Restricted Earth Fault Protection-Lv (Mcag14) : Stabilising Voltage Calculation
Restricted Earth Fault Protection-Lv (Mcag14) : Stabilising Voltage Calculation
RR-relay impedance
Rct-secondary resistance of CT
=787.3/0.135
=5831.85/800
=7.29 A
>26.68V
KNEE POINT VOLTAGE SELECTION:
>2*26.68=53.36V
CT MAGANATISING CURRENT CALCULATION:
=26.68*0.04/(300/2)=0.0071A
Ie-magnatising current of CT
PRIMARY OPREATING CURRENT CALCULATION:
=26.68-(1/0.1)/0.1
=166.8 ohm
RELAY IMPEDANCE CALCULATION:
Rr=VA/I2
=1/0.12
=100 ohm
FAULT VOLTAGE CALCULATION:
Vf=7.29*(3.2+0.461+166.8+100)
=1971.6V
=2*(2*300(1971.6-300))0.5
=2002.9V
When the maximum voltage which appears across the relay circuit on
internal faults exceeds 3000 volts peak a metrosil non-linear resistor must be
The metrosil should be chosen so that the current at the voltage setting of
the relay is less than 30mA for a 1 amp and 100mA for 5 amp current
transformers.
At the maximum secondary internal fault current the metrosil cut-off point
should not be greater than 1500 volts rms or 2120 volts peak.