0% found this document useful (0 votes)
109 views19 pages

NERC Standardized Component Model Manual

This document introduces standardized powerflow and dynamics models libraries created by NERC to address the need for accurate interconnection-wide simulations. It provides background on the issues with existing component models and the goals of the standardized model libraries. It also describes the standardized powerflow parameter and dynamics model libraries and their relationship to NERC reliability standards.

Uploaded by

Nagy Abed
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
109 views19 pages

NERC Standardized Component Model Manual

This document introduces standardized powerflow and dynamics models libraries created by NERC to address the need for accurate interconnection-wide simulations. It provides background on the issues with existing component models and the goals of the standardized model libraries. It also describes the standardized powerflow parameter and dynamics model libraries and their relationship to NERC reliability standards.

Uploaded by

Nagy Abed
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 19

 

NERC Libraries of Standardized


Powerflow Parameters and Standardized
Dynamics Models
Version 1 – October 15, 2015

Introduction
There  is  a  growing  need  for  accurate  interconnection‐wide  powerflow  and  dynamics  simulations  that 
analyze phenomena such as: 
 Frequency response, 
 inter‐area oscillations, and  
 interactions between the growing numbers of wide‐area control and protection systems.  
 
This  requires  that  validated  interconnection‐wide  powerflow  and  dynamics  cases  be  developed  and 
available to the industry. These powerflow and dynamics cases are far more detailed than those envisioned 
when the original “basic data groups” were formed to provide outside‐world models for local analyses. 
 
Interconnection‐wide  powerflow  and  dynamics  cases  are  constructed  from  thousands  of  individual 
component models. Currently, there is a proliferation of component model structures that can be used to 
represent  a  particular  type  of  equipment.  This  multitude  of  model  structures  causes  problems  in  the 
interchange of data, particularly for the construction of interconnection‐wide cases. Some of the model 
structures have information that is considered to be proprietary or confidential, which impedes the free 
flow of information necessary for interconnection‐wide power system analysis and model validation. An 
industry‐wide forum for discussing the validity of these various model structures is needed. The industry 
should  agree  upon  standardized  component  model  structures  and  associated  parameters  for  particular 
types  of  equipment.  Furthermore,  an  industry‐wide  forum  is  also  needed  to  identify  the  need  for  new 
component models and for tracking changes to existing model structures. 
 
To address this problem, the Planning Committee (PC) directed the NERC Modeling Working Group (MWG) 
to  develop,  validate,  and  maintain  a  library  of  standardized  component  models  and  parameters  for 
powerflow  and  dynamics  cases.  These  libraries  are  henceforth  referred  to  as  the  NERC  libraries  of 
standardized  models  (“standardized  models”).  The  standardized  models  in  these  libraries  have 
documentation  describing  their  model  structure,  parameters,  and  operation.  This  information  has  been 
vetted by the industry and thus deemed appropriate for widespread use in interconnection‐wide analysis. 
Standardized models promote the submittal of component model data that is required by the NERC MOD 
Reliability Standards and facilitate the free flow of information necessary to validate model parameters, 
assess model performance, and perform the associated system reliability analyses.  
 

 
 

An initial library of standardized models was created using the contemporary regionally‐approved dynamic 
model libraries. Additional models from the Institute of Electrical and Electronics Engineers (IEEE) and other 
appropriate organizations were added as appropriate. Models for new technological innovations are added 
to the library of standardized models following their development and vetting. The library of standardized 
models is subject to the review and approval of the MWG, which is composed of industry subject matter 
experts and representatives from regional modeling working groups. 

The  libraries  of  standardized  models  are  documented  in  two  lists:    the  NERC  Library  of  Standardized 
Powerflow  Parameters  and  the  NERC  Library  of  Standardized  Dynamics  Models.    The  NERC  Modeling 
Working Group (MWG) has established criteria for what constitutes a standardized model.  MWG has also 
developed  requirements  for  submitting,  evaluating,  and  making  changes  to  the  NERC  Library  of 
Standardized  Powerflow  Parameters  and  NERC  Library  of  Standardized  Dynamics  Models.    These 
requirements  address  modeling  developments  and  “black  box1,”  proprietary,  and  user‐defined  models.  
This  manual  presents  both  the  criteria  for  standardized  models  and  the  process  for  updating  and 
maintaining the lists of standardized models. 
 
NERC Library of Standardized Powerflow Parameters
The NERC Library of Standardized Powerflow Parameters is a library of parameters that have been vetted 
by the industry for use in Interconnection‐wide powerflow cases.  Each parameter in the NERC library has 
been reviewed by MWG and deemed to meet all of the criteria for a standardized powerflow parameter.  
The parameters are for positive sequence powerflow cases.  Some of the parameters are designated as 
having  enumerated  values;  conventional  powerflow  programs  generally  use  an  integer  coding  for  the 
different values that these variables can have. 
 
Some parameters for powerflow elements are not standardized in the industry.  For example, some entities 
only enter two ratings for a transmission line in a powerflow case, while others enter up to 8.  Only those 
powerflow modeling parameters which, in the view of MWG, have truly standardized definitions across the 
industry and do not have conflicting definitions among the major Interconnections are included in the NERC 
library.    Each  Interconnection  may  (and  does)  use  parameters  in  addition  to  those  in  the  library  of 
standardized parameters.  Some interconnections may also accept enumerated values for parameters other 
than those listed in the NERC Library. 
 
The  modeling  requirements  for  each  Interconnection  may  require  the  use  of  additional  powerflow 
parameters.    The  modeling  requirements  for  each  Interconnection  supercede  this  list  and  should  be 
consulted directly. 
 
NERC Library of Standardized Dynamics Models
The NERC Library of Standardized Dynamics Models is a library of component models that have been vetted 
by  the  industry  for  use  in  Interconnection‐wide  models.    Generators,  excitation  systems,  and  turbine‐

                                                       
1 “Black box” refers to a user‐written model which does not have sufficient documentation to fully represent the model dynamics. 

Documentation includes a block diagram, values and names for all model parameters, a list of all state variables, and any dynamic 
characteristics of the model. 

NERC Libraries of Standardized Powerflow Parameters and Standardized Dynamics Models  2 
 

governors are examples of components, and each can have an individual dynamics model.  Each of the 
component models in the NERC library has been reviewed by MWG and deemed to meet all of the criteria 
for a standardized dynamics model. 
 
