DPDPK Manual ProfibusFV
DPDPK Manual ProfibusFV
A5E00224669-03
Preface
DP/DP Coupler
A5E00244669-03 iii
Operating Instructions · Edition 11/2006
Control Unit
CU240S
CU240S DP
CU240S DP-F
SINAMICS
G120
s
Introduction 1
Safety notes 2
Description 3
SINAMICS
Installing/Mounting 4
SINAMICS G120
Control Units CU240S 5
Commissioning (software)
Operation 6
Operating Instructions
Functions 8
Technical data 9
Spare parts/Accessories 10
Appendix A
List of abbreviations B
11/2006
A5E00766042B AA
Safety Guidelines
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
Danger
indicates that death or severe personal injury will result if proper precautions are not taken.
Warning
indicates that death or severe personal injury may result if proper precautions are not taken.
Caution
with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken.
Caution
without a safety alert symbol, indicates that property damage can result if proper precautions are not taken.
Notice
indicates that an unintended result or situation can occur if the corresponding information is not taken into
account.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The device/system may only be set up and used in conjunction with this documentation. Commissioning and
operation of a device/system may only be performed by qualified personnel. Within the context of the safety notes
in this documentation qualified persons are defined as persons who are authorized to commission, ground and
label devices, systems and circuits in accordance with established safety practices and standards.
Prescribed Usage
Note the following:
Warning
This device may only be used for the applications described in the catalog or the technical description and only in
connection with devices or components from other manufacturers which have been approved or recommended by
Siemens. Correct, reliable operation of the product requires proper transport, storage, positioning and assembly
as well as careful operation and maintenance.
Trademarks
All names identified by ® are registered trademarks of the Siemens AG. The remaining trademarks in this
publication may be trademarks whose use by third parties for their own purposes could violate the rights of the
owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
B List of abbreviations................................................................................................................................B-1
B.1 Abbreviations ............................................................................................................................. B-1
Index................................................................................................................................................ Index-1
Tables
Table 3-1 Interfaces of the Control Units CU240S..................................................................................... 3-6
Table 3-2 Following interfaces are available, see also figure "Variants of Control Units CU240S"......... 3-10
Table 3-3 Control terminals...................................................................................................................... 3-10
Table 3-4 Settings of the General I/O DIP switches ................................................................................ 3-13
Table 3-5 Example address for the PROFIBUS DP interface.................................................................. 3-14
Table 3-6 Function Selection of Digital Input and Digital Output ............................................................. 3-16
Table 3-7 BICO Command Parameter..................................................................................................... 3-17
Table 3-8 Command Sources for Fixed Frequencies .............................................................................. 3-17
Table 3-9 Faults, Alarms, Monitoring ....................................................................................................... 3-17
Table 4-1 Example address for the PROFIBUS DP interface.................................................................. 4-11
Table 4-2 PIN assignment of the 9-pin sub-D socket .............................................................................. 4-11
Table 4-3 Permissible cable length for one segment............................................................................... 4-12
Table 4-4 Recommended PROFIBUS connectors .................................................................................. 4-13
Table 4-5 9-way SUB-D connector for RS485 ......................................................................................... 4-17
Table 4-6 Recommended PROFIBUS connectors .................................................................................. 4-17
Table 5-1 Parameter attributes - BICO ...................................................................................................... 5-5
Table 5-2 Parameter attributes - access level ........................................................................................... 5-5
Table 5-3 Parameter attributes - Change state.......................................................................................... 5-6
Table 5-4 Parameter attributes - Data types .............................................................................................. 5-6
Table 5-5 Parameter attributes - Unit......................................................................................................... 5-7
Table 5-6 Parameter attributes - Grouping ................................................................................................ 5-8
Table 5-7 Parameter attributes - Active ..................................................................................................... 5-8
Table 5-8 Parameter attributes - Quick commissioning ............................................................................. 5-9
Table 5-9 Parameter attributes - Value range............................................................................................ 5-9
Table 5-10 Data sets .................................................................................................................................... 5-9
Table 5-11 Pre-assignment of the digital inputs for a CU240S *) .............................................................. 5-11
Table 5-12 OP keys and their functions ..................................................................................................... 5-13
Table 5-13 Changing P0003 - parameter access level.............................................................................. 5-14
Table 5-14 Changing P0700 an index parameter - setting OP control ...................................................... 5-14
Table 5-15 Connection possibilities for STARTER .................................................................................... 5-16
Table 5-16 Quick commissioning ............................................................................................................... 5-21
Available documentation
The following document types are available for the SINAMICS G120 inverters:
● Brochure
● Catalog
● Getting started Guide
● Operating Instructions
● Hardware Installation Manual
● Compact Operating Instructions (for the Control Units)
● Parameter List.
The documents can be downloaded from the Internet via the following link:
http://www.siemens.de/sinamics-g120
Furthermore you will find in the internet:
● Detailed technical information under:
http://support.automation.siemens.com/WW/view/de/22339653/133000
● Application examples under:
http://support.automation.siemens.com/WW/view/de/20208582/136000
Brochure
The brochure is advertising literature designed to introduce the product to the marketplace. It
contains a basic outline of the product with a brief overview of the technical capabilities of
the product.
Catalog
The catalog presents information that allows the customer to select an appropriate inverter
including all available options. It contains detailed technical specifications, ordering and
pricing information to allow the customer to order the appropriate items for their application
or plant.
Operating Instructions
The Operating Instructions gives information for the Control Unit regarding the features of
the product. It gives detailed information on commissioning, control modes, system
parameters, troubleshooting, technical specifications and the available options from the
product.
Parameter List
The Parameter List contains a detailed description of all the parameters that can be modified
and adapted for specific applications. The Parameter List also contains a series of function
diagrams to diagramatically portray the nature and interoperability of the system parameters.
General
Warning
This equipment contains dangerous voltages and controls potentially dangerous rotating
mechanical parts. Non-compliance with the Warnings or failure to follow the instructions
contained in this manual can result in loss of life, severe personal injury or serious damage
to property.
Only suitable qualified personnel should work on this equipment, and only after becoming
familiar with all safety notices, installation, operation and maintenance procedures contained
in this manual. The successful and safe operation of this equipment is dependent upon its
proper handling, installation, operation and maintenance.
Take particular notice of the general and regional installation and safety regulations
regarding work on dangerous voltage installation (e.g. EN 50178) as well as the relevant
regulations regarding the correct use of tools and personal protective equipment (PPE).
Caution
Children and the general public must be prevented from accessing or approaching the
equipment!
This equipment may only be used for the purpose specified by the manufacturer.
Unauthorized modifications and the use of spare parts and accessories that are not sold or
recommended by the manufacturer of the equipment can cause fires, electric shocks and
injuries.
Notice
Keep these operating instructions within easy reach of the equipment and make them
available to all users.
Whenever measuring or testing has to be performed on live equipment, the regulations of
Safety Code BGV A2 must be observed, in particular § 8 "Permissible Deviations when
Working on Live Parts". Suitable electronic tools should be used.
Before installing and commissioning, please read these safety instructions and warnings
carefully and all the warning labels attached to the equipment. Make sure that the warning
labels are kept in a legible condition and replace missing or damaged labels.
Warning
Correct transport, storage as well as careful operation and maintenance are essential for the
proper and safe operation of the equipment.
Caution
Protect the equipment against physical shocks and vibration during transport and storage. It
is important that the equipment is protected from water (rainfall) and excessive
temperatures.
Commissioning
Warning
Working on the equipment by unqualified personnel or failure to comply with warnings can
result in severe personal injury or serious damage to material. Only suitably qualified
personnel trained in the setup, installation, commissioning and operation of the product
should carry out work on the equipment.
Caution
Cable connection
The control cables must be laid separately from the power cables. Carry out the connections
as shown in the installation section in this manual, to prevent inductive and capacitive
interference from affecting the correct function of the system.
Operation
Warning
The SINAMICS G120 inverters operate at high voltages.
When operating electrical devices, it is impossible to avoid applying hazardous voltages to
certain parts of the equipment.
Emergency Stop facilities according to EN 60204, IEC 204 (VDE 0113) must remain
operative in all operating modes of the control equipment. Any disengagement of the
Emergency Stop facility must not lead to an uncontrolled or an undefined restart of the
equipment.
Certain parameter settings may cause the SINAMICS G120 inverter to restart automatically
after an input power failure, for example, the automatic restart function.
Wherever faults occurring in the control equipment can lead to substantial material damage
or even grievous bodily injury (that is, potentially dangerous faults), additional external
precautions must be taken or facilities provided to ensure or enforce safe operation, even
when a fault occurs (e.g. independent limit switches, mechanical interlocks, etc.).
Motor parameters must be accurately configured for motor overload protection to operate
correctly.
This equipment is capable of providing internal motor overload protection according to
UL508C. Refer to P0610 and P0335, i²t is ON by default.
Only Control Units with fail-safe functions can be used as an "Emergency Stop Mechanism"
(see EN 60204, section 9.2.5.4).
Repair
Warning
Repairs on equipment may only be carried out by Siemens Service, by repair centers
authorized by Siemens or by authorized personnel who are thoroughly acquainted with all
the warnings and operating procedures contained in this manual.
Any defective parts or components must be replaced using parts contained in the relevant
spare parts list.
Disconnect the power supply before opening the equipment for access.
Caution
The packaging of the inverter is re-usable. Retain the packaging for future use.
Easy-to-release screw and snap connectors allow you to break the unit down into its
component parts. You can recycle these component parts, dispose of them in accordance
with local requirements or return them to the manufacturer.
3.1 CU240S
This manual …
… decribes functions and features of the control units
● CU240S
● CU240S-DP
● CU240S DP-F
Overview
The following options are available for the SINAMICS G120 Inverters:
Common features
● Modular inverter
● Simple to install
● Signals can be interconnected using BICO technology
● Different data sets selectable
● Fast current limiting (FCL) for trip-free operation
● Easy exchange of power module or control unit (swap or hot swap)
● Rugged EMC design
● Configurable for a wide range of applications
● Non-volatile saving of parameter settings - either in the EEPROM of the CU or on an
MMC
● Status display via LEDs on the control unit
● High pulse frequencies for low noise motor operation
● EM brake relay.
Commissioning functions
● Quick commissioning
● Motor/control data calculation
● Motor data identification
● Application commissioning
● Series commissioning
● Parameter reset to the factory setting.
Operating functions
● Adjustable setpoint channel
● Adjustable ramp-function generator (RFG)
● JOG mode
● Freely-assignable function blocks (FFB)
● Positioning ramp down
● Automatic restart (WEA)
● Flying restart
● Current limiting
● Slip compensation
● Motor holding brake (MHB).
Control functions
● V/f control with different characteristics
● SLVC (Sensorless vector control mode) speed and torque
● VC (Vector control mode with encoder) speed and torque
Protective functions
● Motor protective functions
● Inverter protective functions
● Plant/system protective functions.
352),%86 352),%86
'3$GGUHVV '3$GGUHVV
',3VZLWFKHV ',3VZLWFKHV
'2 '2 '2 '2 '2 '2 '2 '2
1& 12 &20 12 &20 1& 12 &20
(1& (1& (1& (1& (1& (1&
$3 $1 %3 %1 =3 =1
,QYHUWHU '2 '2 '2 '2 '2 '2 '2 '2
1& 12 &20 12 &20 1& 12 &20
(1& (1& (1& (1& (1& (1&
$3 $1 %3 %1 =3 =1
,QYHUWHU '2 '2 '2 '2 '2 '2 '2 '2
1& 12 &20 12 &20 1& 12 &20
(1& (1& (1& (1& (1& (1&
$3 $1 %3 %1 =3 =1
,QYHUWHU
VWDWXV/(' VWDWXV/(' VWDWXV/('
(1& 89 89
IDLOVDIH
', ', ', ', ', ', ', ', ', (1& 89 89 (1& 89 89 ', ', ', ', ', ', ',$ ',% ',$ ',%
6833/< ', ', ', ', ', ', ', ', ', 6833/<
6833/<
7HUPLQDOVIRU
IDLOVDIHIXQFWLRQV
Variants
9
$,
ุN˖ 2SWLRQ3RUW
3&&RQQHFWLRQ.LW
$, $'
RSWLRQDO
$,
$, $'
00&
',
*HQHUDO,2',3VZLWFK
',
P$
', 21
9(QFRGHU
'LJLWDOLQSXWV
9(QFRGHU
WHUPLQDWLRQ
WHUPLQDWLRQ
WHUPLQDWLRQ
(QFRGHU$
(QFRGHU%
(QFRGHU=
6XSSO\
6XSSO\
6WDQGDUG
',
$,
$,
',
2))
',
9
',
',
',
89
89
(1&
6XSSO\
37&
37& $'
.7< 37&
$2
P$P$
'$
3RZHU0RGXOH30
RU99
$2
PD[˖
$2
&86
P$P$ '$
PD[˖ $2
&20
'2 12 30,)
1&
/RZ9ROWDJHRQO\
&20
'2
12
9P$
&20
'2 12
1&
9
)URP
H[WHUQDO
9
VRXUFH
1RWFRQQHFWHG
(1&$3
5['7['3
(QFRGHULQWHUIDFH
68%'FRQQHFWRU
(1&$1
77/
,QWHUIDFH
56
(1&%3
(1&%1 9s
(1&=3
5['7['1
(1&=1
&DVH &DEOH6KLHOG
9
$, 2SWLRQ3RUW
ุN˖
3&&RQQHFWLRQ.LW
$, $' RSWLRQDO
$,
$, $' 00&
',
*HQHUDO,2',3VZLWFK
', P$
21
9(QFRGHU
',
9(QFRGHU
WHUPLQDWLRQ
WHUPLQDWLRQ
WHUPLQDWLRQ
(QFRGHU$
(QFRGHU%
(QFRGHU=
'LJLWDOLQSXWV
6XSSO\
6XSSO\
$,
$,
', 6WDQGDUG
',
2))
', 9
', 352),%86$GGUHVV',3VZLWFK
',
21
',
%LW
%LW
%LW
%LW
%LW
%LW
%LW
89
89
2))
(1&
6XSSO\
37&
37& $'
.7< 37&
$2
P$P$
RU99 '$
&86'3
3RZHU0RGXOH30
$2
PD[˖
$2
P$P$ '$
PD[˖ $2
&20
12
'2
30,)
1&
/RZ9ROWDJHRQO\
&20
'2
12
9P$
&20
'2 12
1&
9
)URP
H[WHUQDO
9
VRXUFH
1RWFRQQHFWHG
6KLHOG
89
(1&$3
5['7['3
(QFRGHULQWHUIDFH
68%'FRQQHFWRU
(1&$1
352),%86
&1753
,QWHUIDFH
(1&%3 '*1'
(1&%1 93
89
(1&=3
5['7['1
(1&=1
&DVH &DEOH6KLHOG
9
$, 2SWLRQ3RUW
ุN˖
3&&RQQHFWLRQ.LW
$, $' RSWLRQDO
$,
$, $'
00&
',
*HQHUDO,2',3VZLWFK
'LJLWDOLQSXWV
',
P$
6WDQGDUG
', 21
9(QFRGHU
9(QFRGHU
WHUPLQDWLRQ
WHUPLQDWLRQ
WHUPLQDWLRQ
(QFRGHU$
(QFRGHU%
(QFRGHU=
6XSSO\
6XSSO\
',
$,
$,
',
2))
',
9
89
352),%86$GGUHVV',3VZLWFK
'LJLWDOLQSXWV
)',$
)DLOVDIH
3DLUHG 21
)',%
%LW
%LW
%LW
%LW
%LW
%LW
%LW
)',$
3DLUHG
)',%
89 2))
(1&
6XSSO\
37&
37& $'
.7< 37&
&86'3)
$2
P$P$
RU99 '$
3RZHU0RGXOH30
$2
PD[˖
$2
P$P$ '$
PD[˖ $2
&20
12
'2
30,)
1&
/RZ9ROWDJHRQO\
&20
'2
12
9P$
&20
'2 12
1&
9
)URP
H[WHUQDO
9
VRXUFH
1RWFRQQHFWHG
6KLHOG
89
(1&$3
5['7['3
(QFRGHULQWHUIDFH
68%'FRQQHFWRU
(1&$1
352),%86
&1753
,QWHUIDFH
(1&%3 '*1'
(1&%1 93
89
(1&=3
5['7['1
(1&=1
&DVH &DEOH6KLHOG
Overview
Table 3-2 Following interfaces are available, see also figure "Variants of Control Units CU240S"
MMC
The Multi Media Card (MMC) is a small, removable flash storage device, with a low power
consumption which provides the ability to store data sets for the inverter.
The MMC provides non volatile data storage which requires no power to maintain the data
stored on the card.
It is recommended that the SINAMICS-MMC (order number: 6SL3254-0AM00-0AA0) is used
for the storage and transfer of data sets.
Option port
Via the Option port the OP is connected to the inverter, it can also be used to connect a PC
via the PC Connection Kit to the inverter for parameterizing using STARTER.
Terminals
'2 '2 '2 '2 '2 '2 '2 '2 (1& (1& (1& (1& (1& (1&
1& 12 &20 12 &20 1& 12 &20 $3 $1 %3 %1 =3 =1
', ', ', ', ', ', ', ', ', (1& 89 89
6833/<
'2 '2 '2 '2 '2 '2 '2 '2 (1& (1& (1& (1& (1& (1&
1& 12 &20 12 &20 1& 12 &20 $3 $1 %3 %1 =3 =1
)$,/6$)(',*,7$/,13876
', ', ', ', ', ', )',$ )',% )',$ )',%
(1& 89 89
6833/<
21
9(QFRGHU
9(QFRGHU
WHUPLQDWLRQ
WHUPLQDWLRQ
WHUPLQDWLRQ
(QFRGHU$
(QFRGHU%
(QFRGHU=
VXSSO\
VXSSO\
$,
$,
2))
2 3 4 5 6 7
DIP switch 1 2 3 4 5 6 7
Meaning AI0 AI1 24 V Encoder 5 V Encoder Encoder A Encoder B Encoder Z
supply supply termination termination termination
ON 0 mA ... 0 mA ... 24 V 5V Encoder A Encoder B Encoder Z
20 mA 20 mA ON ON ON
21
%LW
%LW
%LW
%LW
%LW
%LW
%LW
2))
DIP switch 1 2 3 4 5 6 7
Add to address 1 2 4 8 16 32 64
Example 1: Address = 3 = 1 + 2
Example 2:
Address = 88 = 8 + 16 + 64
5HDG\
*HQHUDO %XV
)DXOW )DLOXUH
(QG 6DIH
6WDWH 6WRS
6DIH 6DIHO\
7RUTXH /LPLWHG
2II 6SHHG
For detailed description refer to "LED overview" in section "Service and maintenance".
SUB-D connector
Via the SUB-D connector - depending on the type of Control Unit - the following interfaces
are available:
Note
Setting P0700 = 6 (command source via fieldbus communication) and P1000 = 6 (setpoint
source via fieldbus communication) are not possible with a CU240S
Setting P0700 = 5 (command source via USS communication) and P1000 = 5 (setpoint
source via USS communication) are not possible with a CU240S DP or a CU240S DP-F
Warning
An inverter can be switched on unintentionally if the installation is not performed correctly.
The inverter must be started-up by personnel who are qualified and trained in installing
systems of this type.
Figure 4-1 General layout of a CU240 Control Unit
24 V power supply
Normally the CU is supplied with 24 V from Power Module. But it is also possible to use an
external DC 24 V supply (20.4 V … 28.8 V, 0.5 A). It must be connected to the Control Unit
terminals 31 (+ 24 V In) and 32 (0 V In). Some reasons for using an external 24 V power
supply are:
● The PROFIBUS DP interface is required to communicate with the Control Unit when the
Power Module mains power is not present
● Supply for 24 V encoder
Caution
Care must be taken to ensure that the 24 V DC power is connected correctly or damage
to the Control Unit may occur.
Max. cable length on 24 V DC supply and I/O cables connected to CU must not exceed
10 m. Use of unscreened cables is possible however we recommend to use screened
cables.
Note
If the CU is externally powered with 24 V DC but the power module is disconnected from
the mains supply, the faults F0001 ... F0028 are not generated.
General
To have access to the control terminals, the terminal cover must be removed, as shown in
the figure below. The control terminals have a maximum tighting torque of 0.25 Nm
(2.2 lbf.in) and a nominal cable cross section of 1.5 mm2.
The terminals of the CU240 control units are combined to terminal blocks. They can be
detached from the control unit, as shown in the figure below.This allows the control units to
be swapped out for another of the same type without the need for rewiring.
After all the wiring of the control unit is completed - ensure that the terminal cover is
replaced.
Note
To control the CU240S DP or CU240S DP-F via terminals is also possible, but in this case
the parameter settings for command and setpoint source have to be changed.
In this section examples of controlling a SINAMICS G120 inverter with a CU240S via
terminals are shown.
● Basic control with the default settings
● Frequency setpoint and an additional setpoint via terminals
(AI0 and AI1 used as voltage inputs)
● Frequency setpoint and an additional setpoint via terminals
(AI0 and AI1 used as current inputs).
Control settings
Digital and analog inputs for commands and setpoints are parameterized for a cabling as
shown in the following figure. Furthermore the state of the inverter is monitored via digital
and analog outputs.
'2 '2 '2 '2 '2 '2 '2 '2 (1& (1& (1& (1& (1& (1&
1& 12 &20 12 &20 1& 12 &20 $3 $1 %3 %1 =3 =1
)DXOW :DUQLQJ
/DPS2Q /DPS2Q
5XQ6WRS
5HYHUVH
$FN
ุN˖
$QDORJ2XWSXW$2
P$P$˖
'2 '2 '2 '2 '2 '2 '2 '2 (1& (1& (1& (1& (1& (1&
1& 12 &20 12 &20 1& 12 &20 $3 $1 %3 %1 =3 =1
', ', ', ', ', ', ', ', ', (1& 89 89
6833/<
ุN˖ ุN˖
Figure 4-6 Terminal connection for using AI0 and AI1 as voltage inputs for main and
additionalsetpoint
Note
Index [0] is analog input 0, Index [1] is analog input 1, if you are only using one analog
input then you only need to change those indices for the specific analog input.
'2 '2 '2 '2 '2 '2 '2 '2 (1& (1& (1& (1& (1& (1&
1& 12 &20 12 &20 1& 12 &20 $3 $1 %3 %1 =3 =1
P$ P$
RU RU
P$ P$
Figure 4-7 Terminal connection for using AI0 and AI1 as current inputs for main and additional
setpoint
PROFIBUS DP Interface
The function of the PROFIBUS DP interface is to provide a PROFIBUS DP-based link
between inverters of the SINAMICS G120 product range and higher-level automation
systems e.g. SIMATIC S7.
Note
The address is taken from P0918 if all PROFIBUS DP address DIP switches are in the OFF
position, otherwise the DIP switch setting is valid.
Caution
The power supply must be switched off before the DIP switch settings are changed. DIP
switch setting changes do not take effect until the Control Unit has been powered-up again.
The restart must be initiated by switching the power off and on again irrespective of whether
the Control Unit is supplied with the inverter line supply or its own, separate 24 V connection.
DIP switch 1 2 3 4 5 6 7
Add to address 1 2 4 8 16 32 64
Example 1: Address = 3 = 1 + 2
Example 2: Address = 88 = 8 + 16 + 64
External 24 V supply
If the PROFIBUS DP interface is required to communicate with the Control Unit when the
Power Module mains power is not present, a 24 V supply must be connected to the Control
Unit terminals 31 (+ 24 V In) and 32 (0 V In).
Bus connector
To connect the PROFIBUS cable to the PROFIBUS DP interface, a bus connector of one of
the types described in the following table is recommended.
PG socket No No
Max. baud rate 12 Mbaud 12 Mbaud
Terminating resistor On/Off switch On/Off switch
Outgoing cable unit 180° 180°
Interfaces
PROFIBUS nodes 9-pin sub D socket 9-pin sub D socket
PROFIBUS bus cable 4 modular terminals for wires up 4 modular terminals for wires up
to 1.5 mm2 to 1.5 mm2
Connectable PROFIBUS cable 8 ± 0.5 mm 8 ± 0.5 mm
diameter
Note
We recommend only these two connectors since they can be used without difficulty for all
SINAMICS G120 models and are completely compatible in terms of outgoing cable unit
angle.
Bus terminator
Each bus segment must have a resistor network, i.e. a bus terminator, at both ends.
Where the recommended bus connectors have been used, the bus terminator can be
switched in and out by means of switches as shown in the figure below.
%XV
WHUPLQDWRU
VZLWFK
8S %XVWHUPLQDWLRQ21
'RZQ %XVWHUPLQDWLRQ2))
Using the recommended bus connectors the first and last node on the PROFIBUS network
must be terminated (as shown in the figure below), this switching of the bus terminator
provides both the 220 Ω termination and the 390 Ω biasing. The 390 Ω biasing maintains the
potential difference between the signals in the PROFIBUS network cables.
3/&FRQQHFWRUWHUPLQDWHG
R R R
on on on
off off off
A1 B1 A2 B2 A1 B1 A2 B2
on
R
on
off
A1 B1 A2 B2
)LQDOQRGHWHUPLQDWHG
Warning
It must be ensured that any node, where the biasing components of the bus are connected,
is powered at all times in which the bus is in operation.
Screening
The screen of the PROFIBUS DP cable must be connected in the bus connector. Additional
screening is provided using a screen clamp on the bus cable screen which must make 360°
contact with the protective earth. The solid copper core must not be scored when the
insulation is removed from the core ends. You must also ensure that the screen of each bus
cable is connected to protective earth at both the cabinet entry point and in the inverter
housing.
Note
The bus cables must be internally twisted and screened, and installed separately from power
cables with a minimum distance 20 cm (7.8 inches). The braided screen and underlying
laminated foil screen (if applicable) must be connected in a 360°, positive connection at both
ends, that is, the screen on the bus cable between two inverters must be connected to the
inverter housing at both ends. The same applies to the screen of the bus cable between the
PROFIBUS DP master and inverter.
Crossovers between bus and power cables must be laid at an angle of 90°.
Equipotential bonding
Differences in potential (for example, due to different mains supplies) between the inverters
and the PROFIBUS DP master must be avoided.
● Recommended equipotential bonding cables:
– 16 mm2 Cu for equipotential bonding cables up to 200 m long
– 25 mm2 Cu for equipotential bonding cables of over 200 m long.
● Equipotential bonding cables must be routed as close as possible to signal leads; this
means that the area between the bonding conductor and signal lead is as small as
possible.
● Equipotential bonding cables must be contacted in a 360° connection with the earth
electrode/PE conductor.
RS485 Interface
The built-in connector is a 9-way SUB-D female connector for RS485.
PG socket No No
Max. baud rate 12 Mbaud 12 Mbaud
Terminating resistor On/Off switch On/Off switch
Outgoing cable unit 180° 180°
Note
Upload and download
• Upload means to save the parameters from the EEPROM of an inverter to a PC (via
STARTER), MMC or an OP.
• Download means to write a parameter set held on a PC, MMC or an OP to the RAM or
EEPROM of an inverter.
5.2 Parameters
Overview of parameters
The inverter is adapted to a particular application using the appropriate parameters. This
means that each parameter is identified by a parameter number and specific attributes (e.g.
readable, can be written into BICO attribute, group attribute etc.). Within any one particular
inverter system, the parameter number is unique. On the other hand, an attribute can be
assigned a number of times so that several parameters can have the same attribute.
Parameters can be accessed using the following operator units:
● OP
● PC-based commissioning (start-up) tool "STARTER".
There are two main types of parameters; those that can be altered and those that are read-
only.
3DUDPHWHU
ಯQRUPDOರ ಯQRUPDOರ
5HDGSDUDPHWHUV %,&2RXWSXW :ULWH5HDGSDUDPHWHUV %,&2LQWSXW
Description
Parameters which can be written into and displayed are indicated by the prefix "P".
These parameters directly influence the behavior of a function. The value of this parameter is
saved in non-volatile memory (EEPROM) as long as the appropriate option was selected
(non-volatile data save). Otherwise, these values are saved in the volatile memory (RAM) of
the processor, which are lost after power failure or power-off/power-on operations.
Examples of the standard notation used throughout our manuals is given below.
Notation examples:
P0970 parameter 970
P0748.1 parameter 748, bit 01
P0819[1] parameter 819 index 1
P0013[0 ... 19] parameter 13 with 20 indices (indices 0 to 19)
Description
Parameters which can only be monitored are indicated by the prefix "r".
These parameters are used to display internal quantities, for example states and actual
values.
Notation examples:
r0002 monitoring parameter 2
r0052.3 monitoring parameter 52, bit 03
r0947[2] monitoring parameter 947 index 2
r0964[0 ... 4] monitoring parameter 964 with 5 indices (indices 0 to 4)
Overview
In the Parameter List, the header line of each parameter shows all the attributes and groups
for that specific parameter. The figure below shows the details for parameter P0700 and
r1515.
3>@ 6HOFWLRQRIFRPPDQGVRXUFH&RPPDQGVRXUFHVH
&86'3
&86'3)
$FFHVVOHYHO 3*URXS&RPPDQGV 'DWDW\SH8QVLJQHG
4XLFNFRPP12 $FWLY<(6 'DWDVHW&'6
&DQEHFKDQJHG7 8QLW
0LQ 0D[ )DFWRU\VHWWLQJ
&830YDULDQWV
%,&2LIH[LVW
U &2$GGLWLRQDOWRUTXHVHWSRLQW&2$GGWUTVHW
*
$FFHVVOHYHO 3*URXS&ORVHGORRSFRQWURO 'DWDW\SH)ORDWLQJ3RLQW
8QLW
Index
Using the index, a parameter (e.g. p0013[20]) is defined with several consecutive elements
(in this case, 20). Each individual index is defined using a numerical value.
When transferred to a parameter this means that an indexed parameter can have several
values. The values are addressed using the parameter number including the index value
(e.g. p0013[0], p0013[1], p0013[2], p0013[3], p0013[4], ...).
Indexed parameters are used, for example:
● Drive Data Sets (DDS)
● Command Data Sets (CDS)
● Sub functions.
BICO
The following types of connectable parameters are available. A description of BICO
technology is given in the functions chapter.
BICO Description
BI Binector Input
BO Binector Output
CI Connector Input
CO Connector Output
CO/BO Connector Output/Binector Output
Access level
The access level is controlled using parameter P0003. In this case, only those parameters
are visible at the OP, where the access level is less than or equal to the value assigned in
parameter P0003. On the other hand, for STARTER, only access levels 0 and 3 are relevant.
For example, parameters with access level 3 cannot be changed if the appropriate access
level has not been set.
The following access levels are implemented in the SINAMICS G120 inverter units:
Note
In STARTER, all of the user parameters (access stage 3) are always displayed using the
expert list – for the setting p0003 = 0, 1, 2 or 3.
When changing parameters using STARTER, or via a high-level control system, parameter
value changes always become immediately effective.
Change state
"P" parameters can only be changed depending on the inverter state. The parameter value is
not accepted if the instantaneous state is not listed in the parameter attribute "Change state".
For instance, the quick commissioning parameter P0010 with the attribute "CT" can only be
changed in quick commissioning "C" or ready "T" but not in operation "U".
State Description
C Quick commissioning
U Operation (Drive running)
T Drive ready to run
Data types
The data type of a parameter defines the maximum possible value range. Five data types
are used for SINAMICS G120. They either represent an unsigned integer value (U16, U32)
or a floating-point value (float). The value range is frequently restricted by a minimum and
maximum value (min, max) or using inverter/motor quantities.
Unit
For SINAMICS G120, the units of a particular parameter involve the physical quantity (e.g.
m, s, A). Quantities are measurable properties/characteristics of physical objects, operations,
states and are represented using characters of a formula (e.g. V = 9 V).
Unit Description
- No dimension
% Percentage
A Ampere
V Volt
Ohm Ohm
us Microseconds
ms Milliseconds
s Seconds
Hz Hertz
kHz Kilohertz
1/min Revolutions per minute [RPM]
m/s Meters per second
Nm Newton meter
W Watt
kW Kilowatt
Hp Horse power
kWh Kilowatt hours
°C Degrees Celsius
m Meter
kg Kilograms
° Degrees (angular degrees)
Grouping
The parameters are sub-divided into groups according to their functionality. This increases
the transparency and allows a quicker and more efficient search for specific parameters.
Furthermore, parameter P0004 can be used to control the specific group of parameters that
are displayed on the OP.
Active
This attribute is only of importance in conjunction with an OP. The "Yes" attribute indicates
that this value is already accepted when scrolling (when changing the value with or ).
Especially parameters which are used for optimization functions have this property (e.g.
constant voltage boost P1310 or filter time constants). On the other hand, for parameters
with the attribute "First confirm", the value is only accepted after first pressing the key
. These include, for example, parameters where the parameter value can have different
settings/meanings (e.g. selecting the frequency setpoint source P1000).
Active Description
Yes The value becomes valid by either scrolling with or
First confirm The value is only accepted by pressing
Note
Parameter values that are changed using STARTER or a higher-level control do not have to
be acknowledged.
Quick commissioning
This parameter attribute identifies as to whether the parameter is included in the quick
commissioning (QC) (P0010 = 1).
QC Description
No The parameter is not included in the quick commissioning
Yes The parameter is included in the quick commissioning
Value range
The value range, which is specified as a result of the data type, is restricted by the minimum
and maximum values (min, max) and using the inverter/motor quantities. Straightforward
commissioning is guaranteed in so much that the parameters have a default value. These
values (min, max, def) are so permanently saved in the inverter and cannot be changed by
the user.
Data sets
A detailed description for the data sets is given in the respective section
BICO Description
CDS Command data set
DDS Drive data set
To start and stop the motor Using DI0 with external switch
To reverse direction of rotation Using DI1 with external switch
To reset faults Using DI2 with external switch
To enter a frequency setpoint Using AI0 with external potentiometer;
the default setting of the AI: Voltage input
To display the actual frequency value Using AO0 as current output
The potentiometer and the external switches can be connected through the inverter internal
power supply, as shown in section "Connecting the Control Unit via terminals".
Notice
If settings have to be made which go beyond the factory settings, then depending on the
complexity of the application, when commissioning the inverter, the particular function
description as well as the parameter list including function charts must be carefully taken into
consideration.
Note
The OP sometimes displays "bUSY" when changing parameter values. This means that the
inverter is presently handling another higher-priority task.
Overview
A G120 inverter can be parameterized by downloading a parameter set from the MMC to the
inverter.
The download can be performed as
● manual download
● automatic download
● start-up download
A detailed download description can be found in the operation section.
Note
The file format for the MMC is FAT. Any other format, such as FAT32 or NTFS are not
compatible with uploading and downloading parameter sets from the inverter.
Formatting can be accomplished using the DOS command line as follows:
C:\>format volume /FS:FAT - where volume has to be replaced by the name of the MMC
drive, for example A
Please keep in mind that formatting will delete all the contents of the MMC.
STARTER projects
Using STARTER either a new project can be created or an already existing project can be
opened.
To create a new project in STARTER one of the following methods can be used:
● Search inverter
● Wizard
● Select inverter.
When opening an existing project or creating a new project STARTER is in the offline mode.
To go online the button has to be pressed.
Note
Via P0014 the store mode can be changed,
• P0014 = 0: parameter changes stored in RAM (default)
• P0014 = 1: parameter changes stored in EEPROM
Parameter sets that have been changed offline can be transferred to the inverter using the
download button.
Caution
Parameters for fail-safe functions can only be changed in the online mode.
When downloading parameters via STARTER, parameters belonging to fail-safe functions
will not be downloaded.
Commissioning overview
Before commissioning is started, the following data must must be available:
● Line supply frequency
● Motor rating plate data
● Command/setpoint sources
● Min./max. frequency or ramp-up/ramp-down time
● Control mode
An example for a rating plate is shown in the figure below. The precise definition and
explanation of this data is defined in DIN EN 60034-1.
3~Mot. 1LA70904-4AA10 H
D-91056 Erlangen E0107/471101 01 001 IEC/EN 60034
16kg IM B3 090L IP55 Th.Cl.F
50 Hz 230/400 V / 60 Hz 460 V
1.5 kW 5.9/3.4 A 1.75 kW 3.4 A
cos 0.81 1420/min cos 0.81 1720/min
220-240/380-420 V / 440-480 V
6.2-5.4/3.6-3.2 A 3.6-3.3 A
Note
Commissioning the inverter with STARTER can be performed via "Configure drive unit".
Notice
Behavior of inverter on completion of commissioning
The following behavior should be taken into account when commissioning the inverter:
• standard commissioning with P0014 = 0:
Parameters are only stored in RAM. RAM -> EEPROM can be started:
– with OP: via setting P0971 = 1
– with SATRTER in the online mode: via pressing
RAM -> EEPROM will automatically be performed when starting data transfer from
inverter to MMC (P0802 = 2).
• standard commissioning with P0014 = 1:
All parameter changes will be saved in both RAM and EEPROM.
• While commissioning the fail-safe functions - only possible with a CU240S DP-F - the
relating parameters are automatically stored in RAM and EEPROM
• Data from EEPROM can be transferred to MMC via P0802 = 2.
• Parameters can be changed independent whether an MMC is plugged in or not.
Depending on the settings in P8458 after power cycle the parameters from EEPROM or
MMC are used for start up. The customer has to take of the proper settings of P8458.
– P8458 = 0, no automatic parameter download from the MMC.
– P8458 = 1, automatic parameter download from the MMC only once (at the next start-
up of the CU (default setting)). After the download P8458 is set to 0.
– P8458 = 2, automatic parameter download from the MMC after each start-up of the
CU with plugged-in MMC.
Warning
In case of automatic parameter download from the MMC at start up, F0395 will be
generated.
By acknowledging F0395 the customer automatically agrees to carry out an confirmation test
in standard applications and an acceptance test in fail-safe applications immediately after the
fault was acknowledged.
Parameter Description (Parameter name and factory setting (if not variable) in bold) Setting
Parameter Description (Parameter name and factory setting (if not variable) in bold) Setting
Parameter Description (Parameter name and factory setting (if not variable) in bold) Setting
Parameter Description (Parameter name and factory setting (if not variable) in bold) Setting
Warning
The motor data identification routine MUST not be used for loads which are potentially
hazardous (for example, suspended loads for crane applications). Before the motor data
identification routine is started, the potentially hazardous load must be carefully secured (for
example, by lowering the load to the floor or by clamping the load using the motor holding
brake).
Parameter Description (Parameter name and factory setting (if not variable) in bold)
P0625 = ? Ambient motor temperature (entered in °C)
The motor ambient temperature is entered at the instant that motor data is being determined (factory
setting: 20 °C).
The difference between the motor temperature and the motor ambient temperature P0625 must lie in the
tolerance range of approx. ± 5 °C.
Is the motor temperature (P0625) within the tolerance described above? If not the motor must be allowed to cool down.
P0010 = 0 Commissioning parameter filter*
Check if P0010 = 0 (Ready)
P1900 = 3 Select motor data identification*
0: Disabled
2: Identification of all parameters in standstill.
3: Identification of all parameters in standstill including saturation curve
ON command Start motor data identification
Once P1900 ≠ 0, alarm A0541 (motor data identification active) is generated that states, the next ON
command will initiate the motor data identification. When the ON Command is given, current flows through
the motor and the rotor aligns itself.
Note: When motor data identification is complete A0541 will be cleared and P1900 will be set to zero.
OFF1 In order to set the inverter into a defined state, an OFF1 command must be issued before the next step.
END Motor identification is finished.
Parameter Description (Parameter name and factory setting (if not variable) in bold)
P0010 = 0 Commissioning parameter filter*
Check if P0010 = 0 (Ready)
P1960 = 1 Speed control optimisation
0: Disable
1: Enable
ON Start Speed control optimisation
command We recommend the Speed control optimisation if vector mode (P1300 = 20 or 21) is selected. Once P1960 =
1, alarm A0542 is generated, that states, the next ON command will initiate the optimisation. If there is a
problem with speed control optimisation due to instability the drive may trip with fault F0042, because no
stable value has been obtained on the ramp up within a reasonable time.
Note: When Speed control optimisation is complete A0542 will be cleared and P1960 will be cleared to zero.
6WDWRUUHV 5RWRUOHDNLQGXFW
>˖@
2QVWDWHYROWDJH *DWLQJGHDGWLPH 3' 3'
>9@ >XV@ &DEOHUHVLVWDQFH 6WDWRUOHDNLQGXFW 5RWRUUHVLVWDQFH
3 3 >˖@ >˖@
3' 3' 3'
0DLQLQGXFWDQFH
/0
&FDEOH
3'
In addition to the ECD data, the motor magnetizing characteristic (see the figure above) can
be determined using the motor data identification (P1910 = 3). If the motor combination is
operated in the field-weakening range (which is above the nominal frequency of the motor),
then this characteristic should be determined, especially when Vector control is being used.
As a result of this magnetizing characteristic, the Inverter can, in the field-weakening range,
accurately calculate the current which is generated in the field and in-turn achieve a higher
torque accuracy.
˓>@
3
3
3
3
3 3 3 3 L w>@
L >$@
Lw>@ w
U
Figure 5-8 Magnetizing characteristic
After selecting the motor data identification using parameter P1910, alarm A0541 is
immediately generated. The motor identification routine is started by the ON command and
different excitation signals are impressed in the motor (DC and AC voltages). This
measurement is carried-out with the motor at a standstill and it takes, including the data
calculation per selection (P1910 = 1 or 3), between 20 seconds and 4 minutes to complete.
The identification time depends on the motor and increases with its size (this takes approx.
4 min. for a 200 kW motor).
The motor data identification routine must be carried-out with the motor in the cold condition
so that the motor resistance values saved can be assigned to the parameter of the ambient
temperature P0625. Only then is the correct temperature adaptation of the resistances
possible during operation.
The motor data identification routine operates with the results of the "Complete
parameterization" P0340 = 1 or the motor equivalent diagram data which was last saved.
The results become increasingly better the more times that the identification routine is
executed (up to 3 times).
Warning
It is not permissible to carry-out the motor identification routine for loads which are potentially
hazardous (e.g. suspended loads for crane applications). Before starting the motor data
identification routine, the potentially hazardous load must be secured (e.g. by lowering the
load to the floor or clamping the load using the motor holding brake).
When starting the motor data identification routine, the rotor can move into a preferred
position. This is more significant for larger motors.
Note
The equivalent circuit data (P0350, P0354, P0356, P0358, P0360) and the motor cable
resistance (P0352) are entered as phase values.
During the motor identification routine, the stator resistance (P0350) and the motor cable
resistance (P0352) are determined.
If the motor cable resistance is known, it should be entered into parameter P0352 after the
motor data identification. The value of P0350 then will be changed in dependenccy of P0352
and is more precisely as the calculated value.
It is not necessary to lock the motor rotor for the motor data identification routine. However, if
it is possible to lock the motor rotor during the identification routine (i.e. by closing the motor
holding brake), then this should be used to determine the equivalent circuit diagram data.
The following formula can be applied to check the correctness of the motor rating plate data:
PN = √3 ∗ VNΥ ∗ INΥ ∗ cosϕ ∗ η ≈ √3 ∗ VNΔ ∗ INΔ ∗ cosϕ ∗ η
Where:
PN rated motor power
VN Υ, VN Δ rated motor voltage (star/delta)
IN Υ, IN Δ rated motor current (star/delta)
cosϕ power factor
η efficiency
If Problems occur during the identification run, for example, the current controller oscillates,
then the rating plate data should be re-checked and an approximately correct magnetizing
current P0320 entered. The motor data identification routine should then be re-started by
called P0340 = 1.
Step-by-step table for motor data identification see section "Quick commissioning".
Overview
Internal motor/control data is calculated using parameter P0340 or, indirectly using
parameter P3900 or P1910. The functionality of parameter P0340 can, for example, be used
if the equivalent circuit diagram data or the moment of inertia values are known. The
following settings are possible for P0340:
0 No calculation
1 Complete parameterization
2 Calculation of the equivalent circuit diagram data
3 Calculation of V/f and Vector control
4 Calculation of the controller settings
For the complete parameterization (P0340 = 1), in addition to the motor and control
parameters, parameters are also pre-assigned which refer to the motor rated data (for
example, torque limits and reference quantities for interface signals). A complete list of all of
the parameters depending on P0340 is included in the parameter manual.
When calculating the motor/control data using P0340, there are different scenarios, which
can be called-up as a function of the known data.
Note
When exiting quick commissioning with P3900 > 0, internally P0340 is set to 1 (complete
parameterization).
For the motor data identification, after the measurement has been completed, internally
P0340 is set to 3.
Parameter Description (Parameter name and factory setting (if not variable) in bold) Setting
P0340 = 1 Calculation of motor parameters
This parameter is required during commissioning in order to optimize the operating behavior of
the inverter. For the complete parameterization (P0340 = 1), in addition to the motor/control
parameters, parameters are pre-assigned which refer to the rated motor data (e.g. torque limits
and reference quantities for interface signals). A list of the parameters, which are calculated,
depending on the setting of P0340, are included in the parameter list.
0: No calculation
1: Complete parameterization
2: Calculation of equivalent circuit data
3: Calculation of V/f and Vector control data
4: Calculation of controller settings only
If additional catalog data is known enter the data in P0341, P0342 and P0344.
