Installation Manual - SMD V3
Installation Manual - SMD V3
SMD
Installation Manual
01/2017
www.schneider-electric.com
Substation Monitoring Device Installation manual
1 About this document ..........................................................................................................................................3
2 Acronyms and definitions ..................................................................................................................................3
2.1 Acronyms ..................................................................................................................................................3
2.2 Definitions .................................................................................................................................................3
3 SMD General description ..................................................................................................................................4
3.1 Functions ..................................................................................................................................................4
3.1.1 Thermal monitoring ...............................................................................................................................4
3.1.2 Substation alarming ..............................................................................................................................4
3.1.3 Local and remote monitoring ................................................................................................................4
3.2 Hardware & Connections ..........................................................................................................................4
3.2.1 Architecture ...........................................................................................................................................4
3.2.2 TM251MESE.........................................................................................................................................5
3.2.3 Local HMI ..............................................................................................................................................7
3.2.4 Zigbee concentrator ZBRN32 ...............................................................................................................7
3.2.5 Easergy TH110 thermal sensor ............................................................................................................8
3.2.6 Connectivity ..........................................................................................................................................8
3.2.7 Hardware reference table .................................................................................................................. 10
4 Installation ...................................................................................................................................................... 11
4.1 Hardware configuration .......................................................................................................................... 11
4.2 Physical installation ............................................................................................................................... 11
4.3 Power supply ......................................................................................................................................... 11
4.4 Wiring ..................................................................................................................................................... 11
4.4.1 Main components .............................................................................................................................. 11
4.4.2 GSM option ........................................................................................................................................ 13
4.5 Nearby HMI ............................................................................................................................................ 13
4.6 Remote communication ......................................................................................................................... 14
5 SMD Configuration ......................................................................................................................................... 14
5.1 Presentation of the SMD configurator ................................................................................................... 14
5.2 Configurator installation ......................................................................................................................... 14
5.3 How to use the SMD configurator .......................................................................................................... 14
5.3.1 Principle ............................................................................................................................................. 14
5.3.2 Switchboards screen ......................................................................................................................... 15
5.3.3 Switchboard edit screen for switchboard configuration ..................................................................... 15
5.3.4 Cubicle edit screen for cubicles configuration ................................................................................... 18
5.4 Print the configuration file ...................................................................................................................... 24
6 Download the configuration into the SMD ...................................................................................................... 25
6.1.1 Hardware needed .............................................................................................................................. 25
6.1.2 Generating files to download ............................................................................................................. 25
6.1.3 Transferring files on memory device ................................................................................................. 25
2
Substation Monitoring Device Installation manual
6.1.4 Copying files into SMD ..................................................................................................................... 25
7 Programming the HMI .................................................................................................................................... 26
8 Configuring the Zigbee concentrator .............................................................................................................. 26
9 Pairing sensors with the Zigbee concentrator ................................................................................................ 27
9.1 Pairing .................................................................................................................................................... 27
9.2 Configuration back-up............................................................................................................................ 29
9.2.1 Equipment needed, prerequisite ........................................................................................................ 29
9.2.2 Operation ........................................................................................................................................... 29
10 ANNEX 1 : Modbus address ...................................................................................................................... 29
2.1 Acronyms
BMS Building Management System
CT Current Transformer
HMI Human Machine Interface
I/O Input/Output
LV Low Voltage
MV Medium Voltage
PLC Programmable Logic Controller
RSP Remote Service Platform
RTU Remote Terminal Unit
SCADA Supervision Control And Data Acquisition
SMD Substation Monitoring Device
2.2 Definitions
Zigbee Green Power Radio frequency (2.4GHZ) communication for protocol based on the standard
IEEE 802.15.4. It is commonly used for devices with very low bit rate and
energy consumption.
3
Substation Monitoring Device Installation manual
3.1 Functions
Loose connection is one of the major causes of MV switchboard failure. The purpose of this function is
to monitor the temperature of connections to detect deteriorated one before any damage occurs. It
monitors cable, busbar or CB withdrawable connections thanks to an innovative wireless sensor.
3.2.1 Architecture
4
Substation Monitoring Device Installation manual
3.2.2 TM251MESE
- It acquires all the sensors information: digital, IO, analog IO or Zigbee sensors.