Some  dynamics  component  models  are  not  used  in  some  Interconnections.    (In  fact,  some  models  are 
prohibited for use in some Interconnections.) However, as long as a particular model meets the criteria 
established by MWG for a standardized model, MWG includes that particular component model in the NERC 
library.  In particular, IEEE models used in the industry are included as they have clear definitions.  Given 
the large variety of equipment in use, MWG believes that the largest variety of models that meet the criteria 
for inclusion ought to be included in the Library so that the broadest choices are available to represent 
equipment.    Accordingly,  any  dynamics  model  in  use  in  at  least  one  of  the  major  Interconnections  is 
included  in  the  library  so  long  as  it  meet  the  criteria.    Some  Interconnections  may  accept  or  require 
parameters for component models in addition to the parameters identified in the model documentation. 
 
Some of the models in this library may not be acceptable for use in all Interconnections.  The modeling 
requirements for each Interconnection supercede this list and should be consulted directly.  The Western 
Interconnection in particular has a library of dynamics models [W1] that are approved for use in Western 
Interconnection base cases. 
 
Relationship Between Standardized Models and NERC Modeling
Standards (MOD-032-1)
Use of the NERC Libraries of Standardized Powerflow Parameters and Dynamics Models is not specifically 
required by the NERC standards for data submittal for interconnection cases (i.e., MOD‐032‐1).  However, 
the dynamics models in the library meet the documentation requirements of MOD‐032‐1. 
 
Perspective on Common Information Model (CIM)
MWG appreciates the work done by various parties in developing the Common Information Model (CIM) 
and  recognizes  the  value  in  standardizing  parameters  and  models.    CIM  is  a  possible  future  means  for 
standardizing powerflow parameters and dynamics models.  However, at present, it is not in widespread 
use for exchanging Interconnection powerflow and dynamics cases.  One reason for this situation is the 
enormous file sizes that result when employing the model for Interconnection cases.  
 
Justification for Standardized Models
Standardized models are needed in the industry for a number of reasons: 
1. Availability of industry approved and validated component models to be applied in all software 
that is used for powerflow and dynamics analysis 
a. Portability of data between programs 
b. Ability for new software to be developed 
2. Assembly of data by equipment manufacturers and owners in a consistent format that can be 
reliably used in interconnection‐wide models 

NERC Libraries of Standardized Powerflow Parameters and Standardized Dynamics Models  3 
 

3. Reliable simulation of the models in the programs 
a. Maintenance of the models in program version changes 
b. Facilitate comparison of component model behavior between programs 
4. Documentation of the model characteristics, including block diagrams and model logic 
5. Ease of use for newly planned and operating equipment 
6. Identifies need for new model creation (if a new type of equipment cannot be properly 
represented by existing standardized models) 
7. Allows for rapid dissemination of models of new, innovative equipment 
8. Facilitates a group dialogue between equipment manufacturers, software developers, entities, and 
model users 
a. Thorough vetting of the models 
b. Informing software vendors, equipment manufacturers, and users regarding modeling needs 
and issues related to improving interconnection‐wide powerflow and dynamics modeling 
c. Creates a subject matter expert (SME) forum for annual industry‐wide dialogue that: 
i. fosters inclusion of operational and planned models, and  
ii. for update of library of standardized models 
9. Enhances and strengthens the NERC modeling standards   
a. Creates an industry‐wide submittal and posting process for operational and planned models 
b. Develops a library of standardized models 
c. Clarifies industry‐wide modeling requirements for software vendors, equipment 
manufacturers, and users 
d. Supports industry‐wide model development, validation, and maintenance through the SME 
forum 
10. Minimize duplication of efforts in the creation and testing of new models 
 
Criteria for Standardized Powerflow Parameters and Standardized
Dynamics Component Models
1. Publicly available documentation 
a. Block diagrams 
b. Model logic 
c. List of parameters including description and units 
d. Typical parameter values with recommended range 

NERC Libraries of Standardized Powerflow Parameters and Standardized Dynamics Models  4 
 

2. The collection of standardized models is capable of representing all operating or planned 
equipment attached to the power system with reasonable accuracy 
a. Generally, standardized models represent equipment in widespread use 
b. A standardized model with enough options to replace installation‐specific models should be 
used for equipment that are similar in function 
c. Where feasible, a standardized model that aggregates installation specific models may be used 
to represent multiple equipment installations, which are similar in function 
d. In some cases, a separate standardized model may need to be created to represent a single 
unique type of equipment  
3. Thoroughly vetted, validated, and deemed acceptable for use by the industry by one or more of 
the following: 
a. WECC Modeling and Validation Work Group (M&VWG) model approval process 
b. Other Regional modeling working groups 
c.  Task Force with subject matter experts organized under auspices of MWG 
d. IEEE 
e. North American Transmission Forum 
4. Standardized, unique name that is recognized throughout the industry 
 
Additions to NERC Library of Standardized Powerflow Parameters
Parameters for powerflow cases will be added to the NERC Library of Standardized Powerflow Parameters 
after the following steps: 
1. A thorough vetting, validation, and approval for use by the industry by one or more of the 
following: 
a. WECC System Review Work Group (SRWG) 
b. ERAG Multi‐regional Modeling Working Group (MMWG) 
c. Other Regional powerflow working groups 
d.  Task Force with subject matter experts organized under auspices of MWG 
e. IEEE 
f. North American Transmission Forum 
2. Approval by MWG 
 
Additions to NERC Library of Standardized Dynamics Models
Dynamics component models will be added to the NERC Library of Standardized Dynamics Models after the 
following steps: 
 

NERC Libraries of Standardized Powerflow Parameters and Standardized Dynamics Models  5 
 

1. A thorough vetting, validation, and approval for use by the industry by one or more of the 
following: 
a. WECC M&VWG 
b. Other Regional modeling working groups 
c. Task Force with subject matter experts organized under auspices of MWG 
d. IEEE 
e. North American Transmission Forum 
2. Approval by MWG 

Any model added to the NERC Library of Standardized Dynamics Models will need to meet the criteria for 
standardized models listed above. 
 