P0341 = ? Motor inertia [kg*m2]
P0342 = ? Total/motor inertia ratio
P0344 = ? Motor weight (entered in kg)
If the ECD data is known, enter the data in P0350, P0354, P0356, P0358, P0360.
If the ECD data is not known, then: Set P0340 = 4. To calculate the controller settings and skip to END.
P0350 = ? Stator resistance (line) (entered in Ω)
Stator resistance in Ω of the motor which is connected (line). This parameter value doesn't
include the cable resistance.
P0354 = ? Rotor resistance (entered in Ω)
Defines the rotor resistance of the motor equivalent diagram (phase value).
P0356 = ? Stator leakage inductance (entered in mH)
Defines the stator leakage inductance of the motor equivalent diagram (phase value).
P0358 = ? Rotor leakage inductance (entered in mH)
Defines the rotor leakage inductance of the motor equivalent diagram (phase value).
P0360 = ? Main inductance (entered in mH)
Defines the main (magnetizing) inductance of the motor equivalent diagram (phase value).
P0340 = 3 Calculation of motor parameters
3: Calculation of V/f and Vector control
All of the parameters, dependent on the ECD data are calculated and, in addition, the controller
settings (P0340 = 4).
END The motor parameters have been calculated and it is now possible to return to the additional
parameterization in the Section "Adaptation to the application".
Note
In the factory setting, parameter changes are stored in the volatile memory of the inverter
(RAM). To safe the changes in the EEPROM one of the following methods can be used:
• Set P0014 = 1 all changes stored immediately in the EEPROM
• start data transfer from RAM to EEPROM via P0971 = 1 (when using OP) via (with
STARTER).
The durartion of the data transfer depends on the number of changed parameters. In some
cases it can last up to 3 minutes.
With the OP data transfer is displayed with "bUSY".
When using STARTER it is displayed via a progress bar. The sucessful transfer is displayed
via a dialog box.
General settings
Parameter Description (Parameter name and factory setting (if not variable) in bold) Setting
P0003 = 3 User access level*
1: Standard: Allows access into most frequently used parameters.
2: Extended: Allows extended access e.g. to inverter I/O functions
3: Expert: For expert use only
P0210 = ? Supply voltage (enter the voltage in V)
This parameter enters the real line supply voltage to which the Inverter is connected. Only
necessary if P1254 = 0 (default: P1254 = 1).
P0290 = 2 Inverter overload reaction
This defines the response of the Inverter to an internal overtemperature.
0: Reduce output frequency
1: Trip (F0004)
2: Reduce pulse frequency and output frequency
3: Reduce pusle frequency then trip (F0004)
P0335 = 0 Motor cooling (enter the motor cooling system)
0: Self-cooled using the shaft mounted fan attached to the motor
1: Force-cooled using the separately powered cooling fan
2: Self-cooled and internal fan
3: Force-cooled and internal fan
Pulse Encoder
Parameter Description (Parameter name and factory setting (if not variable) in bold) Setting
P0400 = 0 Select encoder type *
or 0: Disabled (no encoder fitted)
P0400 = ? 2 or 12: Two quadrature encoder (two channels)
P0408 = ? Number of encoder pulses (Only if encoder is fitted)
Enter the number of encoder pulses per revolution. The number of encoder pulses per
revolution P0408 is limited by the maximum pulse frequency of the pulse encoder module
(fmax = 300 kHz)
Temperature Sensor
Parameter Description (Parameter name and factory setting (if not variable) in bold) Setting
P0601 = 0 Motor temperature sensor
or 0: No sensor (→ P0610)
P0601 = ? 1: PTC thermistor (→ P0604)
2: KTY84 (→ P0604)
P0604 = ? Threshold motor temperature
Enter the warning threshold for motor overtemperature protection. The trip temperature
(threshold) is where either the inverter is tripped or Imax is reduced (P0610) which is always
10 % above the warning threshold.
P0610 = 2 Motor I2t temperature reaction
Defines the reaction when the mtor temperature reaches the warning threshold.
0: No reaction, only a warning
1: Warning and Imax reduced (this results in a reduced output frequency)
2: Warning and trip (F0011)
Parameter Description (Parameter name and factory setting (if not variable) in bold) Setting
P0621= 1 Motor temperature identification after restart
0: No identification
1: Temperature identification only at first "motor on" after power cycle
2: Temperature identification at each motor on.
P0622 = Motor magnetizing time for temperature identification after stator restistance identification
This parameter will be initialised with a value for one calculating cycle of the motor
temperature. It depends on the identified rotor time constant. Due to accuracy reasons this
calculation may be performed several times.
Parameter Description (Parameter name and factory setting (if not variable) in bold) Setting
P0700 = 2/6 Selection of command source
This selects the digital command source
0: Factory default setting
1: OP (keypad)
2: Terminal (P0701 … P0709), factory setting for CU240S
4: USS on RS232
5: USS on RS485 (not available with CU240S DP and CU240S DP-F)
6: Fieldbus (P2050 … P02091), factory setting for CU240S DP and CU240S DP-F, not
available with CU240S)
Parameter Description (Parameter name and factory setting (if not variable) in bold) Setting
P0701 = 1 Terminal 5: factory settings for Possible values for P0701 to P0709:
Digital Input 0 (DI0) CU240S 0: Digital input disabled
P0702 = 12 Terminal 6: 1: ON/OFF1
Digital Input 1 (DI1) 2: ON reverse /OFF1
P0703 = 9 Terminal 7: 3: OFF2 - coast to standstill
Digital Input 2 (DI2) 4: OFF3 - quick ramp-down
9: Fault acknowledge
P0704 = 15 Terminal 8: 10: JOG right
Digital Input 3 (DI3) 11: JOG left
P0705 = 16 Terminal 16: 12: Reverse
Digital Input 4 (DI4) 13: MOP up (increase frequency)
P0706 = 17 Terminal 17: 14: MOP down (decrease frequency)
Digital Input 5 (DI5) 15: Fixed frequency selector bit0
16: Fixed frequency selector bit1
P0707 = 18 Terminal 40: factory settings for 17: Fixed frequency selector bit2
Digital Input 6 (DI6) CU240S 18: Fixed frequency selector bit3
P0708 = 0 Terminal 41: not availble with 25: DC brake enable
Digital Input 7 (DI7) CU240S DP-F 27: Enable PID
P0709 = 0 Terminal 42: 29: External trip
Digital Input 8 (DI8) 33: Disable additional freq setpoint
99: Enable BICO parameterization
P0724 = 3 Debounce time for digital inputs
Defines the debounce time (filtering time) used for digital inputs.
0: No debounce time
1: 2.5 ms debounce time
2: 8.2 ms debounce time
3: 12.3 ms debounce time
P9603 = 00 Terminal 62, 63: SLS via FD1A and FD1B not availble with CU240S and CU240S DP
P9603 = 01 Terminal 60, 61: SLS via FD0A and FD0B
P9603 = 02 Terminal 62, 63: SS1 via FD1A and FD1B
P9603 = 03 Terminal 60, 61: SS1 via FD0A and FD0B
P9603 = 04 Terminal 62, 63: STO via FD1A and FD1B
P9603 = 05 Terminal 60, 61: STO via FD0A and FD0B
Parameter Description (Parameter name and factory setting (if not variable) in bold) Setting
P0731 = 52:3 BI: function of digital output 0 (DO0), defines the source for digital output 0
Terminal 18: DO0, NC/Terminal 19: DO0, NO/Terminal 20: DO0, COM
52:3 Inverter fault active
P0732 = 52:7 BI: function of digital output 1,defines the source for digital output 1
Terminal 21: DO1, NO/Terminal 22: DO1, COM
52:7 Inverter warning active
P0733 = 0:0 BI: function of digital output 2, defines the source for digital output 2
Terminal 23: DO0, NC/Terminal 24: DO0, NO/Terminal 25: DO0, COM
0:0 Digital output disabled
P0748 Invert digital outputs
Bits 0, 1 and 2 can be used to invert the signals of digital outputs 0, 1 and 2
Parameter Description (Parameter name and factory setting (if not variable) in bold) Setting
P1000 = ? Selection of frequency setpoint
0: No main setpoint
1: MOP setpoint (P1031 … P1040)
2: Analog setpoint (P0756 … P0762), factory setting for CU240S
3: Fixed frequency (P1001 … P1023)
6: Fieldbus (P2050 … P02091), factory setting for CU240S DP and CU240S DP-F, not
available with CU240S)
7: Analog setpoint 2
10: Additional setpoint (1 = MOP) + Main setpoint (0 = No main setpoint)
11: Additional setpoint (1 = MOP) + Main setpoint (1 = MOP)
12: Additional setpoint (1 = MOP) + Main setpoint (2 = Analog setpoint)
…
62: Additional setpoint (6 = Fieldbus) + Main setpoint (2 = Analog setpoint)
63: Additional setpoint (6 = Fieldbus) + Main setpoint (3 = Fixed frequency)
…
Parameter Description (Parameter name and factory setting (if not variable) in bold) Setting
P1031 = 0 Setpoint memory of the MOP
The last motorized potentiomenter setpoint, which was active before the OFF command or
switching-off, can be saved.
0: MOP setpoint will not be stored
1: MOP setpoint will be stored in P1040
P1032 = 1 Inhibit reverse direction of MOP
0: reverse direction is allowed
1: Reverse direction inhibited
P1040 = 5 Setpoint of the MOP
Defines the setpoint [Hz] of the motorized potentiometer (MOP).
Parameter Description (Parameter name and factory setting (if not variable) in bold) Setting
P0756 = 0 AI type
Defines the type of the analog input and also enables analog input monitoring.
0: Unipolar voltage input (0 to +10 V)
1: Unipolar voltage input with monitoring (0 V … +10 V)
2: Unipolar current input (0 mA … 20 mA)
3: Unipolar current input with monitoring (0 mA … 20 mA)
4: Bipolar voltage input (-10 V … +10 V)
NOTE: The following applies for P0756 … P0760:
Index 0: Analog input 0 (AI0), terminals 3 and 4
Index 1: Analog input 1 (AI1), terminals 10 and 11
3!
P0757 = 0 Value x1 of AI scaling [V/mA] 33__ !3!3
P0758 = 0.0 Value y1 of AI scaling
this parameter represents the value of x1 as a
percentage of P2000 (reference frequency) $63PD[
K
$63PLQ
Parameter Description (Parameter name and factory setting (if not variable) in bold) Setting
P1016 = 1 Fixed frequency mode, defines The fixed frequency can be selected via four digital
the selection method for fixed inputs (default DI3 … DI6).
frequencies. Fixed frequences via direct selection (P1016 = 1):
1: direct selection With the default settings additional combinations as
2: binary coded follows are possible:
P1001 = 0 Fixed frequency 1, (FF1) )L[HG)UHTXHQF\ ))3DU ))
Value given in Hz. VHOHFWHGYLD >+]@
P1002 = 5 Fixed frequency 2
',3 3GHIDXOW +]
P1003 = 10 Fixed frequency 3 ',3 3GHIDXOW +]
3GHIDXOW +]
P1004 = 15 Fixed frequency 4 ',3
',3 3GHIDXOW +]
P1005 = 20 Fixed frequency 5 ',', 33
33
P1006 = 25 Fixed frequency 6 ',',
',', 33
P1007 = 30 Fixed frequency 7 ',', 33
33
P1008 = 35 Fixed frequency 8 ',',
',',', 333
P1009 = 40 Fixed frequency 9 ',',', 333
333
P1010 = 45 Fixed frequency 10 ',',',
',',',', 3333
P1011 = 50 Fixed frequency 11 Fixed frequences via binary coded selection
P1012 = 55 Fixed frequency 12 (P1016 = 2):
With binary coded selection each frequency, set in one
P1013 = 60 Fixed frequency 13
of the parameters P1002 … P1015 can be directly
P1014 = 65 Fixed frequency 14 selected.
P1015 = 65 Fixed frequency 15 Fixed Frequency FF-default
FF-
setting
P1020 = 722.3 Fixed frequency selection - Bit 0 selected via Par
[Hz]
Selects DI3 for FF selection
DI3 (P1020 =722.3) P1001 0
P1021 = 722.4 Fixed frequency selection - Bit 1 DI4 (P1021 =722.4) P1002 5
Selects DI4 for FF selection DI5 (P1022 =722.5) P1003 10
P1022 = 722.5 Fixed frequency selection - Bit 2 DI6 (P1023 =722.6) P1004 15
DI3, DI4 P1005 20
Selects DI5 for FF selection
DI4, DI5 P1006 25
P1023 = 722.6 Fixed frequency selection - Bit 3 DI5, DI6 P1007 30
Selects DI6 for FF selection DI3, DI5 P1008 35
DI4, DI6 P1009 40
DI3, DI6 P1010 45
DI3, DI4, DI5 P1011 50
DI4, DI5, DI6 P1012 55
DI3, DI5, DI6 P1013 60
DI3, DI4, DI6 P1014 65
DI3, DI4, DI5, DI6 P1015 65
Analog outputs
Parameter Description (Parameter name and factory setting (if not variable) in bold) Setting
P0771 = 21 CI: Analog output
Defines the function of the 0 mA … 20 mA analog output
21: CO: actual frequency (scaled according to P2000)
24: CO: actual output frequency (scaled according to P2000)
25: CO: actual output voltage (scaled according to P2001)
26: CO: actual DC-link voltage (scaled according to P2001)
27: CO: Output current (scaled according to P2002)
NOTE: The following applies for P0771 … P0785:
Index 0: analog output 0 (AO0), terminals 12 and 13
Index 1: analog output 1 (AO1), terminals 26 and 27
P0775 = 0 Permit absolute value
Decides if the absolute value of the analog output is used.
If enabled, this parameter will take the absolute value of the value to be outputed.
If the value was originally negative then the corresponding bit in r0785 is set.
P0776 = 0 Type of analog output
Scaling of r0774.
0: Current output
1: Voltage output
NOTE: P0776 changes over the scaling of r0774 (0 mA … 20 mA ⇔ 0 V … 10 V).
Scaling parameters P0778, P0780 and the deadband are always entered in 0 mA … 20 mA.
Analog output 0 can be switched to a voltage output with a range 0 … 10 V.
Analog output 1 is only a current output. When it is used as voltage output, it must be
terminated using a 500 Ω resistor.
P0777 = 0.0 Value x1 of the analog output scaling
Defines x1 output characteristic in percentage. This parameter represents the lowest analog
value as a percentage of P200x (depending on the setting of P0771).
P0778 = 0 Value y1 of the analog output scaling
This parameter represents the value of x1 in mA. P$
JOG frequency
Parameter Description (Parameter name and factory setting (if not variable) in bold) Setting
P1057 = 1 JOG Enable
P1057 = 0 JOG-function diabled
P1057 = 1 JOG-function enabled
P1058 = 5 JOG frequency right
Frequency in Hz when the motor is being jogged in the clockwise direction of roatation.
P1059 = 5 JOG frequency left
Frequency in Hz when the motor is being jogged in the counter-clockwise direction of rotation.
I
P1060 = 45 JOG ramp-up time
Ramp-up time in seconds from 0 to the 3
IPD[
maximum frequency (P1082). The JOG ramp-up
is limited by P1058 or P1059. 3
Additional Setpoints
Parameter Description (Parameter name and factory setting (if not variable) in bold) Setting
P1074 = 1.0 BI: disable additional setpoint
P1075 = 775 CI: additional setpoint
Defines the source of the additional setpoint which is added to the main setpoint.
Common settings:
755: Analog input setpoint
1024: Fixed frequency setpoint
1050: MOP setpoint
P1076 = 1.0 CI: additional setpoint scaling
Defines the source to scale the additional setpoint.
Common settings:
1: Scaling of 1.0 (100 %)
755: Analog input setpoint
1024: Fixed frequency setpoint
1050: MOP setpoint
Skip Frequency
Parameter Description (Parameter name and factory setting (if not variable) in bold) Setting
P1091 = 7.5 Skip frequency 1 (entered in Hz)
Avoids mechanical resonance effects and suppresses (skips) IRXW
frequencies in the range around the skip frequency ± P1101
(skip frequency bandwidth).
P1092 = 0.0 Skip frequency 2
P1093 = 0.0 Skip frequency 3
P1094 = 0.0 Skip frequency 4
P1101 = 1.0 Skip frequency bandwidth (entered in Hz)
3
6NLSIUHTXHQF\
Ramp times
Parameter Description (Parameter name and factory setting (if not variable) in bold) Setting
I
P1120 = 10 Ramp-up time
Enter the acceleration time in seconds. 3
IPD[
P1121 = 10 Ramp-down time I
Enter the deceleration time in seconds.
W
3 3
Rounding
Parameter Description (Parameter name and factory setting (if not variable) in bold) Setting
P1130 = 5.0 Ramp-up initial rounding time (in seconds) The rounding times are recommended, as
P1131 = 5.0 Ramp-up final rounding time (in seconds) abrupt responses can be avoided therefore
reducing stress and damage to the
P1132 = 5.0 Ramp-down initial rounding time (in seconds) mechanical system.
P1133 = 5.0 Ramp-down final rounding time (in seconds) The ramp-up and ramp-down times are
P1134 = 0 Rounding type extended by the component of the rounding
0: continuous smoothing (jerk-free) ramps.
1: Discontinuous smoothing
NOTE: for discontinuous rounding (P1134 = 1),
after the setpoint is reduced or an OFF1
command, the final rounding at ramp-up (P1131)
and the initial rounding at ramp-down (P1132)
are not executed.
Parameter Description (Parameter name and factory setting (if not variable) in bold) Setting
P1800 = 4 Pulse frequency (kHz)
The pulse frequency can be changed in 2 kHz steps. The range extends from 4 kHz up to
16 kHz. The complete inverter output current at 50 °C is reached with 4 kHz.
The maximum output frequency is limited by the pulse frequency. Operation up to 266 Hz is
possible with a pulse frequency of 4 kHz. If a higher output frequency is required, then the
pulse frequency should also be increased (10 kHz pulse frequency - maximum output
frequency of 650 Hz)
If low-noise operation is not required, then the inverter losses and the high-frequency
disturbances emitted by the inverter can be reduced by selecting lower pulse frequencies.
P2000 = 50 Reference frequency (Hz)
The reference frequency in Hertz corresponds to a value of 100 %.
This setting should be changed if a maximum frequency of higher than 50 Hz is required.
NOTE: This scaling acts on the maximum frequency of the analog setpoints, fixed frequencies
and motorized potentiometer normalization operations are referred to 100 %.
P2001 = 1000 Reference voltage (V)
The reference voltage in Volts (output voltage) corresponds to a value of 100 %.
NOTE: This setting should only be changed if it is necessary to output the voltage with another
scaling.
P2002 = ? Reference current (A)
The reference current in Apmeres (output current) corresponds to a value of 100 %. Factory
setting is 200 % of the rated motor current (P0305).
NOTE: This setting should only changed if it is necessary to output the current with another
scaling.
P2003 = ? Reference torque (Nm)
The reference torque in Newton-metres corresponds to a value of 100 %. Factory setting is
200 % of the rated motor torque, determined from the motor data, for a constant motor torque.
NOTE: This setting should only changed if it is necessary to output the torque with another
scaling.
P2004 = ? Reference power (kW or hp)
The reference power in kW or hp corresponds to a value of 100 %. Factory setting is 200 % of
ther rated motor power at constant motor torque.
This setting should only be changed if it is necessary to output the power with another scaling.
bUSY Once the save command is given, "bUSY" will be displayed
END When the save is completed, the display will return to normal and parameterization is complete.
Parameter Description (Parameter name and factory setting (if not variable) in bold) Setting
P0971 = 1 Transfer data from RAM to EEPROM
0: Disabled
1: Start data transfer, RAM → EEPROM
All of the parameter changes are transferred from the RAM into the EEPROM which means
that they are saved in a non-volatile state within the Inverter (data is not lost when the power
fails).
While the transfer is active, "bUSY" will be displayed on the OP. Once the transfer is
completed P0970 will be set internally to "0" and the "P0970" will be displayed.
Note: Data transfer RAM → EEPROM is not necesarry when the commissioning is performed
via the OP, because all parameter settings are stored in EEPROM immediately when changed
by the OP.
Overview
Series commissioning means the possibility to transfer the parameter set from one inverter
into a number of other inverters which allows fast commissioning for identical applications
(for example series machines or group inverters).
The series commissioning is divided into the following steps:
● create a valid parameter set
● upload this parameter set
● download of the uploaded parameter set into the new inverter
To perform series commissioning an appropriate parameter set must be available. This
parameter set can be created by parameterizing an Inverter via OP or STARTER.
Caution
Parameter download between different types of control units and of different firmware
versions is not recommended.
It is possible to download parameter sets from different CU types, however, as the
parameter sets might differ, the user is fully responsible for the consistency of the
downloaded parameter set.
Therefore, the customer has to confirm his responsibility in case of an automatic download
by acknowledging F0395.
During download of a parameter set from an MMC to the EEPROM of the Control Unit
CU240S (e.g. during serial commissioning) you have to note that the LEDs are flashing
correctly. If the Control Unit CU240S is in a fault state, the LEDs indicate this fault state with
higher priority than the download. It is not sure that the parameter set is downloaded
correctly.
Once an inverter with an appropriate parameter set is available, the parameter set can be
uploaded and in the next step downloaded into the new inverter via OP, STARTER or MMC.
The various interfaces are shown in the figure below.
3&
FRQQHFWLRQ 2SWLRQ3RUW
NLW
866RQ56
56!56FRQYHUWHU 'W\SHFRQQHFWRU
ထ866RQ56
ထ352),%86
Figure 5-9 Series commissioning interfaces
Warning
For series commissioning, all of the communication interfaces as well as also the digital and
analog interfaces are re-initialized. This results in a brief communications failure or causes
the digital outputs to switch.
Potentially hazardous loads must be carefully secured before starting a series
commissioning.
Potentially hazardous loads can be secured as follows before starting series commissioning:
• Lower the load to the floor, or
• Clamp the load using the motor holding brake.
Note
Upload
Before the upload starts, the parameters will be copied from RAM to EEPROM
Manual and automatic download
With a manual download all necessary parameters excluding the fail-safe parameters (only
with CUs with fail-safe functions) are downloaded into the inverter. A manual download can
be triggered by the customer as described in the following.
With an automatic download even the fail-safe parameters are downloaded into the inverter.
An automatic download can only be performed with an MMC.
An automatic download can be performed at Start-up or by swapping an inverter component
(CU or PM), details are described in the following sections and in the chapter "Operation" of
this manual.
Note
Restrictions to be considered when performing upload and download:
• Only the parameter set stored in the EEPROM of the inverter is uploaded.
• Fail-safe parameters cannot be uploaded via OP or STARTER.
• Once the upload or download procedure has started, it should not be interrupted.
• Parameter download from a standard CUs to a CUs with fail-safe functions and vice
versa is not possible.
• During the up or download all LEDs are flashing (the "BF" LED is not relevant). After
finishing that process successfully the "RDY" LED is on.
• During the upload process any data already held by the OP is overwritten.
• If the download fails, the inverter will not function correctly and the "SF" LED (red) is on.
– Possible fault messages in case of download failure with OP
F0055, F0056, F0057 or F0058
– Possible fault messages in case of download failure with MMC
F061, F0062 or F0063
Notice
After upload and download of parameters between differing Control Units, the parameter
settings must be checked.
Parameter download from a different CU might fail with F0063 if parameters cannot be
downloaded (Check P949 for the (first) parameter number which cannot be downloaded).
If F0061 or F0063 occurs during startup it cannot be cleard except via a power cycle.
Parameter Description (Parameter name and factory setting (if not variable) in bold) Setting
Fit the OP to the Inverter - for the parameter set to be uploaded, perform the following steps:
P0003 = 3 User access level*
1: Standard: Allows access into most frequently used parameters
2: Extended: Allows extended access e.g. to inverter I/O functions
3: Expert: For expert use only
P0010 = 30 Commissioning parameter*
0: Ready
1: Quick commissioning
2: Inverter
30: Factory setting, parameter transfer
95: Safety commissioning (for CUs with fail-safe functions only)
P0802 = 1 Transfer data from EEPROM
0: Disabled
1: Start OP transfer
2: Start MMC Transfer
While the upload is active "bUSY" will be displayed on the OP and the inverter will not react to
any commands.
If the upload has been completed successfully, P0010 and P0802 will be set to 0 and the OP
display will return to normal.
If the upload has failed, F00055 (failure while saving parameter on OP) or F00057 (OP fault)
will be displayed.
In this case attempt another upload.
After a successful upload disconnect the OP from the upload inverter.
Parameter Description (Parameter name and factory setting (if not variable) in bold) Setting
Fit the OP to the inverter and perform the download according the flow chart.
P0003 = 3 User access level*
1: Standard: Allows access to the most frequently used parameters
2: Extended: Allows extended access e.g. to inverter I/O functions
3: Expert: For expert use only
P0010 = 30 Commissioning parameter*
0: Ready
1: Quick commissioning
2: Inverter
30: Factory setting, parameter transfer
95: Safety commissioning (for CUs with fail-safe functions only)
P0803 = 1 Transfer data to EEPROM
0: Disabled
1: Start OP transfer
2: Start MMC Transfer
While the download is active "bUSY" will be displayed on the OP and the inverter will not
react to any commands.
If the download has been completed successfully, P0010 and P0803 will be set to 0 and the
OP display will return to normal.
If the download has failed, F00055 (failure while saving parameter to EEPROM), F00057 (OP
fault) or F00058 (OP contents incompatible) will be displayed.
In this case attempt another download or perform a factory reset to allow the inverter to return
to a known state.
After a successful download the OP can be removed and connected to another inverter for
download. Then perform the download steps again until the series commissioning has been
completed for all inverters.
Note
Upload with STARTER to MMC
If you want to upload a parameter set with STARTER to an MMC, P0010, P0802 must be set
via the expert list.
Note
If you want to perform an manual download of a parameter set with STARTER from an
MMC, P0010, P0803 and P0804 must be set via the expert list.
6,1$0,&6
6,1$0,&6
Warning
When inserting an MMC during operation Alarm A0564 appears if P8458 is set to 0. This is a
hint that with P8456 = 0 no automatic download will be performed at startup.
If the MMC is inserted to perform an upload this alarm can be quitted without any further
action.
If the MMC is inserted to perform an automatic download P8456 must be set accordingly.
6,1$0,&6
6,1$0,&6
Note
During a parameter download from a MMC to the EEPROM of the Control Unit (e.g.
during serial commissioning) normally the LEDs are flashing.
If the Control Unit is in a faulty state, the fault will be displayed by the LEDs (SF on, RDY
off), although the download is performed.
If the parameter download has been performed successfully F0395 appears.
Note
Before uploading, the parameters will be copied from RAM to EEPROM
Parameter Description (Parameter name and factory setting (if not variable) in bold) Setting
Insert the MMC to the inverter - for the parameter set to be uploaded, perform the following
steps:
P0010 = 30 Commissioning parameter*
0: Ready
1: Quick commissioning
2: Inverter
30: Factory setting, parameter transfer
95: Safety commissioning (for CUs with fail-safe functions only)
P0804 = ? Select Clone file
0: clone00.bin
…
99: clone99.bin
Note: Via P0804 the name of the clone file can be selected. Theoretically up to 100 (0 … 99)
parameter sets can be stored on an MMC.
P0802 = 2 Transfer data from EEPROM
0: Disabled
1: Start OP Transfer
2: Start MMC Transfer
If the upload has been completed successfully, P0010 and P0802 will be set to 0 and the
"RDY" LED is on.
If the upload has failed, F0061 (MMC-PS not fitted) will be displayed, LED "SF" (red) is on.
In this case insert an MMC and attempt another upload.
After a successful upload remove the MMC from the upload inverter.
Note
The following important restrictions should be considered when using the download
procedure:
• During the download the inverter will not react to any commands.
• Once the download procedure has started, it cannot be interrupted.
• After upload and download of parameters between differing Control Units, parameter
settings must be checked.
• Parameter download from a different CU might fail with F0063 if parameters cannot be
downloaded (Check P949 for the (first) parameter number which cannot be downloaded).
• If the download fails, the inverter reverts to the previous parameters from the EEPROM.
Prerequisites
● Supply voltage is active for the download inverter
● The download inverter is in "Ready State".
Parameter Description (Parameter name and factory setting (if not variable) in bold) Setting
Insert the MMC to the download inverter and perform the manual download according the flow
chart.
P0010 = 30 Commissioning parameter*
0: Ready
1: Quick commissioning
2: Inverter
30: Factory setting, parameter transfer
95: Safety commissioning (for CUs with fail-safe functions only)
P0804 = ? Select Clone file (for download)
0: clone00.bin
…
99: clone99.bin
P0803 = 2 Transfer data to EEPROM
0: Disabled
1: Start OP Transfer
2: Start MMC Transfer
If the download has been completed successfully, P0010 and P0803 will be set to 0 and the
"RDY" LED is on.
If the upload has failed, F0061 (MMC-PS not fitted) or F0062 (MMC-PS contents invalid) resp.
F0063 (MMC-PS contents incompatible) will be displayed, LED "SF" (red) is on.
In this case insert a proper MMC and attempt another download or perform a factory reset.
After a successful manually download remove the MMC from inverter and insert it to the next
download inverter. Then perform the download steps again until the series commissioning has
been completed for all inverters.
Automatic Download
The automatic download at start-up is controlled via P8458. With the automatic download all
necessary parameters including the parameters regarding fail-safe functions are downloaded
into the inverter.
Note
MMC for "automatic download"
For an automatic download always the file clone00.bin will be used.
The user has to take care, that clone00.bin (saved as "clone00.bin" with STARTER on PC or
via setting P0804 = 00 with the OP) is available on the MMC, used for an automatic
parameter download at start-up. Otherwise automatic download will not be processed.
Power ON
QR yes go to
swap?
Swap behavior
QR yes
MMC plugged?
QR P8458 = 1? yes
(Clone Control)
P7844 = 1? yes
P8458 = 0
(acceptance test/
(Clone Control)
confirmation)
QR
QR
Power Stack type
compliant?
F0395
wait for
MMC fault
Ready acceptance test /
F0061/F0063
confirmation
The possible settings for P8458 and their functions are given below.
Warning
The user is responsible for ensuring that the parameters held in the CU are the correct
parameters for their application.
Acceptance test
On CUs with integrated fail-safe functions it is necessary to do an acceptance test (refer to
the "Fail-safe functions" section in this manual). To clear F0395 on CUs with integrated fail-
safe functions the following procedure has to be followed:
● P0010 = 30
● P9761 = fail-safe password
● P7844 = 0
● Carry out acceptance test
Overview
With a factory setting a defined initial state of all of the inverter parameters can be realized.
You can re-establish the initial state by carrying-out a factory via p0970. The factory setting
values are designated as "Factory setting" in the parameter list.
After a factory reset, the inverters have the following basic settings:
CUs with RS485 interface (no PROFIBUS interface)
● Control using the digital inputs
– ON/OFF using DI0
– Direction of rotation reversal using DI1
– Fault acknowledgement using DI2.
● Setpoint input using analog input 0
● Signal output using the digital outputs
– Fault active using DO0
– Warning active using DO1.
● Actual frequency using the analog output
● The basic V/f characteristic is the control mode (P1300 = 0)
● Asynchronous motor (P0300 = 1).
CUs with PROFIBUS interface
● For the PROFIBUS variants the command source and setpoint source will be set to
PROFIBUS communication.
● The basic V/f characteristic is the control mode (P1300 = 0)
● Asynchronous motor (P0300 = 1).
Note
When resetting the parameters to the factory setting, the communications memory is re-
initialized. This means that communications are interrupted for the time it takes to perform
the reset.
Warning
Fail-safe parameters
When using Standard CUs, only the factory reset with P0970 = 1 must be taken into
account.
When using CUs with fail-safe functions two reset methods are available:
• P0970 = 1 resets only non fail-safe function relating parameters (application
parameters).
If a factory reset with P0970 =1 is performed on a Control Unit with fail-safe functions
all application parameters will be reset, previous parameters settings regarding fail-
safe functions remain unchanged. This means, no acceptance test has to be
performed.
• P0970 = 10 (password protected) resets only fail-safe function relating parameters
If parameters regarding fail-safe functions must be changed, an acceptance test has
to be performed.
Parameter or action Description (Parameter name and factory setting (if not variable) in bold)
P0003 = 1 User access level*
1: Standard: Allows access into most frequently used parameters.
P0004 = 0 Parameter filter
0: All parameters
P0010 = 30 Commissioning parameter*
30: Factory setting, parameter transfer
P0970 = 1 Factory reset*
1: Parameter reset to the default values
BUSY (on OP) The inverter carries-out a parameter reset (duration, approx. 10 s) and then automatically
Progress bar (STARTER) exits the reset menu and sets
P0970 = 0: Disabled
P0010 = 0: Ready
Note
The following parameters will not be changed with a factory reset:
• P0014 Store mode
• P0100 Europe / North America
• P0201 power stack code number
• Communication parameters (USS and PROFIBUS settings)
• Data depending on actual Power module
Warning
PROFIsafe address
The PROFIsafe address is per default identical to the PROFIBUS address. Due to safety
reasons it must be changed to a different value.
It must especially differ from the address determined by the DIP switches (see following
tables).
The PROFIsafe address needs to be changed as well in P9810 of the inverter as in the
higher level control system (in case of SIMATIC S7 in HW config), otherwise F1640 will
occur.
Note
Via terminal you can use up to two of the three fail-safe functions (STO, SS1 and SLS) while
via PROFIsafe all three functions are available.
Warning
In particular, it must be observed that the PROFIsafe address is not determined by the DIP
switches (Case 4). In this case a possible hardware fault of the DIP switches will cause a
change of the PROFIsafe address.
Notice
Behavior of inverter on completion of commissioning
The following behavior should be noted when commissioning the inverter:
• After commissioning the fail-safe functions the fail-safe parameters are automatically
stored in the RAM and EEPROM.
• If an MMC is plugged into the CU, this is not affected by normal commissioning or
commissioning the fail-safe functions.
• To save the EEPROM content on a MMC, a transfer EEPROM to MMC via P0802 = 2
must be performed.
• After commissioning the fail-safe functions, an acceptance test must be carried out.
5.8.3 Checksums
Checksums
All parameters for fail-safe functions are verified by the use of checksums. These checksums
ensure the integrity of the data held within the drive processors memory.
There are four checksum, two for each of the processors, these are:
● r9798 – actual checksum for P1.
● P9799 – reference checksum for P1.
● r9898 – actual checksum for P2.
● P9899 – reference checksum for P2.
Change password
Safely-limited Speed
Parameter Description (Parameter name and factory setting (if not variable) in bold)
P0003 = 3 User access level*
1: Standard: Allows access into most frequently used parameters.
2: Extended: Allows extended access e.g. to inverter I/O functions
3: Expert: For expert use only
P0004 = 0 Parameter filter*
0: All parameters
P0010 = 30 Commissioning parameter*
0: Ready
30: Factory setting, parameter transfer
P9761 SI input password
Enter the safety password
P0970 = 10 Factory reset*
0: Disabled
1: Parameter reset
10: Safety reset
BUSY (on OP) The inverter carries-out a reset of the fail-safe related parameters (duration, approx. 10 s)
and then automatically exists the reset menu and sets
P0010 = 0: Ready
P0970 = 0: Disabled
Description
In order to verify the parameters for the fail-safe functions, an acceptance test must be
carried-out after commissioning, reset and also when changing a completely backed-up data
set of the parameters for the fail-safe functions (e.g. by MMC). This acceptance test must be
appropriately logged and documented. An example for an appropriate acceptance log is
included in the Appendix. The acceptance logs should be adequately archived.
Acceptance test
The machinery construction company (OEM) must carry-out an acceptance test for the fail-
safe functions that have been activated at the machine.
Note
The information/instructions and descriptive information regarding commissioning in Section
"Commissioning the fail-safe applications" of this Manual must be carefully observed.
If parameters for the fail-safe functions are changed, then a new acceptance test must be
carried-out and included as acceptance log.
The template for the acceptance log is provided in printed form as example or
recommendation in this Operating Instructions.
Note
A form for an acceptance log is attached in the appendix of the operating instructions.
Description
Prior to using the PROFIBUS DP interface, the address of the node (inverter) must be set.
Caution
The inverter power supply must be switched off before the DIP-switch settings are
changed. DIP-switch setting changes do not take effect until the Control Unit has been
powered-up again. The restart must be initiated by switching the power off and then on
again, irrespective of whether the interface is supplied from the inverter mains supply or
its own, separate 24 V connection.
352),%86$GGUHVV',36ZLWFKHV
21
%LW
%LW
%LW
%LW
%LW
%LW
%LW
352),%86'3
VWDWXV/('
352),%86'3
,QWHUIDFH
The PROFIBUS DP address can be set between 1 and 125, as shown in the table below.
DIP switch 1 2 3 4 5 6 7
Add to address 1 2 4 8 16 32 64
Example 1: Address = 3 = 1 + 2
Example 2: Address = 88 = 8 + 16 + 64
PROFIBUS DP parameters
The following parameters must be set to start-up the PROFIBUS DP interface:
Parameter Content
P0918 PROFIBUS address
P0700 Fast selection command source
P0922 Selects the PROFIBUS telegram standard
P1000 Fast selection frequency setpoint
P2038 Selects the communications profile
P2042 Selects if native ident number or NAMUR ident number is send to the PLC
r2050 Process data setpoint source (BICO)
P2051 Process data actual values (BICO)
P2041 Communication board functions
P2040 Process data telegram failure time
P0927 Modification source for parameters
r2054 Communication board diagnostics
Note
r2050 also acts as a display parameter through which the setpoints received by the
PROFIBUS DP interface can be checked.
Caution
The watchdog function should not be deactivated! If the monitoring function is deactivated
and the PROFIBUS DP interface fails, the inverter will not recognize a fault condition and
continue to operate even if a fault condition exists.
Caution
Shutdown on faults can only take place if both monitoring functions are activated!
When the PROFIBUS DP interface is in operation, parameter P2040 should also be set to a
value of > 0. The process data monitoring function is thus activated/deactivated solely using
the PROFIBUS watchdog function. The monitoring time then corresponds to the watchdog
time setting plus the time set in P2040.
Note
Process data whose complete control word (PZD1) is set to zero are not transferred from the
PROFIBUS DP interface to the inverter.
Result: Alarm A0703 and possibly fault F0070.
Telegrams
The selection of a telegram via P0922 determines on the drive unit side which process data
is transferred between master and slave.
From the perspective of the slave, the received process data comprises the receive words
and the process data to be sent the send words.
The receive and send words comprise the following elements:
● Receive words: Control words or setpoints
● Send words: Status words or actual values
BICO connection
When a telegram is selected, the corresponding BICO connection parameters will be fixed
and cannot be changed (except P0701 and the following digital inputs). If P0922 = 999, it
keeps the actual BICO connection parameters but now BICO parameters can be changed.
!,QRUGHUWRFRPSO\ZLWKWKH352),GULYHSURILOH3='PXVWEHXVHGDV67:RU=6:
!6WXFWXUHOLNHDVWDQGDUGWHOHJUDP
!3ODFHKROGHUIRU3&6SURFHVVGDWD
67:UU &RQWUROZRUG 0,67U 7RUTXHDFWXDOYDOXH
=6:UU 6WDWXVZRUG 3,67U $FWLYH3RZHU
162//B$
3 6SHHGVHWSRLQW$ELW 0B/,03 7RUTXHOLPLW
1,67B$
U 6SHHGDFWXDOYDOXH$ELW )$8/7B&2'(U )DXOWFRGH
,$B,67U 2XWSXWFXUUHQW :$51B&2'(U :DUQFRGH
162//B$1,67B$DUH)62//DQG),67IRU6,1$0,&6*
Description
67: 162//B$
6SHHGFRQWURO
9,.1$085 1,67B$ ,$,67B 0,67B 3,67B
=6: !
B*/$77 */$77 */$77 */$77
If VIK/NAMUR telegram is selected with P0922 = 20, the parameter P2038 "Selection of
actual profile" will be set to VIK/NAMUR automatically.
It is also necessary to set the ident number (GSD) via parameter P2042:
● SIMATIC Object Manager (Slave-OM)
For drives configured with SIMATIC Object Manager (Slave-OM) parameter P2042 has to
be set to 0 (default).
● VIK/NAMUR GSD (Device Data File)
For all other configurations the setting of parameter P2042 must be changed to 1
(NAMUR). That means that the VIK/NAMUR ID of the PROFIBUS Nutzerorganisation
(PNO) will be send to the PLC.
Note
If changing PROFIBUS standard telegrams to VIK/NAMUR telegram or back
(parameters: P0922, P2038 and P2042) the drive ID is changed. A power cycle is
necessary for the Control Unit CU240S to take the changed drive ID effective.
To change back from VIK/NAMUR to Standard telegrams it is necessary to set
P0922 = 999 (Free BICO connection) and then reset P2038 and P2042 to PROFIdrive
Profile. If P0922 = 999, it keeps the actual BICO connection parameters but now BICO
parameters can be changed.
Description
The fail-safe functions can be triggered via the fail-safe digital inputs FDI0 and FDI1 or via
PROFIsafe signals (see P9603 and 9803).
To use PROFIsafe for triggering the fail-safe functions the G120 GSD file must be installed
in the control system e.g. SIMATIC S7.
Input and output address, 6 byte each (input and otuput address are identical)
Address Function
1 E 0.0 STO bit from inverter
2 E 0.1 SS1 bit from inverter
…
Address Function
9 E 1.0 SLS bit from inverter
Address Function
1 A 0.0 STO bit to inverter
2 A 0.1 SS1 bit to inverter
…
9 A 1.0 SLS to from inverter
Overview
Description
The control and status words comply with the specifications for PROFIdrive Profile, version
4.0 for "Closed-loop speed control mode".
An example
In the remote control operating mode the commands and target values come from a superior
control system to the inverter by means of a PROFIBUS. By switching to local operation, the
command and target value source is switched and operation is now performed locally on the
system by means of digital inputs and the analog target values.
Local operation = Command data set 0: In this case the command code of the terminal strip
P0700 Index 0 = 2 and the frequency target value is the analog target value P1000
Index 0 = 2.
Remote operation = Command data set 1: In this case the command code corresponds with
the control word (word 0) received from the PROFIBUS P0700 Index 1 = 6 and the
frequency target value corresponds with the control word 1 received from the PROFIBUS
P1000 Index 0 = 6.
Table 5-33 Bit assignments status word 1 (for all PROFIdrive and VIK/NAMUR telegrams)
Word
Byte Byte
Request header Request Reference Request ID
Drive object ID No. of Parameters
1st Parameter Address Attribute No. of elements
Parameter Number (PNU)
Subindex
…
nth Parameter Address Attribute No. of elements
Parameter Number (PNU)
Subindex
1stParameter Value(s) Format No. of Values
(only for request Values
"Change parameter")
…
…
nth Parameter Value(s) Format No. of Values
Values
…
Word
Byte Byte
Response header Request Reference mirrored Response ID
Drive object ID mirrored No. of Parameters
1st Parameter Value(s) Format No. of Values
(only after request "Request") Values or Error Values
…
…
nth Parameter Value(s) Format No. of Values
Values or Error Values
…
Note
Drive ES SIMATIC provides function blocks for parameter write/read tasks within standard
block libraries and some examples.
Install the *.GS* file in the desired language (english, french, german, italian or spanish) from
the folder where you have stored these data.
The following figure shows how to integrate an inverter with integrated fail-safe functions and
a SIEMENS standard telegramm in a SIMATIC S7.
The inverter gives the possibility to work with different kind of telegrams. The selection of the
telegram is made by the parameter P0922 during drive commissioning. The received
telegram is in r2050[8] and transmit telegram is decided by parameter P2051[8].
Note
Take care that the PROFIsafe Module is installed in slot 1. In the following slot a SIEMENS
telegram or a standard telegram can be installed.
Figure 5-17 G120 inverter with fail-safe functions and a standard protocol in HW config of SIMATIC
S7
PROFIsafe Parameters
The PROFIsafe parameters are shown in the following dialog box (to be opened eg. via left
mouse double click on PROFIsafe module).
Only the parameters
● F_Dest_Add: PROFIsafe address
● F_WD_Time: control time for the fail-safe functions
can be changed.
Caution
F_Dest_Add
The PROFIsafe address is per default identical to the PROFIBUS address. Due to safety
reasons it must be changed to a different value. It needs also to be changed in P9810 of the
inverter.
F_WD_Time
In conjunction with the sync/freeze function, the watchdog-time should be increased.
Requirements
● The PROFIBUS master has been commissioned and is fully operational.
● PROFIBUS communication between master and slave is operational.
● The master can read and write data sets in conformance with PROFIBUS DPV1.
Task description
Following the occurrence of at least one fault (ZSW1.3 = 1) the first 8 active fault codes must
be read from the fault buffer r0947[0] … r0947[7]. The accompanied faults values of the fault
code are important for the user. These must be read from parameter r0949 [0] ...r0949[7].
The request is to be handled using a request and response data block.
Procedure
1. Create a request data block e.g. DB1 to read the parameters
Figure 5-19 Request data block e.g. DB1 to read the parameters
Figure 5-20 Response data block e.g. DB2 for the response
1. For the acyclic communication in OB1 a read/write request must be send to the drive with
RD_REC (SFC 59) and WR_REC (SFC 58)
Figure 5-21 Acyclic communication for request and response data block in OB1
Requirements
● The PROFIBUS master has been commissioned and is fully operational.
