hz
Input current
Current consumption (rated value) 80 mA at 120 V AC; 40 mA at 240 V AC
Current consumption, max. 240 mA at 120 V AC; 120 mA at 240 V AC
Inrush current, max. 20 A; at 264 V
Output current
for backplane bus (5 V DC), max. 1 000 mA; Max. 5 V DC for SM and CM
Encoder supply
24 V encoder supply
● 24 V 20.4 to 28.8V
Power loss
Power loss, typ. 11 W
Memory
Work memory
● integrated 75 kbyte
● expandable No
Load memory
● integrated 2 Mbyte
● Plug-in (SIMATIC Memory Card), max. with SIMATIC memory card
Backup
● present Yes
● maintenance-free Yes
● without battery Yes
CPU-blocks
Number of blocks (total) DBs, FCs, FBs, counters and timers. The maximum number of
addressable blocks ranges from 1 to 65535. There is no
restriction, the entire working memory can be used
OB
● Number, max. Limited only by RAM for code
Address area
Process image
● Inputs, adjustable 1 kbyte
Hardware configuration
Number of modules per system, max. 3 comm. modules, 1 signal board, 2 signal modules
Time of day
Clock
● Hardware clock (real-time) Yes
● Backup time 480 h; Typical
● Deviation per day, max. ±60 s/month at 25 °C
Digital inputs
Number of digital inputs 8; Integrated
● of which inputs usable for technological 6; HSC (High Speed Counting)
functions
Source/sink input Yes
Number of simultaneously controllable inputs
all mounting positions
— up to 40 °C, max. 8
Input voltage
● Rated value (DC) 24 V
● for signal "0" 5 V DC at 1 mA
● for signal "1" 15 V DC at 2.5 mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizable 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms,
selectable in groups of four
— at "0" to "1", min. 0.2 ms
— at "0" to "1", max. 12.8 ms
for interrupt inputs
— parameterizable Yes
for technological functions
— parameterizable Single phase: 3 @ 100 kHz & 3 @ 30 kHz, differential: 3 @ 80
kHz & 3 @ 30 kHz
Cable length
● shielded, max. 500 m; 50 m for technological functions
● unshielded, max. 300 m; for technological functions: No
Digital outputs
Number of digital outputs 6; Relays
Switching capacity of the outputs
● with resistive load, max. 2 A
● on lamp load, max. 30 W with DC, 200 W with AC
Output delay with resistive load
● "0" to "1", max. 10 ms; max.
Analog inputs
Number of analog inputs 2
Input ranges
● Voltage Yes
Input ranges (rated values), voltages
● 0 to +10 V Yes
— Input resistance (0 to 10 V) ≥100k ohms
Cable length
● shielded, max. 100 m; twisted and shielded
Analog outputs
Number of analog outputs 0
Encoder
Connectable encoders
● 2-wire sensor Yes
1. Interface
Interface type PROFINET
Physics Ethernet
Isolated Yes
automatic detection of transmission rate Yes
Autonegotiation Yes
Autocrossing Yes
Interface types
● Number of ports 1
● integrated switch No
Protocols
● PROFINET IO Controller Yes
● PROFINET IO Device Yes
Protocols
Supports protocol for PROFINET IO Yes
PROFIBUS Yes; CM 1243-5 (master) or CM 1242-5 (slave) required
Communication functions
S7 communication
● supported Yes
● as server Yes
● as client Yes
● User data per job, max. See online help (S7 communication, user data size)
Number of connections
● overall 16; dynamically
Interrupts/diagnostics/status information
Diagnostics indication LED
Integrated Functions
Number of counters 4
Counting frequency (counter) max. 100 kHz
Frequency measurement Yes
controlled positioning Yes
Number of position-controlled positioning axes, max. 8
Number of positioning axes via pulse-direction Up to 4 with SB 1222
interface
PID controller Yes
Number of alarm inputs 4
Potential separation
Potential separation digital inputs
● Potential separation digital inputs 500V AC for 1 minute
● between the channels, in groups of 1
Potential separation digital outputs
● Potential separation digital outputs Relays
● between the channels No
● between the channels, in groups of 2
EMC
Interference immunity against discharge of static electricity
● Interference immunity against discharge of Yes
static electricity acc. to IEC 61000-4-2
— Test voltage at air discharge 8 kV
— Test voltage at contact discharge 6 kV
Interference immunity to cable-borne interference
● Interference immunity on supply lines acc. to Yes
IEC 61000-4-4
● Interference immunity on signal cables acc. to Yes
IEC 61000-4-4
Interference immunity against voltage surge
● Interference immunity on supply lines acc. to Yes
IEC 61000-4-5
Interference immunity against conducted variable disturbance induced by high-frequency fields
● Interference immunity against high-frequency Yes
radiation acc. to IEC 61000-4-6
Emission of radio interference acc. to EN 55 011
● Limit class A, for use in industrial areas Yes; Group 1
● Limit class B, for use in residential areas Yes; When appropriate measures are used to ensure compliance
with the limits for Class B according to EN 55011
Ambient conditions
Free fall
● Fall height, max. 0.3 m; five times, in product package
Ambient temperature during operation
● min. -20 °C
● max. 60 °C; Number of simultaneously activated inputs or outputs 4 or
3 (no adjacent points) at 60 °C horizontal or 50 °C vertical, 8 or 6
at 55 °C horizontal or 45 °C vertical
● horizontal installation, min. -20 °C
● horizontal installation, max. 60 °C
● vertical installation, min. -20 °C
● vertical installation, max. 50 °C
Ambient temperature during storage/transportation
● min. -40 °C
● max. 70 °C
Air pressure acc. to IEC 60068-2-13
● Operation, min. 795 hPa
● Operation, max. 1 080 hPa
● Storage/transport, min. 660 hPa
● Storage/transport, max. 1 080 hPa
Altitude during operation relating to sea level
● Installation altitude, min. -1 000 m
● Installation altitude, max. 2 000 m
Relative humidity
● Operation, max. 95 %; no condensation
Vibrations
● Vibration resistance during operation acc. to 2 g (m/s²) wall mounting, 1 g (m/s²) DIN rail
IEC 60068-2-6
● Operation, tested according to IEC 60068-2-6 Yes
Shock testing
● tested according to IEC 60068-2-27 Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak
value), duration 11 ms
Configuration
Programming
Programming language
— LAD Yes
— FBD Yes
— SCL Yes
Know-how protection
● User program protection/password protection Yes
● Copy protection Yes
● Block protection Yes
Access protection
● Protection level: Write protection Yes
● Protection level: Read/write protection Yes
● Protection level: Complete protection Yes
Cycle time monitoring
● adjustable Yes
Dimensions
Width 90 mm
Height 100 mm
Depth 75 mm
Weights
Weight, approx. 425 g