- It runs the different functions: Thermal monitoring, transformer monitoring and generate 2 levels
of alarms.
- It drives the HMI
- It communicates to external world thanks to SMS or Ethernet link.
5
Substation Monitoring Device Installation manual
16DI, Optional
16DI, Optional
16DI, Optional
16DI, Optional
TM251MESE
4AI, Optional
4AI, Optional
TM3DM8R
TM3DI16
TM3DI16
TM3DI16
TM3DI16
TM3TI4
TM3TI4
3.2.2.1 Module TM3DM8R
The TM3DM8R extension module is equipped with 4 contact outputs, normally open and 4 binary inputs.
Contact outputs are used for local signalling of substation global status (Green, Yellow, Red).
Binary inputs are used to collect alarming signals or switchgear position
The TM3DI16 extension module has 16 Digital Inputs. It is use to collect alarming signals or switchgear
position.
The TM3TI4 extension module has 4 Analog Inputs. It will be used for future function of SMD
Please refer to document "Modicon_TM3_TM3TI4.pdf" for more information
The local HMI displays all information and alarm. It allows to locate the origin of the problem thanks to :
single line diagram view
synthesis and detailed views
It is used also to help to install and commission the SMD and its sensors.
The local HMI is made of a Magelis HMISTU855 colour touch screen panel 5''7.
Please refer to the document "Magelis_STO___STU_HMISTU855.pdf" for more information.
7
Substation Monitoring Device Installation manual
The Easergy TH110 is a wireless, battery free thermal sensor. It is used for thermal monitoring of power
connection.
It communicates thanks to Zigbee Green Power protocol (ZGP)
Please refer to document " 2016 Easergy TH110 User Guide V15.pdf" for more information.
3.2.6 Connectivity
SMD offers multiple choices to communicate locally or remotely.
8
Substation Monitoring Device Installation manual
As an option, the SMD is able to send SMS upon alarm or pre-alarm event.
This is achieved thanks to the use of GMS Modem SR2MOD03.
SMS can be sent either directly to one correspondent or to Facility Hero server. Facility Hero is a
digitized log book which allows you to manage your equipments and share maintenance information
inside facility management team.
Please refer to : "http://www.schneider-electric.com/b2b/en/services/partner-managed-services/facility-
hero/facility-hero-overview.jsp" for more information
All data, pre-alarms and alarms are available using Ethernet port and Modbus-TCP/IP protocol.
It could be used for
- direct connection to a SCADA or a BMS
- connection to Schneider service, thanks to Com'x 210/510 gateway
9
Substation Monitoring Device Installation manual
Optional modules
Allow to send SMS or to connect to facility
GSM modem SR2MOD03 0 to 1 hero
Allow wifi connection to SMD. It is used for
Wifi acces point - Wifer TCSEGWB13FA0 0 to 1 nearby HMI
4 Ethernet switches TM4ES4 0 to 1 Allow to add 4 ethernet port RJ45
Sensors
10
Substation Monitoring Device Installation manual
4 INSTALLATION
The I/O board of PLC TM251MESE should respect the following order:
- 1 TM3DM8R board (mandatory)
- 0 to 4 TM3DI16 boards
- 0 to 2 TM3TI4 boards
4.4 Wiring
11
Substation Monitoring Device Installation manual
4.4.1.3 Communication
The Zigbee concentrator is connected on serial port of the PLC TM251MESE. In case of several Zigbee
concentrator, there are daisy chained using the second port of the Zigbee concentrator.
12
Substation Monitoring Device Installation manual
It uses a wifi connection to communicate between the Magelis screen and the mobile device.
Wifi connection can be established using Schneider wifi access point "Wifer" (see § 3.2.7) or equivalent,
directly connected to Ethernet port 1 of PLC TMS215MESE or connected to the same subnetwork as the
Magelis HMI.
13
Substation Monitoring Device Installation manual
The display of Magelis HMI screen on mobile device is realize thanks to the mobile application "Vijeo
Air" available for IOS or Android mobile device.
5 SMD CONFIGURATION
5.3.1 Principle
SMD configurator is a web application using your web browser to display configuration screen.