Removals from NERC Library of Standardized Powerflow Parameters
Parameters for powerflow cases will be removed from the NERC Library of Standardized Powerflow 
Parameters after the following steps: 
1. Determination that the parameter is no longer suitable for use by the industry by one or more of 
the following: 
a. WECC SRWG 
b. ERAG MMWG 
c. Other Regional powerflow working groups 
d.  Task Force with subject matter experts organized under auspices of MWG 
e. IEEE 
f. North American Transmission Forum 
2. Approval by MWG of a decision to remove the parameter 
 
Removals from NERC Library of Standardized Dynamics Models
Dynamics component models will be removed from the NERC Library of Standardized Dynamics Models 
after the following steps: 
1. Determination that the model is no longer suitable for use in the industry by one or more of the 
following: 
a. WECC M&VWG 
b. Other Regional modeling working groups 
c.  Task Force with subject matter experts organized under auspices of MWG 
d. IEEE 

NERC Libraries of Standardized Powerflow Parameters and Standardized Dynamics Models  6 
 

e. North American Transmission Forum 
2. Approval by MWG of a decision to remove the model 

Industry Notification of New Version of NERC Libraries of Standardized


Powerflow Parameters and Standardized Dynamics Models
After changes are made to either of these lists, the updated version of the lists will be posted on the MWG 
page of the NERC web site: 
 
http://www.nerc.com/comm/PC/Pages/Model‐Working‐Group‐(MWG)‐2013.aspx 
 
An announcement of the posting will be made.   

Periodic Review of NERC Library of Standardized Dynamics Models


MWG will periodically review whether: 
1. All models on the approved model lists for each Interconnection are included in the NERC Library 
of Standardized Dynamics Models (3 times per year) 
2. All models in use in the Interconnection‐wide dynamics cases for each Interconnection are 
included in the NERC Library of Standardized Dynamics Models (annual) 

MWG will determine the reason for any discrepancy that is found and adjust the NERC Library Standardized 
Dynamics Models as appropriate.  In a few cases, there may be legitimate reasons for discrepancies to exist. 

Modeling Developments and Requirements for User-defined Models


MWG recognizes that the on‐going development of new technologies for generation and load will require 
a corresponding on‐going development of new dynamics component models.  As the vetting of such models 
takes some time, ad hoc user‐defined models will need to be used on an interim basis in some situations.  
The requirements for such models are already specified in both the Interconnection‐specific requirements 
for dynamics cases and the recently approved MOD‐032 standard.  In particular, “black box” models without 
proper  documentation,  including  block  diagrams,  are  not  allowed  to  be  used  in  Interconnection‐wide 
dynamics cases. 
 

NERC Libraries of Standardized Powerflow Parameters and Standardized Dynamics Models  7 
NERC LIBRARY OF STANDARDIZED POWERFLOW PARAMETERS
1. Case heading
a. Case title line 1 ID first line of case title String.
b. Case title line 2 ID second line of case title String.
c. System base (MVA) ID value of system base for transmission per unit quantities in MVA Real.
2. Bus Data: 1 record for each bus
a. Bus number ID label identifying the particular bus represented by this data record Integer, positive.
b. Bus name ID short name for bus String.
c. Base voltage EQ base value in kV for bus voltage per unit quantities Real.

Powerflow constraints for this bus; 4 possible values: PQ bus (no generator, real and reactive power injection at bus
d. Bus Type DEP fixed), PV bus (generator directly connected, real power injection at bus and bus voltage magnitude fixed), slack bus Enumerated type
(bus voltage magnitude and angle fixed), bus out-of-service (not part of network solution)

e. Area number ID area to which bus is assigned Integer, positive.


f. Zone number ID zone to which bus is assigned Integer, positive.
g. Owner number ID Owner to which bus is assigned. Integer.
h. Voltage magnitude DEP value in per unit on bus base voltage (item 2c) Real.
i. Voltage angle DEP value in degrees Real.
j. Voltage regulation setpoint OP setpoint of all devices regulating the voltage of this bus, value in per unit Real.
3. Load Data: 1 record for each load
a. Bus number ID number of bus in bus data (section 2) to which load is attached Integer.
String, maximum 2
b. Load identifier ID label identifying the particular load represented by this data record
characters*.
c. Status OP 0: load out-of-service, 1: load in-service Integer, 0 or 1.
d. Area Number ID number of the area in area data (section 9) to which load is assigned Integer.
e. Zone Number ID number of the zone in zone data (section 10) to which load is assigned Integer.
f. Owner Number ID number of the owner in owner data (section 11) to which load is assigned Integer.
g. P OP constant real power in MW drawn by load from bus Real.
h. Q OP constant reactive power in MVAR drawn by load from bus Real.
i. IP OP constant current real power in MW drawn by load from bus at 1.0 per unit voltage Real.
j. IQ OP constant current reactive power in MVAR drawn by load from bus at 1.0 per unit voltage Real.
k. YP OP constant impedance real power in MW drawn by load from bus at 1.0 per unit voltage Real.
l. YQ OP constant impedance reactive power in MVAR drawn by load from bus at 1.0 per unit voltage Real.
m. Load Type: Scalable/Non-conforming EQ 2 possible values: load scalable, load non-conforming and should not be scaled Enumerated type
4. Generating Units: 1 record for each generator
a. Bus number ID number of bus in bus data (section 2) to which generator is attached Integer.
String, maximum 2
b. Unit identifier ID label identifying the particular generator represented by this data record
characters*.
c. P gen OP real power in MW of generator injected into bus Real.
d. Q gen OP reactive power in MW of generator injected into bus Real.
e. Maximum Reactive Power Limit (MVAR) EQ maximum continuous reactive power output in MVAR of unit (limit specified with item 4p) Real.
f. Minimum Reactive Power Limit (MVAR) EQ minimum continuous reactive power output in MVAR of unit (limit specified with item 4p) Real.
g. Regulated Bus Number OP number of bus in bus data (section 2) whose voltage this generator is regulating Integer.
h. Machine Base (MVA) EQ machine base value in MVA Real.
i. Status OP 0: out-of-service, 1: in-service Integer, 0 or 1.
j. Regulated MVAR Percentage OP percentage or fraction of regulating reactive power provided by this generator Real.
k. Maximum Power Limit (MW) EQ maximum continuous real power output in MW of unit Real.
l. Minimum Power Limit (MW) EQ minimum continuous real power output in MW of unit Real.
m. Owners (provision for at least 4) ID One owner number (integer, positive) and one ownership fraction (real) for each owner or partial owner (from owner Integer. (4 values)
n. Owner Fraction (provision for at least 4) ID data, section 11). Ownership fractions must sum to one. Real. (4 values)

o. Generator Type EQ Primary fuel type; possible values: hydro, nuclear, coal, natural gas, oil, diesel, wind, solar, pumped storage, other Enumerated type

p. Type of reactive limits EQ possible values: constant, number of reactive capability curve (section 13), constant power factor Enumerated type

