Multiple Output Power Supply
Multiple Output Power Supply
Measure the current Use output lists on Use overcurrent Turn on / off multiple
draw of a device with a multiple output protection to shut down power buses in a
multiple power buses power supply multiple outputs sequence
Go to Tip 1 > Go to Tip 2 > Go to Tip 3 > Go to Tip 4 >
LEARN MORE
MEASURE CURRENT OUTPUT POWER SUPPLY OVERCURRENT PROTECTION TURN ON/OFF LEARN MORE
• Simple
• Readback accuracy specified
• Reduces cabling, connections, and loops which add inductance along with noise
susceptibility Figure 1. Keysight E36312A is simultaneously displaying voltage and current on three outputs
MEASURE CURRENT OUTPUT POWER SUPPLY OVERCURRENT PROTECTION TURN ON/OFF LEARN MORE
MEASURE CURRENT OUTPUT POWER SUPPLY OVERCURRENT PROTECTION TURN ON/OFF LEARN MORE
MEASURE CURRENT OUTPUT POWER SUPPLY OVERCURRENT PROTECTION TURN ON/OFF LEARN MORE
Output lists are a series of steps; each step contains a voltage-current pair, a
dwell time, and optional external triggers. In normal operation, the power supply
will output the voltage for the specified time in each step. The power supply
outputs the voltage provided the load requires less current than the limit set in
the step. At the current limit, the power supply switches to constant current
mode. To learn more about constant current mode — see Tip 1, Building Your
Power Supply Skill Set (5992-2716EN.)
MEASURE CURRENT OUTPUT POWER SUPPLY OVERCURRENT PROTECTION TURN ON/OFF LEARN MORE
By default, the output lists for each channel are independent. The list starts
independently and shares nothing in common with each other. However, many tests
require synchronization between outputs.
1 Use a common trigger to start the lists. If the lists share a common number of steps
and dwell times, the outputs are synchronized.
2 An external trigger can advance each step. All the outputs are set to advance on the
same external trigger.
Figure 4. An output list containing eight steps
3 One of the outputs is used to advance the other outputs. For example, output one can
advance steps using the dwell times and send an external trigger with each step. The
other output lists are configured to advance on the external trigger from channel one.
When more channels are necessary, the digital I/O port can connect multiple power
supplies allowing more outputs to be synchronized. List mode has the functionality to
vary the output and create timing between outputs. If you can imagine it, you can set it
up using the list mode.
MEASURE CURRENT OUTPUT POWER SUPPLY OVERCURRENT PROTECTION TURN ON/OFF LEARN MORE
MEASURE CURRENT OUTPUT POWER SUPPLY OVERCURRENT PROTECTION TURN ON/OFF LEARN MORE
1 The OCP function is configurable with or without delay. Some devices as part
of their normal operation will draw current above the limit for a brief period. Higher
current is allowed during the OCP delay. If the overcurrent persists beyond the delay,
OPC shuts down the output and generates a fault.
2 The digital I/O port has three pins, one of which is configurable to output the fault
output signal. An external wire needs to connect the fault out signal pin to the inhibit
input pin.
3 The inhibit function is designed to shut down all the outputs based on an external
signal. It is often wired to an emergency shut off switch. In our application, the fault
output signal will generate the inhibit condition.
If more than one power supply is in use, the digital IO ports are daisy-chained
so all outputs, even across mainframes, will shut down on an overcurrent event.
Overcurrent protection, fault-out, and the inhibit function are three powerful features Figure 5. OPC shuts down channel 1 as overcurrent persists, yellow; fault out signal goes
low on OPC, red; inhibit shuts down all three channels, yellow, green, and blue
to use together to provide additional protection to a device.
MEASURE CURRENT OUTPUT POWER SUPPLY OVERCURRENT PROTECTION TURN ON/OFF LEARN MORE
MEASURE CURRENT OUTPUT POWER SUPPLY OVERCURRENT PROTECTION TURN ON/OFF LEARN MORE
• The coupling function creates a subset of outputs that turn on and off with each
other. The coupled outputs use the sequencing delays. When power is cycled on
coupled channels, the outputs not coupled are not affected.
• The digital I/O port is configurable to couple outputs on multiple power supplies.
Using multiple power supplies meets the needs of applications requiring many
voltage outputs.
Each output should have a voltage and a current level configured before enabling the
power supply’s outputs. When you are setting delays, consider the output transient
Figure 6. The timing diagram at the top of the display is created from delays entered
response time. Depending on the load and the voltage setting the output can take 10 to
50 ms to reach its set voltage.
As an example, output one is used to power control logic and needs power up before
output two and three which power mechanical actuators; see Figure 6 — output two
and three are coupled. The “All on” button executes a sequence that allows the control
logic to be operational before power is sent to the actuators.
At any time, the coupled outputs that drive the actuators can be powered up or down
by pressing either of the output buttons for output two or three. When powered down, WATCH NOW
the output two delay is two seconds, and channel three by three seconds. Channel one
is not affected by the coupled channels. “All off” shuts down all the outputs following the For additional information: see Power Supply Output Sequencing video
delay sequence that ensures the actuators are powered down before the control logic.
MEASURE CURRENT OUTPUT POWER SUPPLY OVERCURRENT PROTECTION TURN ON/OFF LEARN MORE
Evaluate the voltage, current and power for your device upfront and select a
power supply that slightly exceeds the device’s limits so that you have enough
Form Factor?
power to handle transient or surge currents which are common when powering Bench power supplies should be small, but have large bright displays and front
up a device. If you are designing a low power device, use a power supply with panel connectors. System power supplies are designed to minimize rack space
a low range that can accurately measure current being drawn. but their longer depth and loud fans do not belong on a bench!
LEARN MORE COMPARE FEATURES AND PRICES Visit Comparison Webpage >
MEASURE CURRENT OUTPUT POWER SUPPLY OVERCURRENT PROTECTION TURN ON/OFF LEARN MORE