Configuration files are stored in a database on the computer running the SMD configurator. No need to
be connected to internet.
14
Substation Monitoring Device Installation manual
Click on "Run Browser"
Configurator will execute as a web based application in your default internet browser.
Configuration is made of two mains steps, with different screens for each :
General configuration of the switchboard.
Detailed configuration of each cubicles part of the switchboard.
The switchboard edit screen displays all the tabs to be filled out to describe the switchboard
configuration:
15
Substation Monitoring Device Installation manual
In this tab you can fill information that will appear to identify the substation:
The substation name
The substation description
The click boxes allow to select the function that will be effectively run by the SMD :
- Connection thermal monitoring : Check that box to monitor the temperature of all power
connection. Detail of connection to be monitored will be configurated later.
In this tab you type all the information and identification of the project to document it properly in printing
out :
- Name of the project
- Identification of the project
- The customer which has ordered the project
- The Schneider entity which is handling the project
- The identification of output document : reference to be used for the printed output of the
configurator
16
Substation Monitoring Device Installation manual
- Number of Digital Input board: From 0 to 4 inputs boards of 16 Digital Inputs (D)I each. DI are used
to connect switchgear auxiliary contact for position monitoring and for any digital information that
can be interesting to collect as an alarm (See Free alarms tab).
- Number of Analog Input board: From 0 to 2 inputs boards of 4 Analog Input (AI) each. DI are used
to monitor dry transformer internal temperature thanks to embedded PT100 probe.
- Number of ZGP concentrator: From 0 to 3 Zigbee Green Power concentrator. Each of them allows
to get the measurement of up to 60 thermal sensors (Easergy TH110)
- GSM : Check that box if you intend to use SMS or Facility Hero to notify alarms of SMD. A
dedicated field will appears to enter the phone number. Please refer to Facility Hero documentation
to find out phone number of Facility Hero server.
17
Substation Monitoring Device Installation manual
Free alarms tab allow to create alarm and pre-alarm information related to the switchboard or the
substation based on a Digital Input by keying :
The text to be displayed when alarm or Pre-Alarm occurs
The status to be chosen between Alarm or Pre-Alarm
The normal level of the DI (when not an Alarm/Pre-Alarm) Normally open or Normally closed
The reference of the DI through the Board number (0..4) and the Input number (0..15)
18
Substation Monitoring Device Installation manual
The cubicle edit screen displays all the tabs to be filled out to describe the cubicle configuration. It has to
be filled for each cubicle of the switchboard.
The down connection describe how the cubicle is connected on the low part:
19
Substation Monitoring Device Installation manual
Down connection apply to function Riser, LBS, or CB but not to CB+riser which has already a down
connection defined
The cubicle rated current and CT/Fuse rate current are used to determine the threshold value for
connection thermal monitoring function. Threshold will take into account that cubicle will never be fully
loaded if the CT (or Fuse) rated current is significantly lower than the cubicle rated current.
If they aren't any CT neither fuse, key the cubicle rated current value in the field CT/fuse rated current.
If LBS (or CT) position display is Yes the position of the LBS (or CB) will be displayed and animated on
the HMI on regards of the actual position. If it is No the HMI will display a fix drawing. To animate the
LBS or CB you need to connect 2 digital inputs to the SMD.
20
Substation Monitoring Device Installation manual
- Internal winding monitoring should be Yes to run the thermal monitoring algorithm. It uses 3 Pt100
probes to be connected to analogue Input board.
21
Substation Monitoring Device Installation manual
The thermal monitoring tab allows setting up the different location of the cubicle and the transformer
where sensors will be installed to monitor the electrical connection.
22
Substation Monitoring Device Installation manual
The sensor tab allows setting up the information to address the sensor on Zigbee communication.
Only the location described in the previous tab will be concerned.
The number of the ZGP concentrator used for the cubicle and/or the transformer should be set-up, then
for each sensor:
- The Zigbee Id (not mandatory, it could be determined at pairing time)
- The type of sensor TH110 for thermal monitoring, CL110 for future use
- The input number used in ZGP concentrator. 60 inputs are available. Only one sensor per input
should be set up.
Threshold tab allows adapting the threshold set automatically based on characteristic of the cubicle.