● PROFIBUS communication between master and slave is operational.
● The master can read and write data sets in conformance with PROFIBUS DPV1.
Procedure
1. Create a request data block e.g. DB1 to write the parameter
Figure 5-22 Request data block e.g. DB1 to write the parameter
Description
Warning
Before installing and commissioning, please read these safety instructions and warning
carefully and all the warning labels attached to the equipment. Make sure that the warning
labels are kept in a legible condition and replace missing or damaged labels.
This equipment contains dangerous voltages and controls potentially dangerous rotating
mechanical parts.
Non-Compliance with Warnings or failure to follow the instructions contained in this manual
can result in loss of life, severe personal injury or serious damage to property.
Only suitably qualified personnel should work on this equipment, and only after becoming
familiar with all safety notices and maintenance procedures contained in this manual.
The successful and safe operation of this equipment is dependent upon its proper handling,
storage, installation, operation and maintenance.
National safety regulations are also applicable.
The actions required to commission the encoder depend upon the type (HTL or TTL) that is
connected to the encoder interface. The following table gives an overview about the single
steps depending on the type of encoder.
Note
The cable from the encoder to the Encoder Module should be one complete length.
TTL-encoder specific
If the encoder type is a TTL differential and a long cable length is required (>50 m), DIP
switches 5, 6, and 7 may be set to ON.
If the encoder type is a TTL single-ended encoder, there will be a three wires for the ‘A’, 'B'
and 'Z' Channels.
HTL-encoder specific
The terminating impedance which is selected using the DIP-switches must not be used in
conjunction with an HTL encoder.
The encoder voltage is using the general I/O DIP switches 3 and 4.
The following table shows the possible settings:
On
9(QFRGHU
9(QFRGHU
9(QFRGHU
9(QFRGHU
9(QFRGHU
9(QFRGHU
9(QFRGHU
9(QFRGHU
VXSSO\
VXSSO\
VXSSO\
VXSSO\
VXSSO\
VXSSO\
VXSSO\
VXSSO\
OFF
3 4 3 4 3 4 3 4
Encoder supply 0V 24 V 5V 24 V
voltage
Encoder type No encoder HTL encoder TTL encoder HTL encoder
Warning
DIP switches 3 and 4 in ON position provide a supply voltage of 24 V to the encoder.
Therefore it is not allowed to connect a TTL encoder to the inverter if both DIP switches, 3
and 4 are in ON position.
Encoder parameterization
To enable the Encoder to function correctly with the inverter, the parameters in the table
below, must be modified.
Parameter Name
Comment
P0400[3] Encoder type
• 0: No encoder
• 2 or12: Quadrature encoder (channel A + B) –
the term "quadrature" means two periodic functions separated by a quarter cycle or 90 degrees
P0405 Encoder pulse types
Enables selection of various pulse types. Only bits 04 and 05 are used for the SINAMICS G120. See
parameter list.
P0408[3] Pulses per revolution
Specifies the number of encoder pulses per revolution. The manufacturer of the speed encoder
specifies this value. 360, 500 or 1024 are values that are generally used.
The encoder resolution (pulses per revolution p0408) which may be entered will be limited by the max.
pulse frequency of the encoder circuits (f_max = 300 kHz). The following equation calculates the
encoder frequency depending on the encoder resolution and the rotational speed (rpm). The encoder
frequency has to be less than the max. pulse frequency:
3[8PLQ
IPD[!I
P0410 Reverses internal direction sense
Setting P0410 =1 can be used to reverse the encoder signals instead of changing ENC_A and ENC_B
wiring.
0: Encoder Normal Rotation
1: Encoder Reverse Rotation
P0491[3] Reaction on speed signal loss
Selects reaction on loss of speed signal. Settings:
0: Trip with OFF2
1: Alarm and change to SLVC
Parameter Name
Comment
P0492[3] Allowed speed difference
This parameter defines the frequency threshold for the loss of the encoder signal (fault F0090). The
threshold is used both for low as well as also high frequencies.
1. Signal loss at high frequencies:
Fault F0090 is output if the actual frequency and the frequency difference between two sampling
periods (t_A) is greater than that specified in parameter p0492:
(actual frequency f_act > p0492 and f(t_A2) - f(t_A1) > p0492)
Note
A fixed delay time of 40 ms is stored in the frequency converter. Fault F0090 is only activated when
the encoder signal is lost at a high frequency after this delay time has expired.
2. Signal loss at low frequencies:
Fault F0090 is output if all of the conditions for case 1 or case 2 are simultaneously fulfilled:
Case 1
– actual frequency < p0492
– r0061 = 0 and the torque is limited
– r0061 = 0 with setpoint frequency f_set > 0 for a time > p0494
Case 2
- actual frequency < p0492
- f(t_A2) < p0492 and a fault is detected in channel B
Inter-dependency
This parameter is updated after the motor starting time p0345 has been changed or the speed was
optimized (p1960 = 1).
Caution
p0492 = 0 (no monitoring function):
With p0492 = 0, the loss of the encoder signal at high frequency as well as at a low frequency is de-
activated. As a result, the system does not monitor for the loss of the encoder signal.
If the encoder signal loss is de-activated and the fault occurs, then the closed-loop motor control can
become unstable
P0493[3] Speed difference
Allowed difference between encoder and observer.
P0494[3] Delay speed loss reaction
Used for low speed encoder loss detection.
If the motor shaft speed is less than the value in P0492 then encoder loss is detected using a low
speed encoder loss detection algorithm. This parameter selects the delay between loss of encoder at
low speed and reaction to the encoder loss. (Default = Calculated from inertia, Range from 0 to
64.000s).
Dependency: This parameter is updated when P0345 Motor start-up time is changed or when a speed-
loop optimization is performed (P1960 = 1).
Caution: When this delay is set to 0, then low speed encoder loss detection is disabled and low speed
encoder loss cannot be detected (high speed encoder loss detection will still operate if P0492 > 0). If
low speed encoder loss detection is disabled and encoder should be lost at low speed, then operation
of motor may become unstable.
P1300 Control Mode
21: Closed loop speed control
23: Closed loop torque control
Parameter Name
Comment
r0061 CO: Rotor speed
Indicates the speed of the rotor. Used to check that the system is working correctly.
r0090 CO: Act. rotor angle
Indicates the current angle of the rotor. This function is not available on single input channel encoders.
r0403 CO/BO: Encoder status word
Displays status word of speed encoder in bit format:
Bit 00 - Encoder active 0 = No 1 = Yes
Bit 01 - Encoder fault 0 = No 1 = Yes
Bit 02 - Signal OK 0 = No 1 = Yes
Bit 03 - Encoder low speed loss 0 = No 1 = Yes
Bit 04 - Single edge measurement 0 = No 1 = Yes
Caution
When commissioning the closed-loop Vector control with sensor (VC) the frequency inverter
should first be operated with V/f control (p1300 = 0). When the motor is spinning and the
speed encoder connected (activated using p0400), parameters r0061 and r0021 must match
one another as far as the following quantities are concerned:
• Sign
• Absolute value (a deviation of a few percent is permitted)
The closed-loop Vector control with sensor (encoder) (p1300 = 21 or 23) may only be
activated if both conditions are fulfilled.
Ramp times (P1120 and 1121 can cause F90, encoder feedback loss).
Note
If the encoder is incorrectly connected, incorrect values will be displayed in r0061, r0063,
r0021 and r0022
Description
The Encoder Interface has only one fault code, – F0090. This condition occurs when the
allowed frequency rate of change, set in P0492[3] is exceeded or when low speed encoder
loss is detected.
Note
The reason for the encoder loss will be given in the level 3 parameter P0949:
P0949 = 1 means encoder loss of channel A or channel B or channel A and channel B at
high speed (shaft speed > P0492)
P0949 = 2 means encoder loss of channel A or channel A and channel B at low speed
(shaft < P0492)
P0949 = 7 means excessive flux variance which may cause motor instability - possible due
to encoder loss.
Overview
The operation and start-up behavior depends on the settings during commissioning of the
inverter.
As specific operation features the "Normal start-up behavior" and "Swap behavior" as well as
"up and download of parameter sets" are described in this section.
Note
The file format for the MMC is FAT. Any other format, such as FAT32 or NTFS are not
compatible with uploading and downloading parameter sets from the inverter.
Formatting can be accomplished using the DOS command line as follows:
C:\>format volume /FS:FAT - where volume has to be replaced by the name of the MMC
drive, for example A.
Please keep in mind that formatting will delete all the contents of the MMC.
Caution
Parameter download between different types of control units and of different firmware
versions is not recommended.
Basically, it is possible to download parameter sets off different CU types, however, as
the parameter sets might differ, the user is fully responsible for the consistency of the
downloaded parameter set.
Therefore, the user has to take the responsibility in case of an automatic download by
acknowledging F0395.
During download of a parameter set from a MMC to the EEPROM of the Control Unit
CU240S (e.g. during serial commissioning) you have to note that the LEDs are flashing
correctly. If the Control Unit CU240S is in a fault state, the LEDs indicate this fault state
with higher priority than the download. It is not sure that the parameter set is downloaded
correctly.
Manual download
A manual download can be performed similar to an upload via
● PC (STARTER)
● MMC
● OP
It can be triggered like upload via
● PROFIBUS
● OP
● STARTER
With a manual download a parameter set without the fail-safe parameters is downloaded
from one of the above mentioned devices into the inverter.
Automatic download
An automatic download needs a MMC to be performed. It is not possible to perform an
automatic download from a PC or from the OP.
The automatic download runs as follows according to the settings in P8458 after power cycle
or a after a swap (see "Start-up behavior" in this section).
Table 6-2 P8458 settings after an automatic parameter download from MMC
0 2 2
1 0 0 ---
1 1 0 ---
1 2 2 ---
2 0 0 ---
2 1 0 ---
2 2 2 ---
Contrary to a manual download even the fail-safe parameters are downloaded with an
automatic download.
Note
Manual and automatic download
With a manual download all necessary parameters excluding the fail-safe parameters (only
with Cus with fail-safe functions) are downloaded into the inverter. A detailed description is
given in "Series Commissioning" in the commissioning section.
With an automatic download even the fail-safe parameters are downloaded into the inverter.
An automatic download can only be performed with an MMC at Start-up or by swapping an
inverter component (CU or PM). A detailed description is given in "Start-up behavior" of this
section.
Overview
When starting-up the inverter checks, whether an MMC is plugged in or not.
If it is plugged and no swap has been taken place the start-up runs according the "Normal
start-up behavior". If a component (CU or PM) has been replaced, this is called a swap and
the start-up will be performed according the "Swap behavior" of the inverter.
Description
A normal start-up is a start-up after a power-cycle or a black-out. It can be performed with or
without MMC.
Note
MMC for "automatic download"
For an automatic download always the file clone00.bin will be used.
The user has to take care, that clone00.bin (saved as "clone00.bin" with STARTER via PC or
via setting P0804 = 00 with the OP) is available on the MMC, used for an automatic
parameter download at start-up. If clone00.bin does not exist drive will fail with F0061
Warning
The user is responsible for ensuring that the parameters held in the CU are the correct
parameters for their application.
Acceptance test
On CUs with fail-safe functions it is necessary to do an acceptance test (refer to the "Fail-
safe functions" section in this manual). To clear F0395 on CUs with fail-safe functions the
following procedure has to be followed:
● P0010 = 30
● P9761 = safety password
● P7844 = 0
● Carry out acceptance test
Notice
After upload and download of parameters between differing Control Units, the parameter
settings must be checked.
Parameter download from a different CU might fail with F0063 if parameters cannot be
downloaded (Check P949 for the (first) parameter number which cannot be downloaded).
If F0061 or F0063 occurs during startup it cannot be cleard except via a power cycle.
Overview
This section describes the possibilities to exchange inverter comonents, power modules or
control units, and the necesarry actions, depending on the swap type.
The following swaps are allowed:
● CU swap (neither PM nor CU powered)
● PM swap (neither PM nor CU powered)
● PM swap (CU externally powered)
Note
A swap is indicated by a F395. A downlaod fault during swap will be indicated by F0061
or F0063.
If F0061 or F0063 occurs during startup it cannot be cleard except via a power cycle.
Note
After a PM swap without MMC the parameter settings only stored in RAM will be lost
Successful swap
After a successful swap, F0395 will be displayed.
● In case of a standard CU a confirmation is necessary.
● In the case of CUs with fail-safe functions, an acceptance test must be performed.
Confirmation
On standard CUs the current parameter set needs to be checked and confirmed by clearing
F0395. It can be cleared via:
● Digital input or PLC signal (depends on the settings of P0700)
● setting P7844 = 0.
● Via the button on the OP
Warning
The user is responsible for ensuring that the parameters held in the CU are the correct
parameters for their application.
Acceptance test
On CUs with fail-safe functions it is necessary to do an acceptance test (refer to the "Fail-
safe functions" section in this manual). To clear F0395 on CUs with fail-safe functions the
following procedure has to be followed:
● P0010 = 30
● P9761 = safety password
● P7844 = 0
● Carry out acceptance test
Swap fault
A swap fault is indicated if the automatic download fails. In this case, the CU will return to the
parameter set previously held in the EEPROM and F0395 as well as one of F0061, F0062
and F0063 will be generated.
First F0395 must be cleared via:
● Digital input or PLC signal (depends on the settings of P0700)
● setting P7844 = 0.
● Via the button on the OP
In the next step F0061 / F0062 or F0063 has to be cleared via power cycle.
Note
F0395 cannot be cleared via power cycle. F0061, F0062 and F0063 can only be cleared via
power cycle.
In case of a swap fault check, whether the MMC is defective or a parameter set clone00.bin
is available or the parameter set is valid.
A valid parameter set means, it is not from a different type (eg. CU20S DP and CU240S or
failsafe and standard CUs)
Danger
Do not attempt to hot swap a power module (PM)
Before attempting to swap a PM it must be fully powered-down. Any attempt to swap-out a
PM when power is still applied could result in death of personnel and severe damage to
property and equipment.
Warning
Swap restrictions
Before performing a swap take care of the following:
• It is the responsibility of the user to ensure that only CUs of the same type are swapped
• It is the responsibility of the user to ensure that the MMC contains the correct parameter
set
• It is the responsibility of the user to ensure that only PMs of the same type and power
rating are swapped.
• It is the responsibility of the user to ensure that the application is in a safe state before
any swap of equipment is performed.
Swapping a CU
The following procedure is given as a guide to perform a swap of a CU.
Caution
Data set compatibility
To ensure complete data set compatibility, it is recommended to perform an upload of the
parameter set from the CU to a new MMC prior to swapping the CU.
Swapping the PM
Caution
To ensure complete data set compatibility, make sure that all parameters are stored in the
EEPROM of the Control Unit (see P0014 or P0971) prior to swapping the PM).
Europe/Africa (Erlangen)
Tel: +49 (180) 5050 222
Fax: +49 (180) 5050 223
Email: [email protected]
Asia/Pacific (Beijing)
Tel: +86 (1064) 757 575
Fax: +86 (1064) 747 474
Email: [email protected]
China (Beijing)
Tel: +86 (1064) 71 9990
Fax: +86 (1064) 71 9991
Email: [email protected]
Contact address
Should any questions or problems arise while reading this manual, please contact Siemens
at the following address:
Siemens AG
Automation & Drives
A&D SD SPA PM4
Postfach 3269
D-91050 Erlangen
Germany
Email: [email protected]
Regional contacts
For questions regarding services, prices and conditions of technical support, please contact
your local Siemens partner.
Faults
In the event of a failure, the inverter switches off and the red LED "SF" will be on. The fault
code will be displayed via OP, STARTER or Communication interface (if fitted, resp.
connected).
Note
To reset the fault code, one of three methods listed below can be used:
1. Cycle the power to the inverter.
2. Press the Fn button on the OP
3. Use digital input 2 (default setting).
4. Set bit 7 in control word 1 (r0054)
Fault messages are stored in parameter r0947 under their code number (e.g. F0003 = 3).
The associated error value is found in parameter r0949. The value 0 is entered if a fault has
no error value. It is possible to read out the point in time that a fault occurred (r0948) and the
number of fault messages (P0952) stored in parameter r0947.
A detailed description of the fault messages is provided in the Parameter List.
The fault state indication by LEDs is shown in the following sections.
Alarm messages
The alarm code will be displayed via OP, STARTER or Communication interface (if fitted,
resp. connected). Alarm messages are stored in parameter r2110 under their code number
(e.g. A0503 = 503) and can be read out from there. A detailed description of the alarm
messages is provided in the Parameter List.
6WDWXV/('RQ 6WDWXV/('RQ
&X6 &86'3)
&86'3
(QG 6DIH
5HDG\ 5HDG\ 6WDWH 6WRS
Figure 7-1 State LEDs on the CU240S, CU240S DP, CU240S DP-F
Colours
The colours of the LEDs are self explanatory. The Status of the inverter is displayed by the
following different LED colours and states:
LED description
● System-Fault LED (SF)
The system-fault LED indicates a general system error either software or hardware
related.
● Ready LED (RDY)
The ready LED indicates whether the inverter is ready to operate by transmitting a
control-word.
This LED does not indicate whether the drive is running or not. For that purpose an OP
would be more convenient. The information of interest is the actual speed, which can be
displayed on an OP which can be easily plugged in and out at any time during operation.
● Bus-Failure LED (BF)
The Bus-failure LED indicates if any bus failure occurred. A bus failure can be
characterised as corrupted communication (e.g. a frame of the PROFIBUS) due to
signalling problems on the bus itself.
Note that faults according to the inner data structure of the transmitted communication
frames (e.g. CRC check of PROFIsafe telegram) are not denoted as bus failure. Thus,
such failures have to be indicated by the general fault LED.
The Bus-failure LED indicates the following states:
– Bus-failure LED off: no Bus failure
– Bus-failure LED on: no connection to the DP-Master (searching for baud rate)
– Bus-failure LED flashing 0.5 Hz: I/O device is not configured or is wrongly configured
(baud rate found, no data exchange).
● End-state LED (ES)
The end-state LED indicates if the end state of a triggered fail-safe function has been
reached
● Safe Torque Off LED (STO)
The safe torque off LED indicates the fail-safe function Safe Torque Off.
● Safe Stop 1 LED (SS1)
The safe stop 1 LED indicates the fail-safe function Safe Stop 1.
● Safely-Limited Speed LED (SLS)
The safely-limited speed LED indicates the fail-safe function Safely-Limited Speed.
For fail-safe functions please refer to section Function.
LED Description
SF RDY BF
red green red
No supply available
LED Description
SF RDY BF ES STO SS1 SLS
red green red yellow
not relevant not relevant not relevant not relevant not relevant
STO parameterized
not relevant not relevant not relevant not relevant not relevant
STO reached
LED Description
SF RDY BF ES STO SS1 SLS
red green red yellow
not relevant not relevant not relevant
SS1 parameterized
not relevant not relevant not relevant not relevant not relevant
SS1 triggered
not relevant not relevant not relevant not relevant not relevant SS1 reached,
STO reached,
end state for SS1
LED Description
SF RDY BF ES STO SS1 SLS
red green red yellow
not relevant not relevant not relevant
SLS parameterized
not relevant not relevant not relevant not relevant not relevant
SLS triggered
not relevant not relevant not relevant not relevant not relevant
SLS reached
LED Description
SF RDY BF ES STO SS1 SLS
red green red yellow
not relevant
Safety commissioning
Overview
There are three types of diagnostic display:
● LEDs
● Alarm Numbers
● Diagnostic parameters.
Alarm Meaning
Number
A0700 Cause The parameter or configuring settings by the PROFIBUS master are
invalid.
Remedy Correct the PROFIBUS configuration
A0702 Cause The link to the PROFIBUS is interrupted.
Remedy Check connector, cable and PROFIBUS master.
A0703 Cause No setpoints or invalid setpoints (control word = 0) are being received
from the PROFIBUS master.
Remedy Check setpoints from the PROFIBUS master. Switch SIMATIC CPU to
"RUN".
A0704 Cause At least one configured internode transmitter is not yet active, or has
failed.
Remedy Activate internode transmitter.
A0705 Cause No actual values received from inverter.
Remedy None (fault is with the inverter).
A0706 Cause PROFIBUS DP software error.
Remedy None diagnostic parameter r2041.
A0710 Cause Inverter has detected failure of PROFIBUS communications link.
Remedy Communication interface on Control Unit may be broken.
A0711 Cause Invalid value of PROFIBUS parameter.
Remedy Check P0918 address and P2041.
F0070 Cause No communication via PROFIBUS. Triggered by A0702, A0703 and
A0704. The telegram failure time set in P2040 has run out. Details see
section "Faults and Alarns" in the Parameter List.
Remedy Check connection of the communication devices and ensure that a
valid control word is being used.
Parameter Meaning
r2053.00 0: Inverter cannot identify the communications interface
1: PROFIBUS DP detected
2: Not assigned
56: Undefined communications error
r2053.01 Firmware version
r2053.02 Constant "0"
r2053.03 Firmware date (year)
r2053.04 Firmware date (day and month)
Standard diagnostics
When the parameter P2041.03 = 0, then by using the read-only parameter r2054 and it’s
indices, it is possible to obtain detailed diagnostic information regarding the PROFIBUS DP
interface. This information is listed in table below.
Parameter Meaning
r2054.00 PROFIBUS DP status:
0: Off
1: Baud rate search
2: Baud rate found
3: Cyclical data exchange
(> 100: other diagnostic screen active)
r2054.02 Number of acyclical links with class 2 master (PC, OP): 0 … 2
r2054.03 Error number of last unsuccessful parameter access operation through an acyclical
link.
r2054.04 Parameter number of last unsuccessful parameter access operation
r2054.05 Sub-index of last unsuccessful parameter access operation
When parameter accessing errors occur, r2054.03 display the appropriate error number,
these are listed in table below.
Description
If the motor fails to start when the ON command has been given:
● Check that P0010 = 0.
● Check the inverter state via r0052
● Check command and setpoint source (P0700 and P1000)
Warnings and faults are displayed on the OP with Axxx and Fxxx respectively. The individual
messages are shown in the Parameter List.
Note
Motor data must relate to the inverter data power range and voltage.
Description
The following parameters can be used to quickly interconnect setpoints and control signals:
● P0700 Selection of command source
● P1000 Selection of setpoint source
These parameters are used to define through which interface the inverter receives the
setpoint or the power-on/power-off command. The interfaces, shown in the table below can
be selected for the command source P0700.
The following internal or external sources or interfaces can be selected for the frequency
setpoint source P1000. In addition to the main setpoint (second position), a supplementary
setpoint (first position) can be selected. This is shown in the table below.
Note
The complete list of all the possible settings is contained within Parameter Manual (see
P1000).
The selection of the command source is made independently of the selection of the
frequency setpoint source. This means that the source to enter the setpoint does not have to
match the source to enter the power-on/power-off command (command source). This
means, for example, that the frequency setpoint P1000 = 6 can be connected using an
external device and ON/OFF is entered using digital inputs DI (terminals, P0700 = 2).
Caution
When P0700 or P1000 are modified, then the frequency inverter also changes the
subordinate BICO parameters (refer to the Parameter Manual for P0700 or P1000 in the
appropriate tables).
There is no prioritization (priority assignment) between direct BICO parameterization and
P0700/P1000. The last modification is valid.
Description
Using BICO technology (Binector Connector Technology), process data can be freely
interconnected using the "standard" inverter parameterization. For this all values which can
be freely interconnected (for example, frequency setpoint, frequency actual value, current
actual value, etc.) are defined as "Connectors" and all digital signals which can be freely
interconnected (for example, status of a digital input, ON/OFF, message function when a
limit is violated etc.) are defined as "Binectors".
There are many input and output quantities as well as quantities within the closed-loop
control which can be interconnected in a inverter. It is possible to adapt the inverter to the
various requirements using BICO technology.
A binector is a digital (binary) signal without any units and which can either have the value of
0 or 1. Binectors always refer to functions and are sub-divided into binector inputs and
binector outputs (see the table below). In this case, the binector input is always designated
using a "P" parameter (e.g. P0840 BI: ON/OFF1), while the binector output is always
represented using an "r" parameter (e.g. r1025 BO: FF status).
As can be seen from the examples above, the binector parameters have the following
abbreviations in front of the parameter names:
Example
Interconnecting the BO parameter r1025 with BI parameter P0840: → P0840 = 1025
A connector has a value (16 or 32 bit), which can include a normalized quantity (without
dimension) as well as a quantity with associated units. Connectors always refer to functions
and are sub-divided into connector inputs and connector outputs. Essentially it is the same
as for the binectors, the connector inputs are characterized by a "P" parameter (e.g. P0771
CI: AO (analog output)); while the connector outputs are always represented using an "r"
parameter (e.g. r0021 CO: Act. frequency).
As can be seen from the examples above, connector parameters have the following
abbreviations in front of the parameter names:
Further, there are "r" parameters where several binector outputs are combined in a word
(e.g. r0052 CO/BO: Status word 1). This feature reduces, on one hand, the number of
parameters and simplifies parameterization using the serial interface (data transfer). These
parameters are further characterized by the fact that they do not have any units and each bit
represents a digital (binary) signal.
As can be seen from the examples of parameters, these combined parameters have the
following abbreviation in front of the parameter names:
&2%2
In order to interconnect two signals, a BICO setting parameter (signal sink) must be
assigned the required BICO monitoring parameter (signal source). A typical BICO
interconnection is shown using the following examples (see figure below):
&,0DLQVHWSRLQW
)XQFWLRQ &2$FW$,DIWHUVFDOH>K@ 3 )XQFWLRQ
U >@
3 >@
%LQHFWRURXWSXW%2 !%LQHFWRULQSXW%,
%,212))
)XQFWLRQ %2))6WDWXV 3 )XQFWLRQ
U
3
Note
BICO parameters with the CO, BO or CO/BO attributes can be used a number of times.
Description
For many applications it is advantageous if several parameters can be simultaneously
changed, during operation or in the ready state, using an external signal.
This functionality can be elegantly implemented using indexed parameters. In this case, as
far as the functionality is concerned, the parameters are combined to form groups/data sets
and are indexed. By using indexing, several different settings can be saved for each
parameter which can be activated by changing-over the data set (i.e. toggling between
indexes).
The following data sets apply:
● Command Data Set CDS
● Drive Data Set DDS
Three independent settings are possible for each data set. These settings can be made
using the index of the particular parameter:
● CDS0 … CDS2
● DDS0 … DDS2
Command sources and binector inputs for control commands (digital signals) e.g.
Selects the command source P0700
ON/OFF1 P0840
OFF2 P0844
JOG Enable P1057
Enable JOG right P1055
Enable JOG left P1056
Setpoint sources and connector inputs for setpoints (analog signals) e.g.
Selection of frequency setpoint P1000
Selection of main setpoint P1070
Selection of additional setpoint P1075
The parameters, combined in a command data set, are designated with [x] in the parameter
list in the index field.
Index
Pxxxx[0] Command data set 0 (CDS0)
Pxxxx[1] Command data set 1 (CDS1)
Pxxxx[2] Command data set 2 (CDS2)
Note
A complete list of all of the CDS parameters is contained in the Parameter Manual.
It is possible to parameterize up to three command data sets. This makes it easier to toggle
between various pre-configured signal sources by selecting the appropriate command data
set. A frequent application involves, for example, the ability to toggle between automatic and
manual operation.
Note
The parameters will be altered during data set switchover in the state "Ready" and "Run".
The following parameters will not be changed in the state "run:
P0700, P0701, P0702, P0703, P0704, P0705, P0706, P0707, P0708, P0709, P0712, P0713,
P0719, P0800, P0801, P0840, P0842, P0844, P0845, P0848, P0849, P0852, P1000, P1020,
P1021, P1022, P1023, P1035, P1036, P1055, P1056, P1070, P1071, P1075, P1076, P1110,
P1113, P1124, P1140, P1141, P1142, P1330, P1500, P1501, P1503, P1511, P1522, P1523,
P2103, P2104, P2106, P2220, P2221, P2222, P2223, P2235, P2236.
SINAMICS G120 has an integrated copy function which is used to transfer command data
sets.
This can be used to copy CDS parameters corresponding to the particular application.
P0809 is used to control the copy operation as follows:
3>@ &RS\IURP&'6
3>@ &RS\WR&'6
3>@ 6WDUWFRS\ >@ >@ >@
3
3
3
3
3
3
3
3
&'6 &'6 &'6
The command data sets are changed-over using the BICO parameters P0810 and P0811,
whereby the active command data set is displayed in parameter r0050 (see figure below).
Changeover is possible both in the "Ready" as well as in the "Run" states.
6HOHFWLRQRI&'6
%,&'6ELW &2%2$FW&WUO:G
3 U
U
%,&'6ELW &2%2$FW&WUO:G
3 U
U
W
6ZLWFKRYHUWLPH 6ZLWFKRYHUWLPH
&'6DFWLYH DSSUR[PV DSSUR[PV
U
W
The currently active command data set (CDS) is displayed using parameter r0050:
selected active
CDS CDS
r0055 r0054 r0050
Bit15 Bit15
CDS0 0 0 0
CDS1 0 1 1
CDS2 1 0 2
CDS2 1 1 2
Example
The command source (e.g. terminals → OP) or setpoint (frequency) source (e.g. AI → MOP)
should be changed-over using a terminal signal (e.g. DI3) as a function of an external event
(e.g. the higher-level control unit fails). A typical example in this case is a mixer, which may
come to an uncontrolled stop when the control fails.
&RPPDQGVRXUFH 7HUPLQDO!23
6HWSRLQWIUHTXHQF\VRXUFH $,!023
P0810 = 722.3
DI3
P0700[0] = 2 0
Terminals Sequence control
P0700[1] = 1 1
OP
P1000[0] = 2 0
AI Setpoint Motor
channel control
P1000[1] = 1 1
MOP
CDS0: Command source via terminals and setpoint source via analog input (AI)
CDS1: Command source via OP and setpoint source via MOP
CDS changeover is realized using digital input 3 (DI3)
Commissioningsteps:
1. Carry-out commissioning for CDS0 (P0700[0] = 2 and P1000[0] = 2)
2. Connect P0810 (P0811 if required) to the CDS changeover source
(P0704[0] = 99, P0810 = 722.3)
3. Copy from CDS0 to CDS1 (P0809[0] = 0, P0809[1] = 1, P0809[2] = 1)
4. Adapt CDS1 parameters (P0700[1] = 1 and P1000[1] = 1)
The parameters, combined in a drive data set, are designated with an [x] in the parameter
list in the index field:
Index
Pxxxx[0] Drive data set 0 (DDS0)
Pxxxx[1] Drive data set 1 (DDS1)
Pxxxx[2] Drive data set 2 (DDS2)
Note
A complete list of all of the DDS parameters is contained in the Parameter Manual.
It is possible to parameterize several drive data sets. This makes it easier to toggle between
various inverter configurations (control mode, control data, motors) by selecting the
appropriate drive data set (see figure below).
Note
The parameters will be altered during data set switchover in the state "Ready" and "Run".
The following parameters will not be changed in the state "run": P0300, P0304, P0305,
P0307, P0308, P0309, P0310, P0311, P0314, P0320, P0335, P0340, P0400, P0405, P0408,
P0410, P0491, P0492, P0500, P1082, P1240, P1256, P1300, P1320, P1322, P1324, P1820,
P2000, P2001, P2002, P2003, P2004, P2181.
Just like the command data sets, it is possible to copy drive data sets within the SINAMICS
G120. P0819 is used to control the copy operation as follows:
3>@ &RS\IURP''6
3>@ &RS\WR''6 >@ >@ >@
3>@ 6WDUWFRS\ 3
3
3
3
3
3
3
3
''6 ''6 ''6
Drive data sets are changed-over using the BICO parameter P0820 and P0821 whereby the
active drive data set is displayed in parameter r0051 (see figure below). Drive data sets can
only be changed-over in the "Ready" state and this takes approximately 50 ms.
'ULYHUXQQLQJ
'ULYHUHDG\
W
6HOHFWLRQRI''6
%,''6ELW &2%2$FW&WUO:G
3 U
U
%,''6ELW &2%2$FW&WUO:G
3 U
U
W
''6DFWLYH 6ZLWFKRYHUWLPH 6ZLWFKRYHUWLPH
U>@ DSSUR[PV DSSUR[PV
W
The currently active drive data set (DDS) is displayed using parameter r0051[1]:
selected active
DDS DDS
r0055 r0055 r0051 [0] r0051 [1]
Bit05 Bit04
DDS0 0 0 0 0
DDS1 0 1 1 1
DDS2 1 0 2 2
DDS2 1 1 2 2
Example
The inverter should be switched-over from motor 1 to motor 2.
0 0RWRU
.
*
0 0RWRU
.
Data
Description
External control signals are required for an inverter to be able to operate autonomously.
These signals can be entered using a serial interface as well as using digital inputs (see
figure below). The SINAMICS G120 has depending on CU variant up to 9 digital inputs which
can be expanded by using the 2 analog inputs. The digital inputs can be freely programmed
to create a function. Regarding the programming, it is possible to directly assign the function
using parameters P0701 … P0713 or to freely program the function using BICO technology.
',FKDQQHOHJ',
3
3
'HERXQFHWLPH',
3
)XQFWLRQ
9 7
U 3[[[[%,
U
&2%2%LQLQSYDO
9
The number of available digital inputs is displayed in parameter r0720. The logical states of
the digital inputs can be de-bounced using P0724 and read-out using parameter r0722
(BICO monitoring parameter). Further, this parameter is used for BICO parameterization of
the digital inputs (refer to BICO parameterization in the following section).
Table 8-5 Possible settings of the digital inputs and analog inputs used as digital inputs
Parameter Significance
Value
0 Digital input disabled
1 ON/OFF1
2 ON_REV/OFF1
3 OFF2 – coast to standstill
4 OFF3 – quick ramp-down
9 Fault acknowledge
10 JOG right
11 JOG left
12 Reverse
13 MOP up (increase frequency)
14 MOP down (decrease frequency)
15 Fixed frequency selector Bit 0
16 Fixed frequency selector Bit 1
17 Fixed frequency selector Bit 2
18 Fixed frequency selector Bit 3
25 Enable DC braking
27 Enable PID
29 External trip
33 Disable additional frequency setpoint
99 Enable BICO parameterization
Example
An ON/OFF1 command is to be accomplished using digital input DI0.
● P0700 = 2 Control enabled using the terminal strip (digital inputs)
● P0701 = 1 ON/OFF1 using digital input 0 (DI0).
Note
If an analog input has been configured as a digital input, then the following limit values
apply:
• Voltage > 4 V = logical 1
• Voltage < 1.6 V = logical 0
BICO parameterization
If the setting 99 (BICO) is entered into parameters P0701 … P07013, then the BICO wiring is
enabled for the appropriate digital input. The output parameter number of the function (the
parameter, included in the parameter text BO) should be entered into the command source
(the parameter which contains the code BI in the parameter text).
Example
A relay is to be controlled directly using DI0.
● P0700 = 2 Control enabled using digital inputs
● P0701 = 99 Enable BICO parameterization on DI0
● P0731[0] = 722.0 Relay 1 controlled directly.
This can be useful when the normal relay functions and digital inputs are not required so the
user can use them for their own purposes.
Note
Only experienced users should use the BICO parameterization and for applications where
the possibilities provided by P0701 … P07013 are no longer adequate.
If P0701 … P07013 are set to 99, then the command source can only be changed by the use
of P0700. For example, changing P0701 from 99 to 1 will not change the command source
or alter the existing BICO settings.
Data
Quantity: 3
Parameter range: r0730 … P0748
Function chart number: FP2100
Features:
• cycle time: 10 ms
Description
Three output relays are provided which can be programmed to indicate a variety of states of
the inverter, such as faults, warnings, current limit conditions, etc.
Some of the more popular settings are pre-selected (see table below), but others can be
allocated using the BICO internal connection feature.
Relay:
max. opening/closing time: 5/10 ms
voltage/current 30 V DC/0.5 A maximum
,QYHUW'2V
3 &2%26WDWH'2V
U
%,)FWRI'2 U
3>@
&20
12
,QYHUW'2V
&2%26WDWH'2V 1&
3
U
%,)FWRI'2 U
3>@
&20
12
,QYHUW'2V
3 &2%26WDWH'2V
U
%,)FWRI'2 U
3>@
&20
12
1&
The states, which are to be output, are defined using the "BI" parameters P0731 (digital
output 0), P0732 (digital output 1) and P0733 (digital output 2). For the definition, the "BO"
parameter number or "CO/BO" parameter number and the bit number of the particular state
should be entered into P0731 … P0733. Frequently used states including the parameter
number and bit are shown in the table below.
Note
On the OP the bit numbers are displayed in hex-format (0..9, A..F).
For complete list of all of the binary status parameters (refer to "CO/BO" parameters) in the
Parameter Manual.
Data
Quantity: 2
Parameter range: P0750 … P0762
Function chart number: FP2200
Features:
• cycle time: 4 ms
• resolution: 10 bits
• accuracy: 1 % referred to 10 V / 20 mA
• electrical features: incorrect polarity protection, short-circuit
proof
Description
Analog setpoints, actual values and control signals are read-into the inverter using the
appropriate analog inputs and are converted into digital signals or values using the A/D
converter.
The setting as to whether the analog input is a voltage input (10 V) or a current input (20 mA)
must be selected using the general I/O DIP switch on the control unit as well as also using
parameter P0756 (for details refer to Chapter "Installing/Mounting" Section "Connecting the
Control Unit via terminals").
Note
The setting of P0756 (analog input type) must match that selection on the DIP switch on the
control unit.
The bipolar voltage input is only possible with analog input 0 (AI0).
Depending on the AI type or source, the appropriate connection must be made. Using, as an
example, the internal 10 V voltage source, a connection is shown in the figure below.
./9 ./9
./9 ./9
./$, ./$,
$ $
./$, ./$,
' '
The AI channel has several function units (filter, scaling, dead zone, see figure below).
3
3
3
3
U 3
',3VZLWFK 3 3 3
)XQFWLRQ
./
$, $, $ $, $, $,
VFDOLQJ GHDG]RQH U 3[[[[
./ W\SH ' W\SH
$,
U
U
U;
Note
When the filter time constant P0753 (AI-PT1) is increased, this smooths the AI input signal
therefore reducing the ripple. When this function is used within a control loop, this smoothing
has a negative impact on the control behavior and immunity to noise (the dynamic
performance deteriorates).
Note
The analog inputs can be used as digital inputs. Setting P0712 and P0713 > 0 assign digital
input functions to the analog inputs.
Data
Quantity: 2
Parameter range: r0770 … P0785
Function chart number: FP2300
Features:
• cycle time: 4 ms
• resolution: 12 bit
• accuracy: 1 % referred to 20 mA
Description
Two analog outputs are provided which can be programmed to indicate a variety of
variables. Some of the more popular settings are pre-selected (see table below), but others
(BICO outputs) can be allocated using the BICO internal connection feature.
Parameter Description
r0020 CO: Frequency setpoint before RFG
r0021 CO: Actual filtered frequency
r0024 CO: Actual filtered output frequency
r0025 CO: Actual filtered output voltage
r0026 CO: Actual filtered DC-link voltage
r0027 CO: Actual filtered output current
… …
r0052 CO/BO: Actual status word 1
r0053 CO/BO: Actual status word 2
r0054 CO/BO: Actual control word 1
… …
In order to adapt the signal, the D/A converter channel has several function units (filter,
scaling, dead zone) which can be used to modify the digital signal before conversion (see
figure below).
3
3
3
3
U
3 3
3
P$
$2 $2 '
)XQFWLRQ U[[[[ 3 $2
VFDOLQJ GHDG]RQH
$ $2
1 U
0 U
Note
The analog output 0 (AO0) can be changed-over from current output (P0776 = 0) to voltage
output (P0776 = 1).
The analog output 1 (AO1) only provide current output (0 … 20 mA). The 0 … 10 V voltage
signal can be generated by connecting a 500 Ω resistor across the outputs. The voltage drop
across the resistor can be read using parameter r0774 if the parameter P0776 is changed-
over from current output (P0776 = 0) to voltage output (P0776 = 1). The D/A scaling
parameters P0778, P0780 and the D/A converter dead zone must still be entered in mA (0
… 20 mA).
With setting parameter P0775 = 1 it is possible to detect negative values on the input side of
the D/A converter channel. If enabled, this parameter will take the absolute value of the
value to be outputed (the AO-linear characteristic is mirrored on the y axis). If the value was
originally negative then the corresponding bit in r0785 is set.
Data
Description
Using the Universal Serial Interface (USS) protocol, a user can establish a serial point-to-
point data link (RS232 interface) and a serial bus data link between a higher-level master
system and several slave systems (RS485 interface). Master systems can be e.g. PLCs (e.g.
SIMATIC S7-200) or PCs. The inverters are always the slaves on the bus system.
The USS protocol allows the user to implement both automation tasks with cyclical telegram
traffic (a fixed telegram length is necessary) as well as visualization tasks. In this case, the
protocol with variable telegram length is advantageous, as texts and parameter descriptions
can be transferred in one telegram without chopping up the information.
With the RS232 interface only direct connections (point-to-point) are possible with cable
lengths of 2 m … 5 m typically. This is typically used to commission a drive where the
commissioning software (e.g. STARTER) runs on a PC. For this configuration the optional
PC Connection Kit is available.
With the RS485 interface simple and cheap networks can be constructed. The topology must
be that of a line with the first and last devices of the line terminated with termination
resistors.
RS485 connector
6 3 8 5
620 Ω 120 Ω 620 Ω
Short branches are possible to connect the devices. Up to 31 inverters can be integrated as
slaves into a network with a PLC as master.
56WHUPLQDWRU
&8 &8 &8
56WHUPLQDWRU
0DVWHU
56
56
6FUHHQLQJ 6FUHHQLQJ 6FUHHQLQJ 56
Description
The following figure shows the structure of a typical USS telegram. It consists of a start
delay, 4 framing bytes (STX, LGE, ADR and BCC) and the n user data.
Start Delay
The length of the start delay is at least the time of two characters and depends on the
baudrate.
Baudrate in bit/s Transfer time per character (= 11 bit) Transfer time per bit Min. Start Delay
9600 1.146 ms 104.170 µs > 2.291 ms
19200 0.573 ms 52.084 µs > 1.146 ms
38400 0.286 ms 26.042 µs > 0.573 ms
57600 0.191 ms 17.361 µs > 0.382 ms
187500 0.059 ms 5.340 µs > 0.117 ms
Note: The time between characters must be smaller than the start delay.
STX
The STX field is a single byte ASCII STX character (0x02) used to indicate the start of a
message.
LGE
The LGE is a single byte field indicating the number of bytes, which follow this in the
message. According to the USS specification, the telegram length is variable, and the length
must be specified in the 2nd telegram byte (i.e. LGE). Depending on the configuration, fixed
telegram lengths can be defined (see description of user data area). Different telegram
lengths can be used for different slave nodes on the bus. The maximum total length of a
telegram is 256 bytes. The LGE is defined as the user data characters (quantity n), address
byte (ADR) and the block check character (BCC). The actual total telegram length will of
course be two bytes longer than the LGE as the STX and LGE bytes are not counted in the
LGE.
Variable length telegrams and fixed length telegrams can both be used. This can be selected
using parameters P2012 and P2013 to define the PZD and PKW lengths. Most common
fixed length applications will use a 4-word (8-byte) PKW area and a 2-word (4-byte) PZD
area giving 12 user data characters. This gives the LGE = 12 + 2 = 14.
ADR
The ADR field is a single byte containing the address of the slave node (e.g. inverter). The
individual bits in the address byte are addressed as follows:
7 6 5 4 3 2 1 0
Bit 5 is the broadcast bit. If it is set to 1, the message is a broadcast message and will be
acted upon by all inverters on the serial link. The node number is not evaluated. The USS
protocol specification requires certain settings in the PKW area, refer to the later example on
using USS broadcast mode.
Bit 6 = 1 indicates a mirror telegram. The node number is evaluated and the addressed slave
returns the telegram unchanged to the master.
Bit 5 = 0 and bit 6 = 0 and bit 7 = 0 means normal data exchange for units. The node number
(bit 0 … bit 4) is evaluated.
BCC
BCC means block check character. It is an exclusive OR (XOR) checksum over all telegram
bytes except the BCC itself.
'DWD%\WHV
3URWRFRO'DWD
3.: 3='
3URWRFRO:RUGV
3 3
The length of the PKW channel is determined by parameter P2013, that for the process data
by parameter P2012. If either no PKW or no PZD is required, the corresponding parameters
can be set to zero ("PKW only" or "PZD only" respectively). It is not possible to transmit
"PKW only" and "PZD only" alternatively. If both channels are required they must be
transferred together.
Description
In this area of the telegram, process data (PZD) are continually exchanged between the
master and slaves. Dependent of the direction the process data channel contains data for a
request to the USS slaves or for a response to the USS master. In the requests are control
words and setpoints for the slaves and in the responses are status words and actual values
for the master.
