Calculations:: Design of Purliins
Calculations:: Design of Purliins
DESIGN OF PURLIINS
ACTUAL DIMENSION
WIND LOAD
L 1125
∆ allow= = =4.69 MM
240 240
5 w L4 5(1.18)(1125 4 )
∆= = 3
=2.65<4.69(OK )
384 EI 37 ( 137 )
384(4570)( )
12
2
w l 2 1.18(1125 )
Mn= =
8 8
2
6 Mn 6(1.18)(1125)
f bn= = =4 MPA
b d2 8(37)( 872)
2
w l 2 1.18 (1125 )
Mt= =
8 8
2
6 Mt 6 (0.25)(1125)
f bt = = =2 MPA
b d2 8( 87)(372)
wL 1.18 (1125)
Vn= =
2 2
3V 3(1.18)(1125)
f vn = = =0.31 MPa
2 bd 2(2)(37)(137)
wL 0.25(1125)
Vn= =
2 2
3V 3( 0.25)(1125 )
f vn = = =0.07 MPa
2 bd 2(2)(37)(137)
Fv= 0.32< 1.08 MPA (OK)
DESIGN OF RAFTER
RAFTER
WIND LOAD
L 1125
∆ allow= = =15.04 MM > 13.08MM (OK)
240 240
6 Mmax 6( 3.61)
f b= 2
= =7.12 MPA<10.3 MPA(OK )
bd ( 87)(187 2)
3 Vmax 3(5.69)
f v= = =0.52 MPa<¿ 1.08 MPA (OK)
2 bd 2(0.087)( 0.187)
USE: 100 X 200 MM APITONG 80% STRESS GRADE FOR RAFTER
LOADINGS
L 6000
∆ allow= = =25 MM
240 240
5 w L4 5 (0.2)(60004 )
∆= = 3
=22.9 MM <25 MM (OK )
384 EI 37 ( 187 )
384(7310)( )
12
2
w l 2 0.9(6 )
M= = =0.9
8 8
6 Mmax 6( 0.9)
f b= 2
= =4.173 MPA <16.5 MPA(OK )
bd ( 0.037)(0.187 2)
wL 0.9(6)
V= = =0.6
2 2
3V 3 (0.6)
f v= = =0.13 MPa<1.73 MPA (OK )
2 bd 2(0.037)(0.187)
T0 0.090 16.5
T1 0.090 9.56
T2 0.718 9.56
T3 0.252 9.56
T4 0.486 16.5
T5 0.682 9.56
T6 0.481 9.56
T7 0.548 9.56
T8 0.665 9.56
ALL MEMBER SECTIONS ARE ADEQUATE SINCE THEIR ACTUAL STRESS DOES NOT EXCEED THEIR
CORRESPONDING ALLOWABLE STRESS
DESIGN OF BEAM
TRIAL SECTION: 200 X 250 MM
YAKAL 80% STRESS GRADE
FB& FT // = 24.5 MPA
E=9.78 GPA
FV// = 2.49 MPA
UNIT WEIGHT = 7.46 KN/M3
L 4500
∆ allow= = =18.75 MM >17.25 MM (OK )
240 240
TRIAL SECTION:
APITONG 80% STRESS GRADE
FB & FT= 16.5 MPA
E = 7.31 GPA
FC// = 9.56 MPA
FC PERPENDICULAR = 2.20 MPA
FV // = 1.73 MPA
P1 = 4.83 KN
P1 4.83
P1 actual = = =0.97 MPA
A (0.05)(0.1)
(9.56)(2.2)
P1 ALLOWABLE = =2.8 MPA>0.97 MPA (OK)
9.56 sin 58.042 +2.2 cos 58.052
P2 =5 KN
P2 5
P2 actual = = =0.384 MPA
A ( 0.1)(0.13)
(9.56)( 2.2)
P2 ALLOWABLE = =2.9 MPA >0.384 MPA (OK )
9.56 sin 54.952+ 2.2cos 54.95 2
DETAIL C
L = 100 MM
b = 2- 16 mm dia.
P = 8.47 KN
Q = 5.41 KN
(T) ALLOWABLE FOR BOLT = 2(8.47) = 16.4 KN > 5.791 KN (OK)
(T) ALLOWABLE FOR WOOD = FT(Anet)= 16.5 (150-2(16+16/16))(100)=198KN > 5.791 KN (OK)
DETAIL A (TOP CHORD)
L = 100 MM
b = 4 - 16 mm dia.
P = 8.47 KN
Q = 5.41 KN
(C) ALLOWABLE FOR BOLT = 4(8.47)=33.88KN > 11.095 KN (OK)
TRIAL SECTION:
63% STRESS GRADE YAKAL
E=7700 MPA
FB= 19.3 MPA
FC=12 MPA
DEAD LOADS:
WT. OF FLOOR JOIST= 7.45 KN/M3(0.05)(0.15) = 0.0559 KN/M
WT. OF HARDWOOD FLOORING, 22MM = 0.19 KPA (0.4) = 0.076 KN/M
LIVE LOAD:
4.8(0.4) = 1.92 KN/M
TOTAL LOAD:
0.0559 + 0.076 + 1.92 = 2.05 KN/M
L 2000
∆ allow= = =8.33
240 240
5 w L4 5( 2.05)(2000 4 )
γ= = =7.14 MM <8.33 MM (OK )
384 EI 37 ( 137 )
384 (7700)( )
12
2
w l 2 2.05(2 )
M= = =1.025 kNm
8 8
6 M 6(1.025)
f b= 2 = =9.07
b d 37 (1372)
8.9<19.3 MPa(OK )
wL 2.05(2000)
V= =
2 2
3V 3 (2050)
f v= = =0.61 MPa
2 bd 2(37)(137)
0.61 MPa<1.96 MPa(OK )
DESIGN OF COLUMN
7700
l e 3300
√
k =0.671 (
12
)
= =37.93
d 137
le
>k
d
0.3(7710)
F ' c=
24.042