23
Substation Monitoring Device Installation manual
For each location where sensors have been declared:
- Absolute alarm threshold will generate an alarm when one phase exceed it
- Absolute pre-alarm threshold will generate a pre-alarm when one phase temperature exceed it
- Discrepancy alarm threshold will generate an alarm when the difference between two phase
temperatures exceed it
- Discrepancy pre-alarm threshold will generate a pre-alarm when the difference between two phase
temperature exceed it
For each threshold a value can be set between Min and Max value
Free alarms tab allow to create alarm and pre-alarm information related to the cubicle or the transformer
based on a Digital Input by keying :
The text to be displayed when alarm or pre-alarm occurs
The status to be chosen between Alarm or Pre-Alarm
The normal level of the DI (when not an Alarm/Pre-Alarm) Normally open or Normally closed
The reference of the DI through the Board number and the Input number
This tab exists only in case of the LBS or CB position is monitored. It allows configuring the digital input
which will be used to monitor the LSB or CB position. For each position open and close the following
information shall be keyed
Board number
Input number on the board
24
Substation Monitoring Device Installation manual
Printing out the configuration file is useful to put on papers all the information necessary for the wiring of
the switchboard and pairing of Zigbee sensors inside it.
25
Substation Monitoring Device Installation manual
Procedure :
- Extract all the files of HMI.7z on the root of a USB key
- Power-up the HMI.
- Select the language you want when it proposes it
- Plug the USB in HMI
- Answer Yes to the question to take into account the new configuration
- HMI will automatically restart
- Wait for completion of the starting (HMI propose to restart)
- Retrieve the USB key
- Answer Yes to restart the HMI
- HMI restart
- Enter the date and time, when displayed
- HMI display SMD screen (green background)
- HMI is ready to be used on SMD.
- Modbus communication speed : Default value on Zigbee concentrator is 19.2 kbaud. It has to be
changed to 38.4 kbaud. See diagram below to proceed.
Navigation on Zigbee concentrator is done by turning the button to choose a value and push it to select
it. The result of the action can be seen on display
You can always go back to the beginning with a long push on the button
If there are more than one Zigbee concentrator, Modbus address of the 2 nd and 3rd Zigbee concentrator
should be modified following the sequence below :
26
Substation Monitoring Device Installation manual
To set the communication speed to 38.4 kbaud, use the following sequence :
9.1 Pairing
Zigbee sensors should be paired with their concentrator. This has to be done once at the installation
time in order to create the links between each sensor and the zigbee concentrator inputs.
To activate the sensors for pairing you will need a AC current injector (mini 10 A, better 20 A) and a way
to establish non permanent connection on both side to each sensor.
27
Substation Monitoring Device Installation manual
- Pairing one by one sensors using the zigbee concentrator.
o Navigation on Zigbee concentrator is done by turning the button to choose a value and push
it to select it. The result of the action can be seen on display
o
o You can always go back to the beginning with a long push on the button
- Find out the zigbee concentrator and the input number (0..59) of the sensor in the printed table.
- The zigbee concentrator should be ON
- Verify that the corresponding temperature appears on the HMI of the SMD by displaying
temperatures measured in the cubicle.