3
3
3
The number of PZD words in a USS-telegram are determined by parameter P2012, where
the first two words are:
● Control word 1(STW1) and main setpoint (HSW)
● Status word 1 (ZSW1) and actual value (HIW)
If P2012 is greater or equal to 4 the additional control word (STW2) is transferred as the 4th
PZD word (default setting).
The sources of all other PZDs are defined with parameter P2019 for a RS485 interface and
P2016 for a RS232 interface.
3.:
3.( ,1' 3:(
VW QG UGDQGWK
ZRUG ZRUG ZRUG
630
$. E318
● Bits 0 to 10 (bPNU) contain the remainder of the parameter number (value range 1 to
1999). For parameter numbers ≥ 2000 it is necessary to add an offset which is defined
with the high byte bits of IND.
● Bit 11 (SPM) is reserved and always = 0.
● Bits 12 to 15 (AK) contain the request or the response identifier.
The meaning of the request identifier for request telegrams (master → inverter) is shown in
the table below. Request identifiers 11 to 14 are specific to the SINAMICS G120.
If the response identifier is 7 (cannot process request), then one of the fault numbers listed in
the next table will be stored in parameter value 2 (PWE2).
No. Meaning
0 Illegal parameter number (PNU) Parameter does not exist
1 Parameter value cannot be modified Parameter is a read-only parameter
2 Minimum/maximum not reached/exceeded –
3 Faulty subindex –
4 No array Single parameter has been accessed
with array request and subindex > 0
5 Parameter type is wrong / incorrect data type Mix-up between word and double
word
6 Setting not allowed (resetting only) –
7 Descriptive element cannot be modified Description can never be modified
11 No status as master control Modification request without status as
master control (see P0927)
12 Key word missing –
15 Text array is not available –
17 Request cannot be processed due to operating Current inverter status is not
state compatible with the received request
20 Change request for a value which is between the There are other reasons why the
lower an the upper limit change request is not allowed; it is a
parameter with defined single values
101 Parameter number currently deactivated Dependent on inverter status
102 Response does not fit into buffer Dependent on the number of PKW
and the maximum net data length in
the drive
104 Illegal parameter value Parameter permits only certain values
106 Request not implemented / Task not supported After request identifier 5, 10, 15
109 PKW request access timeout or number of retries
is exceeded or wait for response from CPU side.
200/201 Modified minimum/maximum not Minimum/maximum can be further
reached/exceeded limited in operation
204 Available access authorization does not cover –
modification of parameters
3.:
3.( ,1' 3:(
VW QG UGDQGWK
ZRUG ZRUG ZRUG
3DJHLQGH[ 3DUDPHWHULQGH[,';
● The low byte of IND is used for the parameter index IDX and can have values between 0
and 255. The IND low byte IDX = 255 has a special meaning. For this index value, the
task is referred to the complete array or the complete parameter description.
● Bits 8 and 9 are always 0.
● Bits 10 to 15 are interpreted as a page index to determine the full parameter number. The
bPNU (bits 0 to 10 of PKE) is limited to values between 0 and 1999. The parameter
number is a concatenation of bPNU and a multiplier determined by the 6 higher bits of
IND. It is defined als follows:
,1'
D G F E I H
Table 8-14 Example coding for parameter no. in PKE and IND for P8820, Index 16
PKE IND
decimal xx 820 8000 16
hex xx 334 20 10
Note
Data types U8 will be transferred as U16 with the upper byte zero. Arrays of U8 will therefore
require one PWE per index.
A PKW area for 3 words is a typical data frame for exchanging 16 bit data or alarm
messages. The mode with a fixed PZD length of 3 is used with p2013 = 3.
A PKW area for 4 words is a typical data frame for exchanging 32 bit data variables and
requires p2013 = 4.
A PKW area for a flexible PZD length is used with p2013 = 127. The length for telegrams
between master and slave can have a different number of PWEs.
If the length of PKW is fixed (p2013 = 3 or 4), then the Master must always correctly send
either 3 or 4 words in the PKW area (if not, the slave will not respond to the telegram). The
slave response PKW will be either 3 or 4 words as well. If a fixed length is used, this should
be 4, as 3 would not be sufficient to support many of the parameters (i.e. double words). For
variable length of PKW (p2013 = 127) the Master sends only the necessary number of words
for the task in the PKW area. The length of the response telegram will also only be as long
as necessary.
Telegram Timeouts
For the timeout monitoring, the character run time is important:
Baudrate in bit/s Transfer time per character (= 11 bit) Transfer time per bit Character run time
9600 1.146 ms 104.170 us 1.146 ms
19200 0.573 ms 52.084 us 0.573 ms
38400 0.286 ms 26.042 us 0.286 ms
187500 0.059 ms 5.340 us 0.059 ms
The following figure shows the meaning of the "residual run time":
&KDUDFWHUGHOD\WLPH &KDUDFWHUUXQWLPH
0D[LPXPWHOHJUDPUHVLGXDOUXQWLPH
The character delay time can be zero and must be smaller than the start delay!
The following figure shows the various delays and transmission times:
Character delay time timeout between characters and must be smaller than 2 time the
character run time but can be zero
Start delay timeout between USS messages. Must be > 2 * character run time
Response delay Processing time of the slave. Must be < 20 ms, but larger than the
start delay!
Residual run time < 1.5 * (n + 3) * character run time (where n = number of data bytes)
"Slave is the sum of "Start delay", "Response delay" and "Residual run
Transmitting"/ time"
"Master
Transmitting"
The master must check the following times:
0DVWHU5HTXHVW
::: %&&
6WDUW'HOD\
The timeout margins that are verified on the USS slave are shown in the figure above. "crt"
stands for "character run time". The factor "1.5" is the maximum margin. The "start delay"
and the minimum "response delay" are fixed minimum values in software. The "residual run
times" are monitoring values that cause a timeout if they are exceeded by the character
reception.
Process Timeouts
Parameter P2014 determines the timeout in ms. A value of zero disables the timeout check.
Parameter P2014 checks the cyclic refresh of Bit10 in control word 1.
When USS is configured as command source of the drive and P2014 is not zero, Bit10 of the
received control word 1 is examined. If the bit is not set, an internal timeout counter is
incremented. If the threshold of p2014 is reached, a process timeout fault is set by the drive.
Other errors
P2025 = USS rejected
P2026 = USS character frame error
P2027 = USS overrun error
P2028 = USS parity error
P2029 = USS start not identified
P2030 = USS BCC error
P2031 = USS length error
Data
Number: 15
Parameter range: P1001 … P1025
Warnings: -
Faults: -
Function chart number: FP3200, FP3210
Description
The fixed frequency functionality allows to enter a setpoint to the drive. This is an alternative
option to enter a setpoint with using the analog inputs, the serial communication interfaces,
the JOG function or the motorized potentiometer. The fixed frequencies are defined using
parameters P1001 … P1015 and selected and combined using binector inputs P1020 …
P1023. The effective fixed frequency setpoint is available through connector output r1024. If
this is to be used as setpoint source, then parameter P1000 should be modified or connector
output r1024 should be connected to the main setpoint P1070 or supplementary setpoint
P1075.
There are two modes to select fixed frequencies, which are set via the parameter P1016:
● Direct selection (P1016 = 1)
● Binary-coded selection (P1016 = 2)
The fixed frequency status bit r1025 (binector output) allows to combine the two selection
modes for fixed frequencies with an ON command. For this, P0840 should be set to 1025.
Please note that the meaning of P0840 may change with using the 2-/3-wire control
functionality.
Note
The standard method has priority over the BICO method.
Examples
The fixed frequencies are selected via the digital inputs 4 … 6 and the analog/digital input
AI0.
● Standard method:
P0704 = 15, P0705 = 16, P0706 = 17 (default) and P0712 = 18, P1023 = 722.11
Each digital input (P0701 and the following) can be connected to each fixed frequency
selector input (P1020 … P1023) with the settings 15, 16, 17 or 18. The different settings
can only be chosen once. If the same setting of a digital input is chosen for more than
one digital input, then only the last setting is valid and the previous digital input setting is
reset to 0.
● BICO method:
P0704 … P0706, P0712 = 99, P1020 … P1022 = 722.3 … 722.5, P1023 = 722.11
(example: DI3 connects to selector P1020 → P0704 = 99, P1023 = 722.3)
Each digital input (P0701 and the following) can be BICO connected to each fixed
frequency selector input (P1020 … P1023). If the same setting of a digital input is chosen
for more than one digital input, then only the last setting is valid and the previous digital
input setting is reset to 0.
P1016 = 1
P1020
DI3 r0722 722:3
P0704 = 15 or P0704 = 99
...
...
P1022
...
DI5 r0722 722:5
P0706 = 17 or P0706 = 99 1 r1025
P1023
AI0 r0722 722:11
P0712 = 18 or P0712 = 99
...
0 +
r1024
P1001
...
0 +
P1003
0
P1004
P1016 = 2
P1020
DI3 r0722 722:3
P0704 = 15 or P0704 = 99
...
...
P1022
...
DI5 r0722 722:5
P0706 = 17 or P0706 = 99 1 r1025
P1023
AI0 r0722 722:11
...
P0712 = 18 or P0712 = 99
)L[HG)UHT
>+]@ 0001
3'
r1024
)L[HG)UHT
>+]@ 1111
3'
Data
Description
Note
Automatic restart function
When a 2-/3-wire control methods is selected, the automatic restart function (P1210) is
disabled. If the automatic restarted function is required, the user must specifically enable this
function. For further details, please see the Parameter List.
The different types of 2-/3-wire control are enabled using parameter P0727 and selecting
one of the following options:
Default value
● P0727 = 0: Siemens standard control (ON/OFF1, REV).
Other settings
● P0727 = 1: 2-wire control (ON_FWD, ON_REV)
● P0727 = 2: 3-wire control (FWDP, REVP, STOP)
● P0727 = 3: 3-wire control (ON_PULSE, REV, OFF1/HOLD)
When any of the control functions are selected using P0727, the settings for the digital inputs
(P0701 … and P0712, P0713 for AI used as DI) are redefined as shown in the table below.
BICO connections
The different 2-/3-wire control methods can also be accomplished using BICO connections.
A summary is given in the table below.
Description
With P0727 = 0 there are two possibilities of control available using the following signals
1. ON/OFF1 and REV.
2. ON/OFF1 and ON_REV/OFF1.
Function
On receiving an ON/OFF1 command the inverter will run the motor in a forward direction and
ramp-up the motor to the frequency setpoint.
When a REV command is issued, the inverter will ramp-down the frequency through 0 Hz
and run the motor in the reverse direction. When the REV command is removed the inverter
will ramp-up through 0 Hz and run in a forward direction until the frequency setpoint is reach.
When the ON/OFF1 command is removed, the inverter will stop the motor by performing an
OFF1.
The REV command initiated by itself cannot start the motor.
212))
5(9
212)) $FWLYH
&RQWURO
FRPPDQGV
5(9 $FWLYH $FWLYH
,QYHUWHU
IUHTXHQF\
R 7LPH
IRXW
R 2))
Function
The ramp down phase can be interrupted by start command in the same direction: if the
drive was operating in forward and OFF1 was applied, an ON/OFF1 will work correctly and
accelerate again the drive up to the setpoint speed. The same is valid for reverse and
ON_REV/OFF1
Giving a start command for the opposite direction of which the inverter frequency output is
ramping down, the drive ignores the new setting and the drive will ramp down to 0 Hz and
then remain at standstill.
Without any control signal enabled the drive will ramp down to a stop and remain at
standstill.
212))
21B5(92))
&RPPDQGLJQRUHG
212)) $FW $FWLYH
&RQWURO
&RPPDQGLJQRUHG
FRPPDQGV
21B5(92)) $FWLYH
,QYHUWHU
R
IUHTXHQF\ R
R 7LPH
IRXW
R 2))
Description
This method uses two maintained signals, ON_FWD and ON_REV which start/stop the
inverter and determine the direction of the motor.
The advantage of this method of control is that ON_FWD and ON_REV can be switched at
any time, independently of the setpoint or frequency output or direction of rotation, and there
is no requirement of the motor to ramp-down to 0 Hz before the command is performed.
Function
With ON_FWD closed and maintained closed the drive is ON and runs in forward direction.
Applying only ON_REV (and keeping the contact closed) the drive is ON and runs in reverse
direction.
If both signals are however enabled (contacts are closed) the drive will perform an OFF1 and
ramp down to a stop.
If both signals are disabled the drive is in OFF1 state.
21B):'
21B5(9
,QYHUWHU
IUHTXHQF\ R
R
R R
IRXW R 7LPH
R 2))
Description
This method uses three commands to control the operation of the motor:
1. STOP: Causes on OFF1 command to be performed by the inverter.
2. FWDP: Causes the motor to run in a forward direction (run right).
3. REVP: Causes the motor to run in the reverse direction (run left).
Function
The STOP signal uses negative logic: Opening the contact or maintaining it open causes an
OFF1 condition and the drive stops. The STOP contact will need to be maintained closed to
start and run the inverter.
Then a momentary closure (positive edge) of the FWDP or REVP contact latches and starts
the inverter.
A momentary closure (positive edge) of the FWDP contact will set the forward direction.
A momentary closure of the REVP contact will change to the reverse direction.
Closing FWDP and REVP will cause a Stop (OFF1).
The ramp down can be interrupted by a single new pulse FWDP or REVP.
A momentary closure of the FWDP or REVP contacts while the drive is operating in the
respective direction will not cause any change.
Only by opening the STOP contact the drive will switch off regularly, apart from the special
case that both signals FWDP and REVP are present.
6723
):'3
5(93
,QYHUWHU
IUHTXHQF\
R R
IRXW 7LPH
R 2))
Description
There are three signals associated with this function:
OFF1/HOLD: Being maintained closed the opening of the contact will switch the
inverter OFF and cause a ramp down to 0 Hz.
ON_PULSE: This will run the motor in a forward direction (run right).
REV: This will change the direction of the motor to reverse (run left).
Function
The switch OFF1/HOLD uses negative logic: the contact will need to be maintained closed in
order to switch the inverter ON or keep it running.
A momentary closure (positive edge) of the ON_PULSE switch latches and starts the inverter
if it was OFF before.
The direction can be determined and changed any time using the REV signal.
Opening or closing the ON_PULSE switch while the drive runs has no effect.
Only enabling (i.e. Opening) OFF1/HOLD will unlatch the run-state and then stop the
inverter.
21B38/6(
2))+2/'
5(9
&RPPDQGLJQRUHG
21B38/6( $FWLYH
,QYHUWHU
IUHTXHQF\
R R
IRXW 7LPH
R 2))
Data
Description
This function emulates an electromechanical potentiometer to enter setpoints. The motorized
potentiometer (MOP) value is adjusted using the "Raise" and "Lower control signal" which is
selected using BICO parameters P1035 and P1036. The value which has been set is
available through connector output r1050 so that it can be utilized and connected.
',
3
W
%23
866RQ 3
W
56
866RQ
56 3
W
)LHOGEXV I
3
3
W
3 3
3
IDFW
U
3
The behavior of the MOP also depends on the duration of the up and down command:
● P1035 (P1036) = 1 for < 1 s :
Frequency changes in steps of 0.1 Hz.
● P1035 (P1036) = 1 for > 1 s :
Frequency ramps up (down) with the time of P1120 (P1121) but not faster than 2 s.
The MOP functionality can be selected using the operator panel, digital inputs or the serial
interface. Parameterization is also possible directly using BICO parameters P1035 and
P1036 as well as parameter P0700. In this case, for a value assigned to P0700, the BICO
parameter is appropriately modified.
Example
Command source via "USS on RS232" (using the PC connection kit on the option port)
Standard method P0700 = 4
BICO method P1035 = 2032.13
P1036 = 2032.14
…
(for a complete list refer to Parameter List P0700)
If the motorized potentiometer is to be used as a setpoint source, then parameter P1000
should be modified or the BICO parameter r1050 should be connected to the main setpoint
P1070 or supplementary setpoint P1075. When parameter P1000 is modified, this implicitly
changes BICO parameters P1070, P1075.
Example
8.11 JOG
Data
Description
The JOG function is used as follows:
● To check the functionality of the motor and inverter after commissioning has been
completed (the first traversing motion, checking the direction of rotation, etc.)
● Positioning a motor or a motor load into a specific position
● Traversing a motor, e.g. after a program has been interrupted
The motor is traversed using this function by entering fixed frequencies P1058, P1059. The
JOG mode can be selected using the operator panel, digital inputs or the serial interface. An
ON/OFF command is not used to move the motor, but instead when the "JOG keys" are
pressed movement takes place. These "JOG keys" are selected using the BICO parameters
P1055 and P1056. The JOG function can be disabled via P1057.
ಯರ
-2*HQDEOH
W
3 ಯರ
$ $
',
ಯರ
-2*ULJKW
%23 W
3 ಯರ
56
56
ಯರ
-2*OHIW
)LHOGEXV W
3 ಯರ
I
3
3
3
3
3
3
3
3
Pressing the appropriate key accelerates the motor to the frequency in P1058 (JOG right) or
P1059 (JOG left) at the ramp rate set in P1060. When the key is released, the motor stops,
decelerating at the rate set in P1061. If JOG right and JOG left signals are given at the same
time, there is no reaction, and a warning A0923 is raised. Internal BICO connections may
also be used to select other settings and control methods.
Example
Command source via "USS RS232" interface (using the PC connection kit on the option port)
Standard method P0700 = 4
BICO method P1055 = 2032.8
P1056 = 2032.9
…
(for a complete list refer to Parameter List P0700)
Note
The JOG fuction as used in the SINAMICS G120 inverter does not correspond to the
definition in PROFIdrive profile.
Data
Description
The SINAMICS G120 has an integrated technology controller (PID controller, enabled
through P2200). This can be used to process basic higher-level closed-loop control
functions. These typically include:
● Closed-loop pressure control for extruders
● Closed-loop water level control for pump motors
● Closed-loop temperature control for fan motors
● Closed-loop dancer roll position control for winder applications
● And similar control tasks
The technology controller setpoints and actual values can be entered using the PID
motorized potentiometer (PID-MOP), PID fixed setpoint (PID-FF), analog inputs (AI) or
through the serial interface as shown in the figure below. The appropriate parameterization
of the BICO parameter defines which setpoints or actual values are to be used.
3,'
023
3
$,
0RWRU
3,' 3,' 3,' FRQWURO
3 3,'
3,' 680 5)* 37
)) ಥ
ෙ3,' 3,'2XWSXW
56 3,' 3,'
3
56 37 6&/
3
)LHOGEXV 3
$,
Example
PID controller enable and PID setpoint input via PID fixed frequencies and PID actual value via the
analog input
Permanent PID enable P2200 = 1.0
Setpoint input via PID-FF P2253 = 2224
Actual value input via analog input AI P2264 = 755
Setpoint input via PID P2251 = 0
The supplementary (additional) setpoint is added to the main setpoint (PID-SUM) and the
sum is fed to the setpoint-actual value summation point through the PID ramp-function
generator (PID-RFG). The source of the supplementary setpoint (BICO parameter P2254),
the ramp-up/ramp-down times of the PID ramp-function generator (P2257, P2258) as well as
the filter time (P2261) can be adapted to the particular application by appropriately
parameterizing the corresponding parameters.
Similar to the PID setpoint branch, the actual value branch of the technological controller has
a filter (PID-PT1) which can be set using parameter P2265. In addition to the smoothing, the
actual value can be modified using a scaling unit (PID-SCL).
The technological controller can be parameterized as either P, I, PI or PID controller using
parameters P2280, P2285 or P2274.
3
3
.S 7Q \
3,' G
VHWSRLQW [ 0RWRU
GW
FRQWURO
U
3 U U
3,'
3
IHHGEDFN
U
3
For specific applications, the PID output quantity can be limited to defined values. This can
be achieved using the fixed limits - P2291 and P2292. In order to prevent the PID controller
output exercising large steps at power-on, these PID output limits are ramped-up with ramp
time P2293 from 0 to the corresponding value P2291 (upper limit for the PID output) and
P2292 (lower limit for the PID output). As soon as these limits have been reached, the
dynamic response of the PID controller is no longer limited by this ramp-up/ramp-down time
(P2293).
Data
Description
The PID controller has a PID motorized potentiometer (PID-MOP) which can be separately
adjusted. The functionality is identical with the motorized potentiometer, whereby the PID
parameters are emulated in the range from P2231 … r2250.
Data
Quantity: 15
Parameter range: P2201 … P2225
Warnings: -
Faults : -
Function chart number: FP3300, FP3310
Description
Similar to the fixed frequencies, the PID controller has separate programmable PID fixed
setpoints (PID-FF). The values are defined using parameters P2201 … P2215 and are
selected and combined using binector inputs P2220 … P2223. The selected PID fixed
setpoint is available using connector output r2224 where it can be further processed (e.g. as
PID main setpoint → P2253 = 2224).
Two modes are available to select the PID fixed setpoints, similar to the fixed frequencies.
They are set via parameter P2216:
● Direct selection (P2216 = 1)
● Binary-coded selection (P2216 = 2)
The fixed frequency status bit r2225 (binector output) allows to combine the two selection
modes for fixed frequencies with an ON command. For this, P0840 should be set to 2225.
Please note that the meaning of P0840 may change with using the 2/3 wire functionality.
All logical connections are like the connections with fixed frequencies and for each selection
mode there are the two connection methods:
● Standard method
● BICO method
Note
The standard method has priority over the BICO method.
P2216 = 1
P2220
DI3 r0722 722:3
P0704 = 15 or P0704 = 99
1
...
r2225
...
...
0 +
r2224
P2201
...
Figure 8-37 Directly selected PID fixed setpoint using DI3
Data
Description
For various continuous production processes, for example, in the paper and pulp industry or
in the manufacture of cables, it is necessary to control (closed-loop) the velocity of stations
along the production process so that the continuous material web is not subject to any
unwanted tension levels. It is important that no folds or creases are formed. For applications
such as these, it is practical to provide a type of material buffer in the form of a loop with a
defined tension. This provides a de-coupling between the individual inverter locations. This
loop represents the difference between the material fed-in and that fed-out and therefore
indicates the process quality.
Using the PID dancer roll control, with SINAMICS G120 it is possible to ensure that
continuous material webs have a constant tension.
$SSOLFDWLRQ Y Y
[
680 0RWRU
Y
$)0 5)*
VHWSRLQW FRQWURO
6WUXFWXUH
Note
When selecting the closed-loop dancer roll control it should be noted that neither PID-MOP
nor PID-FF should be used - but instead the MOP (motorized potentiometer) or the FF (fixed
frequencies).
The structure and important parameters for the PID dancer roll control are shown below.
3
3
3
023
3 680 $)0 5)*
$,
3
3
3
3
3
3
)) 0RWRU
3,' 3,' 3,' 3,' FRQWURO
866RQ 3 680 5)* 37
56 B
3,'2XWSXW
3
3
∆3,'
866RQ
56
3,' 3,'
)LHOGEXV 3
37 6&/ 3
3 3
$, 3
Description
The setpoint channel (see figure below) forms the coupling element between the setpoint
source and the closed-loop motor control. The SINAMICS G120 inverter has a special
characteristic which allows the setpoint to be entered simultaneously from two setpoint
sources. The generation and subsequent modification (influencing the direction, suppression
frequency, up/down ramp) of the complete setpoint is carried-out in the setpoint channel.
023
$GGLWLRQDO
$,
VHWSRLQW
0RWRU
)) 680 $)0 /LPLW 5)* FRQWURO
56 0DLQ
56 VHWSRLQW
)LHOGEXV
$,
0RWRU
6HWSRLQWVRXUFH 6HWSRLQWFKDQQHO
FRQWURO
Data
Description
For applications where the control quantities are generated from central control systems, fine
tuning is often required locally on-site (correction quantity). For SINAMICS G120, this can be
elegantly realized using the summation point where the main and supplementary (additional)
setpoints are added in the setpoint channel. In this case, both quantities are simultaneously
read-in through two separate or one setpoint source and summed in the setpoint channel.
Depending on external circumstances, the supplementary setpoint can be dynamically
disconnected or switched-in to the summation point (see figure below). This functionality can
be used to advantage, especially for discontinuous processes.
&,0DLQVHWSRLQW
3&
&,0DLQVHWSVFDO
3&
U
$)0 /LPLW 5)* 0RWRUFRQWURO
%,'LVDEDGGVHWS
3&
&,$GGVHWSVFDO
3&
&,$GGVHWSRLQW
3&
SINAMICS G120 has the following possibilities to select the setpoint source:
1. P1000 – selecting the frequency setpoint source
2. BICO parameterization
– P1070 CI: Main setpoint
– P1075 CI: Additional setpoint
Further, the main setpoint as well as the supplementary (additional) setpoint can be scaled
independently of one another. In this case, for example, a user can simply implement an
override function using the appropriate parameterization.
A scan sequence is generally associated with a forwards and a backwards motion. When
selecting the reversing functionality, after reaching the end position, a direction of rotation
reversal can be initiated in the setpoint channel (see figure below).
On the other hand, if a direction of rotation reversal or a negative frequency setpoint is to be
prevented from being entered using the setpoint channel, then this can be inhibited using
BICO parameter P1110.
680 6NLS /LPLW 5)*
3
Motors can have one or several resonance points in the range from 0 Hz up to the reference
frequency. These resonance points result in oscillations which, under worst case conditions,
can damage the motor load. Using skip frequencies, SINAMICS G120 allows these resonant
frequencies to be passed through as quickly as possible. This means that the skip
frequencies increase the availability of the motor load over the long term.
Data
Description
The ramp-function generator (RFG) is used to limit the acceleration when the setpoint
changes according to a step function. This therefore helps to reduce the stressing on the
mechanical system of the machine. An acceleration ramp and a braking ramp can be set
independently of one another using the ramp-up time P1120 and the ramp-down time
P1121. This allows a controlled transition when the setpoint is changed (see figure below).
I
IPD[
:LWKRXWURXQGLQJ
I
I W
3 3
I
IPD[
I
I
3 3 3 3 W
:LWKURXQGLQJ
WXS WGRZQ
P1130+ P1131
IRU > P1120
2 P1130 + P1131 f 2 - f1 P1132 + P1133 f 2 - f1
t up = ( + P1120)⋅ t down = ( + P1121)⋅
DQG p1132 + P1133 2 P1082 2 P1082
> P1121
2
P1130+ P1131
IRU ≤ P1120
2 P1130+ P1131 f 2 - f1 P1132+ P1133 f 2 - f1
t up = + P1120⋅ t down = + P1121⋅
DQG P1132+ P1133 2 P1082 2 P1082
≤ P1121
2
3ಹ3!
I
6HWSRLQWUHDFKHG
IVHW
6HWSRLQWQRWUHDFKHG
3
I
6HWSRLQWUHDFKHG
IVHW
6HWSRLQWQRWUHDFKHG
3
In addition to the rounding-off times, the ramp-function generator can be influenced using
external signals. The ramp-function generator provides the following functionality using BICO
parameters P1140, P1141 and P1142 (see table below).
The ramp-function generator itself is enabled after the pulses have been enabled (inverter
enable) and after the excitation time has expired (P0346). After limiting to the maximum
speeds for the positive and negative directions of rotation (アP1082 or 0 Hz for the direction of
rotation inhibit) the setpoint speed for the control is obtained (r1170).
While the V/f characteristic operates up to 650 Hz, the control (vector mode) is limited to a
maximum frequency of 200 Hz (r1084).
Parameter Description
P1140 BI: RFG enable The ramp-function generator output is set to 0 if the binary signal
= 0.
P1141 BI: RFG start The ramp-function generator output keeps its actual value if the
binary signal = 0.
P1142 BI: RFG enable setpoint If the binary signal = 0, then the ramp-function generator input is
set to 0 and the output is reduced to 0 through the ramp-function
generator ramp.
Note
The maximum frequency of the setpoint channel is set using parameter P1080.
In V/f mode the maximum frequency is 650 Hz.
In vector mode the maximum frequency is 200 Hz (r1084).
Data
Description
The inverter and the user must respond to an extremely wide range of situations and stop
the inverter. In this case, both requirements relating to operations as well as the inverter
protective functions (for example, electrical and thermal overload) and man-machine
protective functions have to be taken into account. As a result of the different OFF/braking
functions (OFF1, OFF2, OFF3) the SINAMICS G120 can flexibly respond to the
requirements mentioned above.
OFF1
The OFF1 command is closely coupled to the ON command. When the ON command is
withdrawn, then OFF1 is directly activated. The motor is braked by OFF1 with the ramp-
down time P1121. If the output frequency falls below the parameter value P2167 and if the
time in P2168 has expired, then the inverter pulses are cancelled.
IDFW
3
IPD[
I 2))
3
W
3
WGRZQ2))
U%LW
3
2SHUDWLRQ
I
3XOVH WGRZQ2)) 3ವ
W 3
FDQFHOODWLRQ
Note
OFF1 can be entered using a wide range of command sources via BICO parameter P0840
(BI: ON/OFF1) and P0842 (BI: ON/OFF1 with reversing).
BICO parameter P0840 is pre-assigned by defining the command source using P0700.
The ON and the following OFF1 command must have the same source.
If the ON/OFF1 command is set for more than one digital input, then only the digital input
that was last set, is valid, e.g. DI3 is active.
OFF1 is low active.
When simultaneously selecting the various OFF commands, the following priority applies:
• OFF2 (highest priority)
• OFF3
• OFF1.
OFF1 can be combined with DC current braking or compound braking.
When the motor holding brake MHB (P1215) is activated, for an OFF1, P2167 and P2168
are not taken into account.
OFF2
The inverter pulses are immediately cancelled by the OFF2 command. This means that the
motor coasts down and it is not possible to brake in a controlled fashion.
IDFW
3
IPD[ 2))
W
U%LW
2SHUDWLRQ
3XOVH W
FDQFHOODWLRQ
Note
The OFF2 command can have one or several sources. The command sources are defined
using BICO parameters P0844 (BI: 1. OFF2) and P0845 (BI: 2. OFF2).
As a result of the pre-assignment (default setting), the OFF2 command is set to the OP. This
source is still available even if another command source is defined (e.g. terminal as
command source → P0700 = 2 and OFF2 is selected using DI2 → P0702 = 3).
OFF2 is low-active.
When simultaneously selecting the various OFF commands, the following priority applies:
• OFF2 (highest priority)
• OFF3
• OFF1.
OFF3
The braking characteristics of OFF3 are identical with those of OFF1 with the exception of
the autonomous OFF3 ramp-down time P1135. If the output frequency falls below parameter
value P2167 and if the time in P2168 has expired, then the inverter pulses are cancelled as
for the OFF1 command.
IDFW
3
IPD[
I 2))
3
W
3
WGRZQ2))
U%LW
3
2SHUDWLRQ
I
3XOVH WGRZQ2)) 3ವ
W 3
FDQFHOODWLRQ
Note
OFF3 can be entered using a wide range of command sources via BICO parameters P0848
(BI: 1. OFF3) and P0849 (BI: 2. OFF3).
OFF3 is low active.
When simultaneously selecting the various OFF commands, the following priority applies:
• OFF2 (highest priority)
• OFF3
• OFF1.
Data
Description
It is necessary to change-over from the automatic mode into the manual mode to load and
unload production machines and to feed new materials (e.g. batch processing). The machine
operator carries-out the preparatory activities for subsequent automatic operation in the
manual mode. In the manual mode, the machine operator locally controls the machine
(enters the ON/OFF command as well as also the setpoint). A changeover is only made into
the automatic mode after the set-up has been completed. In the automatic mode, the control
(open-loop) of the machines and production processes are handled by a higher-level control
system (e.g. PLC). This operation is maintained until it is necessary to again load and unload
the machine or feed new material into the machine or production process.
In the SINAMICS G120, indexed parameters P0700 or P1000 and BICO parameters P0810
and P0811 are used to changeover (toggle between) the manual/automatic modes. The
command source is defined using P0700 and the setpoint source is defined using P1000,
whereby index 0 (P0700[0] and P1000[0]) defines the automatic mode and index 1 (P0700[1]
and P1000[1]) the manual mode. BICO parameters P0810 and P0811 are used to
changeover (toggle between) the automatic and manual modes. These BICO parameters
can be controlled from any control source. In so doing, in addition to P0700 and P1000, also
all of the other CDS parameters are changed over (manual/automatic changeover is
generalized as a CDS changeover).
3
3
3>@
&RPPDQGVRXUFH
&PG
UHPRWH
7HUPLQDOV
3
3>@ 6HWSRLQW
023
UHPRWH
3
6HWSRLQW 0RWRU
3>@ 6HWSRLQW FRQWURO
$, FKDQQHO
ORFDO
)) 6HWSRLQW
&'6
Figure 8-48 Changing-over using the BICO parameters P0810 and P0811
Data
Description
For many applications, interlocking logic is required in order to control (open-loop) the
inverter. This interlocking logic couples several states (e.g. access control, plant/system
state) to form a control signal (e.g. ON command). Previously this was implemented using
either a PLC or relays. This represented additional costs for the plant or system. In addition
to logic operations, increasingly, arithmetic operations and storage elements are required in
inverters which generate a new unit from several physical quantities. This simplified PLC
functionality is integrated in the SINAMICS G120 using the freely programmable function
blocks (FFB).
The table below shows the function blocks that are integrated in the SINAMICS G120
inverter:
A B C
P2810
A 0 0 0
C
Index0
Index1
B & r2811 0
1
1
0
0
0
1 1 1
3 OR OR 1
P2800 P2801[3]
A B C
P2816
0 0 0
A C
Index0
Index1
B 1 r2817 0
1
1
0
1
1
1 1 1
3 XOR XOR 1
P2800 P2801[6]
A B C
P2822
0 0 0
Index0 A C
Index1
B =1 r2823 0
1
1
0
1
1
1 1 0
3 NOT NOT 1
P2800 P2801[9]
P2828
A C A C
Index0
1 r2829
0 1
1 0
P2834
SET (Q=1)
Index0
Index1 D Q r2835
Index2
Index3
STORE
Q r2836
RESET (Q=0)
POWER ON
1
SET RESET D STORE Q Q
1 0 x x 1 0
0 1 x x 0 1
1 1 x x Qn-1 Q n-1
0 0 1 1 0
0 0 0 0 1
POWER-ON 0 1
3 RS-FlipFlops RS-FlipFlop 1
P2800 P2801[14]
P2840
SET
Index 0 (Q=1) Q r2841
Index 1
POWER ON 1 RESET
(Q=0) Q r2842
SET RESET Q Q
0 0 Q n-1 Qn-1
0 1 0 1
1 0 1 0
1 1 Q n-1 Qn-1
POWER-ON 0 1
4 Timer Timer 1
P2850 (0.000) P2851(0)
P2800 P2802.0 Delay Time Mode
ON Delay
T 0/10
0
OFF Delay
1/11
0 T
P2849 In
Index0
Out r2852
ON/OFF Delay
2/12
T T NOut
Pulse Generator
1 r2853
T 3/13
2 ADD ADD 1
P2800 P2802[4]
P2869
x1 200%
Index 0 Result r2870
Index 1 x2
-200 %
x1 + x2
Result = x1 + x2
If: x1 + x2 > 200% → Result = 200%
x1 + x2 < -200%→ Result = -200%
P2873
x1 200%
Index 0 Result r2874
Index 1 x2
-200 %
x1 + x2
Result = x1 - x2
If: x1 - x2 > 200% → Result = 200%
x1 - x2 < -200% → Result = -200%
2 MUL MUL 1
P2800 P2802[8]
P2877
x1 200%
Index 0 Result
x2 r2878
Index 1
-200 %
x1 ∗ x 2
x1∗ x2
100% Result =
100%
x1∗ x 2
If: > 200% → Result = 200%
100%
x1∗ x 2
< -200%→ Result = -200%
100%
2 DIV DIV 1
P2800 P2802[10]
P2881
x1 200%
Index 0 Result
x2 r2882
Index 1
-200 %
x1 ∗ 100%
X2 x1∗ 100%
Result =
x2
x1∗ 100%
If: > 200% → Result = 200%
x2
x1∗ 100%
< -200% → Result = -200%
x2
2 CMP CMP 1
P2800 P2802[12]
P2885
Index 0 x1
Out
CMP r2886
Index 1 x2
Out = x1 ≥ x2
x1 ≥ x2 → Out = 1
x1 < x2 → Out = 0
Connector Setting in %
2 FFB setpoints P2889
(connector P2890
settings) Range : -200% ... 200%
3ULRULW\
/RZ +LJK
/HYHO
3ULRULW\
/HYHO
/HYHO
,QDFWLYH
3>@56))
3>@56))
3>@56))
/RZ
3>@7LPHU
3>@7LPHU
3>@7LPHU
3>@7LPHU
3>@'))
3>@'))
3>@&03
3>@&03
3>@127
3>@127
3>@127
3>@;25
3>@;25
3>@;25
3>@08/
3>@08/
3>@$''
3>@$''
3>@$1'
3>@$1'
3>@$1'
3>@68%
3>@68%
3>@',9
3>@',9
3>@25
3>@25
3>@25
Example 1
Example 2
Warning
Dimensioning the electro-mechanical motor brake
The electro-mechanical brake must be dimensioned that, in case of a fault, the complete
motor can be braked to zero from any possible operational speed. If no electro-mechanical
brake is present, the machine manufacturer must adopt other suitable measures to protect
against motion after the energy supply to the motor has been cut (for example, to protect
against sagging loads).
The electro-mechanical brake can be used as motor holding brake or as an instant brake.
● As motor holding brake it is used to prevent the motor from unintented rotation (e.g. lifting
or lowering the load in lifting applications) by applying torque in order to compensate
brake release times. The motor holding brake functionality is triggered by an OFF1 or
OFF3 command. For details see section motor holding brake.
● As an instant brake it slows down the motor from any speed down to zero speed as fast
as possible. The related brake release times are not considered in the case. The instant
brake function is triggered by an OFF2 command. The OFF2 command can be given
manually or triggered automatically by an internal fault condition on the inverter. On Fail-
safe inverters this braking function can also be triggered by the Safe Torque Off (STO)
command or the LSTO fault condition. (reference to the Chapter "Functions", Section
"Safe Brake Control
To keep the electro-mechanical brake open, it must be energised. When power is lost, or
removed from the brake, the brake closes and the motor shaft is held in position.
Note
If an electro-mechanical brake is attached, parameter P1215 needs to be enabled, otherwise
it will not be possible to run the motor!
Overview
There are two types of brake control relays:
● Brake Module (Relay Brake Module)
● Safe Brake Module (Safe Brake Module)
The Safe Brake Module and the Brake Module are different variants of the same device (for
details see option description "Brake Module Instructions".
Connections of Brake Module and Safe Brake Relay:
)O\LQJOHDGWR3RZHU0RGXOH
&RQQHFWLRQWREUDNHFRLO
*URXQG(DUWK LQVLGHWKHPRWRU
to
Power Module
PE
Brake Module
To Power
Module (A/B) &75/ M
5(/$<
3~
'&9
$&9
)O\LQJOHDGWR3RZHU0RGXOH
&RQQHFWLRQWR
&RQQHFWLRQWREUDNHFRLO H[WHUQDO9VXSSO\
LQVLGHWKHPRWRU
to
Power Module
To Power PE
Module (A/B) &75/ Safe
Brake %5
M
H[W'&
9 0 Module %5
3~
0
With the Safe Brake Module 24 V motor brakes up to a current consumption of 2 A can be
operated. Necessary is an external controlled power supply for 2.5 A and an output voltage
which can be adjusted at a voltage of 26 V, e.g. SITOP modular. The higher voltage is
required to compensate the voltage drop across the cables to the coil of the brake.
Note
On fail-safe reasons it is not allowed to take the 24 V supply of the Control Unit.
The power supply for the Safe Brake Module must be a separate additional power supply.
During power ON for the drive it is necessary to supply the Safe Brake Module first, so that
the Control Unit is able to check its function, otherwise the fault F1601 will occur.
The Safe Brake Module is designed to reaction to a stepped voltage input, which allows the
braking mechanism to be tested. The Brake Module does not have this functionality.
Note
During forced dynamisation all connections of the Safe Brake Module are checked but in
operation the connection between Safe Brake Module and brake coil is not monitored.
Triggering the Brake Control with Contol Units with fail-safe functions
Prerequisite: P1215 = 1
Warning
The brake can be triggered via both, a Brake Module and a Safe Brake Relay.
Triggering via a Brake Module is not fail-safe!
For a fail-safe triggering of a Safe Brake Module the following parameters must be set:
P9602 = P9802 = 1 (factory setting is 0). If P9602 ≠ P9802 a fault will be generated.
In case of P9602 = P9802 = 1 a test signal regarding the signal to the Safe Brake Control is
generated and monitored.
This test signal does not interfere with the normal function of the mechanical brake. If the
mechanical brake is fitted and the test fails, a fault condition will be indicated by the inverter.
If the Safe Brake Control is deactivated by setting P9602 = P9802 = 0 the Safe Brake
Module will still work as intendet but will not be monitored in a safe way.
Data
Description
For motors which must be secured when powered-down to prevent undesirable movement,
the SINAMICS G120 brake sequence control (enabled through P1215) can be used to
control the motor holding brake.
Before opening the brake, the pulse inhibit must be removed and a current impressed which
keeps the motor in that particular position. In this case, the impressed current is defined by
the min. frequency P1080. A typical value in this case is the rated motor slip r0330. In order
to protect the motor holding brake from continuous damage, the motor may only continue to
move after the brake has been released (brake release times are between 35 ms and
500 ms). This delay must be taken into account in parameter P1216 "Holding brake release
delay" (see figure below).
212))2))
21
2))2)) W
0RWRUH[FLWDWLRQ
ILQLVKHG
U%LW W
3
I
IPLQ
3
W
3 3
U%LW
W
%UDNH 2SHQ
6WDWXV
&ORVHG W
%UDNH5HOHDVH7LPH %UDNH&ORVLQJ7LPH
The motor holding brake is either closed using OFF1 or OFF3. When the minimum
frequency P1080 is reached, the motor is operated at this frequency until the brake has been
applied (closing times of brakes are between 15 ms and 300 ms). The actual time is
specified using parameter P1217 "Holding time after ramp down" (see figure above). If, on
the other hand, an OFF2 command has been output, then independent of the motor state,
the status signal r0052 bit 12 "Brake active" is reset. This means that the brake immediately
closes after OFF2 (instant brake).
The mechanical brake is controlled using the status signal r0052 bit 12 "Brake active" of the
brake control. This signal is connected to terminal A and B of the power module.
Warning
It is not sufficient to select the status signal r0052 bit 12 "Brake active" in P0731 … P0733. In
order to activate the motor holding brake, in addition, parameter P1215 must also be set to
1.
If SINAMICS G120 controls the motor holding brake, then a series commissioning may not
be carried-out for potentially hazardous loads (e.g. suspended loads for crane applications)
unless the load has been secured. Potentially hazardous loads can be secured as follows
before series commissioning is started:
• Lower the load to the floor, or
• Clamp the load using the motor holding brake
(Caution: During the series commissioning, SINAMICS G120 must be prevented from
controlling the motor holding brake).
Note
Motors have optional holding brakes which are not designed to be used as brakes for normal
operation. The holding brakes are only designed for a limited number of emergency braking
operations / motor revolutions with the brake closed (refer to the Catalog data).
When commissioning a motor with integrated holding brake it is therefore absolutely
imperative that it is ensured that the holding brake functions perfectly. A "clicking noise" in
the motor indicates that the brake has been correctly released.
Before the motor holding brake is applied, a torque must be established that maintains the
motor at the required position. The pulses, from the inverter, must be enabled to allow the
necessary torque to be generated. The torque is defined by the minimum frequency in
parameter P1080. A typical value for this is the rated motor slip r0330. Additionally, this
torque can be modified using the following parameters:
● V/f control – boost parameter P1310
● SLVC – boost parameters P1610 and P1611
● VC – supplementary torque setpoint P1511
The motor holding brake can be permanently damaged, if the motor shaft is moved when the
motor holding brake is applied. It is imperative that the release of the motor holding brake is
timed correctly.
Data
Description
An instant brake is an electro-mechanical brake which has to brake down the motor from any
speed down to zero speed. The instant brake function is activated after an OFF2 command
and additional in the case of a fail-safe application after a Safe Torque Off (STO) or a LSTO
fault condition (refer to Chapter "Functions", Section "Safe Brake Control").
The behavior of the instant brake function is described below.
212))
Inactive
OFF2
Active t
Motor excitation
finished
U%LW t
P0346
U%LW
1
0 t
%UDNH Open
6WDWXV Closed t
Brake Release Time Brake Closing Time
Warning
Dimensioning the electro-mechanical motor brake
The electro-mechanical brake must be dimensioned that, in case of a fault, the complete
motor can be braked to zero from any possible operational speed.
Overview
The SINAMICS G120 inverter has three electronic braking technologies:
● DC braking
● Compound braking
● Dynamic braking
These brakes can actively brake the motor and avoid a possible DC link overvoltage
condition. The figure below shows the inter-dependency of the electronic braking functions.
QR &RPSRXQG QR '\QDPLF QR
'&EUDNLQJ
EUDNLQJ EUDNLQJ
3!
3! 3!