5. AC Transmission Line or Circuit (series capacitors and reactors shall be explicitly modeled as individual line segments): 1 record for each transmission line/circuit
a. From Bus Number ID number of bus in bus data (section 2) to which first end (“from end”) of line is attached Integer.
b. To Bus Number ID number of bus in bus data (section 2) to which second end (“to end”) of line is attached Integer.
String, maximum 2
c. Circuit Identifier ID label identifying the particular line represented by this data record
characters*.
d. Resistance (R) EQ value of branch resistance in per unit on system base (item 1c) and “from bus” voltage base (item 2c) Real.
e. Reactance (X) EQ value of branch reactance in per unit on system base (item 1c) and “from bus” voltage base (item 2c) Real.
f. Susceptance (Charging) (B) EQ value of branch charging in per unit on system base (item 1c) and “from bus” voltage base (item 2c) Real.
g. Ratings (minimum 2) EQ normal and emergency ratings of branch in MVA Real. (2 values)
h. Line G (From) EQ value of line shunt conductance at “from end” in MW at 1.0 per unit voltage Real.
i. Line B (From) EQ value of line shunt susceptance at “from end” in MVAR at 1.0 per unit voltage Real.
j. Line G (To) EQ value of line shunt conductance at “to end” in MW at 1.0 per unit voltage Real.
k. Line B (To) EQ value of line shunt conductance at “to end” in MVAR at 1.0 per unit voltage Real.
l. Status OP 0: out-of-service, 1: in-service Integer, 0 or 1.
m. Metered Bus EQ 0: metered end is “from end”, 1: metered end is “to end” Integer, 0 or 1.
n. Owners (provision for at least 4) ID One owner number (integer, positive) and one ownership fraction (real) for each owner or partial owner (from owner Integer. (4 values)
o. Owner Fraction (provision for at least 4) ID data, section 11). Ownership fractions must sum to one. Real. (4 values)
6. Two Winding Transformer (voltage and phase-shifting) – 1 record for each two-winding transformer
a. From Bus Number ID number of bus in bus data (section 2) to which winding 1 is attached Integer.
b. To Bus Number ID number of bus in bus data (section 2) to which winding 2 is attached Integer.
String, maximum 2
c. Transformer Identifier ID label identifying the particular transformer represented by this data record
characters*.
d. Magnetizing Conductance EQ magnetizing conductance (units specified in item 6ab) Real.
e. Magnetizing Susceptance EQ magnetizing susceptance (units specified in item 6ab) Real.
f. Metered Bus EQ 0: metered end is “from end”, 1: metered end is “to end” Integer, 0 or 1.
g. Status OP 0: transformer out-of-service, 1: transformer in-service Integer, 0 or 1.
h. Owners (provision for at least 4) ID One owner number (integer, positive) and one ownership fraction (real) for each owner or partial owner (from owner Integer. (4 values)
i. Owner Fraction (provision for at least 4) ID data, section 11). Ownership fractions must sum to one. Real. (4 values)
j. Resistance (R) EQ value of transformer resistance (units specified in item 6aa) Real.
k. Reactance (X) EQ value of transformer reactance (units specified in item 6aa) Real.
l. Winding 1 Ratio OP turns ratio of winding 1 (units specified in item 6z) Real.
m. Winding 1 Angle OP angle of winding 1 in degrees Real.
n. Ratings (minimum 2) EQ normal and emergency ratings of transformer in MVA Real. (2 values)
o. Regulation Mode EQ 3 possible values: fixed tap (no regulation), voltage regulating, MW regulating Enumerated type
p. Regulated Bus Number OP number of bus in bus data (section 2) whose voltage this transformer is regulating Integer.
q. Maximum Ratio or Angle EQ maximum tap ratio (units specified in item 6z) Real.
r. Minimum Ratio or Angle EQ minimum tap ratio (units specified in item 6z) Real.
s. Maximum Voltage OP upper limit in per unit of voltage regulation band Real.
t. Minimum Voltage OP lower limit in per unit of voltage regulation band Real.
u. Tap positions EQ number of tap positions (tap step = (<6q> - <6r>)/(<6u> - 1)) Integer.
v. Impedance Table EQ number of impedance correction table (section 12) being applied, or 0 if not applicable Integer.
w. Transformer base EQ Transformer base in MVA Real.
x. Winding 1 nominal voltage (kV) EQ Nominal voltage of winding 1 in kV Real.
y. Winding 2 nominal voltage (kV) EQ Nominal voltage of winding 2 in kV Real.
3 possible values: per unit of winding bus voltage base (item 2c), voltage in kV, per unit of nominal winding voltage
z. Tap ratio units EQ Enumerated type
(item 6x)
3 possible values: per unit on system base/winding bus voltage base (item 1c & 2c), per unit on transformer
aa. Impedance units EQ base/winding bus voltage base (items 6w & 2c), load loss in W & X in per unit on transformer base/winding bus Enumerated type
voltage base (items 6w & 2c)
2 possible values: per unit on system base/winding 1 bus voltage base (items 1c & 2c), no load loss in W & current per
ab. Magnetizing units EQ Enumerated type
unit on transformer base/winding 1 base (items 6w & 6x)
ac. Winding 2 Ratio OP turns ratio of winding 2 (units specified in item 6z) Real.
ad. Winding 2 Angle OP angle of winding 2 in degrees Real.
7. Three Winding Transformer – 1 record for each three-winding transformer
a. From (winding 1) Bus Number ID number of bus in bus data (section 2) to which winding 1 is attached Integer.
b. To (winding 2) Bus Number ID number of bus in bus data (section 2) to which winding 2 is attached Integer.
c. Last (winding 3) Bus Number ID number of bus in bus data (section 2) to which winding 3 is attached Integer.
String, maximum 2
d. Transformer Identifier ID label identifying the particular transformer represented by this data record
characters*.
e. Resistance 1-2 EQ value of transformer resistance between winding 1 and winding 2 (units specified in item 6bg) Real.
f. Reactance 1-2 EQ value of transformer reactance between winding 1 and winding 2 (units specified in item 6bg) Real.
g. Resistance 2-3 EQ value of transformer resistance between winding 1 and winding 2 (units specified in item 6bg) Real.
h. Reactance 2-3 EQ value of transformer reactance between winding 1 and winding 2 (units specified in item 6bg) Real.
i. Resistance 3-1 EQ value of transformer resistance between winding 1 and winding 2 (units specified in item 6bg) Real.
j. Reactance 3-1 EQ value of transformer reactance between winding 1 and winding 2 (units specified in item 6bg) Real.
k. Star Bus Voltage DEP value in per unit on bus base voltage (item 2c) Real.
l. Star Bus Angle DEP value in degrees Real.
m. Magnetizing Conductance EQ magnetizing conductance (units specified in item 6bh) Real.
n. Magnetizing Susceptance EQ magnetizing susceptance (units specified in item 6bh) Real.
5 possible values: transformer out-of-service, transformer in-service (all windings), winding 2 only out-of-service,
o. Status OP Enumerated type
winding 3 only out-of-service, winding 1 only out-of-service
p. Non-metered Bus EQ designates non-metered winding Integer, 1 to 3.
q. Winding 1 Ratio OP turns ratio of winding 1 (units specified in item 6bf) Real.
r. Winding 1 Angle OP angle of winding 1 in degrees Real.
s. Winding 2 Ratio OP turns ratio of winding 2 (units specified in item 6bf) Real.
t. Winding 2 Angle OP angle of winding 2 in degrees Real.
u. Winding 3 Ratio OP turns ratio of winding 3 (units specified in item 6bf) Real.
v. Winding 3 Angle OP angle of winding 3 in degrees Real.
w. Winding 1 ratings (minimum 2) EQ normal and emergency ratings of transformer winding 1 in MVA Real. (2 values)
x. Winding 2 ratings (minimum 2) EQ normal and emergency ratings of transformer winding 2 in MVA Real. (2 values)
y. Winding 3 ratings (minimum 2) EQ normal and emergency ratings of transformer winding 3 in MVA Real. (2 values)

