How Much Quantity of Chemical Reuqired For Chilled Water System

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 3

Chilled water Sy

Chilled Water Volume In B.S. Pipes SCH 40


Pipe (Dia) in inches Pipe (radius) in inches

1.25 0.625
1.5 0.75
2 1
2.5 1.25
3 1.5
3.5 1.75
4 2
4.5 2.25
5 2.5
6 3
8 4
10 5
12 6
14 7

A 0029 (Corrosion Inhibitor)


A 0029 (Corrosion Inhibitor)
MICROBIOCIDE- A2400
MICROBIOCIDE- A2400
Chilled water System Volume

40
Pipe (radius) in metre Area of pipe (m2) Pipe Length (m)

0.015875 0.0007913290625 130.00


0.01905 0.00113951385 30.00
0.0254 0.0020258024 112.00
0.03175 0.00316531625 72.00
0.0381 0.0045580554 102.00
0.04445 0.00620401985 90.00
0.0508 0.0081032096 106.00
0.05715 0.01025562465 80.00
0.0635 0.012661265 132.00
0.0762 0.0182322216 40.00
0.1016 0.0324128384 30.00
0.127 0.05064506 28.00
0.1524 0.0729288864 25.00
0.1778 0.0992643176 20.00

Total chilled water volume 11.89 m3


Safety factor 20% 2.378811129465
Total chilled water volume 14.27 m3
1m3 3kg chemical
Chemical needed for chilled water system 42.81860033037 kg
1m3 100ml
Chemical needed for chilled water system 1427.286677679 ml
Total volume
(m3)
0.10
0.03
0.23
0.23
0.46
0.56
0.86
0.82
1.67
0.73
0.97
1.42
1.82
1.99
11.89

m3