In case of unsuccessful pairing or mistake, the input shall be cleared using the following sequence:
28
Substation Monitoring Device Installation manual
If the back-up is not done, in case of failure of the Zigbee concentrator which need its
replacement, all sensors connected to it should be replaced also which lead to :
Over cost (sensor + installation)
Shut down of the substation to access to the sensor
9.2.2 Operation
Back-up of the configuration is made that way :
All modbus data are byte, accessible thanks to Modbus function code 03
30
Substation Monitoring Device Installation manual
5 : CB up, pre-alarm phase 1
6 : CB up, pre-alarm phase 2
7 : CB up, pre-alarm phase 3
8 : CB up, phase discrepancy pre-alarm
9 : CB down, alarm phase 1
10 : CB down, alarm phase 2
11 : CB down, alarm phase 3
12 : CB down, phase discrepancy alarm
13 : CB down, pre-alarm phase 1
14 : CB down, pre-alarm phase 2
15 : CB down, pre-alarm phase 3
16 : CB down, phase discrepancy pre-alarm
Cubicle 1 : Alarm, Pre-Alarm for cables 105 Bit detail
1 : Cable 1, alarm phase 1
2 : Cable 1, alarm phase 2
3 : Cable 1, alarm phase 3
4 : Cable 1, phase discrepancy alarm
5 : Cable 1, pre-alarm phase 1
6 : Cable 1, pre-alarm phase 2
7 : Cable 1, pre-alarm phase 3
8 : Cable 1, phase discrepancy pre-alarm
9 : Cable 2, alarm phase 1
10 : Cable 2, alarm phase 2
11 : Cable 2, alarm phase 3
12 : Cable 2, phase discrepancy alarm
13 : Cable 2, pre-alarm phase 1
14 : Cable 2, pre-alarm phase 2
15 : Cable 2, pre-alarm phase 3
16 : Cable 2, phase discrepancy pre-alarm
Cubicle 2 : Alarm, Pre-Alarm for busbar 106 Same as cubicle 1 busbar
Cubicle 2 : Alarm, Pre-Alarm for CB 107 Same as cubicle 1 CB
Cubicle 2 : Alarm, Pre-Alarm for cables 108 Same as cubicle 1 cables
Cubicle 3 : Alarm, Pre-Alarm for busbar 109 Same as cubicle 1 busbar
Cubicle 3 : Alarm, Pre-Alarm for CB 110 Same as cubicle 1 CB
Cubicle 3 : Alarm, Pre-Alarm for cables 111 Same as cubicle 1 cables
Cubicle 4 : Alarm, Pre-Alarm for busbar 112 Same as cubicle 1 busbar
Cubicle 4 : Alarm, Pre-Alarm for CB 113 Same as cubicle 1 CB
Cubicle 4 : Alarm, Pre-Alarm for cables 114 Same as cubicle 1 cables
Cubicle 5 : Alarm, Pre-Alarm for busbar 115 Same as cubicle 1 busbar
Cubicle 5 : Alarm, Pre-Alarm for CB 116 Same as cubicle 1 CB
Cubicle 5 : Alarm, Pre-Alarm for cables 117 Same as cubicle 1 cables
Cubicle 6 : Alarm, Pre-Alarm for busbar 118 Same as cubicle 1 busbar
Cubicle 6 : Alarm, Pre-Alarm for CB 119 Same as cubicle 1 CB
Cubicle 6 : Alarm, Pre-Alarm for cables 120 Same as cubicle 1 cables
Cubicle 7 : Alarm, Pre-Alarm for busbar 121 Same as cubicle 1 busbar
Cubicle 7 : Alarm, Pre-Alarm for CB 122 Same as cubicle 1 CB
Cubicle 7 : Alarm, Pre-Alarm for cables 123 Same as cubicle 1 cables
Cubicle 8 : Alarm, Pre-Alarm for busbar 124 Same as cubicle 1 busbar
Cubicle 8 : Alarm, Pre-Alarm for CB 125 Same as cubicle 1 CB
Cubicle 8 : Alarm, Pre-Alarm for cables 126 Same as cubicle 1 cables
Cubicle 9 : Alarm, Pre-Alarm for busbar 127 Same as cubicle 1 busbar
Cubicle 9 : Alarm, Pre-Alarm for CB 128 Same as cubicle 1 CB
Cubicle 9 : Alarm, Pre-Alarm for cables 129 Same as cubicle 1 cables
Cubicle 10 : Alarm, Pre-Alarm for busbar 130 Same as cubicle 1 busbar
31
Substation Monitoring Device Installation manual
Cubicle 10 : Alarm, Pre-Alarm for CB 131 Same as cubicle 1 CB
Cubicle 10 : Alarm, Pre-Alarm for cables 132 Same as cubicle 1 cables
Cubicle 11 : Alarm, Pre-Alarm for busbar 133 Same as cubicle 1 busbar