z. Regulation Mode 1 EQ Winding 1 regulation; 3 possible values: fixed tap (no regulation), voltage regulating, MW regulating Enumerated type

aa. Regulated Bus Number 1 OP number of bus in bus data (section 2) whose voltage this winding is regulating Integer.
ab. Maximum Ratio or Angle 1 EQ maximum tap ratio of winding 1 (units specified in item 6bf) Real.
ac. Minimum Ratio or Angle 1 EQ minimum tap ratio of winding 1 (units specified in item 6bf) Real.
ad. Maximum Voltage 1 OP upper limit of voltage regulation band of winding 1 Real.
ae. Minimum Voltage 1 OP lower limit of voltage regulation band of winding 1 Real.
af. Tap Positions 1 EQ number of tap positions on winding 1 Integer.
ag. Impedance Table 1 EQ number of impedance correction table (section 12) being applied, or 0 if not applicable Integer.

ah. Regulation Mode 2 EQ Winding 2 regulation; 3 possible values: fixed tap (no regulation), voltage regulating, MW regulating Enumerated type

ai. Regulated Bus Number 2 OP number of bus in bus data (section 2) whose voltage this winding is regulating Integer.
aj. Maximum Ratio or Angle 2 EQ maximum tap ratio of winding 2 (units specified in item 6bf) Real.
ak. Minimum Ratio or Angle 2 EQ minimum tap ratio of winding 2 (units specified in item 6bf) Real.
al. Maximum Voltage 2 OP upper limit of voltage regulation band of winding 2 Real.
am. Minimum Voltage 2 OP lower limit of voltage regulation band of winding 2 Real.
an. Tap Positions 2 EQ number of tap positions on winding 2 Integer.
ao. Impedance Table 2 EQ number of impedance correction table (section 12) being applied, or 0 if not applicable Integer.

ap. Regulation Mode 3 EQ Winding 3 regulation; 3 possible values: fixed tap (no regulation), voltage regulating, MW regulating Enumerated type

aq. Regulated Bus Number 3 OP number of bus in bus data (section 2) whose voltage this winding is regulating Integer.
ar. Maximum Ratio or Angle 3 EQ maximum tap ratio of winding 3 (units specified in item 6bf) Real.
as. Minimum Ratio or Angle 3 EQ minimum tap ratio of winding 3 (units specified in item 6bf) Real.
at. Maximum Voltage 3 OP upper limit of voltage regulation band of winding 3 Real.
au. Minimum Voltage 3 OP lower limit of voltage regulation band of winding 3 Real.
av. Impedance Table 3 EQ number of impedance correction table (section 12) being applied, or 0 if not applicable Integer.
aw. Tap Positions 3 EQ number of tap positions on winding 3 Integer.
ax. Owners (provision for at least 4) ID One owner number (integer, positive) and one ownership fraction (real) for each owner or partial owner (from owner Integer. (4 values)
ay. Owner Fraction (provision for at least 4) ID data, section 11). Ownership fractions must sum to one. Real. (4 values)
az. Transformer base (windings 1-2) EQ Transformer base for windings 1-2 in MVA Real.
ba. Transformer base (windings 2-3) EQ Transformer base for windings 2-3 in MVA Real.
bb. Transformer base (windings 3-1) EQ Transformer base for windings 3-1 in MVA Real.
bc. Winding 1 nominal voltage (kV) EQ Nominal voltage of winding 1 in kV Real.
bd. Winding 2 nominal voltage (kV) EQ Nominal voltage of winding 2 in kV Real.
be. Winding 3 nominal voltage (kV) EQ Nominal voltage of winding 3 in kV Real.
3 possible values: per unit of winding bus voltage base (item 2c), voltage in kV, per unit of nominal winding voltage
bf. Tap ratio units EQ Enumerated type
(item 7bc-be)
3 possible values: per unit on system base/winding bus voltage base (item 1c & 2c), per unit on transformer
bg. Impedance units EQ base/winding bus voltage base (items 7az-bb & 2c), load loss in W & X in per unit on transformer base/winding bus Enumerated type
voltage base (items 7az-bb & 2c)