"
" "
8.15.2.1 DC braking
Data
Description
The motor decelerates along a parameterized braking ramp if an OFF1 or OFF3 command is
output. A "flat" ramp must be selected so that the inverter is not tripped (shutdown) due to
the high regenerative energy which would cause a DC link overvoltage condition. The DC
brake should be activated while the OFF1 or OFF3 command is present if the motor is to be
braked faster. For DC braking, instead of continually reducing the output frequency/voltage
during the OFF1 or OFF3 phase, from a selectable frequency, a DC voltage/current is input
(refer to sequence 1).
The motor can be brought to a standstill in the shortest time using DC current braking (DC
brake). DC braking is selected as follows:
Sequence 1
1. Enabled using P1233
2. DC braking is activated with the OFF1 or OFF3 command (see figure below)
3. The inverter frequency is ramped down along the parameterized OFF1 or OFF3 ramp
down to the frequency at which DC braking is to start - P1234. This means that the kinetic
energy of the motor can be reduced without endangering the inverter. However, if the
ramp-down time is too short, there is a danger that a fault will be output as a result of an
overvoltage condition in DC link - F0002.
4. The inverter pulses are inhibited for the duration of the de-magnetizing time P0347.
5. The required braking current P1232 is then impressed for the selected braking time
P1233. The status is displayed using signal r0053 bit 00.
The inverter pulses are inhibited after the braking time has expired.
21
2))2)) W
3
2))
W
_I_
2))
3
'&EUDNLQJ
W
'&EUDNLQJDFWLYH
U
%LW W
3
Sequence 2
1. Enabled and selected using BICO parameter P1230 (see figure below).
2. The inverter pulses are inhibited for the duration of the de-magnetizing time P0347.
3. The requested braking current P1232 is impressed as long as DC braking is enabled
(P1230 = 1) and the motor is braked. This state is displayed using signal r0053 bit 00.
4. After DC braking has been cancelled, the motor accelerates back to the setpoint
frequency until the motor speed matches the inverter output frequency. If there is no
match, then there is danger that a fault will be output as a result of overcurrent - F0001.
This can be avoided by activating the flying restart function.
5. If any fault occurs during P1230 = 1 the DC current is set to zero. The motor doesn't ramp
up even the fault is acknowledged. A new ON command is necessary.
6. If the DC brake is enabled again, the braking current P1232 is impressed as long as
P1230 = 1.
2
21
$FNQRZOHGJH W
)DXOWVWDWH
W
%,(QDEOH'&%UDNH
.
3&
I W
IBVHW
I
'&EUDNLQJ '&EUDNLQJ
IBDFW
W
L 3 3
W
'&EUDNLQJDFWLYH
U
%LW
W
1RWH'&EUDNHFDQEHDSSOLHGLQGULYHVWDWHVU RU
Note
1. The "DC braking" function is only practical for induction motors!
2. DC braking is not suitable to hold suspended loads!
3. For DC current braking, the motor kinetic energy is converted into thermal energy in
the motor. If braking lasts too long, then the motor can overheat!
4. While DC braking, there is no other way of influencing the motor speed using an
external control. When parameterizing and setting the motor system, then as far as
possible, it should be tested using real loads!
Data
Description
For compound braking (this is enabled using P1236) DC braking is superimposed with
regenerative braking (where the motor regenerates into the line supply as it brakes along a
ramp). If the DC link voltage exceeds the compound switch-in threshold VDC-Comp (see
figure below), then a DC current is impressed as a function of P1236. In this case, braking is
possible with a controlled (closed-loop) motor frequency and minimum regenerative
feedback. Effective braking is obtained without having to use additional components by
optimizing the ramp-down time (P1121 for OFF1 or when braking from f1 to f2, P1135 for
OFF3) and using compound braking P1236.
3 3!
:LWKRXW&RPSRXQGEUDNLQJ :LWK&RPSRXQGEUDNLQJ
_I_ _I_
IBVHW IBVHW
IBDFW IBDFW
W W
L L
W W
9'&OLQN 9'&OLQN
9'&&RPS
W W
Warning
For compound braking, regenerative braking is superimposed on the DC braking (braking
along a ramp). This means that components of the kinetic energy of the motor and motor
load are converted into thermal energy in the motor. If this power loss is too high or if the
braking operation takes too long, then this can cause the motor to overheat!
Note
Only active in conjunction with V/f control.
Compound braking is deactivated, if:
• flying restart is active,
• DC braking is active, and
• Vector control is selected.
The compound switch-in threshold VDC-Comp is dependent on P1254:
VDC-Comp(P1254 = 0) ≠ VDC-Comp(P1254 ≠ 0)
Data
Description
For several motor applications, in certain operating states, the motor can regenerate.
Examples of these applications include:
● Cranes
● Traction motors
● Conveyor belts which transport loads downwards.
When the motor is in the regenerative mode, the energy from the motor is fed back into the
DC link of the motor through the inverter. This means that the DC link voltage increases and
when the maximum threshold is reached, the inverter is shutdown (tripped) with fault F0002.
This shutdown (trip) can be avoided by using dynamic braking. Contrary to DC and
compound braking, this technique requires that an external braking resistor is installed.
The advantages of dynamic resistor braking include:
● The regenerative energy is not converted into heat in the motor.
● It is significantly more dynamic and can be used in all operating states (not only when an
OFF command is output).
&KRSSHUUHVLVWRU
* '&35 5
&KRSSHU
a FRQWURO
a a
The braking energy in the DC link is converted into heat when dynamic braking is activated
(enabled using P1237). The energy is converted into heat using the voltage-controlled
chopper resistor (ballast resistor). When regenerative energy is fed back to the DC link and
in consequence the DC link threshold VDC, Chopper is exceeded, then the chopper resistor is
switched in using an electronic semiconductor switch.
Switch-in threshold of the chopper resistor:
If P1254 = 0: VDC, Chopper = 1.13 ⋅ 2 ⋅ Vline supply = 1.13 ⋅ 2 ⋅ P0210
Otherwise: VDC, Chopper = 0.98 ⋅ r1242
The chopper switch-in threshold VDC chopper is calculated as a function of parameter P1254
(Auto detect VDC switch-on levels), either directly using the line supply voltage P0210 or
indirectly using the DC link voltage and r1242.
9'&DFW
[
[ W&KRSSHU21 yW&KRSSHU
ದ ෙ9 9
9'&&KRSSHU
3
'XW\F\FOH $ODUP
PRQLWRULQJ $
0DLQV
9 9 9
ෙ9 9 9 9
The regenerative (braking) energy is converted into thermal energy using the chopper
resistor. A braking module (chopper control) is integrated in the DC link for this purpose. The
chopper of the braking module switches the resistor with a mark-space ratio corresponding
to the regenerative power to be dissipated. The braking module is only active if, as a result of
the regenerative operation, the DC link voltage lies above the chopper switch-in threshold
VDC chopper. This means that the braking module is not active in normal operation when
motoring.
The chopper resistor is only designed for a specific power and a certain load duty cycle and
can only absorb a limited amount of braking energy within a specific time period. The
chopper resistors, specified in SINAMICS G120 Catalog, have the following load duty cycle
as shown in the figure below.
3RZHU
3
3'%
W>V@
3'% FRQWLQXRXVSRZHU
3 y3'% SHUPLVVDEOHSRZHUIRUVHYHU\V
This load duty cycle is saved in the SINAMICS G120 inverter for P1237 = 1 (→ 5 %). If the
values are exceeded due to the load required, then when the maximum acceptable braking
energy is reached, the load duty cycle monitoring controls the chopper so that the value is
reduced to the value entered in parameter P1237. This means that the energy to be
dissipated in the chopper resistor is reduced, which means that the DC link voltage quickly
increases due to the regenerative energy available and the inverter is shutdown (tripped)
due to a DC link overvoltage condition.
If the continuous power or the load duty cycle for a resistor is too high, then the continuous
rating can be quadrupled using four resistors in a bridge circuit configuration (see figure
below). In this case, in addition, the load duty cycle must be increased using parameter
P1237 from P1237 = 1 (→ 5 %) to P1237 = 3 (→ 20 %). When using the bridge circuit, the
overtemperature switch of the resistors should be connected in series and incorporated in
the fault circuit. This guarantees, that when a resistor overheats, the complete
system/inverter is shut down.
5 5
5 5 5
'&35 5 '&35 5
&KRSSHU &KRSSHU
FRQWURO FRQWURO
3 3
Figure 8-63 Increasing the level of braking energy which can be absorbed
The continuous power and the load duty cycle are modified using parameter P1237. If the
load duty cycle monitoring switches from the peak power (100 %) to the continuous power,
then this is dissipated for an unlimited length of time in the braking resistor. Contrary to the
braking resistor, as listed in the Catalog, the chopper control can be permanently operated
with 100 % power.
D
3 W21 W2)) WF\FOH 3'%
3
E
3
3'%
W
W
W3 W2))
For SINAMICS G120, the braking module is integrated in the inverter and the braking
resistor can be connected using the external terminals DCP/R1 and R2 (for more details
refer to Operating Instructions of the corresponding Power Module). Where the DCP/R1 is
the positive terminal for the braking resistor and R2 is the negative terminal for the braking
resistor.
Warning
Braking resistors, which are to be mounted on SINAMICS G120, must be designed so that
they can tolerate the power dissipated.
If an unsuitable braking resistor is used there is a danger of fire and that the associated
inverter will be significantly damaged.
The chopper control, integrated in the inverter is designed for the braking resistor value
assigned in Catalog; e.g.:
• Power Module PM240 6SL3224-0BE24-0AA0
• brake resistor 6SL3201-0BE12-0AA0
• brake resistor value 160 Ω
A brake resistor with a lower resistance value will destroy the inverter. In this case, an
external braking unit must be used.
When operational, the temperature of braking resistors increases – do not touch! Ensure that
there is sufficient clearance around the unit and there is adequate ventilation.
A temperature protection switch must be used to protect the units against overheating.
Note
The switch-on threshold VDC chopper of the dynamic resistor braking is dependent on P1254
VDC chopper(P1254 = 0) ≠ VDC chopper(P1254 ≠ 0).
External braking modules (chopper units) including braking resistor can be used with all of
the sizes of inverters. When engineering the system, the particular braking module/resistor
must be taken into consideration.
Data
Description
For certain drive applications, the motor can operate as a generator in specific operating
states. Typical examples of these types of applications include:
● Cranes
● Traversing drives
● Conveyor belts where the material is being transported downwards
For regenerative motor operation, the motor energy is fed back into the mains supply via the
inverter and the mains-commutated rectifier of the inverter. The advantages of regenerative
braking include:
● The kinetic energy is not converted into heat in the motor
● The kinetic energy does not have to be converted into heat in an external resistor
● It has a significantly higher dynamic response and can be used in all operating states (not
only for an OFF command)
● It allows precise braking along a down ramp
● Continuous regenerative operation is possible - e.g. for cranes
● Only a low level of harmonics are injected back into the mains supply for regenerative
braking
Note
If regenerative feedback into the line supply is required at the rated frequency the
maximum frequency (p1082) must be greater than the rated motor frequency (p0310).
Caution
If the power fed back into the mains supply exceeds the rated power of the inverter, the
inverter will trip with F0028.
Data
Description
After a power failure (F0003 "Undervoltage"), the "Automatic restart" function, enabled using
P1210, will on next power up automatically acknowledge any faults and start the inverter
again.
The automatic restart function will only take place if a RUN command was present prior to
the power failure. For automatic restart to be performed a RUN command must be present
on power up and must also have been present prior to power failure.
When it comes to power failures (line supply failure), then a differentiation is made between
the following conditions:
Caution
*) Automatic restart with external 24 V supply
If the Control Unit is powered by an external 24 V supply and the mains line supply fails, the
Power Module will lose power, but the Control Unit will remain active. If this situation occurs
then the Control Unit will not perform an automatic restart. This situation could result in the
inverter being in an undetermined state and may not react as predicted.
Source command for automatic restart
The automatic restart function has been designed to ignore command source time-outs. That
is, if the command sources is, for example, a PLC or through USS communications and the
PLC or USS times-out an automatic restart will not be initiated.
The number of start attempts is specified using parameter P1211. The number is internally
decremented after each unsuccessful attempt. After all attempts have been made (as
specified in parameter P1211), automatic restart is cancelled with the message F0035. After
a successful start attempt, the counter is again reset to the initial value.
Danger
For longer line supply failures (blackouts) and when the automatic restart function is
activated, over a longer period of time it may be assumed that SINAMICS G120 is powered-
down. However, when the line supply returns, inverters can automatically start to run again
without any operator intervention.
If the operating range of the motor is entered in this status, this can result in death, severe
injury or material damage.
Note
In addition the "Flying restart" function must be activated if, for an automatic restart, the
inverter is to be connected to a motor which may already be spinning.
Data
Description
The "Flying restart" function (this is enabled using P1200) allows the inverter to be switched
to a motor which is still spinning. If the inverter was to be powered-up without using the flying
restart function, there would be a high possibility that a fault with overcurrent F0001 would
occur. The reason for this is that the flux must first be established in the motor and the V/f
control or closed-loop Vector control must be set corresponding to the actual motor speed.
The inverter frequency is synchronized with the motor frequency using the flying restart
function.
When the inverter is normally powered-up it is assumed that the motor is stationary and the
inverter accelerates the motor from a standstill and the speed is ramped-up to the setpoint
which has been entered. However, in many cases this condition is not fulfilled. A fan motor is
a typical example. When the inverter is powered-down the air flowing through the fan can
cause it to rotate in any direction.
I
IVHDUFKPD[ 6HWSRLQWIUHTXHQF\
W
'HPDJQHWL]DWLRQ )O\LQJUHVWDUW 0DJQHWL]DWLRQ 5DPSXS
WLPH 3 WLPH
3 3 3
Warning
When "Flying restart" is activated (P1200 > 0), although the motor is at a standstill and the
setpoint is 0, it is possible that the motor can be accelerated as a result of the search
current!
If the operating range of the motor is entered when the motor is in this state, this can result in
death, severe injury or material damage.
Note
If a higher value is entered for the search velocity P1203 this results in a flatter search curve
and therefore to an extended search time. A lower value has the opposite effect.
For "Flying restart", a braking torque is generated which can cause motors, with low
moments of inertia, to brake.
For group motors, "Flying restart" should not be activated due to the different characteristics
of the individual motors when coasting down.
Overview
Warning
Installation and protection level of Control Units in fail-safe systems
All installation areas for Control Units with fail-safe functions as well as outside installed
components of the according fail-safe system, if correctly installed, must comply with the
minimum protection level of IP54 [see EN 60529 (IEC 60529)].
Change of Control Units with fail-safe functions
When carrying out a swap of Control Units, it is not allowed to replace a Control Unit with
fail-safe functions with a Standard Control Unit. Replacing a Control Unit with fail-safe
functions with a Standard Control Unit disables all fail-safe functions that have been
implemented and therefore can lead to personal injury and damage to the machine. A
replacement of fail-safe components with standard components has to be considered as a
completely new application and re-commissioned as such.
Dimensioning of the Motor
If regenerative loads occur in the application, the motor must be dimensioned so that its slip
in super-synchronous operation always remains below the rated slip.
Dimensioning of the Motor holding brake
The motor holding brake must be dimensioned that in case of a fault the complete drive can
be braked to zero from any possible operational speed. If no holding brake is present, the
machine manufacturer must adopt other suitable measures of protection against motion after
the power to the motor has been cut (e.g. to protect against sagging loads).
Regenerative load with SLS
With the fail-safe functions "safely limited speed" (SLS) and "safe stop 1" (SS1) operation
with permanent regenerative loads is not permitted.
Note
In order to verify the parameters for the fail-safe functions, an acceptance test must always
be carried-out after commissioning, reset and also when changing a completely backed-up
data set of the parameters for the fail-safe functions. This acceptance test must be
appropriately logged and documented. For more details refer to Section "Acceptance Test
and Acceptance Log" In Chapter "Commissioning".
The Control Unit with fail-safe functions has specific fail-safe functions integrated into its
system. These are:
● Safe Torque Off (STO)
● Safe Stop 1 (SS1)
● Safely-Limited Speed (SLS)
● Safe Brake Control (SBC)
These functions are controlled using either the fail-safe digital inputs on the front of the CU,
PROFIsafe via PROFIBUS-DP interface located at the bottom of the CU. See figure below.
(QG 6DIH
5HDG\ 6WDWH 6WRS
)$,/6$)(',*,7$/,13876
5/ 5/ 5/ 5/ 5/ 5/ 5/ 5/ (1& (1& (1& (1& (1& (1&
1& 12 &20 12 &20 1& 12 &20 $3 $1 %3 %1 =3 =1
',1 ',1 ',1 ',1 ',1 ',1 )', )', )', )', (1&
8989
$ % $ % 6833/<
$'& $'& '$& '$& $'& $'& '$& '$& 9 9 9 9 37& 37&
,1 ,1
352),%86'3
,QWHUIDFH
Fail-safe functions are only available on the Control Units with fail-safe functions. On the
standard CUs, the fail-safe features are not available.
The parameters for the fail-safe functions are held on two separate processors within the
control unit. Each processor holds a unique copy of the parameterized fail-safe function.
These unique copies of the parameterized fail-safe function are accomplished by double-
parameters. Double-parameters have their own unique number, but have identical
functionality. Each processor controls two separate and isolated shutdown control
mechanisms which are continually monitored by the system to ensure they are operating
correctly. Should a discrepancy occur, then the Latched Safe Torque Off is activated.
Overview
There are three monitoring procedures:
● Time controlled request for forced dynamisation
● Forced dynamisation
● Process dynamisation
The dynamisation process is designed to detect software and hardware faults of the two
shutdown paths. The forced dynamisation consists of a processor self-test of both
processors within the Control Unit and a hardware test. The hardware test includes a test to
ensure, that if fitted, the Safe Brake Control is functioning correctly.
Note
In fail-safe applications it is necesarry that the forced dynamisation process takes place
during regular intervals. The minimum is once a year.
Forced dynamisation
The forced dynamisation process delays the switch-on process after a Safe Torque Off
(STO), but it ensures that all the fail-safe features of the inverter are functioning correctly.
However, should this delay after a STO be unacceptable for the user application, it can be
disabled by setting parameters P9601 = P9801 = 0.
The forced dynamisation process is automatically initiated by the following events:
● On power-up of the inverter.
● When the Latched Safe Torque Off (LSTO) function is deactivated.
● When the Safe Torque Off (STO) is left (if P9601 = P9801 = 2).
● When Safe Stop 1 (SS1) is left after STO was reached (if P9601 = P9801 = 2).
● When commissioning of fail-safe functions is left.
Note
When carrying-out the forced dynamisation, the shutdown paths of the motor brake are
also tested. This results a brief opening command (2 ms to 30 ms) in the motor brake.
The mechanical part of the brake generally requires longer than 30 ms to open. This
means that this dynamic operation generally has no influence on the motor shaft itself.
Process dynamisation
The process dynamisation will be performed after STO initialisation or SS1 end only if P9601
= P9801 = 2.
The testing includes both shutdown paths, but does not perform a processor self-test or a
test of the Safe Brake Control.
Warning
Dynamisation of the shutdown paths
For safety reasons, it is necessary to initiate a safe torque off as a test at intervals of
maximal 8760 hours (one year) in order to check its operability. Thus, 8760 hours after the
last activation of the safe torque off the converter sets a status bit that specifies this
requirement.
The process control must then initiate the safe torque off at the next opportunity, for
example, when the drive has in any case a short phase with zero speed. If the converter
returns the "safe torque off initiated" status signal, the torque off can be released again. The
setting and clearing of the status bit and the dynamisation must be logged as process data
by the higher-level control.
actual
frequency
LSTO limit
setpoint
frequency
envelope
envelope fault
delay reac-
Δtenvelope tion
time
Δtreact.
time W
Description
When parameterising the limiting envelope for SLS and SS1 with P9680/P9880 and
P9691/P9891 the following minimum tolerances should be considered to provide maximum
performance of the drive:
I
˂)
˂)VOLS
)PD[
˂)KLJK
˂)
)PD[ 3
)WRO3
˂)VOLS
˂)
P' 6/6
P' 66
˂)ORZ
˂)
The safe frequency envelope results from a time delay (p9680) in t-direction and an
additional frequency tolerance ∆F (caused by measurement inaccuracies) and ∆Fslip (caused
by slipcompensation) in F-direction.
I
actual shifted envelope
frequency
maximum application related
reachable frequency Fmax reached
LSTO limit
setpoint
frequency
envelope fault
delay reac-
Δtenvelope tion
time
Δtreact.
time W
The maximum envelope shift corresponds to the fault reaction time ∆t reactiontime
(maximum LSTOlimit) wich is given as:
) )
ෙWUHDFWLRQWLPH PD[UHDFK PD[
P
Data
Description
Safe Torque Off (STO) is the simplest fail-safe function and its purpose is to shutdown the
motor safely. Once the motor is at a standstill, STO then enables a switch-on lock which
prevents the inverter from starting the motor, unless the STO signal is removed. Shutting
down of the triggering pulses on the Power Module effectively stops the motor and should a
mechanical brake be connected, it will be closed immediately.
When the STO function is initiated the inverter performs the following actions:
1. The triggering pulses on the Power Module are disabled.
2. The mechanical brake (if connected) is closed immediately.
3. The status LED STO starts flashing.
4. The status LED ES is switched on, indicating the end-of-state has been reached.
When the STO signal is removed the inverter performs the following actions:
1. The process dynamisation is carried out (always).
2. The forced dynamisation procedure is carried out (if parameterised by p9601 and p9801).
3. The forced dynamisation timer (p9660) is reset to the value in p9659 (if the forced
dynamisation procedure was carried out successfully).
4. The mechanical brake is opened (if connected), if not closed by holding brake function
(P1215).
5. The status LED STO is switched on and ES is switched off.
6. The pulse-lock must be released by applying a rising edge signal (OFF1/ON).
These actions are shown in the figure below.
$FWXDO
IUHTXHQF\ )UHTXHQF\
VHWSRLQW
7LPH
U
6WDWXVZRUG
U
U
U
U
U
U
U
/('
6)
672
66
6/6
(6
The STO function has the highest priority and cannot be intercepted by any other function.
Note
The state of the fail-safe functions is announced by r9772.
Caution
Reaction time
The reaction time for a STO is 20 ms.
Fault reaction time
An internal failure during a STO will be detected within 20 ms and leads immediately to a
LSTO.
The overall reaction time is the sum of reaction time and fault reaction time.
'HDFWLYDWLRQ 6WDUWLQJGULYHYLD
/672 RI672 2))
DFWLYDWHG VHW2)) $FNQRZOHGJH
21
)UHTXHQF\
$FWXDO
IUHTXHQF\ )UHTXHQF\
VHWSRLQW
)DXOW
7LPH
U
6WDWXVZRUG
U
U
U
U
U
U
U
/('
6)
672
66
6/6
(6
Caution
After an STO or LSTO it is possible (but almost unlikely) that the field generating
components become faulty in a way that they will generate one single rising edge of a
rotating field causing the motor to jerk for a defined maximum electrical angle of 60 °.
The resulting rotating angle at the motor shaft is smaller than the maximum electrical
angle due to inertia and the number of pole pairs.
Note
A latched safe torque off is always initiated by a safety fault condition within the drive.
Therefore, the drive always performs a forced dynamisation procedure before it is
allowed to restart.
Data
Description
In contrast to STO, the actual speed of the motor has an influence on the behavior of the
SS1 (Safe Stop 1) function. When SS1 is initiated the speed of the motor is detected, if the
speed of the motor is lower than the minimum speed for standstill detection set in P9682 and
P9882, the STO function is initiated immediately to bring the motor to a standstill. If the
motor speed is higher than the minimum speed for standstill detection, then the motor is
slowed down using the safe braking-ramp time set in P9681 and P9881. See figure below.
)UHTXHQF\
$FWXDO
IUHTXHQF\
)UHTXHQF\
VHWSRLQW
6WDQGVWLOOGHWHFWLRQ
33
7LPH
U
6WDWXVZRUG
U
U
U
U
U
U
U
/('
6)
672
66
6/6
(6
When SS1 is activated, the following actions are performed by the inverter:
1. Both shutdown paths initiate a controlled safe brake ramp function, including detecting
the speed of the motor.
2. The motor is slowed down by the safe brake ramp function.
3. The status LED SS1 starts flashing.
4. When the minimum speed for standstill detection is reached, the STO function is
activated.
5. The mechanical brake (if fitted) is closed.
6. The status LED ES is switched on.
The SS1 function can be interrupted by either an OFF2 command or the STO function.
When SS1 is deactivated before the "minimum speed for standstill detection" (P9682/P9882)
is reached, the following actions are performed by the inverter:
1. The monitoring of the actual speed is deactivated.
2. The drive accelerates to the set speed
3. The status LED SS1 changes from flashing to on state.
When SS1 is deactivated after the "minimum speed for standstill detection" (P9682/P9882)
is reached, the following actions are performed by the inverter:
1. STO is deactivated.
2. The forced dynamisation procedure is carried out (if parameterised by p9601 and p9801).
3. The forced dynamisation timer (p9660) is reset to the value in p9659 (if the forced
dynamisation procedure was carried out successfully).
4. The mechanical brake (if fitted) is opened, if not closed by holding brake function
(P1215).
5. The status LED SS1 changes from flashing to on state.
6. The status LED ES is switched off.
Note
The state of the fail-safe functions is announced by r9772.
Note
The fail-safe function SS1 should not be activated during following processes are active:
• Search process in flying restart
• Motor data identification
• Speed control optimisation
It is recommended not to use the torque contol (P1300 = 22, 23 or P1501 > 0) as a control
mode for the fail-safe function SS1.
Caution
Reaction time
The reaction time for a SS1 is 20 ms.
Fault reaction time
An internal failure during a SS1, which leads to a LSTO, will be detected within the time
specified in "Fault reaction time" of section "Limiting values for SS1 and SLS".
The overall reaction time is the sum of reaction time and fault reaction time.
Caution
The frequency setpoint can increase related to the following functions
• PID Trim
• Vdc max controller
• Slip compensation
• Resonance damping
• Imax
As the frequency is monitored after adding these values, this increasement should be taken
into account by the user when parameterising the safe frequency envelope.
)UHTXHQF\
PRQLWRULQJ
)UHTXHQF\
)UHTXHQF\
VHWSRLQWWR
VHWSRLQW
+ + + - + 3RZHU
IURP5)*
VWDFN$6,&
3,'DVWULP
3 3 3 ,PD[
9GFPD[ 6OLS 5HVRQDQFH
FRQWUROOHU FRPSHQVDWLRQ GDPSLQJ
*) If PID as trim is active when SS1, SLS0 or SLS1 is triggered, the PID as trim is
deactivated and has no influence to the frequency setpoint at the latest 1 s after the fail-safe
function has been activated.
Data
Description
The purpose of the Safely-Limited Speed (SLS) function is to monitor the speed of the motor
to ensure that it does not exceed the upper SLS limit set by parameters P9691 and P9891.
Should the upper SLS limit be exceeded a braking process will be initiated which is
monitored using the safe braking ramp function. If a stationary state is detected, the Safe
Torque Off (STO) will be initiated to bring the motor to a safe standstill. If the braking
functions fails, which is detected as a fault, then the Latched Safe Torque Off (LSTO)
function is initiated and cannot be cleared without explicitly acknowledgment of the fault.
The SLS function can be intercepted by the following commands:
● Safe Torque Off (STO)
● OFF1 (only SLS Mode 2)
● OFF2
● OFF3 (only SLS Mode 2)
However, the reaction of the system to the standard OFF commands may produce
unpredictable results. If the standard OFF commands are to be used with the fail-safe
functions, the interaction of the commands on the system are automatically monitored in the
background by the fail-safe system (i.e. the commands, which are not fail-safe, cannot cause
the inverter to accelerate in an unsafe way as the LSTO function will be triggered
automatically).
Note
The fail-safe function SLS should not be activated during following processes are active:
• Search process in flying restart
• Motor data identification
• Speed control optimisation
It is recommended not to use the torque contol (P1300 = 22, 23 or P1501 > 0) as a control
mode for the fail-safe function SLS.
Caution
Reaction time
The reaction time for a SLS is 20 ms.
Fault reaction time
An internal failure during a SLS, which leads to an LSTO, will be detected within the time
specified in "Fault reaction time" of section "Limiting values for SS1 and SLS".
The overall reaction time is the sum of reaction time and fault reaction time.
Modes of behavior
The SLS function has three modes of behavior giving the user a choice of functionality to suit
their specific application. These modes of behavior of the SLS function are controlled by
setting the required values in parameters P9692 and P9892.
Caution
Due to monitoring reasons, the so called "accuracy limit for SLS" with a value of 1 Hz is set.
If - in SLS mode - the actual frequency under-runs this value, an STO is triggered.
Warning
If due to dynamic loads the frequency runs above the SLS limit (P9691/P9891) an LSTO is
triggered; if it falls below the accuracy limit an STO is triggered. Therefore when designing
the plant, dynamic load changes must be taken into account to prevent unintented activation
of fail-safe functions.
Furthermore the acceptance test should be performed under worst-case load conditions.
SLS Mode 0
P9692 = P9892 = 0
If, after initiation of SLS, the motor exceeds the upper SLS limit set with P9691 and P9891,
then the latched STO (LSTO) function is initiated to bring the motor to a standstill.
If the motor speed is below the upper SLS limit, all control signals that can affect the speed
of the motor are blocked. No external control of the motor speed is possible.
Once the motor is locked at its present speed, if the motor again falls below this speed (for
example additional load on the motor), it is not interpreted as a fault condition and no action
is taken. See the following table.
During SLS mode 0 is active the the fault reaction time for a STO is given according to the
5HDFWLRQWLPH PV
formular )DFW
Case 1: SLS monitoring (p9691/p9891) > Frequency setpoint > SLS setpoint
Initiation of SLS => • Ramp monitoring activated
• SLS-LED flashing
• ES-LED on
• Frequency setpoint deactivated
• Ramp down with SS1 to SLS setpoint
When SLS is reached => • SLS monitoring on
• Frequency setpoint inactive
Deactivation of SLS => • Ramp monitoring off
• Frequency setpoint activated
• SLS monitoring off
• SLS-LED and ES-LED off
$FWLYDWLRQ 6/6VHWSRLQW 'HDFWLYDWLRQ
RI6/6 UHDFKHG RI6/6
)UHTXHQF\
)UHTXHQF\
VHWSRLQW
6/6PRQLWRULQJ (QYHORSH
33 $FWXDO
IUHTXHQF\
66OHDGLQJWR6/6VHWSRLQW
6/6VHWSRLQW
33
6WDQGVWLOOGHWHFWLRQ
33
$FFXUDF\OLPLW
+]
7LPH
U
6WDWXVZRUG
U
U
U
U
U
U
U
/('
6)
672
66
6/6
(6
Case 2: SLS setpoint > Frequency setpoint > standstill detection (p9682/p9882)
Initiation of SLS => • Ramp monitoring activated
• SLS-LED flashing
• ES-LED on
• Frequency setpoint deactivated
When SLS is reached => • SLS monitoring on
• Frequency setpoint inactive
Deactivation of SLS => • Ramp monitoring off
• Frequency setpoint activated
• SLS monitoring off
• SLS-LED and ES-LED off
$FWLYDWLRQ 'HDFWLYDWLRQ
RI6/6 RI6/6
)UHTXHQF\
(QYHORSH
6/6PRQLWRULQJ
33 )UHTXHQF\
VHWSRLQW
6/6VHWSRLQW
33 $FWXDO
IUHTXHQF\
6WDQGVWLOOGHWHFWLRQ
33
$FFXUDF\OLPLW
+]
7LPH
U
6WDWXVZRUG
U
U
U
U
U
U
U
/('
6)
672
66
6/6
(6
Case 3: Standstill detection (p9682/p9882) > Frequency setpoint > accuracy limit
Initiation of SLS => • Ramp monitoring activated
• SLS-LED flashing
• ES-LED on
• Frequency setpoint deactivated
When SLS is reached => • SLS monitoring on
• Frequency setpoint inactive
Deactivation of SLS => • Ramp monitoring off
• Frequency setpoint activated
• SLS monitoring off
• SLS-LED and ES-LED off
$FWLYDWLRQ 'HDFWLYDWLRQ
RI6/6 RI6/6
)UHTXHQF\
(QYHORSH
6/6PRQLWRULQJ
33
6/6VHWSRLQW
33 )UHTXHQF\
VHWSRLQW
6WDQGVWLOOGHWHFWLRQ
33 $FWXDO
IUHTXHQF\
$FFXUDF\OLPLW
+]
7LPH
U
6WDWXVZRUG
U
U
U
U
U
U
U
/('
6)
672
66
6/6
(6
(QYHORSH
6/6PRQLWRULQJ
33 )UHTXHQF\
VHWSRLQW
6/6VHWSRLQW
33
$FWXDO
IUHTXHQF\
6WDQGVWLOOGHWHFWLRQ
33
$FFXUDF\OLPLW
+]
7LPH
U
6WDWXVZRUG
U
U
U
U
U
U
U
/('
6)
672
66
6/6
(6
(QYHORSH
6/6PRQLWRULQJ
33
6/6VHWSRLQW
33
6WDQGVWLOOGHWHFWLRQ
33 )UHTXHQF\
$FWXDO
VHWSRLQW
$FFXUDF\OLPLW
IUHTXHQF\
+]
7LPH
U
6WDWXVZRUG
U
U
U
U
U
U
U
/('
6)
672
66
6/6
(6
Case 5.1: Frequency setpoint > SLS monitoring (p9691/p9891) primary fault
Initiation of SLS => • Ramp monitoring activated
• SLS-LED flashing
• Frequency setpoint deactivated
• Ramp down with SS1 to standstill
detection
When standstill detection is • Frequency setpoint inactive
reached => • LSTO activated
Deactivation of SLS => • No action
• To start again, LSTO must be
acknowledged and a new on command is
necesarry to ramp up to frequency
setpoint.
6/6
$FWXDO $FWLYDWLRQ 6/6VHWSRLQW /672 'HDFWLYDWLRQ 6WDUWLQJGULYHYLD )UHTXHQF\
XSSHUOLPLW
IUHTXHQF\ RI6/6 UHDFKHG DFWLYDWHG RI6/6 2)) VHWSRLQW
UHDFKHG
DFNQRZOHGJH
)DXOW 21
)UHTXHQF\
(QYHORSH
6/6PRQLWRULQJ
33
66OHDGLQJWR/672
6/6VHWSRLQW
33
6WDQGVWLOOGHWHFWLRQ
33 /672
$FFXUDF\OLPLW
+]
7LPH
U
6WDWXVZRUG
U
U
U
U
U
U
U
/('
6)
672
66
6/6
(6
Case 5.2: Frequency setpoint > SLS monitoring (p9691/p9891) secondary fault
Initiation of SLS => • Ramp monitoring activated
• SLS-LED flashing
• Frequency setpoint deactivated
• Ramp down with SS1 to standstill
detection
When actual frequency runs • Frequency setpoint inactive
above SS1 ramp down • LSTO activated immediately
monitoring before standstill
detection is reached
Deactivation of SLS => • No action
• To start again, LSTO must be
acknowledged and a new on command is
necesarry to ramp up to frequency
setpoint.
6/6
$FWXDO $FWLYDWLRQ /672 'HDFWLYDWLRQ 6WDUWLQJGULYHYLD
XSSHUOLPLW
IUHTXHQF\ RI6/6 DFWLYDWHG RI6/6 2)) )UHTXHQF\
UHDFKHG
DFNQRZOHGJH VHWSRLQW
)DXOW 21
)UHTXHQF\
(QYHORSH
6/6PRQLWRULQJ
33 )DXOW
VHFRQGDU\
6/6VHWSRLQW
33
66OHDGLQJWR/672
6WDQGVWLOOGHWHFWLRQ
33 /672
$FFXUDF\OLPLW
+]
7LPH
U
6WDWXVZRUG
U
U
U
U
U
U
U
/('
6)
672
66
6/6
(6
Note
It must be observed that with detecting a fault during the fail-safe function SLS mode 0 is
active, first it will be tryed to brake the drive at the safe brake ramp.
The brake time is determined by parameters P9681/P9881. As the drive at this time is in a
fail-safe mode, it is not possible to interrupt the braking ramp by an other function (e.g. STO).
It is recommended to parameterise the shortest possible ramp time for the application.
SLS Mode 1
P9692 = P9892 = 1
In addition to the speed limit set in parameters P9691 and P9891, a further SLS setpoint can
be set in parameters P9690 and P9890. This additional SLS setpoint is used to set the
speed of the motor to a specific frequency, instead of bringing the motor to a standstill.
If the actual speed of the motor falls below the SLS setpoint set in P9690 and P9890, the
motor is allowed to run at that speed. See the following table.
Case 1: SLS monitoring (p9691/p9891) > Frequency setpoint > SLS setpoint
Initiation of SLS => • Ramp monitoring activated
• SLS-LED flashing
• Frequency setpoint deactivated
• Ramp down with SS1 to SLS setpoint
When SLS is reached => • SLS monitoring on
• ES-LED on
• Frequency setpoint inactive
Deactivation of SLS => • Ramp monitoring off
• SLS monitoring off
• SLS-LED and ES-LED off
• activate freq. setpoint and ramp to freq.
setpoint
$FWLYDWLRQ 6/6VHWSRLQW 'HDFWLYDWLRQ
RI6/6 UHDFKHG RI6/6
)UHTXHQF\
)UHTXHQF\
VHWSRLQW
6/6PRQLWRULQJ (QYHORSH
33 $FWXDO
IUHTXHQF\
66OHDGLQJWR6/6VVHWSRLQW
6/6VHWSRLQW
33
6WDQGVWLOOGHWHFWLRQ
33
$FFXUDF\OLPLW
+]
7LPH
U
6WDWXVZRUG
U
U
U
U
U
U
U
/('
6)
672
66
6/6
(6
Case 2: SLS setpoint > Frequency setpoint > standstill detection (p9682/p9882)
Initiation of SLS => • Ramp monitoring activated
• SLS-LED flashing
• Frequency setpoint deactivated
When SLS is reached => • SLS monitoring on
• ES-LED on
• Frequency setpoint inactive
Deactivation of SLS => • Ramp monitoring off
• SLS monitoring off
• SLS-LED and ES-LED off
• activate freq. setpoint and ramp to freq.
setpoint
$FWLYDWLRQ 'HDFWLYDWLRQ
RI6/6 RI6/6
)UHTXHQF\
(QYHORSH
6/6PRQLWRULQJ
33 )UHTXHQF\
VHWSRLQW
6/6VHWSRLQW
33 $FWXDO
IUHTXHQF\
6WDQGVWLOOGHWHFWLRQ
33
$FFXUDF\OLPLW
+]
7LPH
U
6WDWXVZRUG
U
U
U
U
U
U
U
/('
6)
672
66
6/6
(6
Case 3: standstill detection (p9682/p9882) > Frequency setpoint > accuracy limit
Initiation of SLS => • Ramp monitoring activated
• SLS-LED flashing
• Frequency setpoint deactivated
When SLS is reached => • SLS monitoring on
• ES-LED on
• Frequency setpoint inactive
Deactivation of SLS => • Ramp monitoring off
• SLS monitoring off
• SLS-LED and ES-LED off
• activate freq. setpoint and ramp to freq.
setpoint
$FWLYDWLRQ 'HDFWLYDWLRQ
RI6/6 RI6/6
)UHTXHQF\
(QYHORSH
6/6PRQLWRULQJ
33
6/6VHWSRLQW
33 )UHTXHQF\
VHWSRLQW
6WDQGVWLOOGHWHFWLRQ
33 $FWXDO
IUHTXHQF\
$FFXUDF\OLPLW
+]
7LPH
U
6WDWXVZRUG
U
U
U
U
U
U
U
/('
6)
672
66
6/6
(6
(QYHORSH
6/6PRQLWRULQJ
33
6/6VHWSRLQW
33
6WDQGVWLOOGHWHFWLRQ
33 )UHTXHQF\
$FWXDO VHWSRLQW
$FFXUDF\OLPLW IUHTXHQF\
+]
7LPH
U
6WDWXVZRUG
U
U
U
U
U
U
U
/('
6)
672
66
6/6
(6
)DXOW
(QYHORSH
6/6PRQLWRULQJ
33
6/6VHWSRLQW
33
/672
6WDQGVWLOOGHWHFWLRQ
33
$FFXUDF\OLPLW
+]
7LPH
U
6WDWXVZRUG
U
U
U
U
U
U
U
/('
6)
672
66
6/6
(6
Case 6: SLS setpoint > Frequency setpoint > standstill detection (p9682/p9882)
Initiation of SLS => • Ramp monitoring activated
• SLS-LED flashing
• Frequency setpoint deactivated
When actual frequency runs • LSTO activated immediately
above SLS monitoring
Deactivation of SLS => • No action
• To start again, LSTO must be
acknowledged and a new on command
is necesarry to ramp up to frequency
setpoint.
$FWLYDWLRQ /672 'HDFWLYDWLRQ 6WDUWLQJGULYHYLD
RI6/6 DFWLYDWHG RI6/6 2))
DFNQRZOHGJH
)DXOW 21
)UHTXHQF\
(QYHORSH
6/6PRQLWRULQJ
33 )UHTXHQF\
VHWSRLQW
6/6VHWSRLQW
33
$FWXDO
IUHTXHQF\
6WDQGVWLOOGHWHFWLRQ
33
$FFXUDF\OLPLW
+]
7LPH
U
6WDWXVZRUG
U
U
U
U
U
U
U
/('
6)
672
66
6/6
(6
SLS Mode 2
P9692 = P9892 = 2
Warning
Safe brake ramp not actived
Mode 2 means that the safe brake ramp is not activated, therefore it is the users
responsibility to ensure that the motor is ramped down to or below the SLS setpoint.
In Mode 2, only the monitoring ramp (envelope) is activated, the safe brake ramp will is not
active.
If the motor speed exceeds the upper SLS limit set in P9691 and P9891, the motor must be
ramped down using an external control channel (for example, a PLC, potentiometer or USS
etc.). If the control channel tries to set the speed of the motor to exceed the upper SLS limit,
this will be interpreted as a fault condition and the motor will be stopped and latched. To start
the motor again, the fault condition needs to be explicitly acknowledged. See the following
table.
Fault reactions according the selected SLS mode 2
VHWSRLQW
(QYHORSH
6/6PRQLWRULQJ
33
/672
$FFXUDF\OLPLW
+]
7LPH
U
6WDWXVZRUG
U
U
U
U
U
U
U
/('
6)
672
66
6/6
(6
(QYHORSH
6/6PRQLWRULQJ
33
$FWXDO
IUHTXHQF\ )UHTXHQF\
VHWSRLQW
$FFXUDF\OLPLW
+]
7LPH
U
6WDWXVZRUG
U
U
U
U
U
U
U
/('
6)
672
66
6/6
(6
(QYHORSH
6/6PRQLWRULQJ
33
$FWXDO )UHTXHQF\
IUHTXHQF\ VHWSRLQW
$FFXUDF\OLPLW
+]
7LPH
U
6WDWXVZRUG
U
U
U
U
U
U
U
/('
6)
672
66
6/6
(6
)DXOW
(QYHORSH
6/6PRQLWRULQJ
33
)UHTXHQF\
VHWSRLQW
/672
$FWXDO
IUHTXHQF\
$FFXUDF\OLPLW
+]
7LPH
U
6WDWXVZRUG
U
U
U
U
U
U
U
/('
6)
672
66
6/6
(6
Note
Inside SLS tolerance means a value between upper and lower SLS limit.
Caution
In SLS modes 0 and 1, the frequency setpoint can increase related to the following functions
• PID Trim
• Vdc max controller
• Slip compensation
• Resonance damping
• Imax
As the frequency is monitored after adding these values, this increasement should be taken
into account by the user when parameterising the safe frequency envelope.
)UHH]HVDIHW\ )UHTXHQF\
IUHTXHQF\ PRQLWRULQJ
)UHTXHQF\
)UHTXHQF\
VHWSRLQWWR
VHWSRLQW
+ + + - + 3RZHU
IURP5)*
VWDFN$6,&
3,'DVWULP
3 3 3 ,PD[
9GFPD[ 6OLS 5HVRQDQFH
FRQWUROOHU FRPSHQVDWLRQ GDPSLQJ
*) If PID as trim is active when SS1, SLS0 or SLS1 is triggered, the PID as trim is
deactivated and has no influence to the frequency setpoint at the latest 1 s after the fail-safe
function has been activated.
Data
Description
The Safe Brake Control function (SBC) is to create a fail-safe signal to control an
electromechanical motor brake.
Caution
The connection between the brake on the motor and the Safe Brake Control Relay is
supervised at forced dynamisation but not during operation.
Note
When carrying-out the forced dynamisation, the shutdown paths of the motor brake are also
tested. This results a brief opening command (2 ms to 28 ms) in the motor brake.
The mechanical part of the brake generally requires longer than 30 ms to open. This means
that this dynamic operation generally has no influence on the motor shaft itself. However it is
the user's responsibility to use brakes with opening times > 30 ms.
Overview
In addition to DC, compound and dynamic braking, for the SINAMICS G120 it is possible to
prevent a DC link overvoltage condition using the closed-loop Vdc controller. With this
technique, the output frequency is automatically modified during operation using the closed-
loop Vdc controller so that the motor doesn't go too far into the regenerative mode.
