Product Data Sheet: Alarmline II Analogue LHD Cable W/ PVC Sheath, 100m

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Product Data Sheet

AA-0100
Alarmline II Analogue LHD Cable w/ PVC Sheath, 100m

General

The AA-0100 is an analogue linear heat detection cable in a


PVC outer sheath, supplied in 100m lenghts. It is suitable for
indoor applications where sensor cable is unlikely to be
subjected to physical damage or exposed to harsh
environmental conditions.

In temperature sensitive environments early detection of an


abnormal change is crucial to protect safety of life, critical
processes and reduce losses. The AA analogue range of linear
heat detection cable use exceptionally durable linear heat
detection technologies which provide extensive and continuous
coverage, is easy to install and fully integrate with building
management systems. The products offer an enviable set of
features bringing enhanced benefits and increased safety to the
fire protection industry worldwide. Standard Features
E UL521 Approved, UL/ULC Listed, RoHS compliant and CE
Fast Response Time certified to meet end user specifications
E Open and short circuit detection reduces the risk of false
This unique sensor cable and its method of control continuously alarms
responds to changes in temperature. The technology offers the E Optional pre-alarm setting allows the user to manage risk
facility to programme an early warning pre-alarm as well as the more effectively
specified alarm temperature. If the temperature surrounding the E Cable based sensing allows detection at the point of risk
cable reaches the pre-alarm point, the control unit triggers a E Low installation and maintenance costs reduce total cost of
warning giving the user time to survey the area at risk. Only ownership
when the temperature reaches the specified set alarm point will E Suitable for installation in hazardous areas
the control unit trigger full alarm. E Approved to the latest standards

The Controller

The optional two stage programmable alarm settings make the


system and method of overheat detection incredibly flexible and
ideal for use in a variety of different environments and
applications. The technology automatically compensates for
changes in the ambient temperature to maintain the accuracy of
alarm temperature as well as offering up to 500 metres of
continuous detection per control unit.

Both versions of control unit carry UL521 approval. One is a


self-contained unit or, for finer control, a version requiring a PC
prevents uninvited system access. Both designs are compatible
with any conventional or addressable fire alarm panel or other
building management system.

Reset and Reuse

Analogue LHD cable is “self-restorable” which means it not


always necessary to replace the cable after an incident. Once
the alarm has been triggered and depending on the severity of
the incident the system can simply be reset with minimum
disruption and inconvenience.
AA-0100
Alarmline II Analogue LHD Cable w/ PVC Sheath, 100m

Specifications Ordering Information


Mechanical Part No. Description
Outside diameter (Nominal) 4.57mm +/-0.075mm (0.180” +/-0.003”) AA-0100 Alarmline II Analogue LHD Cable w/ PVC Sheath, 100m
No of cores 4
AACULP Alarmline II Analogue LHD Control Unit - PC Programmable
Core colours Red, White, Clear, Clear
Zone length (min to max) 30.5m to 500m AACUSP Alarmline II Analogue LHD Control Unit - Self Programmable
Weight 2.370kg
Environmental
Operating temperature -40°C to +125°C
limits
Operating temperature -40°C to +90°C
(continuous)
Relative humidity 0% to 99%

As a company of innovation, UTC Fire & Security reserves the right to change product
specifications without notice. For the latest product specifications, visit UTC Fire & Security
online or contact your sales representative.
AA-0100-2016-10-18 02:36:45 Released :14-OCT-16