2 possible values: per unit on system base/winding 1 bus voltage base (items 1c & 2c), no load loss in W & current per
bh. Magnetizing units EQ Enumerated type
unit on transformer base/winding 1 base (items 7az-bb & 7bc-be)

8. Shunt compensation (shunt capacitors, reactors, SVC, STATCOM, etc.) – 1 record for each shunt
a. Bus number ID number of bus in bus data (section 2) to which shunt is attached Integer.
String, maximum 2
b. Shunt Identifier ID label identifying the particular shunt represented by this data record
characters*.
c. Status OP 0: shunt out-of-service, 1: shunt in-service Integer, 0 or 1.
d. Regulation Mode EQ 3 possible values: fixed, discrete control, continuous control Enumerated type
e. Regulated Bus Number OP number of bus in bus data (section 2) whose voltage this shunt is regulating Integer.
f. Regulated MVAR Percentage OP percentage or fraction of regulating reactive power provided by this shunt Real.
g. Shunt Conductance (MW) OP value of shunt conductance in MW at 1.0 per unit voltage Real.
h. Shunt Susceptance (MVAR) OP value of shunt susceptance in MVAR at 1.0 per unit voltage Real.
i. Maximum Continuous Susceptance (MVAR) EQ maximum value of continuous element of shunt (0 if no continuous element) Real.
j. Minimum Continuous Susceptance (MVAR) EQ minimum value of continuous element of shunt (0 if no continuous element) Real.
k. Maximum Voltage Regulation Setpoint OP upper limit of voltage regulation band Real.
l. Minimum Voltage Regulation Setpoint OP lower limit of voltage regulation band Real.
m. Block Steps (provision for at least 8) EQ Integer. (8 values)
number of discrete shunts (integer) in block and the size of each discrete shunt in MVAR (real) in that block
n. Block Size (provision for at least 8) EQ Real. (8 values)
9. Area Interchange – 1 record for each area
a. Area number ID label identifying the particular area represented by this data record Integer.
b. Area name ID short name for area String.

c. Desired net interchange/Scheduled interchange OP desired interchange value in MW, positive indicates export, while negative indicates import Real.

10. Zone Data – 1 record for each zone


a. Zone number ID label identifying the particular zone represented by this data record Integer.
b. Zone name ID short name for zone String.
11. Owner Data – 1 record for each owner
a. Owner number ID label identifying the particular owner represented by this data record Integer.
b. Owner name ID short name for owner String.
12. Transformer Impedance Correction Tables
a. Table number EQ label identifying the particular table represented by this data record Integer.
b. Winding ratio (provision for at least 11) EQ winding ratio (real) and the scaling factor to be applied to the transformer impedance at that winding ratio (real); Real.
c. Scaling factor (provision for at least 11) EQ scaling factor is linearly interpolated for other winding ratios Real.
13. Reactive Capability Curves
a. Table number EQ label identifying the particular reactive capability curve represented by this data record Integer.
b. Real power point (provision for at least 10) EQ Real power dispatch point Real.
c. Maximum reactive power (provision for at least 10) EQ Maximum reactive power at corresponding real power dispatch point. Real.
d. Minimum reactive power (provision for at least 10) EQ Minimum reactive power at corresponding real power dispatch point. Real.

* - permitted characters: upper case letters, numbers, spaces


ID Identifier: provided by PC/TP
EQ Equipment characteristic: provided by equipment owner
OP Operating state: reflects current state of the system
for past date/time (event reconstruction): filled with recorded data from TOP/GOP/RC
for day ahead/seasonal study: filled by TOP with values appropriate to scenario under study, taking into account
known forced and scheduled outages of equipment

for near-term or long-term planning: filled by PC/TP with values appropriate to scenario under study

DEP Dependent variable; value is a function of the other variables and is calculated by Powerflow solution

NOTE: A Powerflow case for a particular interconnection may contain additional parameters not included on this list, including additional ratings and/or additional owners.
NOTE: Some Interconnections may allow the use of additional values for enumerated type variables in addition to the ones given in this library. Enumerated type variables are typically represented by integers in
conventional data formats.
NERC LIBRARY OF STANDARDIZED DYNAMICS MODELS
Siemens PTI (v. 33) GE PSLF (v. 19) PowerWorld (v. 19) PowerTech DSATools (v. 15) V&R Energy POM Suite (2015)
(PSSE) (PSLF) (PSSE) (PSLF) (PSSE) (PSLF)
1. Generator
a) Synchronous machines:

IEEE Std 1110 §5.3.2 round-rotor (Model 2.2) - note A [1] GENROU genrou (1) GENROU genrou GENROU genrou GENROU genrou

IEEE Std 1110 §5.3.1 salient-pole (Model 2.1) - note B [1] GENSAL gensal (1) GENSAL gensal GENSAL gensal GENSAL gensal

IEEE Std 1110 §5.3.2 round-rotor (Model 2.2) - note C [1] GENROE -- GENROE -- GENROE -- GENROE --

IEEE Std 1110 §5.3.1 salient-pole (Model 2.1) - note D [1] GENSAE -- GENSAE -- GENSAE -- GENSAE --

Cross compound WECC Type F [2] -- gencc (1) -- gencc -- gencc -- gencc
WECC Type F [2] -- gentpf (1) -- gentpf -- gentpf -- gentpf
WECC Type J [2] GENTPJU1 gentpj (1) -- gentpj GENTPJU1 gentpj -- gentpj
IEEE Std 1110 §5.4.2 classical [1] GENCLS gencls (1) GENCLS gencls GENCLS gencls GENCLS gencls
CBEST -- CBEST -- -- -- CBEST --