Using the Vdc controller, it is also possible to prevent the inverter from being shut down
(tripped) during brief line supply dips – which cause a DC link undervoltage condition. Also in
this case, the output frequency is automatically modified by the Vdc controller during
operation. Contrary to an overvoltage condition, in this case the motor is operated with
increased regenerative operation in order to support and buffer the DC link voltage.
DC link overvoltage
● Cause:
The motor regenerates and feeds too much energy back into the DC link.
● Remedy:
The DC link voltage is further reduced using the Vdc_max controller by reducing the
regenerative torque down to zero.
DC link undervoltage
● Cause:
Line supply voltage failure or dip (blackout or brownout)
● Remedy:
A regenerative torque is entered for the operational motor which compensates the
existing losses and therefore stabilizes the voltage in the DC link. This technique is
carried-out using the Vdc_min controller and is known as kinetic buffering.
Data
Description
A brief regenerative load can be handled using this function (enabled using P1240) without
the inverter being shut down (tripped) with fault message F0002 ("DC link overvoltage"). In
this case, the frequency is controlled (closed-loop) so that the motor doesn't go too far into
regenerative operation.
If the inverter regenerates too much when braking the machine due to a fast ramp-down time
P1121, then the braking ramp/ramp time is automatically extended and the inverter is
operated at the DC link voltage limit r1242 (see figure below). If the DC link again falls below
the threshold r1242, then the Vdc_max controller withdraws the extension of the braking
ramp.
9'&
U
W
9'&BPD[FRQWUROOHUDFWLYH
$
U%LW
W
_I_
IDFW
IVHW
On the other hand, if the Vdc_max controller increases the output frequency (e.g. for a
steady-state regenerative load), then the Vdc_max controller is disabled by an internal
inverter monitoring function and the warning A0910 is output. If the regenerative load
continues, the inverter is protected using fault F0002.
In addition to controlling the DC link (closed-loop), the Vdc_max controller supports the
stabilizing processes of the speed at the end of an acceleration phase. This is especially the
case if there is an overshoot and the motor therefore briefly goes into regenerative operation
(damping effect).
Note
If the DC link voltage exceeds the power-on threshold r1242 (switch-on level of Vdc_max.) of
the Vdc_max controller in the "Ready" state, then the Vdc_max controller is de-activated and
warning A0910 is output.
Cause: The line supply voltage does not match the application situation
Remedy: Refer to parameters P1254 and P0210.
If, in the "Run" state, the DC link voltage exceeds the power-on threshold r1242 and if the
Vdc_max controller output is limited by parameter P1253 for approx. 200 ms, then the
Vdc_max controller is de-activated and the warning A0910 and, where relevant, fault F0002
are output.
Cause: Line supply voltage P0210 or ramp-down time P1121 too low
The moment of inertia of the motor load is too high
Remedy: Refer to parameters P1254, P0210, P1121
Use a braking resistor
Data
Description
Brief line supply failures can be buffered using the kinetic buffering function (enabled using
P1240). Line supply failures are buffered using the kinetic energy (i.e. moments of inertia) of
the motor load. In this case the prerequisite is that the motor load has a sufficiently high
moment of inertia - i.e. has sufficient kinetic energy.
Using this technique, the frequency is controlled (closed-loop), so that energy is fed to the
inverter from the regenerating motor thus covering the system losses. The losses during the
line supply failure still remain which means that the motor speed decreases. When using
kinetic buffering it has to be taken into consideration that the motor speed is reduced.
9'&
3RZHUIDLOXUH
ຘ 3
3
ຘ ຘ 3
3
3RZHUUHVWRUDWLRQ
9GFBPLQ
W
.,%DFWLYH
U
%LW W
,I,
I
I I
W E ຘ 3
3
I
W
WE
When the line supply returns, the energy feed is again from the line side and the output
frequency of the inverter returns to the selected setpoint along the ramp defined by the
ramp-function generator.
Note
When the DC link voltage falls below the minimum VDC_min, fault F0003 "Undervoltage" is
output and the inverter is shut down. The shutdown threshold VDC_min depends on the
inverter type and line supply voltage.
For the SINAMICS G120 the DC link undervoltage shutdown threshold is 430 V.
Data
Description
The positioning ramp down can be used for applications where it is necessary that a residual
distance is moved-through up to the stop dependent on an external event (e.g. BERO
switch). In this case, the SINAMICS G120 generates a continuous braking ramp by selecting
OFF1 depending on the actual load speed and velocity. The motor is then stopped and
positioned along this braking ramp (see figure below).
0RWRU *HDU
I
V 3 ವI2))ವW3
2))
I2))
W
W3
In this case, the remaining distance P2488 moved through must be entered, referring to the
load. In order to carry-out the residual distance calculation on the load side, the mechanical
arrangement of the axis (gearbox ratio, linear or rotary axis) must be appropriately
parameterized (see figure below).
'LVSRVLWLRQ 3DUDPHWHU
VOLQ
0RWRUUHYROXWLRQV 3
/RDG L
/RDGUHYROXWLRQV 3
0RWRU *HDU
] 1RRIUHYROXWLRQV
] VFUHZOHDG 3
L >XQLW@
Q0RWRU Q/RDG
/RDG
L
Q0RWRU Q/RDG
Using this data, SINAMICS G120 calculates the ratio between the distance and the motor
revolutions and can therefore consider the movement on the load side.
Note
The "Switch-off frequency" (P2167) can have an influence on the final positioning result.
Data
Description
The SINAMICS G120 has an extensive range of monitoring functions and messages which
can be used for open-loop process control. The control can either be implemented in the
inverter or using an external control (e.g. PLC). The interlocking functions in the inverter as
well as the output of signals for external control are implemented using BICO technology.
The status of the individual monitoring functions and messages are emulated in the following
CO/BO parameters:
Note
On the OP the bit numbers are displayed in hex-format (0..9, A..F).
Data
Description
This function allows the mechanical force transmission between the motor and motor load to
be monitored. Typical applications include, for example, pulley belts, flat belts or chains, or
pulleys for toothed wheels of motor-in and motor-out shafts which then transmit
circumferential velocities and circumferential forces (see figure below). The load torque
monitoring function can then detect whether the motor load is locked or the force
transmission has been interrupted.
'ULYH
VKDIW
'HIOHFWLRQ
UROO
For the load torque monitoring function, the actual frequency/torque characteristic is
compared with the programmed frequency/torque characteristic (refer to P2182 … P2190). If
the actual value lies outside the programmed tolerance bandwidth, then, depending on
parameter P2181, either warning A0952 or fault F0452 is generated. Parameter P2192 can
be used to delay the output of the warning or fault message. This avoids erroneous alarms
which could be caused by brief transient states (see figure below).
7RUTXH>1P@
3
3
3
3
$FWXDO
3 WRUTXH
3
3
)UHTXHQF\
3 3 3 >+]@
3
$
%LW W
3 3
The frequency/torque tolerance bandwidth is defined by the gray shaded area in the figure
below. The bandwidth is determined by the frequency values P2182 … P2184 including the
max. frequency P1082 and the torque limits P2186 … P2189. When defining the tolerance
bandwidth it should be ensured that a specific tolerance is taken into account in which the
torque values are allows to vary corresponding to the application.
7RUTXH>1P@ 3
0D[IUHTXHQF\
3
8SSHUWRUTXHWKUHVKROG
3
/RZHUWRUTXHWKUHVKROG
3
8SSHUWRUTXHWKUHVKROG
3
/RZHUWRUTXHWKUHVKROG
3
8SSHUWRUTXHWKUHVKROG
3
/RZHUWRUTXHWKUHVKROG
)UHTXHQF\
3 >+]@
3 7KUHVKROGIUHTXHQF\ 3
7KUHVKROGIUHTXHQF\ 7KUHVKROGIUHTXHQF\
Data
Description
The SINAMICS G120 has a completely new integrated concept for thermal motor protection.
There are numerous possibilities of effectively protecting the motor but at the same time
ensuring high motor utilization. The basic philosophy of this innovative concept is to detect
critical thermal states, output warnings and initiate the appropriate responses. By responding
to critical states it is possible to operate the motor at the thermal power limit and to avoid,
under all circumstances, an immediate shutdown (where the inverter is tripped).
Features
The protective concept (see figure below) distinguishes itself as a result of the following
individual features:
● Protection is effective without using any temperature sensor (P0601 = 0). The
temperatures of various locations in the motor are indirectly determined using a
temperature model.
● It is possible to evaluate temperature sensors. This has the advantage that after a line
supply failure, precise initial temperatures are immediately available. Both PTC sensors
(P0601 = 1) as well as KTY84 sensors (P0601 = 2) can be connected and evaluated.
● When using a KTY84 sensor, the inverter can be parameterized so that a sensor wire
breakage or short-circuit F0015 is detected and the system automatically changes-over to
the temperature model. This means that the inverter is not shut down (tripped) and
operation can continue.
● Selectable temperature warning thresholds P0604 (default: 130 ーC) for operation with the
temperature model or KTY84 sensor. The inverter is shut down or the current reduced
depending on P0610 for a value of P0604 +10 %.
● Selectable responses P0610 which are to be initiated when the warning threshold is
exceeded in order to prevent an overload condition.
● The motor protection has been designed to be completely independent of the inverter
protection. Warning thresholds and responses for inverter protection must be separately
parameterized.
● Various data sets are taken into account in the model. The model is separately calculated
for each data set so that when changing-over between various motors the cooling of the
presently non-active (fed) motors are taken into account.
)DXOW
)
9 3 U
%LW
7 V
6LJQDO 1RVHQVRU
$'& 0RWRU
ORVV 37& LW
GHWHFWLRQ .7< ุ WHPS
37& UHDFWLRQ
.7< U
˽
3
9 3
(TXLYDOHQWFLUXLWGDWD
7KHUPDO U
PRWRU 3
3RZHUGLVVLSDWLRQ3YPRW U
PRGHO
U
Description
The data, required for the thermal motor model, is estimated from the rating plate data
entered during the quick commissioning. This data permits reliable, stable operation for
standard Siemens motors. If required, parameter changes must be made for motors from
third-party manufacturers. We always recommend that an automatic motor data identification
run is made after quick commissioning so that the electrical equivalent circuit diagram data
can be determined. This allows a more precise calculation of the losses which occur in the
motor which has an impact on the accuracy of the thermal motor model.
Example
A stator resistance, which is parameterized to be too high, would result, in the model, higher
losses than in a real motor and an excessively high calculated motor temperature would be
displayed.
If changes are required in order to optimize the thermal model, then as a first step, the motor
weight (P0344) should be checked for plausibility. Generally, the motor weight is taken from
the Catalog data of the motor manufacturer. The thermal model can be further optimized by
adapting the standard overtemperatures for the stator iron P0626, the stator winding P0627
and the rotor P0628. The standard overtemperatures represent the steady-state
temperatures to be expected in rated operation with respect to the environment and are used
to estimate the thermal resistances. Generally, these overtemperatures are not listed in the
Catalog.
The ambient temperature P0625 is another important parameter which influences the
precision of the thermal model.
Data
Description
The thermal motor model can be used to calculate the motor temperature. Not only this it
can be also used to optimize the control loops for closed-loop vector control and for
temperature monitoring. A KTY84 sensor is then no longer required for temperature sensing.
After the power supply (24 V) has been powered-down, the motor temperature - internally
calculated using the thermal motor model - is no longer available. The model then starts with
the ambient temperature value (P0625).
If the "Determining the motor temperature after motor start" function is active, the motor
temperature is detected by measuring the current after magnetization and the thermal motor
model is then pre-assigned this value.
Parameter P0621 is used to select when the function is active:
P0621 = 0: The function is de-activated. The thermal motor model then uses the ambient
temperature value (P0625).
P0621 = 1: The motor temperature is determined once when the motor first starts after the
power supply has been switched-in. This setting is used for standard motors.
P0621 = 2: For this setting, a new temperature measurement is carried-out each time the
motor starts. This technique is practical for motors whose thermal behavior differs from
standard motors. In these cases, it is possible that the thermal model is too inaccurate and
would supply larger deviations.
Note
If a KTY84 sensor is being used and is functional, then the temperature of the sensor is used
in all settings of parameter P0621. In this case, the temperature is not measured using the
stator resistance.
Note
In the following cases, the motor temperature is not measured:
• V/f operation
• Fault when measuring the current, e.g. the current isn’t sufficiently constant
• For a flying restart the speed is too high
In these cases - when first accelerating after the power supply has been powered-up - an
average temperature value is used (approx. 47 °C). When the motor starts without powering-
down the power supply, the temperature does not change.
Data
Description
When the motor is operated below the rated speed the cooling effect of the shaft-mounted
fan is reduced. As a result, for most motors when continually operated at lower frequencies,
the power has to be reduced. Under these conditions, motor protection against overheating
can only be guaranteed if either a temperature sensor (PTC or KTY84 sensor) is integrated
in the motor and is connected to the control terminals (see figure below) of the SINAMICS
G120 or the motor temperature model was determined.
9
N˖
.7< $
37&
'
˖
Note
In order to avoid EMC noise from being coupled-in to the motor/inverter electronics the
associated disturbances is not permissible to use free conductors in the motor cable to
connect the temperature sensor to the motor/inverter.
The temperature sensor must be connected to the motor/inverter using a separate cable (if
at all possible, this cable should be shielded).
Data
Description
Just the same as for motor protection, the SINAMICS G120 provides extensive protection for
the power components. This protection concept is sub-divided into two levels:
● Warning and response
● Fault and shutdown
Using this concept, a high utilization of the power module components can be achieved
without the inverter being immediately shut down.
The monitoring thresholds for the faults and shutdowns are permanently saved in the
inverter and cannot be changed by the user. On the other hand, the threshold levels for
"Warning and response" can be modified by the user to optimize the system. These values
have default settings so that the "Fault and shutdown" thresholds do not respond.
Data
Description
Similar to motor protection, the main function of the thermal power module monitoring is to
detect critical states. Parameterizable responses are provided for the user which allows the
motor system to still be operated at the power limit avoiding immediate shutdown. However,
the possibilities of assigning parameters only involves interventions below the shutdown
threshold which cannot be changed by users.
The SINAMICS G120 has the following thermal monitoring functions:
● i2t monitoring
The i2t monitoring is used to protect components which have a long thermal time constant
in comparison to the semiconductors. An overload with reference to i2t is present if the
inverter utilization r0036 indicates a value greater than 100 % (utilization as a % refers to
rated operation).
● Heatsink temperature
The heatsink temperature of the power semiconductors (IGBT) is monitored and
displayed in r0037[0].
● Chip temperature
Significant temperature differences can occur between the junction of the IGBT and the
heatsink. These differences are taken into account by the chip temperature monitoring
and are displayed in r0037[1].
When an overload occurs regarding one of these three monitoring functions, initially, a
warning is output. The warning threshold P0294 (i2t monitoring) and P0292 (heatsink
temperature and chip temperature monitoring) can be parameterized relative to the
shutdown values.
Example
The warning threshold P0292 for the temperature monitoring (chip/heatsink temperature) is
set to 15 ーC in the factory. This means that warning A0504 is output 15 ーC below the
shutdown threshold.
At the same time that the warning is output, the parameterized responses are initiated using
P0290 (default: P0290 = 2). Possible responses include:
● Reducing the pulse frequency (P0290 = 2 or 3)
This is an extremely effective method to reduce losses in the power module, as the
switching losses represent a very high proportion of the overall losses. In many
applications, a temporary reduction of the pulse frequency can be tolerated in favor of
maintaining the process
Disadvantage
The current ripple is increased when the pulse frequency is reduced. This can result in an
increase of the torque ripple at the motor shaft (for low moments of inertia) and an increase
in the noise level. When the pulse frequency is reduced this has no influence on the dynamic
response of the current control loop as the current control sampling time remains constant!
● Reducing the output frequency (P0290 = 0 or 2)
This is advantageous if it is not desirable to reduce the pulse frequency or if the pulse
frequency is already set to the lowest level. Further, the load should have a characteristic
similar to that of a fan, i.e. a square-law torque characteristic for decreasing speed. When
the output frequency is reduced, this significantly reduces the inverter output current and
in turn reduces the losses in the power module.
● No reduction (P0290 = 1)
This option should be selected if neither a reduction in the pulse frequency nor a
reduction in the output current is being considered. In this case, the inverter does not
change its operating point after the warning threshold has been exceeded so that the
motor can continue to be operated until the shutdown values are reached. After the
shutdown threshold has been reached, the inverter shuts down (trips) with fault F0004.
The time which expires up to shutdown is however not defined and depends on the
magnitude of the overload. Only the warning threshold can be changed in order to obtain
an earlier warning and, if required, externally intervene in the motor process (e.g. by
reducing the load, lowering the ambient temperature).
Note
If the inverter fan fails, this would be indirectly detected by the measurement of the
heatsink temperature.
A wire breakage or short circuit of the temperature sensor(s) is also monitored.
Overview
There are several open-loop and closed-loop techniques for closed-loop speed and torque
control for inverters with induction and synchronous motors. These techniques can be
roughly classified as follows:
● V/f characteristic control (known as: V/f control)
● Field-orientated closed-loop control technique (known as: Vector control)
The field-orientated control technique – Vector control – can be further sub-divided into two
groups:
● Vector control without speed feedback (sensorless Vector control (SLVC))
● Vector control with speed feedback (Vector control (VC))
These techniques differ from one another both regarding the control ability and in the
complexity of the technique, which in turn are obtained as a result of the requirements
associated with a particular application. For basic applications (e.g. pumps and fans), to a
large extent, V/f control is used. Vector control is mainly used for sophisticated applications
(e.g. winders), where a good control and behavior in noisy conditions are required regarding
the speed and torque. If these requirements are also present in the range from 0 Hz to
approx. 1 Hz, then the speed/torque accuracy without encoder is not sufficient. In this case,
Vector control with speed feedback must be used.
Data
Description
The V/f characteristic represents the simplest control technique. In this case the stator
voltage of the induction motor or synchronous motor is controlled proportionally to the stator
frequency. This technique has proven itself for a wide range of "basic" applications, such as
● Pumps, fans
● Belt motors
and similar processes.
The goal of V/f control is to keep the flux Φ constant in the motor. In this case, this is
proportional to the magnetizing current Iμ and the ratio between voltage V and frequency f.
Φ ~ Iμ ~ V/f
The torque M, developed by induction motors, is proportional to the product (precisely the
Vectorial product Φ x I) of flux and current.
M~Φ*I
In order to generate the highest possible torque from a given current, the motor must operate
with a constant flux which is as high as possible. In order to keep the flux Φ constant, when
frequency f changes, the voltage V must be changed in proportion so that a constant
magnetizing current Iμ flows. The V/f characteristic control is derived from these basic
principles.
803˓
83
5DWHGPRWRU
0Q˓Q RSHUDWLQJSRLQW
83
0˓
IQ IPD[
Figure 8-84 Operating ranges and characteristics of an induction motor when fed from an inverter
There are several versions of the V/f characteristic as shown in the table below.
3
I
IQ
1 FCC Can give a more efficient and better load response than other V/f
modes because the FCC characteristic automatically compensates
the voltage losses of the stator resistance for static (steady-state) or
dynamic loads (flux current control FCC). This is used especially for
small motors which have a relatively high stator resistance.
2 Square-law This is a characteristic which
characteristic takes into consideration the 9
characteristic of the
3
3
synchronous motor).
3
3
I
I I I I IQ IPD[
+] 3 3 3 3 3
Data
Description
For low output frequencies, the V/f characteristics only output a low output voltage. Even at
low frequencies, the ohmic resistances of the stator winding play a role, which are neglected
when determining the motor flux in V/f control. This means that the output voltage can be too
low in order to:
● implement the magnetization of an induction motor,
● to hold the load
● to equalize losses (ohmic losses in the winding resistances) in the system or
● to provide a breakaway/accelerating/braking torque.
The output voltage can be increased (boosted) in the SINAMICS G120 using the parameters
as shown in the table below.
Note
Especially at low frequencies, the motor temperature is additionally increased as a result of
the voltage boost (the motor overheats)!
The voltage value at 0 Hz is determined from the product of rated motor current P0305,
stator resistance P0350 and the appropriate parameters P1310 … P1312.
Using very high boost values may cause the motor to stuck at a low frequency due to the
Imaxcontroller (very high boost may cause overcurrent failure).
9PD[
9Q
3 JH
R OWD
X WY
WS
DFWXDO9%RRVW 2X
9&RQ%RRVW
I
9
DO
UP
1R
3
9&RQ%RRVW
I
I%RRVWHQG IQ IPD[
3 3 3
P1311 Voltage boost when The voltage boost is only effective when accelerating or braking.
accelerating or 9 /LQHDU9I
braking
9PD[
9Q
3
JH
R OWD
X WY
DFWXDO9%RRVW WS
2X I
9&RQ%RRVW 9
DO
UP
1R
3
9&RQ%RRVW
I%RRVWHQG IQ IPD[
3 3 3
9PD[
9Q
3
JH
ROWD
X WY
DFWXDO9%RRVW WS
2X I
9&RQ%RRVW 9
DO
UP
1R
3
9&RQ%RRVW
I%RRVWHQG IQ IPD[
3 3 3
Data
Description
In the V/f characteristic operating mode the motor frequency is always lower than the inverter
output frequency by the slip frequency fs. If the load (the load is increased from M1 to M2) is
increased with a constant output frequency, then the slip increases and the motor frequency
decreases (from f1 to f2). This behavior, typical for an induction motor, can be compensated
using slip compensation P1335. This therefore eliminates the speed reduction, caused by
the load, by boosting (increasing) the inverter output frequency (see figure below).
:LWKRXWVOLSFRPSHQVDWLRQ :LWKVOLSFRPSHQVDWLRQ
0 0
0 0
0 0
I I
ෙI ෙI
I I I I IRXW0
IRXW0
Data
Description
Resonance effects result in an increased noise level and also can damage or destroy the
mechanical system. These resonance effects can occur for:
● Geared motors
● Reluctance motors
● Large motors
(low stator resistance → poor electrical damping)
The V/f resonance damping function is working between 6 % and 80 % of the rated motor
frequency when enabled.
Contrary to the "skip frequency" function and parameters P1091 … P1094, where the
resonance frequency is passed through as quickly as possible, for the V/f resonance
damping (P1338), the resonance effects are dampened from a control-related perspective.
The advantage of this function is that by using this active damping, operation is possible in
the resonance range.
The V/f resonance damping is activated and adjusted using parameter P1338. This
parameter represents a gain factor that is a measure for the damping of the resonance
frequency. The following oscillogram indicates the effect of the resonance damping function
using as an example a reluctance motor with gearbox. The phase output currents are
displayed for an output frequency of 45 Hz.
Data
Description
The inverters have a current measurement function. This permits the output current to be
precisely determined referred to the motor voltage. This measurement guarantees that the
output current is sub-divided into a load component and a flux component. Using this sub-
division, the motor flux can be controlled and can be appropriately adapted and optimized in-
line with the prevailing conditions.
FCC operation is only activated after the FCC starting frequency P1333 has been exceeded.
The FCC starting frequency P1333 is entered as a percentage to the rated motor frequency
P0310. For a rated motor frequency of 50 Hz and a factory setting of P1333 = 10 %, this
results in an FCC starting frequency of 5 Hz. The FCC starting frequency may not be
selected too low as this has a negative impact on the control characteristics and can result in
oscillation and system instability.
The "V/f with FCC" control type (P1300 = 1) has proven itself in many applications. It has the
following advantages with respect to the standard V/f control:
● Higher motor efficiency
● Improved stabilizing characteristics
– higher dynamic response
– improved behavior to disturbances/control.
Note
Contrary to closed-loop vector control, for the V/f open-loop control mode with FCC, it
is not possible to specifically influence the motor torque. This is the reason that it isn’t
always possible to avoid the motor stalling – even when using "V/f with FCC".
An improvement in the stabilizing behavior and in the motor efficiency can be
expected when using the closed-loop vector control when compared to V/f control with
FCC.
Data
Description
In the V/f characteristic mode, the inverter has a current limiting controller in order to avoid
overload conditions (Imax controller, see figure below). This controller protects the inverter
and the motor against continuous overload by automatically reducing the inverter output
frequency by fImax (r1343) or the inverter output voltage by VImax (r1344). By either reducing
the frequency or voltage, the stressing on the inverter is reduced and it is protected against
continuous overload and damage.
,PD[FWUOSUSJDLQ ,PD[FWUOLQWWLPH
>V@
3' 3'
.S
7Q
0RWRU7HPSHUDWXUH &2,PD[FWUO)RXWS
,QYHUWHU7HPSHUDWXUH I,BPD[
U
LtWLQYHUWHU
30RWRU ,PD[FRQWUROOHUVHWSRLQW
UDWHGFXUUHQW .S
7Q
U &2,PD[FWUO9RXWS
0RWRURYOIDFW>@ 8,BPD[
>@ &22XWSFXUOLPLW>$@ U
3'
&XUUHQWIHHGEDFN
U
&22XWSXWFXUUHQW>$@
,PD[YROWSUSJDLQ ,PD[YROWLQWWLPH
>V@ >V@
3' 3'
Note
The inverter load is only reduced when the frequency is reduced if the load decreases at
lower speeds (e.g. square-law torque –speed characteristic of the motor load).
Description
Field-orientated Vector control (known as: Vector control) significantly improves torque
control when compared to V/f control. The Vector control principle is based on the fact that
for a specific load situation or required torque, the required motor current is impressed with
respect to the motor flux so that the appropriate torque is obtained. If the stator current is
emulated in a circulating coordinate system, linked with the rotor flux Φ, then it can be
broken-down into the flux-generating current component id in-line with the rotor flux and into
a torque-generating current component iq, vertical to the rotor flux. These components are
corrected to track their setpoints in the current controller using their own dedicated PI
controllers and are equal quantities in steady-state operation.
0HDVXUHGVWHDG\VWDWHWUDMHFWRULHV
L6W
5RWRUD[LV
˶
LT
˶
LE
)OX[D[LV
LG
LP5 ˶P5
LD 6WDWRUD[LV
Data
Description
When Vector control is used without a speed encoder (SLVC) then the position of the flux
and the actual speed must be determined using the motor model. In this case, the model is
supported by the accessible currents and voltages. At low frequencies (≈ 0 Hz), the model is
not able to determine the speed. Inability of the model to determine the speed at ≈ 0 Hz,
uncertainty in model parameters and measurement inaccuracy are the reasons why there is
a changeover from closed-loop to open-loop controlled operation in this range.
The changeover between closed-loop controlled and open-loop controlled operation is
controlled using the time and frequency conditions (P1755, P1756, P1758) (see figure
below). The system does not wait for the time condition if the setpoint frequency at the ramp-
function generator input and the actual frequency simultaneously lie below P1756.
_IBDFW_
3
3>+]@
6/9&RSHQORRS
6/9&FORVHGORRS W
3
3>@
3>+]@ 3>+]@ವ
>@
In the open-loop controlled mode, the speed actual value is the same as the setpoint. For
suspended loads or when accelerating, parameter P1610 (constant torque boost) and P1611
(torque boost when accelerating) must be modified in order to allow the motor to provide the
steady-state and/or dynamic load torque. If P1610 is set to 0 %, then only the magnetizing
current r0331 is impressed for a value of 100 % of the rated motor current P0305. In order
that the motor does not stall when accelerating, P1611 can be increased or the acceleration
pre-control can be used for the speed controller. This is also practical in order that the motor
is not thermally overloaded at low speeds.
For Vector control without speed actual value encoder the SINAMICS G120 has, in the low
frequency range, the following outstanding features with respect to other AC inverters:
● Closed-loop controlled operation down to ≈ 1 Hz
● Can start in the closed-loop controlled mode (immediately after the motor has been
energized)
● The low frequency range (0 Hz) is passed-through in closed-loop controlled operation.
6WDUW
I I =HURFURVVLQJ
&ORVHGORRS &ORVHGORRS
3 3
2SHQORRS 2SHQORRS
W W
3
The following advantages are obtained as a result of closed-loop controlled operation down
to approx. 1 Hz (this can be selected using parameter P1755) as well as the possibility to
immediately start closed-loop controlled at 0 Hz or to reverse closed-loop controlled (this can
be set using parameter P1750):
● No changeover operation is required within the closed-loop control (smooth behavior –no
frequency dips)
● Continuous closed-loop speed-torque control is possible down to approx. 1 Hz.
Note
For closed-loop controlled reversing or closed-loop controlled starting from 0 Hz it must
be taken into account that when staying too long (> 2 s or > P1758) in the range around
0 Hz, that the closed-loop control automatically changes over from closed-loop into the
open-loop controlled mode.
Data
Description
For Vector control with speed encoder (VC), a pulse encoder, e.g. an encoder with 1024
pulses per revolution is required. In addition to the correct wiring, the pulse encoder must be
activated, corresponding to the encoder type, using the parameter range P0400 … P0494.
P0400 = 2 A
VLQJOHHQGHG
B
AN
GLIIHUHQWLDO
B
BN
Data
Description
Both of the control techniques (SLVC and VC) have the same speed controller structure
which includes the following components:
● PI controller
● Speed controller pre-control
● Droop
The sum of the output quantities forms the speed setpoint, which is reduced to the
permissible level using the torque setpoint limiting function.
Speed controller (SLVC: P1470, P1472, P1452 VC: P1460, P1462, P1442)
The speed controller (see figure below) receives its setpoint r0062 from the setpoint channel,
the actual value r0063 either directly from the speed actual value encoder for VC or through
the motor model for SLVC. The system error is amplified by the PI controller and, together
with the pre-control, forms the torque setpoint.
For increasing load torques, when the droop function is active, the speed setpoint is
proportionally reduced so that the load on an individual motor within a group (where two or
several motors are mechanically coupled) is reduced when excessively high torques occur.
'URRS
3UHFRQWURO
6SHHGFRQWURO .S 7Q
U U
ದ
3, U U
6SHHG
)UHTVHWSRLQW FRQWUROOHU
ದ
7L 7RUTXH
U
VHWSRLQW
U U
$FWIUHTXHQF\
RQO\DFWLYHLISUHFRQWUROLVHQDEOHG3! 7L .S 7Q
6/9& 3 3 3
9& 3 3 3
If the moment of inertia was entered, the speed controller (Kp,Tn) can be calculated using the
automatic parameterization (P0340 = 4). The controller parameters are defined according to
the symmetrical optimum as follows:
Tn = 4 * T σ
Kp = ス * r0345 / Tσ = 2 * r0345 / Tn
Tσ = sum of the low delay times
If oscillations occur with these particular settings, then the speed controller gain Kp should be
manually reduced. It is also possible to increase the speed actual value smoothing (this is
the usual procedure for gearbox play or high-frequency torsional oscillations) and then re-call
the controller calculation as the value is incorporated in the computation of Kp and Tn.
The following interrelationships apply for the optimization routine:
● If Kp is increased then the controller becomes faster and the overshoot is reduced.
However, the signal ripple and oscillations in the speed controller loop are increased.
● If Tn is reduced, then the controller also becomes faster. However, the overshoot
increases.
When manually adjusting the speed control, the simplest procedure is to initially define the
possible dynamic response using Kp (and the speed actual value smoothing) in order to then
reduce the integral action time as far as possible. In this case it is important to ensure that
the closed-loop control must also remain stable in the field-weakening range.
When oscillations occur in the closed-loop speed control, it is generally sufficient to increase
the smoothing time in P1452 for SLVC or P1442 for VC (or to reduce the controller gain) in
order to dampen oscillations.
The integral output of the speed controller can be monitored using r1482 and the unlimited
controller output can be monitored using r1508 (torque setpoint).
Note
When compared to closed-loop control with encoder, the dynamic response for sensorless
motors is significantly reduced. This is because the speed can only be derived from the
inverter output quantities for current and voltage which have the appropriate noise level.
'URRS
U
.S 7Q
3
$FWIUHTXHQF\
7L .S 7Q
6/9& 3 3 3
9& 3 3 3
When correctly adapted, the speed controller only has to correct noise
quantities/disturbances in its control loop and this is achieved with a relatively low
manipulated quantity change. On the other hand, speed setpoint changes bypass the speed
controller and are therefore executed faster.
The effect of the pre-control quantity can be adapted, depending on the particular
application, using the pre-control factor P1496. Using P1496 = 100 %, the pre-control is
calculated according to the motor and load moment of inertia (P0341, P0342). In order that
the speed controller does not work against the torque setpoint which is entered, a balancing
filter is automatically used. The time constant of the balancing filter corresponds to the
equivalent delay time of the speed control loop. The speed controller pre-control is correctly
set (P1496 = 100 %, calibrated using P0342), if the I component of the speed controller
(r1482) does not change during a ramp-up or ramp-down in the range n > 20 % * P0310.
This means, using the pre-control, it is possible to approach a new speed setpoint without
overshoot (prerequisite: The torque limiting does not intervene and the moment of inertia
remains constant).
If the speed controller is pre-controlled, then the speed setpoint (r0062) is delayed with the
same smoothing (P1442 or P1452) as the actual value (r1445). This ensures that when
accelerating, there is no setpoint – actual value difference (r0064) at the controller input
which would have been exclusively caused by the signal propagation time.
When the speed pre-control is activated, it must be ensured that the speed setpoint is
continuously entered and without any significant noise level (avoid torque surges). An
appropriate signal can be generated by smoothing the analog signal P0753 or by activating
the rounding-off function of the ramp-function generator P1130 to P1133.
Note
The ramp-up and ramp-down times (P1120, P1121) of the ramp-function generator in the
setpoint channel should only be set so fast that when accelerating and braking, the motor
speed can follow the setpoint. This then guarantees the optimum functioning of the speed
controller pre-control.
The starting time r0345 is a measure for the overall moment of inertia of the machine and
describes that time in which the unloaded motor can accelerate from standstill to the rated
motor speed P0311 with the rated motor torque r0333.
U ຘ ˭ຘ Q ຘ ˭ຘ 3
0RW UDWHG
7VWDUWLQJ ˆຘ 3ຘ 3 ຘ
ຘ 0 ຘ U
0RW UDWHG
If these secondary conditions match the particular application, then the starting time can be
used as the shortest value for the ramp-up and ramp-down times.
'URRS 3
3
PV
U
3 U
3UHFRQWURO
.S 7Q
U
3,
ದ U U
6SHHG
)UHTVHWSRLQW &RQWUROOHU U
ದ
7L 7RUTXH
U U VHWSRLQW
$FWIUHTXHQF\
7L .S 7Q
RQO\DFWLYHLISUHFRQWUROLVHQDEOHG3! 6/9& 3 3 3
9& 3 3 3
Droop is the simplest method to implement load sharing control. However, this load sharing
control can only be used if the motors are operated more or less under steady-state
conditions (i.e. at constant speed). For motors, which are frequently accelerated and braked
with high speed changes, this technique is only conditionally suitable.
The most simple load sharing control is, e.g., used for applications where two or several
motors are mechanically coupled or operate on a common shaft and which have to fulfill the
requirements above. In this case, the droop controls torsional stressing associated with the
mechanical coupling by changing the speeds of the individual motors (excessive torques are
reduced for an individual motor).
Prerequisite
● All of the motors must be operated with closed-loop Vector speed control (with or without
speed actual value encoder)
● The ramp-up and ramp-down times of the ramp-function generator must be identical for
all of the motors.
Data
Description
For sensorless closed-loop speed control SLVC (P1300 = 20) or for closed-loop speed
control with sensor VC (P1300 = 21), it is possible to changeover to closed-loop torque
control (slave motor) using BICO parameter P1501. It is not possible to changeover between
closed-loop speed and torque control if the closed-loop torque control is directly selected
using P1300 = 22 or 23. The torque setpoint and supplementary torque setpoint can be
selected using parameter P1500 and also using BICO parameter P1503 (CI: Torque
setpoint) or P1511 (CI: Supplementary torque setpoint). The supplementary torque acts both
for the closed-loop torque control as well as for the closed-loop speed control (see figure
below). As a result of this feature, a pre-control torque for the speed control can be
implemented using the supplementary torque setpoint.
Note
For safety reasons, it is presently not possible to assign fixed torque setpoints.
'URRS
3UHFRQWURO
.3 7Q
3,
ಥ
VSHHG U U
)UHTVHWSRLQW FRQWUROOHU
ಥ
7L
7RUTXH
U U VHSRLQW
$FWIUHTXHQF\
&,7RUTXHVHWSRLQW
3&
%,යWRUTXHFWUO
3&
&,$GGWUTVHWS
3&
7L .3 7Q
RQO\DFWLYHLISUHFRQWUROLVHQDEOHG3!
6/9& 3 3 3
9& 3 3 3
The sum of both torque setpoints is limited in the same way as the torque setpoint of the
speed control. Above the maximum speed (plus 3%), a speed limiting controller reduces the
torque limits in order to prevent the motor accelerating any further.
A "real" closed-loop torque control (with automatically set speed) is only possible in the
closed-loop controlled range but not in the open-loop controlled range. In the open-loop
controlled range, the torque setpoint changes the setpoint speed through a ramp-up
integrator (integration time ~ P1499 * P0341 * P0342). This is the reason that sensorless
closed-loop torque control in the area around standstill (0 speed) is only suitable for
applications which require an accelerating torque and not a load torque (e.g. traversing
motors). For closed-loop torque control with sensors, this restriction does not apply.
If the closed-loop torque control is active, and a fast stop command (OFF3) is output, then
the system automatically changes-over to closed-loop speed control and braking of the
motor is started. If a normal stop command (OFF1) is output, there is no changeover.
Instead, the system waits until a higher-level control has brought the motor to a standstill, in
order to inhibit the pulses. This is necessary in order to allow the master and slave motors to
be shut down together. For P1300 = 22 or 23, for OFF1, the motor is directly powered-down
(as for OFF2).
Data
Description
Caution
Don't use SS1 or SLS in conjunction with Closed-loop torque control
Closed-loop torque control should not be used in conjunction with the failsafe functions SS1
and SLS, because the speed ramp functions, necesarry for SS1 and SLS are not available
together with the closed-loop torque control. So, if activating SS1 or SLS in case of Closed-
loop torque control, an LSTO will be generated immediately (after the time set in P9680 has
been passed) if the actual frequency exeeds the safety envelope.
The STO can be used with Closed-loop torque control without any restrictions.
The closed-loop torque control is switched-on via parameter P1501 during operation or
selected with parameter P1300 = 22, 23.
Data
Description
All of the following limits act on the torque setpoint which is either entered at the speed
controller output for closed-loop speed control or as torque input for closed-loop torque
control. The minimum is used from the various limits. This minimum is cyclically computed in
the inverter and displayed in parameters r1538, r1539.
● r1538 Upper torque limit
● r1539 Lower torque limit
This means that these cyclic values limit the torque setpoint at the speed controller
output/torque input and indicate the instantaneously maximum possible torque. If the torque
setpoint is limited in the inverter, then this is displayed using the following diagnostic
parameters
● r1407 bit 08 Upper torque limit active
● r1407 bit 09 Lower torque limit active
Torque limiting
The value specifies the maximum permissible torque whereby different limits are
parameterizable for motoring and regenerative operation.
● P1520 CO: Upper torque limit value
● P1521 CO: Lower torque limit value
● P1522 CI: Upper torque limit value
● P1523 CI: Lower torque limit value
● P1525 Scaling, lower torque limit value
The currently active torque limit values are displayed in the following parameters:
● r1526 CO: Upper torque limit value
● r1527 CO: Lower torque limit value
U aಧ aಧ
I I
U
3
3
_IDFW_
&RQVWDQW &RQVWDQW IVWDOO 6WDOO
WRUTXH SRZHU SRZHU
Power limits
This value specifies the maximum permissible power, whereby different limits can be
parameterized for motoring and regenerative operation.
● P1530 Motor power limit
● P1531 Regenerative power limit
Stall limiting
The stall limiting (locked rotor limiting) is internally calculated for the drive from the motor
data.
Current limiting
The current limiting additionally limits the maximum torque which the motor can provide. If
the torque limit is increased, more torque is only available if a higher current can flow. It may
be necessary to also adapt the current limit. The current limiting is influenced by:
● P0640
● Thermal motor protection
● Thermal inverter protection
After limiting, the instantaneous maximum possible inverter current is displayed in parameter
r0067 (limited output current).
Feature Specification
Operating voltage 24 V DC from Power Module or External 24 V DC (20.4 V … 28.8 V,
0.5 A) supply using the control terminals 31 and 32
Control method V/f control, output frequency between 0 Hz and 650 Hz:
(CU type dependent) Linear V/f control, Linear V/f control with FCC, Parabolic V/f control, Multi-
point V/f control, V/f control for textile applications, V/f control with FCC
for textile applications, V/f control with independent voltage setpoint,
Vector control, output frequency between 0 Hz and 200 Hz: Sensorless
Vector Control, Sensorless Vector Torque Control, Speed control with
Encoder feedback, Torque control with Encoder feedback.
PFH (only CU240S DP- PFH (probabillity of failures per hour) value = 1 * 10-7
F)
Fixed frequencies 16 programmable
Skip frequencies 4 programmable
Setpoint resolution 0.01 Hz digital; 0.01 Hz serial; 10 bit analog
(motor potentiometer 0.1 Hz [0.1 % in PID mode])
Digital inputs Up to 9 programmable digital inputs, isolated; PNP, SIMATIC-compatible,
(CU type dependent) low < 5 V, high > 10 V, maximum input voltage 30 V
Analog inputs Up to 2 programmable, both can be configured as additional digital inputs.
(CU type dependent) 0 V … 10 V, 0 mA … 20 mA and -10 V … +10 V (AI0)
0 V … 10 V and 0 mA … 20 mA (AI1)
Relay outputs 3 programmable, 30 V DC / 0 A …0.5 A (resistive)
Analog outputs 2 programmable
AO0: 0 V … 10 V & 0 mA … 20 mA, AO1: 0 mA … 20 mA
Dimensions (BxHxD) 73 mm x 178 mm x 55 mm
Weight 0.52 kg
Technical data
To display information about the current operating state of the inverter and the
communication link, the PROFIBUS DP has three LEDs on the Standard Control Unit and
seven on the Control Unit with fail-safe functions.
Its voltage is supplied through the inverter system connector.
The PROFIBUS DP is connected to the PROFIBUS system using a 9-pin sub-D type socket
according to the PROFIBUS standard. All connections to this interface are short-circuit-proof
and isolated.
The PROFIBUS DP supports baud rates of 9.6 kbaud to 12 Mbaud.
PC Connection Kit
The PC Connection Kit is used to connect a PC (with STARTER software) to the inverter via
the Option port. It consists of a Null modem cable (3 m) and a PC inverter connector module.
To prevent inductive and capacitive interference from effecting the correct function of the
system we recommend the screen termination kit. For correct installation refer to the
installation section.
Electromagnetic compatibility
All manufacturers/assemblers of electrical apparatus which "performs a complete intrinsic
function and is placed on the market as a single unit intended for the end user" must comply
with the EMC directive EC/89/336.
There are three routes for the manufacturer/assembler to demonstrate compliance:
Self-certification
This is a manufacturer's declaration that the European standards applicable to the electrical
environment for which the apparatus is intended have been met. Only standards that have
been officially published in the Official Journal of the European Community can be cited in
the manufacturer's declaration.
EMC Standards
The SINAMICS G120 drives have been tested in accordance with the EMC Product
Standard EN 61800-3:2004.
First Environment
An environment that includes domestic premises and establishments that are connected
directly to a public low-voltage power supply network without the use of an intermediate
transformer.
Note
For example: houses, apartments, commercial premises or offices in a residential building.
Second Environment
An environment that includes industrial premises and establishments that are not connected
directly to a public low-voltage power supply network.
Note
For example: industrial and technical areas of buildings fed from a dedicated transformer.
● Category C1
Power Drive System (PDS) of rated voltage less than 1000 V intended for use in the First
(Domestic) Environment.
● Category C2
Power Drive System (PDS) of rated voltage less than 1000 V, which is neither a plug in
device nor a movable device, and when used in the First (Domestic) Environment, is only
intended to be installed and commissioned by a professional.
Note
A professional is a person or an organization having necessary skills in installing and/or
commissioning a Power Drive System (PDS), including their EMC aspects.
● Category C3
Power Drive System (PDS) of rated voltage less than 1000 V intended for use in the
Second (Industrial) Environment and not intended for use within the First (Domestic)
Environment.
Model Remarks
Category C1 - First Environment
-- The SINAMICS G120 drives are not intended for use within the Category
C1 Environment.
Category C2 - First Environment - Professional Use
Filtered Variants Drives FSB … FSF (400 V, 2.2 kW … 90 kW)
6SL3224-0BE**-*A*0 All units (except FSA) with integral filter.
Class A: 25 m screened cable type CY
The FSA power variant (400 V, 370 W … 1.5 kW) requires either a
footprint filter option (6SE6400-2FA00-6AD0) or additional power-line
filtering at the "system level".
When used in the First (Domestic) Environment this product may cause
radio interference in which case mitigation measures may be required.
Category C3 - Second Environment
Unfiltered Variants All units are available as unfiltered variants.
6SL3224-0BE**-*U*0 The use of unfiltered drives within an industrial installation is only possible
if it forms part of a system which includes additional power-line filtering at
the "system level" or, alternatively, the use of filtered variants.
Note
All drives should be installed and commissioned in accordance with the manufacturer’s
guidelines and in accordance with good EMC practices.
