This document provides input data for the Hall way air handling unit (AHU) system in a single zone constant air volume (CAV) configuration. It includes general details on the AHU type and components, as well as zone details. Sizing data indicates the AHU will provide a supply airflow of 3041 L/s at 14.4°C for cooling and 35°C for heating to meet the zone loads. Ventilation is specified at 70.7 L/s.

Uploaded by

thomasjohnkpy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
40 views2 pages

Air System Inputs

This document provides input data for the Hall way air handling unit (AHU) system in a single zone constant air volume (CAV) configuration. It includes general details on the AHU type and components, as well as zone details. Sizing data indicates the AHU will provide a supply airflow of 3041 L/s at 14.4°C for cooling and 35°C for heating to meet the zone loads. Ventilation is specified at 70.7 L/s.

Uploaded by

thomasjohnkpy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Hall way Input Data

Project Name: Untitled 05/04/2017


Prepared by: OME 11:29AM

1. General Details:
Air System Name ........................................................................... Hall way
Equipment Type ........................................................... Chilled Water AHU
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 14.4 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ...................................................................... Chilled Water
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Central Heating Data:


Supply Temperature ............................................................................. 35.0 °C
Heating Source ............................................................................ Hot Water
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type .......................................................................... Forward Curved
Configuration ............................................................................... Draw-thru
Fan Performance ................................................................................... 500 Pa
Overall Efficiency ..................................................................................... 54 %

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 2 %
Duct Leakage ............................................................................................ 2 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Hallway x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.9 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 °K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ................................................................. thermostat


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ................................................................ Hot Water


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:

Hourly Analysis Program v4.90 Page 1 of 2


Hall way Input Data
Project Name: Untitled 05/04/2017
Prepared by: OME 11:29AM

Cooling Supply Temperature ................................................................ 14.4 °C


Supply Fan Airflow ............................................................................ 3041.0 L/s
Ventilation Airflow ................................................................................. 70.7 L/s
Heating Supply Temperature ................................................................ 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T ............................................................................. 5.6 °K
Hot Water Delta-T ................................................................................. 11.1 °K

Safety Factors:
Cooling Sensible ........................................................................................ 0 %
Cooling Latent ........................................................................................... 0 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) (L/s)

1 2980.2 - -

5. Equipment Data
Changeover Controller:
Used ....................................................................................................... No

Hourly Analysis Program v4.90 Page 2 of 2