Note A - Power-speed variations included; L f1d = 0; single saturation increment consisting of quadratic function of ψ'' (added into L ad i fd )
Note B - Power-speed variations included; L f1d = 0; single saturation increment consisting of quadratic function of ψ fd (added into L ad i fd )
Note C - Power-speed variations included; L f1d = 0; single saturation increment consisting of exponential function of ψ'' (added into L ad i fd )
Note D - Power-speed variations included; L f1d = 0; single saturation increment consisting of exponential function of ψ fd (added into L ad i fd )
b) Other technologies, including, as appropriate to the model:
i. inertia constant
ii. damping coefficient
iii. saturation parameters
iv. direct and quadrature axes reactances and time
constants
Model includes IEEE Std 421.5 current compensator
(1) (signs of impedance parameters are opposite of their
specification in IEEE standard)
2. Excitation System
IEEE Std 421.5 Type AC1A [3] ESAC1A esac1a (1) ESAC1A esac1a ESAC1A esac1a ESAC1A esac1a
IEEE Std 421.5 Type AC2A [3] ESAC2A esac2a (1) ESAC2A esac2a ESAC2A esac2a ESAC2A esac2a
IEEE Std 421.5 Type AC3A [3] ESAC3A esac3a (1) ESAC3A esac3a ESAC3A esac3a ESAC3A esac3a
IEEE Std 421.5 Type AC4A [3] ESAC4A esac4a (3) ESAC4A esac4a ESAC4A esac4a ESAC4A esac4a
IEEE Std 421.5 Type AC5A [3] ESAC5A esac5a ESAC5A esac5a ESAC5A esac5a ESAC5A esac5a
IEEE Std 421.5 Type AC6A [3] ESAC6A esac6a (1) ESAC6A esac6a ESAC6A esac6a ESAC6A esac6a
IEEE Std 421.5 Type AC7B* [3] AC7B esac7b (1) AC7B esac7b AC7B esac7b AC7B esac7b
IEEE Std 421.5 Type AC8B [3] AC8B (2) esac8b (1) AC8B esac8b_ge AC8B esac8b AC8B esac8b
Modified IEEE Std 421.5 Type AC8B ESAC8B -- ESAC8B_PTI -- ESAC8B -- ESAC8B --
Modified IEEE Std 421.5 Type AC8B -- exac8b -- exac8b -- exac8b -- exac8b
IEEE Std 421.5 Type DC1A [3] ESDC1A (4),(5) esdc1a (1) ESDC1A esdc1a ESDC1A esdc1a ESDC1A esdc1a
IEEE Std 421.5 Type DC2A [3] ESDC2A (4),(5) esdc2a (1) ESDC2A esdc2a ESDC2A esdc2a ESDC2A esdc2a
IEEE Std 421.5 Type DC3A [3] DC3A esdc3a (1) DC3A esdc3a DC3A esdc3a DC3A esdc3a
IEEE Std 421.5 Type DC4B [3] DC4B esdc4b (1) DC4B esdc4b DC4B esdc4b DC4B esdc4b
IEEE Std 421.5 Type ST1A [3] ESST1A esst1a ESST1A esst1a ESST1A esst1a ESST1A esst1a
IEEE Std 421.5 Type ST2A [3] ESST2A (5) esst2a (6) ESST2A esst2a ESST2A esst2a ESST2A esst2a
IEEE Std 421.5 Type ST3A [3] ESST3A esst3a ESST3A esst3a ESST3A esst3a ESST3A esst3a
IEEE Std 421.5 Type ST4B [3] ESST4B esst4b (7) ESST4B esst4b ESST4B esst4b ESST4B esst4b
IEEE Std 421.5 Type ST5B** [3] ST5B (8) esst5b (8) ST5B esst5b ST5B esst5b ST5B esst5b
IEEE Std 421.5 Type ST6B [3] ST6B (9) esst6b (10) ST6B esst6b ST6B esst6b ST6B esst6b
IEEE Std 421.5 Type ST7B [3] ST7B (11) esst7b (10),(11) ST7B esst7b ST7B esst7b ST7B esst7b
1968 IEEE Type 1 [4] IEEET1 (12) ieeet1 (12),(14) IEEET1 ieeet1 IEEET1 ieeet1 IEEET1 ieeet1
Modified 1968 IEEE Type 1 IEET1A -- IEET1A -- IEET1A -- IEET1A --
1968 IEEE Type 2 [4] IEEET2 (12) -- IEEET2 -- IEEET2 -- IEEET2 --
1968 IEEE Type 3 [4] IEEET3 (12) -- IEEET3 -- IEEET3 -- IEEET3 --
1968 IEEE Type 4 [4] IEEET4 (13) exdc4 IEEET4 exdc4 IEEET4 exdc4 IEEET4 --
Modified 1968 IEEE Type 4 IEEET5 -- IEEET5 -- IEEET5 -- IEEET5 --
1981 IEEE Type AC1 [5] EXAC1 exac1 (14),(15) EXAC1 exac1 EXAC1 exac1 EXAC1 exac1
Modified 1981 IEEE Type AC1 EXAC1A exac1a EXAC1A exac1a EXAC1A exac1a EXAC1A exac1a
1981 IEEE Type AC2 [5] EXAC2 exac2 (14) EXAC2 exac2 EXAC2 exac2 EXAC2 exac2
1981 IEEE Type AC3 [5] EXAC3 exac3 (14),(16) EXAC3 exac3 EXAC3 exac3 EXAC3 --
Modified 1981 IEEE Type AC3 -- exac3a -- exac3a -- exac3a -- exac3a
1981 IEEE Type AC4 [5] EXAC4 exac4 EXAC4 exac4 EXAC4 exac4 EXAC4 exac4
1981 IEEE Type DC1 [5] IEEEX1 exdc1 (14) IEEEX1 exdc1 IEEEX1 exdc1 IEEEX1 exdc1
Modified 1981 IEEE Type DC1 IEEEX2 -- IEEEX2 -- IEEEX2 -- IEEEX2 --
Modified 1981 IEEE Type DC1 IEEX2A -- IEEX2A -- IEEX2A -- IEEX2A --
1981 IEEE Type DC2 [5] EXDC2 exdc2a (14) EXDC2_PTI exdc2a EXDC2 exdc2a EXDC2 exdc2a
Modified 1981 IEEE Type DC2 -- exdc2 -- exdc2_ge -- exdc2 -- exdc2
1981 IEEE Type DC3 [5] IEEEX4 exdc4 IEEEX4 exdc4 IEEEX4 exdc4 IEEEX4 exdc4
1981 IEEE Type ST1 [5] EXST1 exst1 (17) EXST1_PTI exst1_ge EXST1 exst1 EXST1 exst1
1981 IEEE Type ST2 [5] EXST2 exst2 (18) EXST2 exst2 EXST2 exst2 EXST2 exst2
Modified 1981 IEEE Type ST2 EXST2A exst2a EXST2A exst2a EXST2A exst2a EXST2A exst2a
Modified 1981 IEEE Type ST2 IEEEX3 -- IEEEX3 -- IEEEX3 -- IEEEX3 --