For further information refer to SIEMENS application note "EMC Design Guidelines".
EMC Emissions
The SINAMICS G120 drives have been tested in accordance with the emission requirements
of the category C2 (domestic) environment.
Note
To achieve this performance the default switching frequency should not be exceeded.
In order to achieve conducted emissions to EN 55011 Class B there is a range of PM240
external filter options available.
Achieving radiated emissions to EN 55011 Class B is largely dependent on the drive being
correctly installed inside a metallic enclosure. The limits will not be met if the drive is not
enclosed or installed in accordance with good EMC practices.
Harmonic Currents
The harmonic current emissions from the SINAMICS G120 drives is as follows:
Note
Units installed within the category C2 (domestic) environment require connection to the
public low-voltage power supply network. Please contact your local supply network provider.
Units installed within the category C3 (industrial) environment do not require connection
approval.
EMC Immunity
The SINAMICS G120 drives have been tested in accordance with the immunity requirements
of category C3 (industrial) environment:
Note
The immunity requirements apply equally to both filtered and unfiltered units.
A.4 Standards
Underwriters Laboratories
UL and CUL LISTED POWER CONVERSION EQUIPMENT for use in a pollution degree 2 environment.
Note: UL certification is presently in progress.
ISO 9001
Siemens plc operates a quality management system, which complies with the requirements of ISO 9001.
Overview
Designation
Type
Serial No.
Manufacturer
End customer
Block/overview diagram of the machine
Description
The function test must be carried-out separately for each individual drive
(assuming that the machine permits this to be done).
Checksums
Drive Checksums
Name Drive No. Control unit (r9798) Control unit (r9898)
Data back-up/archiving
Signatures
Commissioning engineer
Confirms that the above listed tests and checks have been correctly carried-out.
Abbreviations State
A
AC Alternating Current
A/D Analog digital converter
ADR Address
AFM Additional frequency modification
AG Automation Unit
AI Analog input
AK Request Identifier
AO Analog output
AOP Advanced operation panel
ASIC Application-specific integrated circuit
ASP Analog setpoint
ASVM Asymmetric space vector modulation
B
BCC Block check character
BCD Binary-coded decimal code
BI Binector input
BIA Berufsgenossenschaftliches Institut für Arbeitssicherheit
BICO Binector/connector
BO Binector output
C
C Commissioning
CB Communication board
CCW Counter-clockwise
CDS Command data set
CI Connector input
CM Configuration management
CMD Command
Abbreviations State
CO Connector output
CO/BO Connector output/Binector output
COM Common (terminal is connected to NO or NC)
CT Commissioning, ready to run
CU Control Unit
CUT Commissioning, run, ready to run
CW Clockwise
D
D/A Digital analog converter
DC Direct current
DDS Drive data set
DI Digital input
DIP DIP switch
DO Digital output
DP Distributed I/Os
DP-V1 Acyclic data transfer (extended PROFIBUS function)
DS Drive state
E
ECD Equivalent circuit diagram
EEC European Economic Community
EEPROM Electrical erasable programmable read-only memory
ELCB Earth leakage circuit breaker
EMC Electromagnetic compatibility
EMF Electromagnetic force
ES Engineering System
FAQ Frequently asked question
F
FB Function block
FFB Freely Assignable Function block
FCC Flux current control
FCL Fast current limiting
FF Fixed frequency
FFB Free function block
FOC Field orientated control
FREQ Frequency
FSA Frame size A
FSB Frame size B
FSC Frame size C
FSD Frame size D
FSE Frame size E
FSF Frame size F
G
Abbreviations State
GSD Device Data File (Geräte Stamm Datei)
GSG Getting Started Guide
GUI ID Global unique identifier
H
HIW Main actual value
HMI Human machine interface
HO High Overload (Constant Torque)
HSW Main setpoint
HTL High-voltage transistor logic
I
I/O In-/output
IBN Commissioning
IGBT Insulated gate bipolar transistor
IND Sub-index
J
JOG JOG
K
KIB Kinetic buffering
L
LCD Liquid crystal display
LED Light emitting diode
LGE Length
LO Light Overload (Variable Torque)
LWL Fiber Optic conductor
LSTO Latched Safe Torque Off
M
MHB Motor holding brake
MLP Multi-Language Pack
MOP Motor operated potentiometer
N
NC Normally closed
NEMA National Electrical Manufacturers Association
NO Normally open
O
OLM Optical Link Module
OLP Optical Link Plug
OM Object Manager
OP Operator Panel
OPI Operating Instructions
PA
PID Proportional, integral, derivative controller
PKE Parameter ID
Abbreviations State
PKW Parameter ID value area (Parameterkennung Wert)
PLC Programmable logic control
PM Power module
PM-IF Power module interface
PNU Parameter Number
PNO PROFIBUS Nutzerorganisation
PPO Parameter process data object
PTC Positive temperature coefficient
PWE Parameter value
PWM Pulse-width modulation
Pxxxx Write parameter
PZD Process data area (Prozeßdaten)
Q
QC Quick commissioning
R
RAM Random-access memory
RCCB Residual current circuit breaker
RCD Residual current device
RFG Ramp-function generator
RFI Radio frequency interference
ROM Read-only memory
RPM Revolutions per minute
rxxxx read-only parameters of analogue signals
S
SBC Safe Break Control
SLVC Sensorless vector control
SLS Safe-Limited Speed
SOL Serial option link
SS1 Safe Stop 1
STO Safe Torque Off
STW Control word
STX Start of text
SVM Space vector modulation
T
TTL Transistor-transistor logic
U
USS Universal serial interface
V
V/f Voltage/frequency
VC Vector control
VT Variable torque
W
Abbreviations State
WEA Automatic restart
Z
ZSW Status word
ZUSW Additional setpoint
D
A Data sets, 8-6
Acceptance test, 5-75 DC braking, 8-82
Accessories DC link overvoltage, 8-138
Multi Media Card (MMC), 10-1 DC link undervoltage, 8-138
Operator Panel (OP), 10-1 Device-specific telegrams, 5-83
PC Connection Kit, 10-1 Digital inputs, 8-13
Screen Termination Kit, 10-2 Fixed frequencies, 8-37
Alarm messages, 7-3 Digital outputs, 8-16
Analog inputs, 8-18 Download parameters, 5-47, 5-48
Analog outputs, 8-20 Droop, 8-179
Dynamic braking, 8-88
B
E
BICO parameterization, 8-15
BICO technology, 8-3 Electromagnetic compatibility, A-1
Binector Connector Technology, 8-3 Electronic brakes, 8-82
blackout, 8-93 EMC precautions, 4-15
brownout, 8-93 EMC Standards, A-1
Bus terminator, 4-14 European EMC Directive, A-6
European Low Voltage Directive, A-6
European Machinery Directive, A-6
C Extended configuration for the SINAMICS G120, 5-82
Extended PROFIBUS DP functionality, 5-92
Calculating the motor/control data, 5-29
Changing parameters with the Operator Panel, 5-14
Chip temperature, 8-158
Classification of EMC performance, A-2
F
Closed-loop control, 8-160 Factory setting, 5-10
Closed-loop torque control, 8-180 Reset to, 5-60
Closed-loop Vdc control, 8-138 Fault messages, 7-3
Commissioning, 5-108 Fitting the Control Unit to the Power Module, 4-2
Commissioning functions, 3-3 Fixed frequencies, 8-37
Commissioning the application, 5-31 Flying restart, 8-96
Common features, 3-3 Flying restart with speed encoder, 8-98
Flying restart without speed encoder, 8-97 Motor data identification, 5-26
Forced dynamisation, 8-102 Motor holding brake, 8-78
Free function blocks, 8-69 Motorized potentiometer, 8-48
G N
General I/O DIP switches, 3-13 Normal Status LEDs, 7-6
H O
Heatsink temperature, 8-158 OP, 5-46, 5-47, 5-53
Open-loop control, 8-160
Operating functions, 3-4
I Options for SINAMICS G120, 3-2
Overload responses, 8-150, 8-158
I/O DIP switch, 8-18
i2t monitoring, 8-158
Imax controller, 8-168
Inputs and outputs, 8-13
P
Installation of PROFIBUS DP, 4-11 Parameter
Installing a G120 GSD file, 5-99 upload, 6-2
ISO 9001, A-6 Parameters
Access level, 5-5
Active, 5-8
J Atrributes, 5-4
BICO, 5-5
JOG, 8-50
Change state, 5-6
Data sets, 5-9
Data types, 5-6
K Grouping, 5-8
Kinetic buffering, 8-141 Quick commissioning, 5-9
KTY84 temperature sensor, 8-156 Unit, 5-7
Value range, 5-9
PID controller, 8-52
L PID dancer roll control, 8-56
PID fixed setpoint, 8-54
Limiting the torque setpoint, 8-183
PID motorized potentiometer, 8-54
Line failure, 8-93
PKW mechanism for processing parameters, 8-28
Line undervoltage, 8-93
Positioning ramp down, 8-143
Load torque monitoring, 8-147
Power module protection, 8-157
Power Modules
Fitting the Control Unit to the, 4-2
M Process dynamisation, 8-102
Manufacturer-specific telegrams, 5-83 PROFIBUS DP
Maximum cable lengths, 4-12 Extended functionality, 5-92
MMC PROFIBUS DP
Manual download, 5-54 Setting the address, 5-77
Upload, 5-53, 6-7 Switch over behavior, 5-86
Modification - frequency setpoint, 8-59 PROFIBUS DP
Monitoring functions / messages, 8-145 Conversion of extended functionality, 5-93
Monitoring parameters, 5-3 PROFIBUS DP DIP switches, 3-14
Monitoring the fail-safe functions, 8-101 PROFIBUS DP Interface, 4-10
www.siemens.de/sinamics-g120
Preface
Approbation
see chapter A.1 General technical data
CE label
see chapter A.1 General technical data
DP/DP Coupler
iv A5E00244669-03
Preface
Manual guide
This manual is organized by the following topics:
• Product overview and description of the DP/DP Coupler
• Installation, wiring and commissioning
• Operation and diagnostics
• Appendices
• Important terminology is explained in the glossary.
• The index will help you to quickly find text passages associated with specific
keywords.
Additional support
If you have any questions on the use of the product described in this manual that
are not answered here, please contact your local Siemens partner or branch office.
http://www.siemens.com/automation/partner
GSD files are available to you the Internet:
NOTICE:
Changed Link! http://www.ad.siemens.de/csi_e/gsd
http://support.automation.siemens.com/WW/view/en/23641045/130000
Training center
We offer courses for newcomers to the field of automation engineering. Please
contact your regional training center or the central training center in
D-90327 Nuernberg.
Phone: +49 (911) 895-3200.
Internet: http://www.sitrain.com
DP/DP Coupler
A5E00244669-03 v
Preface
Nuernberg
Johnson City
Beijing
Technical Support
Worldwide (Nuernberg)
Technical Support
The languages of the SIMATIC Hotlines and the authorization hotline are generally German and English.
DP/DP Coupler
vi A5E00244669-03
Preface
DP/DP Coupler
A5E00244669-03 vii
Preface
DP/DP Coupler
viii A5E00244669-03
Contents
Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iii
1 Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
1.1 Field of application and function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
1.2 Compatibility to precursor modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
2.1 Installation principles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
2.2 Installing the P/DP Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
3 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.1 Electrical isolation and grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.1.1 General rules and regulations for operation . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
3.1.2 Operation on a grounded power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
3.2 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
3.3 Connecting the power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
3.4 Connecting PROFIBUS DP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
4 Configuring and commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
4.1 What are my steps in configuring the DP/DP Coupler? . . . . . . . . . . . . . . . 4-2
4.2 Setting the DIL switch on the DP/DP Coupler . . . . . . . . . . . . . . . . . . . . . . . 4-3
4.2.1 Setting the “PS” DIL switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
4.2.2 Setting the “DIA” DIL switch (data validity indication) . . . . . . . . . . . . . . . . . 4-4
4.2.3 Setting the “ADDR” DIL switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
4.2.4 Setting the PROFIBUS address on the DIL switch . . . . . . . . . . . . . . . . . . . 4-6
4.3 Configuring the DP/DP Coupler in STEP 7 . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
4.3.1 Configuring the DP/DP Coupler in STEP 7 . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
4.3.2 Setting the PROFIBUS address in STEP 7 . . . . . . . . . . . . . . . . . . . . . . . . . 4-10
4.3.3 Setting the properties of the DP/DP Coupler in STEP 7 . . . . . . . . . . . . . . . 4-11
4.3.4 Example of a configuration of the DP/DP Coupler I/O in STEP 7 . . . . . . . 4-12
4.4 Configuring the DP/DP Coupler with another engineering tool . . . . . . . . . 4-13
4.5 Commissioning the DP/DP Coupler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-14
5 Operation of the DP/DP Coupler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
5.1 Replacement of a faulty DP/DP Coupler . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
5.2 Response times of the DP/DP Coupler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
DP/DP Coupler
A5E00244669-03 ix
Contents
6 Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
6.1 Diagnostics by means of LED indication . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
6.2 Diagnostics by means of the user program . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
6.2.1 Structure of the slave diagnosis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
6.2.2 Standard diagnosis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6
6.2.3 Status message (module diagnostics) – only for operation on a
DP master (DPV1) or S7 DP master . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-8
6.2.4 Module diagnostics - replacement part mode or operation on a
DP master (DPV0) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-10
6.3 Example of a diagnosis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-11
6.3.1 Task . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-11
6.3.2 Solution with STEP 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-12
A Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
A.1 General technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
A.1.1 Standards and approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2
A.1.2 Electromagnetic compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-6
A.1.3 Transportation and storage conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-8
A.1.4 Mechanical and climatic ambient conditions for operation . . . . . . . . . . . . . A-9
A.1.5 Data on insulation tests, protection class and degree of protection . . . . . A-11
A.1.6 Rated voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-11
A.2 Technical data of the DP/DP Coupler (6ES7 158-0AD01-0XA0) . . . . . . . . A-12
A.3 Use of the DP/DP Coupler in potentially explosive environments
of Zone 2 (in all official EU languages) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-13
B Order numbers and accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
Glossary
Index
DP/DP Coupler
x A5E00244669-03
Contents
Figures
1-1 DP/DP coupling of two PROFIBUS DP networks . . . . . . . . . . . . . . . . . . . . 1-1
1-2 Function principle of the DP/DP Coupler (example) . . . . . . . . . . . . . . . . . . 1-2
1-3 Operator and display elements of the DP/DP Coupler . . . . . . . . . . . . . . . . 1-3
2-1 Remove the slide on the bottom of the module before you install it on
the S7 system rail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
3-1 Termination of the PROFIBUS cable shielding on the grounded
shielding busbar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
3-2 Configuration with a grounded supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
3-3 Connections of the DP/DP Coupler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
3-4 Power supply für den DP/DP Coupler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
4-1 Example of DIL switch settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
4-2 Example: Configuration of the DP/DP Coupler on network 1 . . . . . . . . . . . 4-12
4-3 Example: Configuration of the DP/DP Coupler on network 2 . . . . . . . . . . . 4-13
6-1 Status / error displays of the DP/DP Coupler . . . . . . . . . . . . . . . . . . . . . . . . 6-2
6-2 Structure of the standard diagnosis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6
6-3 Structure of module diagnostics (DPV1 / S7 DP master) . . . . . . . . . . . . . . 6-9
6-4 Structure of module diagnostics (replacement part mode or operation
on a DP master (DPV0)) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-10
6-5 Example of the analysis of diagnostics data from the DP/DP Coupler . . . 6-11
Tables
4-1 How to configure the DP/DP Coupler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
4-2 Meaning of the ”DIA” switch positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
6-1 Meaning of the LEDs ON 1 and ON 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
6-2 Status / error messages of the DP/DP Coupler . . . . . . . . . . . . . . . . . . . . . . 6-3
6-3 Length and start addresses of the diagnostics blocks for operation
on a DP master (DPV1) or S7 DP master . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5
6-4 Length and start addresses of the diagnostic blocks in
replacement mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5
6-5 Structure of station status 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6
6-6 Structure of station status 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7
6-7 Structure of station status 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7
6-8 Structure of the device identifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-8
6-9 Call of the SFC 13 (DPNRM_DG) in the OB 1 . . . . . . . . . . . . . . . . . . . . . . 6-12
6-10 Example: Analysis of the diagnostics data . . . . . . . . . . . . . . . . . . . . . . . . . . 6-13
A-1 Use in industrial environments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-4
A-2 Pulse-type interference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-6
A-3 Sinusoidal interference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-7
A-4 Transportation and storage conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-8
A-5 Mechanical ambient conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-9
A-6 Test for mechanical ambient conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-10
A-7 Climatic ambient conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-10
A-8 Test voltages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-11
B-1 Order numbers for the DP/DP Coupler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
DP/DP Coupler
A5E00244669-03 xi
Contents
DP/DP Coupler
xii A5E00244669-03
Product Overview 1
1.1 Field of application and function
Field of application
DP/DP Coupler is used to interconnect two PROFIBUS DP networks in order to
enable the transfer of data between the master of both networks.
The maximum length of transferred data consists of 244 bytes of input data and
244 bytes of output data.
PG
S7-400
S7-300
DP/DP Coupler
ET 200X S7-300 ET 200L Drive
ET 200S
Configuration
You configure the DP/DP Coupler using either STEP 7 or a programming tool that
integrates the DP/DP Coupler by means of a GSD file.
In STEP 7, you can set up the required length of input and output data. The output
data on one side of the DP/DP Coupler form the input data of the other, and vice
versa.
In STEP 7, define the I/O data areas based on the slot IDs.
DP/DP Coupler
A5E00244669-03 1-1
Product Overview
Example
The example below shows the independence of both networks. That means, you
configure a separate PROFIBUS address for each PROFIBUS DP network.
In the figure below, that is PROFIBUS address 3 in network 1, and PROFIBUS
-address 50 in network 2.
DP/DP Coupler
8 bytes PROFIBUS
PROFIBUS 8 bytes 8 bytes address 50
address 3
Both networks may operate at different baud rates. The rate at which network 1
writes data to the output buffer is slower than the rate at which network 2 reads
these data. Hence, network 2 reads the same data successively. The effect is the
reverse when data are transferred from network 2 to network 1. The output buffer
will be overwritten several times before network 1 reads the data buffer. This
means that only the currently written data are available.
Notice
You need to balance the I/O area of both networks.
DP/DP Coupler
1-2 A5E00244669-03
Product Overview
Appearance
The figure below shows the DP/DP Coupler and its operator and display elements:
SIEMENS
Features
Properties of the DP/DP Coupler:
• Maximum length of data exchanged consists of 244 bytes input data and 244
bytes of output data, of which up to 128 bytes are consistent
• Up to 16 I/O areas for data exchange
• If one side fails, the output values of the other are retained
• DPV1 is supported with full and uniform diagnostic functions
• PROFIBUS address setting either via selector switch on the DP/DP Coupler, or
in STEP 7, or by means of another programming tool
• Different transmission rates and PROFIBUS addresses on both sides of the
DP/DP Coupler
• Electrical isolation between the DP networks
• Dual power supply
DP/DP Coupler
A5E00244669-03 1-3
Product Overview
DP/DP Coupler
1-4 A5E00244669-03
Installation 2
Overview of contents
Mounting position
The mounting position of the DP/DP Coupler is user–specific. Please note, that the
ambient temperature may not exceed 60 C when the device is mounted vertically,
and for all other mounting positions 40 C.
For further information on operational conditions, refer to chapter A.1.
Open equipment
The DP/DP Coupler is an open device. It may only be installed in cubicles,
cabinets or electrical control rooms which can only be accessed by means of a key
or a tool. Only trained or authorized personnel should have access to the housings,
cabinets or electrical control rooms.
Mounting system
The DP/DP Coupler may be mounted on a DIN rail (7.5 mm and 15 mm), or on an
S7 system profile rail . Ample free space of at least 40 mm above and below the
module should be provided for the installation.
For more information on installing S7 modules, refer to the S7-300 Programmable
Controller, Installation manual.
DP/DP Coupler
A5E00244669-03 2-1
Installation
Components required
• DP/DP Coupler
• Profile rail:
– DIN rail (7.5 mm or
– 15 mm), or
– a rail for the S7 mounting system
Component order nos. are found in appendix B.
Step Activity
1 When you install the DIN rail, make sure you provide at least 40 mm of free
space above and below the modules in order to allow easy installation and the
deflection of heat.
Note: Always ensure a low–impedance connection between the DIN rail and
the grounded sheet metal plate or mounting panel. For the installation on
varnished or galvanized sheet metal you should use a suitable contact agent or
contact disks, for example.
2 Hang the DP/DP Coupler onto the DIN rail and then swing it down.
3 Screw–tighten the DP/DP Coupler.
4 Wire the DP/DP Coupler as described in chapter 3.
DP/DP Coupler
2-2 A5E00244669-03
Installation
Installing the DP/DP Coupler on a profile rail for the S7 installation system
Step Activity
1 When you install the S7 profile rail, make sure you provide at least 40 mm of
free space above and below the modules in order to allow easy installation and
the deflection of heat.
Note: Always ensure a low–impedance connection between the DIN rail and
the grounded sheet metal plate or mounting panel. For the installation on
varnished or galvanized sheet metal you should use a suitable contact agent or
contact disks, for example.
2 Remove the slide from the bottom of your DP/DP Coupler with the help of a
screwdriver (see fig. 2-1).
3 Hang the DP/DP Coupler onto the S7 profile rail and then swing it down.
4 Screw–tighten the DP/DP Coupler.
5 Wire the modules as described in chapter 3.
Figure 2-1 Remove the slide on the bottom of the module before you install it on the S7
system rail
DP/DP Coupler
A5E00244669-03 2-3
Installation
DP/DP Coupler
2-4 A5E00244669-03
Wiring 3
Overview of contents
This chapter informs you of general requirements for wiring the DP/DP Coupler
and of the connections you need.
Overview of contents
DP/DP Coupler
A5E00244669-03 3-1
Wiring
Note
The DP/DP Coupler must be operated on a grounded 24 V DC power supply. It
can not be operated on an ungrounded 24 V DC power supply!
Introduction
When the described modules are used in a system, certain rules and regulations
must be followed that depend on the area of application.
This section provides an overview of the most important rules that must be
observed for safe integration in a system.
Specific applications
Please comply with the safety and accident prevention regulations (e.g. machine
protection guidelines) that are valid for specific applications.
EMERGENCY–OFF equipment
EMERGENCY-OFF equipment to IEC 6204 (corresponds with DIN VDE 113) must
retain an operational state in all operating modes of then system or plant.
DP/DP Coupler
3-2 A5E00244669-03
Wiring
Note
For information on lightning protection, refer to the S7–300 PLC; Installation
installation manual.
DP/DP Coupler
A5E00244669-03 3-3
Wiring
Switch cabinet
Figure 3-1 Termination of the PROFIBUS cable shielding on the grounded shielding
busbar
DP/DP Coupler
3-4 A5E00244669-03
Wiring
L1 Low-voltage distribution, e. g.
L2
L3 TN-S system (3 x 400 V)
N
PE
Cabinet
Rail DP/DP Coupler
L+
AC
DC
M
Logic
L+
AC
DC
M
DP/DP Coupler
A5E00244669-03 3-5
Wiring
3.2 Connections
PROFIBUS DP
network 2
24 V DC 24 V DC PROFIBUS DP
from from network 1
network 1 network 2
DP/DP Coupler
3-6 A5E00244669-03
Wiring
Required tool
To connect the power supply, you require a 3 mm screwdriver.
Note
The diagnostic system shows you whether the DP/DP Coupler is connected to the
24 V DC power supply or not. Always set the “PS” switch on the DP/DP Coupler to
the correct position!
For further information on the DIL switch settings, refer to chapter 4.2.
DP/DP Coupler
A5E00244669-03 3-7
Wiring
The maximum conductor cross-section is 2.5 mm2. A cable strain relief is not
provided.
Step Activity
1 Strip the wires to a length of 10 mm.
2 Connect the wires to the 2–pin screw terminals of the connector. This connector
is plugged into the power supply socket on the supplied unit.
When a dual power supply is available for the DP/DP Coupler, you should
connect both.
If you only have one, you should preferably connect it to PS2.
3 Plug the wired 2–pin connector into the power supply socket of your DP/DP
Coupler.
4 Set the “PS” selector switch on the DP/DP Coupler:
• L+/M (PS1) connected to 24 V DC: Selector switch PS (DP1) to “ON”
• L+/M (PS2) connected to 24 V DC: Selector switch PS (DP2) to “ON”
The selector switch “PS” must be set properly in order to allow the correct
evaluation of diagnostic data in STEP 7!
Required tool
You need a screwdriver with a blade width of 3 mm to install the bus connector to
the DP/DP Coupler.
Procedure
To connect PROFIBUS DP:
1. Insert the bus connector into the PROFIBUS socket.
2. Tighten the mounting screws on the bus connector.
DP/DP Coupler
3-8 A5E00244669-03
Configuring and commissioning 4
Contents
This chapter shows you the steps in commissioning the DP/DP Coupler. Details
are found in the relevant subsections.
DP/DP Coupler
A5E00244669-03 4-1
Configuring and commissioning
DP/DP Coupler
4-2 A5E00244669-03
Configuring and commissioning
Contents
Note
The DP/DP Coupler accepts all changes immediately.
DP/DP Coupler
A5E00244669-03 4-3
Configuring and commissioning
The function uses the first bit of the LSB byte of the first configured input byte:
• Bit 1 (LSB inputs) = 1: Data from DP/DP Coupler are valid
• Bit 1 (LSB inputs) = 0: Data from DP/DP Coupler are invalid
Example
• Network 1: 8 byte input data – 16 byte output data
• Network 2: 16 byte input data – 8 byte output data
The first bit of the 8 byte of input data indicates validity of data from network 2, the
first bit of the 16 byte input data indicates validity of data from network 1.
DP/DP Coupler
4-4 A5E00244669-03
Configuring and commissioning
Warning
! When “DIA” is in “ON” position, you may not use the first bit in the LSB of the first
configured input byte for normal input data!
We advise you not to use the first byte of the input data for the inputs when using
the data validity indication function!
Note
The DP/DP Coupler accepts all changes immediately.
Setting “ADDR”
Set the relevant position of the “ADDR” DIL switch for both sides of the
DP/DP Coupler:
• “ADDR” in “OFF” position: The PROFIBUS address is set directly on the
DIL switch of the DP/DP Coupler.
For further information, refer to chapter 4.2.4.
• “ADDR” in “ON” position: The PROFIBUS address is assigned in the STEP 7
program.
For further information, refer to chapter 4.3.2.
DP/DP Coupler
A5E00244669-03 4-5
Configuring and commissioning
Definition
Each bus node must receive a PROFIBUS address so that it can be uniquely
identified on PROFIBUS-DP. The PROFIBUS address is set separately for both
PROFIBUS DP networks directly on the DIL switches of the DP/DP Coupler.
Note:
You can also assign the PROFIBUS address in STEP 7 (cf. chapter 4.3.2).
Rules
Rules for the assignment of a PROFIBUS address:
• Valid PROFIBUS address range: 1 to 125.
• All PROFIBUS addresses assigned must be unique within the DP master
system.
• You assign a PROFIBUS address to each side of the DP/DP Coupler. It is also
possible to assign the PROFIBUS address for one side of the DP/DP Coupler
directly on the Link, and the other in STEP 7.
Required tool
To set the PROFIBUS address, you require a 3 mm screwdriver.
Step Activity
1 Switch off the 24 V DC power supply to the DP/DP Coupler.
2 Open the front panel door of the DP/DP Coupler.
3 Set the required PROFIBUS address with a screwdriver. The PROFIBUS
address is formed by the sum of all values of the switches in “ON” position
(switch in right position).
4 Set the ADDR DIL switch to the left (“OFF” position).
Result: The PROFIBUS address is read from the DIL switch position, rather
than from the non–volatile memory of the DP/DP Coupler.
5 Switch on the 24 V DC power supply to the DP/DP Coupler.
Result: The DP/DP Coupler applies the PROFIBUS address you have set on
the switch.
DP/DP Coupler
4-6 A5E00244669-03
Configuring and commissioning
DP/DP Coupler
PROFIBUS address network 1: PROFIBUS address network 2:
DP1 DP2 64
2 64 + 32
+1 32 +2
16
=3 +1
8
4 = 99
2
ADDR = ON: STEP 7 writes the ADDR = OFF: The PROFIBUS
1
PROFIBUS address to the ADDR
address is fetched from the DIL
DP/DP Coupler DIA switch
PS
DIA = OFF: Data validity DIA = ON: Data validity indication
ON ON
indication is disabled is enabled
PS = ON: 24 V DC of network 1 PS = ON: 24 V DC of network 2
is connected is connected
Note
The changes are not applied to the DP/DP Coupler until you have cycled the
24 V DC supply (off/on).
DP/DP Coupler
A5E00244669-03 4-7
Configuring and commissioning
Contents
Prerequisites
You require the GSD file SI018070.GS? in order to be able to program the
DP/DP Coupler in STEP 7. Integrate this GSD file into your engineering tool.
This GSD file is included in STEP 7 V5.3 and higher.
GSD file
A GSD file (SI018070.GS?) is available for the DP/DP Coupler. You can download
this file free of charge from the Internet, under:
http://www.ad.siemens.de/csi_e/gsd
DP/DP Coupler
4-8 A5E00244669-03
Configuring and commissioning
Notice
You need to balance the I/O area of both networks.
Step Activity
1 Start STEP 7 and open HW Config.
2 Drag–and–drop the DP/DP Coupler from the hardware catalog in the folder
PROFIBUS-DP\Further FIELD DEVICES\Gateway\DP/DP Coupler, Release 2
to the PROFIBUS network.
Result: The properties dialog box for the PROFIBUS interface of the
DP/DP Coupler appears.
3 Set the PROFIBUS address of the DP/DP Coupler. This address must
correspond with the PROFIBUS address set on the DP/DP Coupler. Confirm
your entries with OK.
Result: The DP/DP Coupler is added to the DP master system.
4 Now you configure the slots of the DP/DP Coupler
Starting at slot 1, type in the relevant DP IDs for the input or output data. I you
are using I/O data in mixed mode, use a universal DP identifier module.
5 Type in the input and/or output address for each slot.
6 Confirm your entries with “OK”.
Result: You have now configured one side of the DP/DP Coupler.
7 Repeat steps 2 to 6 for the second PROFIBUS DP system connected to the
DP/DP Coupler.
Important
• Network 1 inputs are outputs of network 2,
• Network 1 outputs are inputs of network 1,
Note
Only with configuration of both sides of the DP/DP Coupler
6ES7 158-0AD01-0XA0:
If your slot configuration (of inputs and outputs) is incongruent, the DP/DP Coupler
reports a configuration error to the networks 1 and 2.
DP/DP Coupler
A5E00244669-03 4-9
Configuring and commissioning
Requirements
The DP/DP Coupler has been configured in STEP 7(cf. chapter 4.3.1).
Definition
Each bus node must receive a PROFIBUS address so that it can be uniquely
identified on PROFIBUS-DP. The PROFIBUS address is set in STEP 7 separately
for each on of the two PROFIBUS DP networks.
Note:
You can also set the PROFIBUS address directly on the DIL switches of the
DP/DP Coupler (cf. chapter 4.2.4).
Rules
Rules for the assignment of a PROFIBUS address:
• The valid PROFIBUS addresses are: 1 to 125.
• Each PROFIBUS address can only be assigned once in a DP master system.
• You assign a PROFIBUS address to each side of the DP/DP Coupler. It is also
possible to assign the PROFIBUS address for one side of the DP/DP Coupler
directly on the Link, and the other in STEP 7.
Step Activity
1 Set the ADDR DIL switch to the left “ON” position.
Result: The PROFIBUS address is fetched from the non–volatile memory area
in the DP/DP Coupler.
2 Switch on the 24 V DC power supply to the DP/DP Coupler.
Result: The LEDs ON1 and/or ON2 are lit.
3 Connect the PG/PC via PG cable to the DP network or to the DP/DP Coupler.
4 Open STEP 7 HW Config and configure the DP/DP Coupler.
5 In HW Config, select the configured DP/DP Coupler.
6 Go to PLC > PROFIBUS > Assign PROFIBUS address.
Result: The “PROFIBUS address” view appears.
7 Enter the configured PROFIBUS address and confirm with “OK”.
Result: The PROFIBUS address is transferred to the non–volatile memory of
the DP/DP Coupler.
DP/DP Coupler
4-10 A5E00244669-03
Configuring and commissioning
Properties – DP slave
In the ”Configuration“ tab of the ”Properties – DP slave” dialog box, you can set the
following properties:
• “Configuration” tab:
– DP alarm mode: DPV0 or DPV1 slave
– Permit external diagnostics
DP/DP Coupler
A5E00244669-03 4-11
Configuring and commissioning
Introduction
This example shows a typical configuration of the DP/DP Coupler using STEP 7.
Task
The following assumptions have been made for this example:
• Network 1:
– The DP/DP Coupler is assigned PROFIBUS address 4.
– To be transferred to the DP master on network 2:
2 bytes inputs (inconsistent)
16 bytes outputs (inconsistent)
8 bytes inputs (consistent)
2 bytes outputs (consistent)
3 bytes inputs / 5 bytes outputs (consistent)
• Network 2:
– The DP/DP Coupler is assigned PROFIBUS address 24.
– To be transferred to the DP master on network 1:
2 bytes outputs (inconsistent)
16 bytes inputs (inconsistent)
8 bytes outputs (consistent)
2 bytes inputs (consistent)
5 bytes inputs / 3 bytes outputs (consistent)
DP/DP Coupler
4-12 A5E00244669-03
Configuring and commissioning
GSD file
A GSD file (SI018070.GS?) is available for the DP/DP Coupler. You can download
this file free of charge from the Internet, under:
http://www.ad.siemens.de/csi_e/gsd
assignment frame
The frame has a length of 15 bytes. Information on the parameter assignment
frame is available on the Internet, under:
http://www.ad.siemens.de/csi_e/gsd
DP/DP Coupler
A5E00244669-03 4-13
Configuring and commissioning
Requirements
Conditions to be met before you commission the DP/DP Coupler:
• You have installed and wired the DP/DP Coupler as described in chapters 2 and
3.
• You have installed both PROFIBUS DP networks. PROFIBUS DP is ready for
operation.
• You have programmed the DP/DP Coupler.
Step Activity
1 Switch on the power supply to the DP/DP Coupler.
2 Download the configuration data to the PLC by executing the PLC > Download
to module command.
DP/DP Coupler
4-14 A5E00244669-03
Operation of the DP/DP Coupler 5
Overview of contents
Step Activity
1 Disconnect the bus connectors from the PROFIBUS DP interfaces.
2 Disconnect the faulty DP/DP Coupler from the power supply.
3 Replace the faulty DP/DP Coupler.
4 Connect the new DP/DP Coupler to the power supply.
5 Connect the PROFIBUS DP interfaces of the new DP/DP Coupler.
Overview
The chapter below shows you the average time required for the transfer of data
from the DP master on network 1 to the DP master on network 2 via
DP/DP Coupler.
DP/DP Coupler
A5E00244669-03 5-1
Operation of the DP/DP Coupler
Response times
The interval expiring between the time data from a DP master are written to the
process image of outputs unit and the time until these can be read in the process
image of the second DP master depends on the following variables:
• CPU scan cycle time of both DP masters
• Bus cycle time of the corresponding DP masters
• Copy cycle within the DP/DP Coupler (TCOPY)
• Overall data length [in bytes] (input/output)
The copy cycle of the DP/DP Coupler is independent of the currently set data
transfer rate.
The following applies:
TCOPY = 1 ms + n x 7 ms
The measurement for the formula above is performed based on the following
criteria:
• CPU 416-2 DP
• Bus cycle time 6 ms
• Data length (n) 1 ... 488 bytes
• Data transfer rate of 12 Mbps
• In the measurement we use neither cyclic diagnostic functions, nor any global
control commands (FREEZE, SYNC).
Note
The copy cycle can usually be neglected when operating at low data transfer
rates.
DP/DP Coupler
5-2 A5E00244669-03
Diagnostics 6
Overview of contents
This chapter shows you the meaning of the LED displays on your DP/DP Coupler.
The tables provide information on error states indicated by the LEDs, the possible
causes and suggested corrective measures.
In the next section, you are made familiar with the diagnostic system of the
DP/DP Coupler. An example is used to illustrate the evaluation of a diagnostic
frame.
DP/DP Coupler
A5E00244669-03 6-1
Diagnostics
ON 1 ON 2 Meaning What to do
Off Off • Voltage not present at DP/DP • Switch the power supply
Coupler, module on.
• Applied supply voltage is not • Check the applied voltage.
within permissible range.
• Hardware fault on the DP/DP • Replace the DP/DP Coupler.
Coupler
On Off The DP/DP Coupler is supplied –
with power from network 1.
Off On The DP/DP Coupler is supplied –
with power from network 2.
On On The DP/DP Coupler is supplied –
with power from network 1 and 2.
DP/DP Coupler
6-2 A5E00244669-03
Diagnostics
DP/DP Coupler
A5E00244669-03 6-3
Diagnostics
Contents
This chapter describes the structure of the DP/DP Coupler diagnostics system. An
example is used to illustrate the evaluation of a diagnostic frame.
Slave diagnosis
Slave diagnosis is performed in accordance with IEC 61784-1:2002 Ed1 CP 3/1.
Depending on the DP master, it can be read out with STEP 7 or other engineering
tools.
In STEP 7, the diagnostic frames of the underlying DP slaves can be displayed in
the online view of the HW Config. See “Diagnosing hardware” in the STEP 7 online
help.
Additional methods of reading out diagnostic information are described in the
SIMATIC Software; Programming with STEP 7 V5.x manual.
Influencing factors
The structure of slave diagnostics data depends on which DP master the
DP/DP Coupler is operating. The DP/DP Coupler operates either:
• on the DP master (according with DPV0)
• on the DP master (according with DPV1)
• on the S7 DP master
• in replacement part mode for the DP/DP Coupler 6ES7 158-0GG30-0XA0
DP/DP Coupler
6-4 A5E00244669-03
Diagnostics
Table 6-3 Length and start addresses of the diagnostics blocks for operation on a DP master (DPV1) or
S7 DP master
Table 6-4 Length and start addresses of the diagnostic blocks in replacement mode
Diagnostic blocks
The structure of diagnostic blocks is described in the following chapters.
DP/DP Coupler
A5E00244669-03 6-5
Diagnostics
Byte 0
Byte 1 Station statuses 1 to 3
Byte 2
Byte 4
Device identifier
Byte 5
Station status 1 to 3
Station status 1 to 3 provides an overview of the DP/DP Coupler status.
DP/DP Coupler
6-6 A5E00244669-03
Diagnostics
Bit Meaning
0 1: The DP/DP Coupler must be assigned new parameters.
1 1: A diagnostic message is queued. The DP/DP Coupler can not resume RUN
until the error is rectified (static diagnostic message).
2 1: This bit is always set to ”1”.
3 1: Response monitoring is enabled on the DP/DP Coupler.
4 1: The DP/DP Coupler has received a “FREEZE” control command.
5 1: The DP/DP Coupler has received a “SYNC” control command.
6 0: This bit is always set to “0”.
7 0: This bit is always set to “0”.
Bit Meaning
0 to 7 0: These bits are always set to “0”.
DP/DP Coupler
A5E00244669-03 6-7
Diagnostics
Device identifier
The device ID is a code that uniquely identifies the DP slave
(PROFIBUS ID number).
Note
Bytes 6 to 16 of the diagnostics dat are reserved!
DP/DP Coupler
6-8 A5E00244669-03
Diagnostics
7 6 5 4 3 2 1 0 Bit no.
Byte 17 0 0 0 0 1 0 0 1
7 6 5 4 3 2 1 0 Bit no.
Byte 24
Reserved
1: The CPU of the other DP network has output a
CLEAR command (sets outputs to “0”)
1: The other segment has changed to UNFREEZE state
1: The other segment has changed to FREEZE state
1: The other segment has changed to UNSYNC state
1: The other segment has changed to SYNC state
Reserved
7 6 5 4 3 2 1 0 Bit no.
Byte 25 0 0 0 0 0 0
DP/DP Coupler
A5E00244669-03 6-9
Diagnostics
7 6 5 4 3 2 1 0 Bit no.
Byte 6 0 0 0 0 0 1 0 1
7 6 5 4 3 2 1 0 Bit no.
Byte 10
Reserved
1: The CPU of the other DP network has output a
CLEAR command (sets outputs to “0”)
1: The other segment has changed to UNFREEZE state
1: The other segment has changed to FREEZE state
1: The other segment has changed to UNSYNC state
1: The other segment has changed to SYNC state
Reserved
DP/DP Coupler
6-10 A5E00244669-03
Diagnostics
Introduction
This practical example shows the call of a diagnostic function on the
DP/DP Coupler:
6.3.1 Task
DP/DP Coupler
Figure 6-5 Example of the analysis of diagnostics data from the DP/DP Coupler
DP/DP Coupler
A5E00244669-03 6-11
Diagnostics
STL Explanation
CALL SFC 13
REQ :=TRUE //Request to read the diagnostic data
LADDR :=W#16#3FE //Diagnostics address
RET_VAL :=MW0 //RET_VAL of SFC 13
RECORD :=P#DB10.DBX 0.0 BYTE 26 //Data mailbox for the diagnosis in DB10
BUSY :=M2.0 //Read operation runs through several OB1
cycles
Appearance of DB 10
Define the following structure for DB 10:
DP/DP Coupler
6-12 A5E00244669-03
Diagnostics
Content of DB10
The relevant diagnostic data in DB 10 have the following meanings:
Result
The network 1 data are valid, the network 1 DP master has switched its stations to
CLEAR mode (e.g. CPU of network is in STOP).
DP/DP Coupler
A5E00244669-03 6-13
Diagnostics
DP/DP Coupler
6-14 A5E00244669-03
Technical data A
Overview of contents
This chapter provides general technical data and the technical data of the
DP/DP Coupler:
DP/DP Coupler
A5E00244669-03 A-1
Technical data
CE certification
The described components fulfil the requirements and safety objectives of the
following EC Directives and comply with the harmonized European standards (EN)
published for programmable logic controllers in the official journals of the EC:
• 73/23/EEC Low Voltage Directive (for electrical equipment)
• 89/336/EEC Electromagnetic Compatibility Directive (EMC Directive)
• Directive 94/9/EC on protective devices and systems for use in potentially
explosive areas (explosion protection directive)
The EC Declarations of Conformity are available for the relevant authorities at the
following address:
Siemens Aktiengesellschaft
Automation and Drives
A&D AS RD ST Type Test
PO Box 1963
D-92209 Amberg
DP/DP Coupler
A-2 A5E00244669-03
Technical data
Approvals
Underwriters Laboratories Inc. to
UL 508 (Industrial Control Equipment)
CSA C22.2 No. 142 (Process Control Equipment)
Or
Note
The approvals currently effective are found on the rating plate of each module.
FM approval
Factory Mutual Research (FM) in accordance with
Approval Standard Class Number 3611, 3600, 3810
APPROVED for use in
Class I, Division 2, Group A, B, C, D T4;
Class I, Zone 2, Group IIC T4
II 3 G EEx nA II T4
DP/DP Coupler
A5E00244669-03 A-3
Technical data
IEC 61131
The described components comply with the requirements and criteria of the IEC
61131-2 standard (programmable logic controllers, Part 2: Equipment requirements
and tests).
PROFIBUS standard
The components described are based on the standard IEC 61784-1:2002 Ed1
CP 3/1.
DP/DP Coupler
A-4 A5E00244669-03
Technical data
Warning
! There is a risk of injury and damage to property.
In areas where there is a risk of explosion, injuries and damage may be caused if
you remove connectors during operation.
In potentially explosive environments, always switch of the power supply before
you disconnect any component connectors.
DP/DP Coupler
A5E00244669-03 A-5
Technical data
Introduction
This chapter contains data on the noise immunity and RF suppression of the
described components.
The described components meet the requirements of the European EMC
legislation for the single market.
Pulse-type interference
The table below shows the electromagnetic compatibility of the described
components with respect to pulse-type interference. The prerequisite for this is that
the system meets and complies with the relevant requirements and guidelines
relating to electrical equipment.
DP/DP Coupler
A-6 A5E00244669-03
Technical data
Sinusoidal interference
The table below shows the EMC behavior of the described components with
respect to sinusoidal interference.
Emitted interference via a.c. supply in accordance with EN 55011: limit value class
A, group 1
DP/DP Coupler
A5E00244669-03 A-7
Technical data
DP/DP Coupler
A-8 A5E00244669-03
Technical data
Operating conditions
The described components are designed for use in a fixed, sheltered location. The
operating conditions exceed the requirements of IEC 61131 Part 2.
The described components meet the operating conditions of Class 3C3 in
accordance with DIN EN 60721 Part 2.
Vibration reduction
When the described components are subjected to major shocks or vibrations, you
must take suitable action to reduce the acceleration or amplitude.
We recommend mounting the described components on damping material (e.g. on
rubber-metal connections).