Cubicle 11 : Alarm, Pre-Alarm for CB 134 Same as cubicle 1 CB
Cubicle 11 : Alarm, Pre-Alarm for cables 135 Same as cubicle 1 cables
Cubicle 12 : Alarm, Pre-Alarm for busbar 136 Same as cubicle 1 busbar
Cubicle 12 : Alarm, Pre-Alarm for CB 137 Same as cubicle 1 CB
Cubicle 12 : Alarm, Pre-Alarm for cables 138 Same as cubicle 1 cables
Cubicle 13 : Alarm, Pre-Alarm for busbar 139 Same as cubicle 1 busbar
Cubicle 13 : Alarm, Pre-Alarm for CB 140 Same as cubicle 1 CB
Cubicle 13 : Alarm, Pre-Alarm for cables 141 Same as cubicle 1 cables
Cubicle 14 : Alarm, Pre-Alarm for busbar 142 Same as cubicle 1 busbar
Cubicle 14 : Alarm, Pre-Alarm for CB 143 Same as cubicle 1 CB
Cubicle 14 : Alarm, Pre-Alarm for cables 144 Same as cubicle 1 cables
Cubicle 15 : Alarm, Pre-Alarm for busbar 145 Same as cubicle 1 busbar
Cubicle 15 : Alarm, Pre-Alarm for CB 146 Same as cubicle 1 CB
Cubicle 15 : Alarm, Pre-Alarm for cables 147 Same as cubicle 1 cables
Cubicle 16 : Alarm, Pre-Alarm for busbar 148 Same as cubicle 1 busbar
Cubicle 16 : Alarm, Pre-Alarm for CB 149 Same as cubicle 1 CB
Cubicle 16 : Alarm, Pre-Alarm for cables 150 Same as cubicle 1 cables
32
Substation Monitoring Device Installation manual
and winding connection
Transformer 3: Alarm, Pre-Alarm for, LV 156 Same as Transformer 1
connection
Transformer 4: Alarm, Pre-Alarm for MV 157 Same as Transformer 1
and winding connection
Transformer 4: Alarm, Pre-Alarm for, LV 158 Same as Transformer 1
connection
Transformer 5: Alarm, Pre-Alarm for MV 159 Same as Transformer 1
and winding connection
Transformer 5: Alarm, Pre-Alarm for, LV 160 Same as Transformer 1
connection
Transformer 6: Alarm, Pre-Alarm for MV 161 Same as Transformer 1
and winding connection
Transformer 6: Alarm, Pre-Alarm for, LV 162 Same as Transformer 1
connection
Transformer 7: Alarm, Pre-Alarm for MV 163 Same as Transformer 1
and winding connection
Transformer 7: Alarm, Pre-Alarm for, LV 164 Same as Transformer 1
connection
Transformer 8: Alarm, Pre-Alarm for MV 165 Same as Transformer 1
and winding connection
Transformer 8: Alarm, Pre-Alarm for, LV 166 Same as Transformer 1
connection
Transformer 9: Alarm, Pre-Alarm for MV 167 Same as Transformer 1
and winding connection
Transformer 9: Alarm, Pre-Alarm for, LV 168 Same as Transformer 1
connection
Transformer 10: Alarm, Pre-Alarm for MV 169 Same as Transformer 1
and winding connection
Transformer 10: Alarm, Pre-Alarm for, LV 170 Same as Transformer 1
connection
Transformer 11: Alarm, Pre-Alarm for MV 171 Same as Transformer 1
and winding connection
Transformer 11: Alarm, Pre-Alarm for, LV 172 Same as Transformer 1
connection
Transformer 12: Alarm, Pre-Alarm for MV 173 Same as Transformer 1
and winding connection
Transformer 12: Alarm, Pre-Alarm for, LV 174 Same as Transformer 1
connection
Transformer 13: Alarm, Pre-Alarm for MV 175 Same as Transformer 1
and winding connection
Transformer 13: Alarm, Pre-Alarm for, LV 176 Same as Transformer 1
connection
Transformer 14: Alarm, Pre-Alarm for MV 177 Same as Transformer 1
and winding connection
Transformer 14: Alarm, Pre-Alarm for, LV 178 Same as Transformer 1
connection
Transformer 15: Alarm, Pre-Alarm for MV 179 Same as Transformer 1
and winding connection
Transformer 15: Alarm, Pre-Alarm for, LV 180 Same as Transformer 1
connection
Transformer 16: Alarm, Pre-Alarm for MV 181 Same as Transformer 1
and winding connection
Transformer 16: Alarm, Pre-Alarm for, LV 182 Same as Transformer 1
33
Substation Monitoring Device Installation manual
connection
Cubicle 1 Temperature 200 Busbar phase 1
Cubicle 1 Temperature 201 Busbar phase 2
Cubicle 1 Temperature 202 Busbar phase 3
Cubicle 1 Temperature 203 CBup phase 1
Cubicle 1 Temperature 204 CBup phase 2
Cubicle 1 Temperature 205 CBup phase 3
Cubicle 1 Temperature 206 CBdown phase 1
Cubicle 1 Temperature 207 CBdown phase 2
Cubicle 1 Temperature 208 CBdown phase 3
Cubicle 1 Temperature 209 Cable1 phase 1
Cubicle 1 Temperature 210 Cable1 phase 2
Cubicle 1 Temperature 211 Cable1 phase 3
Cubicle 1 Temperature 212 Cable2 phase 1
Cubicle 1 Temperature 213 Cable2 phase 2
Cubicle 1 Temperature 214 Cable2 phase 3
Cubicle 2 Temperatures 215-229 See Cubicle 1 disposition (200-214)
Cubicle 3 Temperatures 230-244 See Cubicle 1 disposition (200-214)
Cubicle 4 Temperatures 245-259 See Cubicle 1 disposition (200-214)
Cubicle 5 Temperatures 260-274 See Cubicle 1 disposition (200-214)
Cubicle 6 Temperatures 275-289 See Cubicle 1 disposition (200-214)
Cubicle 7 Temperatures 290-304 See Cubicle 1 disposition (200-214)
Cubicle 8 Temperatures 305-319 See Cubicle 1 disposition (200-214)
Cubicle 9 Temperatures 320-334 See Cubicle 1 disposition (200-214)
Cubicle 10 Temperatures 335-349 See Cubicle 1 disposition (200-214)
Cubicle 11 Temperatures 350-364 See Cubicle 1 disposition (200-214)
Cubicle 12 Temperatures 365-399 See Cubicle 1 disposition (200-214)
Cubicle 13 Temperatures 380-414 See Cubicle 1 disposition (200-214)
Cubicle 14 Temperatures 395-429 See Cubicle 1 disposition (200-214)
Cubicle 15 Temperatures 410-424 See Cubicle 1 disposition (200-214)
Cubicle 16 Temperatures 425-439 See Cubicle 1 disposition (200-214)
Transformer 1 temperature 440 MV connection phase 1
Transformer 1 temperature 441 MV connection phase 2
Transformer 1 temperature 442 MV connection phase 3
Transformer 1 temperature 443 LV connection phase 1
Transformer 1 temperature 444 LV connection phase 2
Transformer 1 temperature 445 LV connection phase 3
Transformer 1 temperature 446 LV connection neutral
Transformer 1 temperature 447 Winding connection 1
Transformer 1 temperature 448 Winding connection 2
Transformer 1 temperature 449 Winding connection 3
Transformer 2 temperatures 450-459 See transformer 1 disposition (440-449)
Transformer 3 temperatures 460-469 See transformer 1 disposition (440-449)
Transformer 4 temperatures 470-479 See transformer 1 disposition (440-449)
Transformer 5 temperatures 480-489 See transformer 1 disposition (440-449)
Transformer 6 temperatures 490-499 See transformer 1 disposition (440-449)
Transformer 7 temperatures 500-509 See transformer 1 disposition (440-449)
Transformer 8 temperatures 510-519 See transformer 1 disposition (440-449)
Transformer 9 temperatures 520-529 See transformer 1 disposition (440-449)
Transformer 10 temperatures 530-539 See transformer 1 disposition (440-449)
Transformer 11 temperatures 540-549 See transformer 1 disposition (440-449)
Transformer 12 temperatures 550-559 See transformer 1 disposition (440-449)
Transformer 13 temperatures 560-569 See transformer 1 disposition (440-449)
34
Substation Monitoring Device Installation manual
Transformer 14 temperatures 570-579 See transformer 1 disposition (440-449)
Transformer 15 temperatures 580-589 See transformer 1 disposition (440-449)
Transformer 16 temperatures 590-599 See transformer 1 disposition (440-449)
35