DP/DP Coupler
A5E00244669-03 A-9
Technical data
DP/DP Coupler
A-10 A5E00244669-03
Technical data
Test voltages
The insulating properties are verified in individual testing with the following test
voltages:
Protection class
Protection class I in accordance with IEC 60536, i. e. PE connection to rail is
required!
DP/DP Coupler
A5E00244669-03 A-11
Technical data
DP/DP Coupler
A-12 A5E00244669-03
Technical data
Chapter overview
Section Topic
A.3.1 Einsatz der Buskopplung DP/PA im explosionsgefährdeten Bereich Zone 2
A.3.2 Use of the DP/DP Coupler in potentially explosive environments of Zone 2
A.3.3 Utilisation du coupleur de bus DP/PA dans un environnement à risque
d’explosion en zone 2
A.3.4 Aplicación del acoplamiento de bus DP/PA en áreas con peligro de explosión,
zona 2
A.3.5 Impiego dell’accoppiamento di bus DP/PA nell’area a pericolo di esplosione
zona 2
A.3.6 Gebruik van de buskoppeling DP/PA in het explosieve gebied zone 2
A.3.7 Brug af buskoblingen DP/PA i det eksplosionfarlige område zone 2
A.3.8 Väyläkytkennän DP/PA käyttö räjähdysvaarannetuilla alueilla, vyöhyke 2
A.3.9 Användning av bussanslutning DP/PA i explosionsriskområde zon 2
A.3.10 Uso do acoplamento de bus DP/PA em área exposta ao perigo de explosão,
zona 2
A.3.11 Χρηση τηζ συσΚευηζ διαυλου DP/PA σε ...
DP/DP Coupler
A5E00244669-03 A-13
Technical Data
Zone 2
Explosionsgefährdete Bereiche werden in Zonen eingeteilt. Die Zonen werden nach der
Wahrscheinlichkeit des Vorhandenseins einer explosionsfähigen Atmosphäre unter-
schieden.
Zone Explosionsgefahr Beispiel
2 explosive Gasatmosphäre tritt Bereiche um Flanschverbindungen mit Flach-
nur selten und kurzzeitig auf dichtungen bei Rohrleitungen in geschlossenen
Räumen
sicherer nein • außerhalb der Zone 2
Bereich • Standardanwendungen von dezentraler
Peripherie
Nachfolgend finden Sie wichtige Hinweise für die Installation des DP/DP-Kopplers im
explosionsgefährdeten Bereich.
Weitere Informationen
Weitere Informationen zum DP/DP-Koppler und zu den verschiedenen Komponenten
finden Sie im Handbuch.
Fertigungsort
Siemens AG, Bereich A&D
Werner-von-Siemens-Straße 50
92224 Amberg
Germany
Zulassung
Hinweis
Baugruppen mit der Zulassung II 3 G EEx nA II T4 dürfen nur in
Automatisierungssysteme SIMATIC S5/S7 / DP-Slaves der Gerätekategorie 3G
eingesetzt werden.
DP/DP Coupler
A-14 A5E00224669-03
Technical Data
Instandhaltung
Für eine Reparatur muss die betroffene Komponente an den Fertigungsort geschickt
werden. Nur dort darf die Reparatur durchgeführt werden.
Besondere Bedingungen
1. Der DP/DP-Koppler muss in einen Schaltschrank oder ein metallisches Gehäuse
eingebaut werden. Diese müssen mindestens die Schutzart IP 54 (nach EN 60529)
gewährleisten. Dabei sind die Umgebungsbedingungen zu berücksichtigen, in denen
das Gerät installiert wird. Für das Gehäuse muss eine Herstellererklärung für Zone 2
vorliegen (gemäß EN 50021).
2. Wenn am Kabel bzw. an der Kabeleinführung dieses Gehäuses unter Betriebs-
bedingungen eine Temperatur > 70 °C erreicht wird oder wenn unter Betriebs-
bedingungen die Temperatur an der Aderverzweigung > 80 °C sein kann, müssen die
Temperatureigenschaften der Kabel mit den tatsächlich gemessenen Temperaturen
übereinstimmen.
3. Die eingesetzten Kabeleinführungen müssen der geforderten IP-Schutzart und dem
Abschnitt 7.2 (gemäß EN 50021) entsprechen.
4. Alle Geräte, einschließlich Schalter etc., die an den Ein- und Ausgängen des
DP/DP-Koppler angeschlossen werden, müssen für den Explosionsschutz
Typ EEx nA oder EEx nC genehmigt sein.
5. Es müssen Maßnahmen getroffen werden, dass die Nennspannung durch
Transienten um nicht mehr als 40 % überschritten werden kann.
6. Umgebungstemperaturbereich: 0° C bis 60° C
7. Innerhalb des Gehäuses ist an einem nach dem Öffnen gut sichtbaren Platz ein Schild
mit folgender Warnung anzubringen:
Warnung
Das Gehäuse darf nur kurze Zeit geöffnet werden, z. B. für visuelle Diagnose.
Betätigen Sie dabei keine Schalter, ziehen oder stecken keine Baugruppen und
trennen keine elektrischen Leitungen (Steckverbindungen).
Diese Warnung kann unberücksichtigt bleiben, wenn bekannt ist, dass keine
explosionsgefährdete Atmosphäre herrscht.
DP/DP Coupler
A5E00224669-03 A-15
Technical Data
Zone 2
Hazardous areas are divided up into zones. The zones are distinguished according to the
probability of the existence of an explosive atmosphere.
Zone Explosion Hazard Example
2 Explosive gas atmosphere Areas around flange joints with flat gaskets in
occurs only seldom and for a pipes in enclosed spaces
short time
Safe area No • Outside zone 2
• Standard distributed I/O applications
Below you will find important information on the installation of the components of the
DP/DP coupler in a hazardous area.
Further Information
You will find further information on the DP/DP coupler and the various components in the
manual.
Production Location
Siemens AG, Bereich A&D
Werner-von-Siemens-Straße 50
92224 Amberg
Germany
Certification
Note
Modules with II 3 G EEx nA II T4 certification can only be used in
SIMATIC S5/S7 / DP Slave automation systems belonging to equipment
category 3G.
DP/DP Coupler
A-16 A5E00224669-03
Technical Data
Maintenance
If repair is necessary, the affected component must be sent to the production location.
Repairs can only be carried there.
Special Conditions
1. The DP/DP coupler must be installed in a cabinet or metal housing. These must
comply with the IP 54 degree of protection as a minimum. The environmental
conditions under which the equipment is installed must be taken into account. There
must be a manufacturer's declaration for zone 2 available for the housing (in
accordance with EN 50021).
2. If a temperature of > 70 °C is reached in the cable or at the cable entry of this housing
under operating conditions, or if a temperature of > 80 °C can be reached at the
junction of the conductors under operating conditions, the temperature-related
properties of the cables must correspond to the temperatures actually measured.
3. The cable entries used must comply with the required IP degree of protection and
Section 7.2 (in accordance with EN 50021).
4. All devices (including switches, etc.) that are connected to the inputs and outputs of a
DP/DP coupler must be approved for EEx nA or EEx nC explosion protection.
5. Steps must be taken to ensure that the rated voltage through transients cannot be
exceeded by more than 40 %.
6. Ambient temperature range: 0° C to 60° C
7. A sign containing the following warning must be put up inside the housing in an easily
visible position when the housing is opened:
Warning
The housing can only be opened for a short time (e.g. for visual diagnostics). If you do
this, do not operate any switches, remove or install any modules or disconnect any
electrical cables (plug-in connections).
You can disregard this warning if you know that the atmosphere is not hazardous (i.e.
there is no risk of explosion).
DP/DP Coupler
A5E00224669-03 A-17
Technical Data
Zone 2
Les environnements à risque d'explosion sont répartis en zones. Les zones se
distinguent par la probabilité de présence d'une atmosphère explosive.
Zone Risque d'explosion Exemple
2 Formation rare et brève d'une Environnement de raccords à joints plats dans le
atmosphère gazeuse explosive cas de conduites dans des locaux fermés
Zone sûre Non • A l'extérieur de la zone 2
• Utilisation standard de périphérie décentralisée
Vous trouverez ci-après des remarques importantes pour l'installation des composantes
du coupleur DP/DP dans un environnement à risque d'explosion.
Informations complémentaires
Des informations complémentaires sur le coupleur DP/DP et les diverses composantes
se trouvent dans le manuel.
Lieu de production
Siemens AG, Bereich A&D
Werner-von-Siemens-Straße 50
92224 Amberg
Germany
Homologation
Nota
Les modules homologués II 3 G EEx nA II T4 ne peuvent être utilisés que
dans des automates SIMATIC S5/S7 / esclaves DP de catégorie 3G.
DP/DP Coupler
A-18 A5E00224669-03
Technical Data
Entretien
Si une réparation est nécessaire, la composante concernée doit être expédiée au lieu de
production. La réparation ne doit être effectuée qu'en ce lieu.
Conditions particulières
1. Le coupleur DP/DP doit être installé dans une armoire ou un boîtier métallique. Ceux-
ci doivent assurer au moins l'indice de protection IP 54. Il faut alors tenir compte des
conditions d'environnement dans lesquelles l'appareil est installé. Le boîtier doit faire
l’objet d’une déclaration de conformité du fabricant pour la zone 2 (selon EN 50021).
2. Si dans les conditions d’exploitation, une température > 70 °C est atteinte au niveau
du câble ou de l’entrée du câble dans ce boîtier, ou bien si la température au niveau
de la dérivation des conducteurs peut être > 80 °C, les capacités de résistance
thermique des câbles doivent corespondre aux températures effectivement mesurées.
3. Les entrées de câbles utilisées doivent avoir le niveau de protection IP exigé et être
conformes au paragraphe 7.2 (selon EN 50021).
4. Tous les appareillages (y compris les interrupteurs, etc.) raccordés aux entrées et
sorties du coupleur DP/DP doivent être homologués pour la protection antidéflagrante
type EEx nA ou EEx nC.
5. Il faut prendre des mesures pour que la tension nominale ne puisse pas être
dépassée de plus de 40% sous l’influence de transitoires.
6. Plage de température ambiante : 0° C à 60° C
7. A l’intérieur du boîtier, il faut placer, à un endroit bien visible après ouverture, une
plaquette comportant l’avertissement suivant :
Avertissement
Ouvir le boîtier le moins longtemps possible, par exemple pour effectuer un diagnostic
visuel. Ce faisant, n’actionnez aucun commutateur, ne déconnectez aucun module et
ne débanchez pas de câbles électriques (connexions).
Le respect de cet avertissement n’est pas impératif s’il est certain que l’environnement
ne présente pas de risque d’explosion.
DP/DP Coupler
A5E00224669-03 A-19
Technical Data
Zona 2
Las áreas con peligro de explosión se clasifican en zonas. Las zonas se diferencian
según la probabilidad de la existencia de una atmósfera capaz de sufrir una explosión.
Zona Peligro de explosión Ejemplo
2 La atmósfera explosiva de gas Áreas alrededor de uniones abridadas con juntas
sólo se presenta rara vez y muy planas en tuberías en locales cerrados
brevemente
Área segura no • fuera de la zona 2
• Aplicaciones estándar de la periferia
descentralizada
Otras informaciones
Encontrará otras informaciones relativas al acoplador DP/DP y a los distintos
componentes en el Manual.
Lugar de fabricación
Siemens AG, Bereich A&D
Werner-von-Siemens-Straße 50
92224 Amberg
Germany
Homologación
Nota
Los módulos con la homologación II 3 G EEx nA II T4 pueden utilizarse
únicamente en los autómatas programables SIMATIC S5/S7/ esclavos DP de la
categoría de equipo 3G.
DP/DP Coupler
A-20 A5E00224669-03
Technical Data
Mantenimiento
Para una reparación se ha de remitir el componente afectado al lugar de fabricación.
Sólo allí se puede realizar la reparación.
Condiciones especiales
1. El acoplador DP/DP se ha de montar en un armario eléctrico de distribución o en una
carcasa metálica. Éstos deben garantizar como mínimo el grado de protección IP 54.
Para ello se han de tener en cuenta las condiciones ambientales, en las cuales se
instala el equipo. La caja deberá contar con una declaración del fabricante para la
zona 2 (conforme a EN 50021).
2. Si durante la operación se alcanzara una temperatura > 70° C en el cable o la entrada
de cables de esta caja o bien una temperatura > 80° C en la bifurcación de hilos,
deberán adaptarse las propiedades térmicas de los cables a las temperaturas
medidas efectivamente.
3. Las entradas de cable utilizadas deben cumplir el grado de protección IP exigido y lo
expuesto en el apartado 7.2 (conforme a EN 50021).
4. Todos los dispositivos –inclusive interruptores, etc.– conectados a las entradas y
salidas del acoplador DP/DP deben estar homologados para la protección contra
explosiones del tipo EEx nA o EEx nC.
5. Es necesario adoptar las medidas necesarias para evitar que la tensión nominal
pueda rebasar en más del 40 % debido a efectos transitorios.
6. Margen de temperatura ambiente: 0° C hasta 60° C
7. Dentro de la caja deberá colocarse en un lugar perfectamente visible tras su apertura
un rótulo con la siguiente advertencia:
Precaución
Abrir la caja sólo brevemente, p.ej. para el diagnóstico visual. Durante este tiempo
Ud. no deberá activar ningún interruptor, desenchufar o enchufar módulos ni separar
conductores eléctricos (conexiones enchufables).
Esta advertencia puede ignorarse si Ud. sabe que en la atmósfera existente no hay
peligro de explosión.
DP/DP Coupler
A5E00224669-03 A-21
Technical Data
Zona 2
Le aree a pericolo di esplosione vengono suddivise in zone. Le zone vengono distinte
secondo la probabilità della presenza di un'atmosfera esplosiva.
Zona Pericolo di esplosione Esempio
2 L'atmosfera esplosiva si Aree intorno a collegamenti a flange con
presente solo raramente e guarnizioni piatte nelle condotte in ambienti chiusi
brevemente
Area sicura No • Al di fuori della zona 2
• Applicazioni standard di periferia decentrata
Qui di seguito sono riportate delle avvertenze importanti per l'installazione dei
componenti dell'accoppiatore di bus DP/DP nell'area a pericolo di esplosione.
Ulteriori informazioni
Ulteriori informazioni sull'accoppiatore di bus DP/DP e sui diversi componenti si trovano
nel manuale.
Luogo di produzione
Siemens AG, Bereich A&D
Werner-von-Siemens-Straße 50
92224 Amberg
Germany
Autorizzazione
Avvertenza
Le unità con l'autorizzazione II 3 G EEx nA II T4 possono essere impiegate
solo nei controllori programmabili SIMATIC S5/S7 / slave DP della categoria di
apparecchiature 3G.
DP/DP Coupler
A-22 A5E00224669-03
Technical Data
Manutenzione
Per una riparazione, il componente interessato deve essere inviato al luogo di
produzione. La riparazione può essere effettuata solo lì.
Condizioni particolari
1. L'accoppiatore di bus DP/DP deve essere montato in un armadio elettrico o in un
contenitore metallico. Questi devono assicurare almeno il tipo di protezione IP 54. In
questo caso bisogna tenere conto delle condizioni ambientali nelle quali
l'apparecchiatura viene installata. Per il contenitore deve essere presente una
dichiarazione del costruttore per la zona 2 (secondo EN 50021).
2. Se nei cavi o nel loro punto di ingresso in questo contenitore viene raggiunta in
condizioni di esercizio una temperatura > 70 °C o se in condizioni di esercizio la
temperatura nella derivazione dei fili può essere > 80 °C, le caratteristiche di
temperatura dei cavi devono essere conformi alla temperatura effettivamente
misurata.
3. Gli ingressi dei cavi usati devono essere conformi al tipo di protezione richiesto e alla
sezione 7.2 (secondo EN 50021).
4. Tutte le apparecchiature, inclusi interruttori, ecc. che vengono collegati agli
ingressi/uscite dell'accoppiatore di bus DP/DP, devono essere state omologate per la
protezione da esplosione tipo EEx nA o EEx nC.
5. Devono essere prese delle misure per evitare che la tensione nominale possa essere
superata per più del 40% da parte di transienti.
6. Campo termico ambientale: da 0° C a 60° C
7. All’interno del contenitore va apportata, in un luogo ben visibile dopo l’apertura, una
targhetta con il seguente avvertimento:
Attenzione
Il contenitore può rimanere aperto solo per breve tempo, ad esempio per una
diagnostica a vista. In tal caso non azionare alcun interruttore, non disinnestare o
innestare unità e non staccare connessioni elettriche (connettori).
Non è necessario tenere conto di questo avvertimento se è noto che non c’è
un’atmosfera a rischio di esplosione.
DP/DP Coupler
A5E00224669-03 A-23
Technical Data
Zone 2
Explosieve gebieden worden ingedeeld in zones. Bij de zones wordt onderscheiden
volgens de waarschijnlijkheid van de aanwezigheid van een explosieve atmosfeer.
Zone Explosiegevaar Voorbeeld
2 Een explosieve gasatmosfeer Gebieden rond flensverbindingen met pakkingen
treedt maar zelden op en voor bij buisleidingen in gesloten vertrekken
korte duur
Veilig neen • Buiten de zone 2
gebied • Standaardtoepassingen van decentrale
periferie
Verdere informatie
In het handboek vindt u verdere informatie over de buskoppeling DP/DP en over de
verschillende componenten.
Productieplaats
Siemens AG, Bereich A&D
Werner-von-Siemens-Strasse 50
92224 Amberg
Germany
Vergunning
Opmerking
Modulen met de vergunning II 3 G EEx nA II T4 mogen slechts worden
gebruikt in automatiseringssystemen SIMATIC S5/S7 / DP-slaves van de
apparaatcategorie 3G.
DP/DP Coupler
A-24 A5E00224669-03
Technical Data
Instandhouding
De te herstellen component moet voor reparatie naar de plaats van vervaardiging worden
gestuurd. Alleen daar mag de reparatie worden uitgevoerd.
Speciale voorwaarden
1. De buskoppeling DP/DP moet worden ingebouwd in een schakelkast of in een
behuizing van metaal. Deze moeten minstens de veiligheidsgraad IP 54 waarborgen.
Hierbij dient rekening te worden gehouden met de omgevingsvoorwaarden waarin het
apparaat wordt geïnstalleerd. Voor de behuizing dient een verklaring van de fabrikant
voor zone 2 te worden ingediend (volgens EN 50021).
2. Als aan de kabel of aan de kabelinvoering van deze behuizing onder
bedrijfsomstandigheden een temperatuur wordt bereikt > 70 °C of als onder
bedrijfsomstandigheden de temperatuur aan de adervertakking > 80 °C kan zijn,
moeten de temperatuureigenschappen van de kabel overeenstemmen met de
werkelijk gemeten temperaturen.
3. De aangebrachte kabelinvoeringen moeten de vereiste IP-veiligheidsgraad hebben en
in overeenstemming zijn met alinea 7.2 (volgens EN 50021).
4. Alle apparaten, schakelaars enz. inbegrepen, die worden aangesloten op de in- en
uitgangen van de buskoppeling DP/DP, moeten zijn goedgekeurd voor de
explosiebeveiliging type EEx nA of EEx nC.
5. Er dienen maatregelen te worden getroffen, zodat de nominale spanning door
transiënten met niet meer dan 40 % kan worden overschreden.
6. Omgevingstemperatuurbereik: 0° C tot 60° C
7. Binnen de behuizing dient op een na het openen goed zichtbare plaats een bord te
worden aangebracht met de volgende waarschuwing:
Waarschuwing
De behuizing mag slechts voor korte tijd worden geopend, bijv. voor een visuele
diagnose. Bedien hierbij geen schakelaar, trek of steek geen modulen en ontkoppel
geen elektrische leidingen (steekverbindingen).
Deze waarschuwing kan buiten beschouwing blijven, indien bekend is dat er geen
explosieve atmosfeer heerst.
DP/DP Coupler
A5E00224669-03 A-25
Technical Data
Zone 2
Eksplosionsfarlige områder inddeles i zoner. Zonerne adskiller sig indbyrdes efter hvor
sandsynligt det er, at der er en eksplosiv atmosfære.
Zone Eksplosionsfare Eksempel
2 Eksplosiv gasatmosfære Områder rundt om flangeforbindelser med flade
optræder kun sjældent og varer pakninger ved rørledninger i lukkede rum
kort
Sikkert Nej • Uden for zone 2
område • Standardanvendelser decentral periferi
I det følgende findes vigtige henvisninger vedr. installation af komponenterne til DP/DP-
kobleren i det eksplosionsfarlige område.
Yderligere informationer
Yderligere informationer om DP/DP-kobleren og de forskellige komponenter findes i
manualen.
Produktionssted
Siemens AG, Bereich A&D
Werner-von-Siemens-Straße 50
92224 Amberg
Germany
Godkendelse
Bemærk
Komponenter med godkendelsen II 3 G EEx nA II T4 må kun monteres i
automatiseringssystemer SIMATIC S5/S7 / DP-slaves - udstyrskategori 3G.
DP/DP Coupler
A-26 A5E00224669-03
Technical Data
Vedligeholdelse
Skal den pågældende komponent repareres, bedes De sende den til produktionsstedet.
Reparation må kun udføres der.
Særlige betingelser
1. DP/DP-kobleren skal monteres i et kontrolskab eller et metalkabinet. Disse skal
mindst kunne sikre beskyttelsesklasse IP 54. I denne forbindelse skal der tages højde
for de omgivelsestemperaturer, i hvilke udstyret er installeret. Der skal være
udarbejdet en erklæring fra fabrikanten for kabinettet for zone 2 (iht. EN 50021).
2. Hvis kablet eller kabelindføringen på dette hus når op på en temperatur på > 70 °C
under driftsbetingelser eller hvis temperaturen på åreforegreningen kan være > 80 °C
under driftsbetingelser, skal kablernes temperaturegenskaber stemme overens med
de temperaturer, der rent faktisk måles.
3. De benyttede kabelindføringer skal være i overensstemmelse med den krævede IP-
beskyttelsestype og afsnittet 7.2 (iht. EN 50021).
4. Alle apparater, inkl. kontakter osv., der forbindes med ind- og udgangene på DP/DP-
kobleren, skal være godkendt til eksplosionsbeskyttelse af type EEx nA eller EEx nC.
5. Der skal træffes foranstaltninger, der sørger for, at den nominelle spænding via
transienter ikke kan overskrides mere end 40 %.
6. Omgivelsestemperaturområde: 0° C til 60° C
7. I kabinettet skal der anbringes et skilt, der skal kunne ses, når kabinettet åbnes. Dette
skilt skal have følgende advarsel:
Advarsel
Kabinettet må kun åbnes i kort tid, f.eks. til visuel diagnose. Tryk i denne forbindelse
ikke på kontakter, træk eller isæt ikke komponenter og afbryd ikke elektriske ledninger
(stikforbindelser).
Denne advarsel skal der ikke tages højde for, hvis man ved, at der ikke er nogen
eksplosionsfarlig atmosfære.
DP/DP Coupler
A5E00224669-03 A-27
Technical Data
Vyöhyke 2
Räjähdysvaarannetut alueet jaetaan vyöhykkeisiin. Vyöhykkeet erotellaan
räjähdyskelpoisen ilmakehän olemassa olon todennäköisyyden mukaan.
Vyöhyke Räjähdysvaara Esimerkki
2 Räjähtävä kaasuilmakehä Alueet putkistojen lattatiivisteillä varustuilla
ilmaantuu vain harvoin ja laippaliitoksilla suljetuissa tiloissa
lyhytaikaisesti
turvallinen ei • vyöhykkeen 2 ulkopuolella
alue • Hajautetun ulkopiirin vakiosovellukset
Lisätietoja
Lisätietoja DP/PA-kytkimeen ja erilaisiin komponentteihin löydätte ohjekirjasta.
Valmistuspaikka
Siemens AG, Bereich A&D
Werner-von-Siemens-Straße 50
92224 Amberg
Germany
Hyväksyntä
Ohje
Rakenneryhmät hyväksynnän II 3 G EEx nA II T4 kanssa saadaan käyttää
ainoastaan laitekategorian 3G automatisointijärjestelmissä SIMATIC S5/S7 / DP-
Slaves.
DP/DP Coupler
A-28 A5E00224669-03
Technical Data
Kunnossapito
Korjausta varten täytyy kyseinen komponentti lähettää valmistuspaikkaan. Korjaus
voidaan suorittaa ainoastaan siellä.
Erityiset vaatimukset
1. DP/PA-kytkin täytyy asentaa kytkentäkaappiin tai metalliseen koteloon. Näiden täytyy
olla vähintään kotelointiluokan IP 54 mukaisia. Tällöin on huomioitava
ympäristöolosuhteet, johon laite asennetaan. Kotelolle täytyy olla valmistajaselvitys
vyöhykettä 2 varten (EN 50021 mukaan).
2. Kun johdolla tai tämän kotelon johdon sisäänviennillä saavutetaan > 70 °C lämpötila
tai kun käyttöolosuhteissa lämpötila voi piuhajaotuksella olla > 80 °C, täytyy johdon
lämpötilaominaisuuksien vastata todellisesti mitattuja lämpötiloja.
3. Käytettyjen johtojen sisäänohjauksien täytyy olla vaaditun IP-kotelointiluokan ja
kohdan 7.2 (EN 50021 mukaan) mukaisia.
4. Kaikkien laitteiden, kytkimet jne. mukaan lukien, jotka liitetään DP/PA-kytkimen tuloille
ja lähdöille, täytyy olla hyväksyttyjä tyypin EEx nA tai EEx nC räjähdyssuojausta
varten.
5. Toimenpiteet täytyy suorittaa, ettei nimellisjännite voi transienttien kautta ylittyä
enemmän kuin 40 %.
6. Ympäristölämpötila-alue: 0° C ... 60° C
7. Kotelon sisälle, avauksen jälkeen näkyvälle paikalle, on kiinnitettävä kilpi, jossa on
seuraava varoitus:
Varoitus
Kotelo saadaan avata ainoastaan lyhyeksi ajaksi, esim. visuaalista diagnoosia varten.
Älä tällöin käytä mitään kytkimiä, vedä tai liitä mitään rakenneryhmiä, äläkä erota
mitään sähköjohtoja (pistoliittimiä).
Tätä varoitusta ei tarvitse huomioida, kun on tiedossa, että minkäänlaista
räjähdysvaarannettua ilmakehää ei ole olemassa.
DP/DP Coupler
A5E00224669-03 A-29
Technical Data
Zon 2
Explosionsriskområden delas in i zoner. Zonerna delas in enligt sannolikheten att en
atmosfär med explosionsfara föreligger.
Zon Explosionsfara Exempel
2 Explosiv gasatmosfär uppstår Områden kring flänsförbindelser med packningar
endast sällan eller kortvarigt vid rörledningar i slutna utrymmen
Säkert Nej • Utanför zon 2
område • Standardanvändning av decentral periferi
Ytterligare information
Ytterligare information om DP/DP-kopplaren och de olika komponenterna finner du i
handboken.
Tillverkningsort
Siemens AG, Bereich A&D
Werner-von-Siemens-Straße 50
92224 Amberg
Germany
Godkännande
Anvisning
Komponentgrupper med godkännande II 3 G EEx nA II T4 får endast
användas i automatiseringssystemen SIMATIC S5/S7 / DP Slaves från
apparatgrupp 3G.
DP/DP Coupler
A-30 A5E00224669-03
Technical Data
Underhåll
Vid reparation måste den aktuella komponenten insändas till tillverkaren. Reparationer får
endast genomföras där.
Särskilda villkor
1. DP/DP-kopplaren måste monteras i ett kopplingsskåp eller metallhus. Dessa måste
minst vara av skyddsklass IP 54. Därvid ska omgivningsvillkoren där enheten
installeras beaktas. För kåpan måste en tillverkardeklaration för zon 2 föreligga (enligt
EN 50021).
2. Om en temperatur på > 70°C uppnås vid husets kabel resp kabelinföring under
driftvillkor eller om temperaturen vid trådförgreningen kan vara > 80°C under
driftvillkor, måste kabelns temperaturegenskaper överensstämma med den verkligen
uppmätta temperaturen.
3. De använda kabelinföringarna måste uppfylla kraven i det krävda IP-skyddsutförandet
och i avsnitt 7.2 (enligt EN 50021).
4. Alla apparater, inklusive brytare osv, som ansluts till DP/DP-kopplarens in- och
utgångar, måste vara godkända för explosionsskydd av typ EEx nA eller EEx nC.
5. Åtgärder måste vidtas så, att märkspänningen ej kan överskridas med mer än 40°%
genom transienter.
6. Omgivningstemperatur: 0° C till 60° C
7. När huset öppnats ska en skylt med följande varning monteras på ett tydligt synligt
ställe huset:
Varning
Huset får endast öppnas under kort tid, t ex för visuell diagnos. Använd därvid inga
brytare, lossa eller anslut inga enheter och frånskilj inga elektriska ledningar
(insticksanslutningar).
Ingen hänsyn måste tas till denna varning om det är säkert att det inte råder någon
explosionsfarlig atmosfär.
DP/DP Coupler
A5E00224669-03 A-31
Technical Data
Zona 2
As áreas expostas ao perigo de explosão são divididas em zonas. As zonas são
diferenciadas de acordo com a probabilidade da existência de uma atmosfera explosiva.
Zona Perigo de explosão Exemplo
2 Só raramente e por um breve Áreas em torno de ligações flangeadas com
período de tempo surgem vedações chatas em tubulações em recintos
atmosferas explosivas fechados
Área segura não • fora da zona 2
• Aplicações descentralizadas de periferia
descentralizada
Mais informações
Para obter mais informações sobre o acoplador DP/DP e sobre os diversos
componentes, consulte o manual.
Local de produção
Siemens AG, Bereich A&D
Werner-von-Siemens-Straße 50
92224 Amberg
Germany
Licença
Aviso
Componentes com a licença II 3 G EEx nA II T4 só podem ser aplicados em
sistemas de automação SIMATIC S5/S7 / escravos DP da categoria de
aparelho 3G.
DP/DP Coupler
A-32 A5E00224669-03
Technical Data
Reparo
Os componentes em questão devem ser remetidos para o local de produção a fim de
que seja realizado o reparo. Apenas lá deve ser efetuado o reparo.
Condições especiais
1. O acoplador DP/DP deve ser montado em um armário de distribuição ou em uma
caixa metálica. Estes devem garantir no mínimo o tipo de proteção IP 54. Durante
este trabalho deverão ser levados em consideração as condições locais, nas quais o
aparelho será instalado. Para a caixa deverá ser apresentada uma declaração do
fabricante para a zona 2 (de acordo com EN 50021).
2. Caso no cabo ou na entrada do cabo desta carcaça sob as condições operacionais
seja atingida uma temperatura de > 70 °C, ou caso sob condições operacionais a
temperatura na ramificação do fio poderá atingir > 80 °C, as caraterísticas de
temperatura deverão corresponder às temperaturas realmente medidas.
3. As entradas de cabo utilizadas devem corresponder ao tipo exigido de proteção IP e à
seção 7.2 (de acordo com o EN 50021).
4. Todos os aparelhos, inclusive as chaves, etc., que estejam conectadas em entradas e
saídas do acoplador DP/DP, devem possuir a licença para a proteção de explosão do
tipo EEx nA ou EEx nC.
5. Precisam ser tomadas medidas para que a tensão nominal através de transitórios não
possa ser ultrapassada em mais que 40 %.
6. Área de temperatura ambiente: 0° C até 60° C
7. No âmbito da carcaça deve ser colocada, após a abertura, em um ponto bem visível
uma placa com a seguinte advertência:
Advertência
A carcaça deve ser aberta apenas por um breve período de tempo, por ex. para
diagnóstico visual. Não acione nenhum interruptor, não retire ou conecte nenhum
módulo e não separe nenhum fio elétrico (ligações de tomada).
Esta advertência poderá ser ignorada caso se saiba que não há nenhuma atmosfera
sujeita ao perigo de explosão.
DP/DP Coupler
A5E00224669-03 A-33
Technical Data
Ζώνη 2
Οι επικίνδυνες για έκρηξη περιοχές χωρίζονται σε ζώνες. Οι ζώνες διαφέρουν σύµφωνα
µε την πιθανότητα ύπαρξης ενός ικανού για έκρηξη περιβάλλοντος.
Ζώνη Κίνδυνος έκρηξης Παράδειγµα
2 Εκρηκτικό περιβάλλον αερίου Περιοχές γύρω από φλαντζωτές συνδέσεις µε
παρουσιάζεται µόνο σπάνια και τσιµούχες σε σωληνώσεις σε κλειστούς χώρους
για σύντοµο χρονικό διάστηµα
Ασφαλής όχι • Εκτός της ζώνης 2
περιοχή • Τυπικές εφαρµογές αποκεντρωµένης
περιφέρειας
Στη συνέχεια θα βρείτε σηµαντικές υποδείξεις για την εγκατάσταση του συζεύκτη DP/DP
σε επικίνδυνη για έκρηξη περιοχή.
Επιπλέον πληροφορίες
Επιπλέον πληροφορίες για το συζεύκτη DP/DP και για τα διάφορα εξαρτήµατα θα βρείτε
στο εγχειρίδιο.
Τόπος κατασκευής
Siemens AG, Bereich A&D
Werner-von-Siemens-Straße 50
92224 Amberg
Germany
Άδεια
Υπόδειξη
Τα δοµικά συγκροτήµατα µε την άδεια II 3 G EEx nA II T4 επιτρέπεται να
τοποθετηθούν µόνο σε συστήµατα αυτοµατισµού SIMATIC S5/S7 / DP-Slaves της
κατηγορίας συσκευής 3G.
DP/DP Coupler
A-34 A5E00224669-03
Technical Data
Συντήρηση
Για µια επισκευή πρέπει να σταλθεί το αντίστοιχο εξάρτηµα στον τόπο κατασκευής. Μόνο
εκεί επιτρέπεται να γίνει η επισκευή.
Ιδιαίτερες προϋποθέσεις
1. Ο συζεύκτης DP/DP πρέπει να ενσωµατωθεί σε ένα ερµάριο ζεύξης ή σε ένα
µεταλλικό περίβληµα. Αυτά πρέπει να εξασφαλίζουν το λιγότερο το βαθµό προστασίας
IP 54. Σε αυτήν την περίπτωση πρέπει να ληφθούν υπόψη οι περιβαλλοντικές
συνθήκες, στις οποίες θα εγκατασταθεί η συσκευή. Για το περίβληµα πρέπει να
προβλέπεται δήλωση του κατασκευαστή για τη ζώνη 2 (σύµφωνα µε το πρότυπο
EN 50021).
2. Εάν στο καλώδιο ή στην είσοδο του καλωδίου αυτού του περιβλήµατος κάτω από
συνθήκες λειτουργίας η θερµοκρασία ξεπεράσει τους 70 °C ή όταν κάτω από
συνθήκες λειτουργίας η θερµοκρασία στη διακλάδωση του σύρµατος µπορεί να είναι
µεγαλύτερη από 80 °C, πρέπει οι θερµοκρασιακές ιδιότητες των καλωδίων να
ταυτίζονται µε τις πραγµατικά µετρηµένες θερµοκρασίες.
3. Οι χρησιµοποιούµενες εισόδοι καλωδίων πρέπει να συµµορφώνονται µε το βαθµό
προστασίας IP 54 στην ενότητα 7.2 (σύµφωνα µε το πρότυπο EN 50021).
4. Όλες οι συσκευές, συµπεριλαµβανοµένων διακοπτών κ.α., που συνδέονται στις
εισόδους και εξόδους του συζεύκτη DP/DP, πρέπει να φέρουν εγκριµένη προστασία
κατά έκρηξης τύπου EEx nA ή EEx nC.
5. Πρέπει να ληφθούν µέτρα, να µην µπορεί να γίνει υπέρβαση της ονοµαστικής τάσης
µέσω αιφνίδιας µεταβολής της τάσης πάνω από 40 %.
6. Περιοχή θερµοκρασίας περιβάλλοντος: 0° C έως 60° C
7. Πρέπει να τοποθετηθεί µέσα στο περίβληµα σε ευδιάκριτο σηµείο µετά το άνοιγµα µία
πινακίδα µε την ακόλουθη προειδοποίηση:
Προειδοποίηση
Το περίβληµα επιτρέπεται να ανοίγει µόνο για µικρό χρονικό διάστηµα, π.χ. για τη
διενέργεια οπτικής διάγνωσης. Μην κάνετε χρήση διακοπτών, µην τραβάτε ή
εµβυσµατώνετε δοµικά συγκροτήµατα και µη διαχωρίζετε ηλεκτροφόρους αγωγούς
(εµβσυµατώσιµες συνδέσεις).
Η προειδοποίηση αυτή δε χρειάζεται να ληφθεί υπ’ όψιν, εάν είναι γνωστό ότι δεν
υφίσταται ατµόσφαιρα παρουσιάζουσα κίνδυνο έκρηξης.
DP/DP Coupler
A5E00224669-03 A-35
Technical Data
DP/DP Coupler
A-36 A5E00224669-03
Order numbers and accessories B
Table B-1 Order numbers for the DP/DP Coupler
DP/DP Coupler
A5E00244669-03 B-1
Order numbers and accessories
DP/DP Coupler
B-2 A5E00244669-03
Glossary
Address
The address of a node is used to identify it on the network. It must be unique
throughout the entire system.
Equipment, electrical
Components, electrical circuits or parts of electrical circuits which are usually
contained in a single enclosure.
Bus
Shared data transfer path to which all nodes are connected; with two defined end
points.
Bus connector
Physical connection between the bus node and the bus cable.
Chassis ground
Chassis ground is formed by the interconnection of inactive equipment parts,
which can not acquire any hazardous contact voltage in the event of a
malfunction.
Diagnostics
Diagnostics is the detection, localization, classification, indication and analysis of
errors, faults and messages.
The diagnostics system provides automatic monitoring functions for system
runtime. This increases the availability of systems by reducing startup times and
downtimes.
DP master
A ³ master that responds in accordance with IEC 61784-1:2002 Ed1 CP 3/1 is
referred to as a DP master.
DP/DP Coupler
A5E00244669-03 Glossary-1
Glossary
DP standard
Represents the bus protocol of the DP system in accordance with
IEC 61784-1:2002 Ed1 CP 3/1.
DP slave
This ³ slave type is operated on PROFIBUS based on the PROFIBUS DP
protocol, and responds in accordance with IEC 61784-1:2002 Ed1 CP 3/1.
Earth
Conductive earth, the electrical potential of which can be set equal to zero at any
point.
Equipotential bonding
An electrical connection (equipotential conductor) that keeps the body of
electrical equipment and external conductive bodies at the same or close to the
same potential, in order to prevent the development of interference or hazardous
voltages between these bodies.
Grounding
Grounding means connecting an electrically conductive component to ground by
means of a grounding system.
GSD file
All slave-specific characteristics are stored in a GSD file. The format of the GSD
file is defined in the PROFIBUS Guideline: Specification for PROFIBUS Device
Description and Device Integration Vol.1: GSD V4.1, 07/2001 of the
PROFIBUS User Organisation (PUO).
HW Config
Hardware configuration component in STEP 7.
DP/DP Coupler
Glossary-2 A5E00244669-03
Glossary
Master
Masters in possession of the token may transmit data to other nodes, and
request data from other nodes (= active node). The CPU 315-2 DP or IM 308-C
are Dp masters, for example.
Parameter assignment
Parameter assignment is the passing of slave parameters from the master to the
slave.
PROFIBUS
Process field bus standard that is defined in the field bus standard to
IEC 61784-1:2002 Ed1 CPF 3 PROFIBUS and PROFInet. It defines functional,
electrical and mechanical properties for a bit-serial field bus system.
PROFIBUS is available with the following protocols: DP (for distributed
I/O systems) and FMS (= Fieldbus Message Specification).
PROFIBUS address
Each bus node must be assigned a PROFIBUS address that uniquely identifies it
on the PROFIBUS-DP.
The PC / PG or hand-held ET200 are assigned the PROFIBUS address “0”.
The PROFIBUS address of the DP masters and DP slaves lie within the range
from 1 to 125.
PROFIBUS DP
This is the PROFIBUS system based on the DP protocol. The abbreviation DP
stands for Distributed Peripherals.
PUO
PROFIBUS user organization
Reference potential
Electrical potential that forms the reference for viewing and/or measuring the
voltage of relevant circuits.
DP/DP Coupler
A5E00244669-03 Glossary-3
Glossary
SELV
Safety extra-low voltage (SELV) is a voltage of vv 30 V AC / 60 V DC
generated by means of a safety isolating transformer, battery, etc.
TN-S system
In a TN-S system, the neutral conductor (N) and protective conductor (PE) are
routed separately. The neutral conductor is always connected to the grounded
protective conductor at a central point. The conductor can be grounded any
number of times.
Terminating resistor
Terminating resistors are used to terminate the data transmission line in order to
avoid reflections.
Transmission rate
The transmission rate defines the number of transmitted bits per second.
Ungrounded
without galvanic connection to earth
DP/DP Coupler
Glossary-4 A5E00244669-03
Index
A D
Accessories, B-1 Data validity indication, 4-4
ADDR, 4-5 Device identifier, 6-8
Address, Glossary-1 DIA, 4-4
Ambient conditions Diagnostics, Glossary-1, Glossary-2,
mechanical, A-9 Glossary-4
operation, A-9 by means of LED indication, 6-2
transport and storage, A-8 by means of the user program, 6-4
Appearance, 1-3 Example, 6-11
Approbation, iv DIN rail, 2-2
Approvals, A-2 Display elements, 1-3, 6-2
Australia – Label, A-3 DP master, Glossary-1
DP slave, Glossary-2
DP Standard, Glossary-2
B DP/DP Coupler
installation , 2-2
Basic knowledge, iii
Technical data, A-12
BF, 6-2
DPV0 / DPV1, 4-11
Bus, Glossary-1
DPV1, iii
Bus connector, Glossary-1
Dual power supply, 3-7
dual power supply, iii
C
C–Tick, iv E
CE, certification, A-2
Electrical isolation, 3-1
CE label, iv
Electromagnetic compatibility, A-6
Certification, CE, A-2
EMERGENCY–OFF equipment, 3-2
Changes compared with the previous version,
Enhancements, iii
iii
Equipment
Chassis ground, Glossary-1
electrical, Glossary-1
Climatic ambient conditions, A-10
open, 2-1
climatic, A-10
Equipotential bonding, Glossary-2
Commissioning, 4-1, 4-14
Error indication, 6-2
Compatibility, 1-4
External diagnostics, 4-11
Components, 2-2
Configuration, 1-1
Procedure, 4-2
Configuration frame, 4-13 F
Configuration in STEP 7, Example, 4-12 Field of application, 1-1
Configuring in STEP 7, 4-8 FM approval, A-3
Configuring using another engineering tool, Function, 1-1
4-13 Further support, v
Connections, 3-6
CSA approval, A-3
DP/DP Coupler
A5E00244669-03 Index-1
Index
G P
Galvanic properties, 3-1 Parameter assignment, 1-1, Glossary-3
Grounding, 3-1, Glossary-2 Parameter assignment frame, 4-13
GSD file, 4-8, 4-13, Glossary-2 Potentially explosive environments, A-13
Power supply
connection, 3-7
H dual, iii, 3-7
Power supply unit, Glossary-3
Hotline, v
Procedure, Configuration, 4-2
HW Config, Glossary-2
PROFIBUS, Glossary-3
PROFIBUS address, Glossary-3
PROFIBUS address of the DP master, 6-8
I PROFIBUS cable, 3-4
IEC 61131, A-4 PROFIBUS DP, Glossary-3
Industrial area, use in the, A-4 connecting, 3-8
Information landscape, iv PROFIBUS standard, A-4
Installation, 2-2 Profile rail for the S7 installation system, 2-3
Insulation test, A-11 Programming, 1-1
Interference Programming example, 1-2
pulse-type, A-6 Properties, 1-3
sinusoidal, A-7 Properties – DP slave, 4-11
Internet address, v Protection class, A-11
Protection type, A-11
PS, 4-3
L PUO, Glossary-3
LED indication, 6-2
LEDs, 6-2
R
Radio interference, emission of, A-7
M Range of validity, iii
Rated voltage, A-11
Manual guide, v
Recycling, v
Manual objectives, iii
Reference potential, Glossary-3
Manuals, Further important manuals, iv
grounded, 3-5
Master, Glossary-3
Removal, 2-3
Module diagnostics
Replacement of a faulty DP/DP Coupler, 5-1
in replacement part mode, 6-10
Residential areas, use in, A-5
status message, 6-8
Response times, 5-2
Module replacement, 5-1
Mounting position, 2-1
Mounting system, 2-1
S
SELV, Glossary-4
N Service, vii
Setting the DIL switch, 4-3
Newsletter, vii
Setting the PROFIBUS address, iii, 4-6, 4-10
SF, 6-2
Slave diagnosis, 6-4
O Standard diagnosis, 6-6
Objectives of this manual, iii Standards, iv, A-2
ON, 6-2 Station status, 6-6
Operating conditions, A-9 Status indication, 6-2
Operator elements, 1-3 Status message, Module diagnostics, 6-8
Order numbers, B-1
DP/DP Coupler
Index-2 A5E00244669-03
Index
DP/DP Coupler
A5E00244669-03 Index-3
Index
DP/DP Coupler
Index-4 A5E00244669-03