1981 IEEE Type ST3 [5] EXST3 exst3 (14) EXST3 exst3 EXST3 exst3 EXST3 exst3
Modified 1981 IEEE Type ST3 -- exst3a -- exst3a -- exst3a -- exst3a
Brown-Boveri static BBSEX1 exbbc BBSEX1 exbbc BBSEX1 exbbc BBSEX1 exbbc
Static PI transformer fed EXELI exeli EXELI exeli EXELI exeli EXELI exeli
-- exst4b -- exst4b -- exst4b -- exst4b
General purpose rotating REXSYS rexs REXSYS rexs REXSYS rexs REXSYS rexs
REXSY1 -- REXSY1 -- REXSY1 -- REXSY1 --
SCR Bridge SCRX scrx SCRX scrx SCRX scrx SCRX scrx
Simplified excitation system SEXS sexs SEXS_PTI sexs_ge SEXS sexs SEXS sexs
IVO excitation system IVOEX exivo IVOEX exivo IVOEX -- IVOEX exivo
EXPIC1 expic1 EXPIC1 expic1 EXPIC1 expic1 EXPIC1 expic1
Basler static voltage regulator feeding dc or ac
EXBAS -- EXBAS -- EXBAS -- EXBAS --
rotating exciter
GE EX2000 excitation system EX2000 -- EX2000 -- EX2000 -- EX2000 --
AEP Rockport excitation system EMAC1T -- EMAC1T -- EMAC1 -- EMAC1T --
Proposed IEEE Type ST5B URST5T -- URST5T -- URST5T -- URST5T --
CELIN -- -- -- CELIN -- CELIN --
USAC6AU -- -- -- -- -- -- --
-- texs -- texs -- texs -- texs
a) Current Compensation
COMP -- COMP -- COMP -- COMP --
IEEE Std 421.5 current compensator [3] IEEEVC † IEEEVC † IEEEVC † IEEEVC †
REMCMP -- REMCMP -- REMCMP -- REMCMP --
COMPCC ccomp COMPCC -- -- -- COMPCC --
Cross-current compensation [14] -- ccomp4 -- ccomp4 -- -- -- --
* - In standard, V_E output comes from 1/(1+sT_E) block; this appears to be a typographical error (should be 1/sT_E).
** - In standard, V_REF is missing.
† - Current compensator is part of the generator model
(1) Software model includes additional option to multiply field voltage output by speed.
(2) In software model, non-windup integrator limits are applied to PID output. Software model also explicitly shows V_UEL and V_OEL.
(3) Software model uses windup limits for E_FD.
(4) In software model, minimum for E_FD is set to 0.
(5) In software model, V_UEL may only be injected at HV gate.
(6) Software model has additional lead-lag block between summing junction and HV gate.
(7) Software model has additional maximum value limiter on V_G = K_G E_FD
(8) In software model, non-windup limits are applied to each individual lead-lag block (6 total).
(9) Software model uses a PID voltage regulator instead of a PI voltage regulator.
(10) In software model, field voltage passes through additional lag with time constant T_S
(11) Software model only has provision for input from one overexcitation limiter, not two.
(12) In software model, V_R has non-windup limits.
(13) In software model, deadband K_R is explicitly specified.
(14) In software model, field voltage signal is multiplied by speed.
(15) Software model has two sets of limits applied to V_R.
(16) Software model also has maximum non-windup limit for V_E.
(17) In software model, there are two lead-lag compensators instead of one, and I_FD affects field voltage through additional logic.
(18) Software model has additional lead-lag block between summing junction and V_R output block.
3. Turbine-governor
WECC double derivative hydro WSHYDD g2wscc WSHYDD g2wscc WSHYDD g2wscc WSHYDD g2wscc
URGS3T gast URGS3T gast_ge URGS3T gast URGS3T gast
General purpose thermal (Ver. 1) [13] GGOV1 (1) -- GGOV1 -- GGOV1 -- GGOV1 --
General purpose thermal (Ver. 2) [7] -- ggov1 -- ggov1 -- ggov1 -- ggov1
-- ggov3 -- ggov3 -- ggov3 -- ggov3
WSHYGP gpwscc WSHYGP gpwscc WSHYGP gpwscc WSHYGP gpwscc
-- hyg3 -- hyg3 -- hyg3 -- hyg3
Hydro turbine-governor HYGOV hygov HYGOV hygov HYGOV hygov HYGOV hygov
Hydro turbine-governor HYGOV2 -- HYGOV2 -- HYGOV2 -- HYGOV2 --
-- hygov4 -- hygov4 -- hygov4 -- hygov4
-- hygovr -- hygovr -- hygovr -- hygovr
1973 IEEE General Steam Turbine System (fig. 4 (A) &
[6] IEEEG1 -- IEEEG1 -- IEEEG1 -- IEEEG1 --
8)
1973 IEEE General Approx. Linear Ideal Hydro (fig. 4
[6] IEEEG2 -- IEEEG2 -- IEEEG2 -- IEEEG2 --
(B) & 10 (B))
1973 IEEE General Mechanical-Hydraulic (fig. 9 (B) &
[6] IEEEG3 ieeeg3 (2) IEEEG3_PTI ieeeg3_ge IEEEG3 ieeeg3 IEEEG3 ieeeg3
10 (A))
1973 IEEE General Steam Turbine System (fig. 4 (A) &
[7] WSIEG1 ieeeg1 WSIEG1 ieeeg1_ge WSIEG1 ieeeg1 WSIEG1 --
8) w/ speed deadband
Hydro turbine and governor PIDGOV pidgov PIDGOV pidgov PIDGOV pidgov PIDGOV pidgov
Steam turbine-governor [7] TGOV1 tgov1 TGOV1 tgov1 TGOV1 tgov1 TGOV1 tgov1
TGOV2
Steam turbine-governor w/ fast valving TGOV2 -- TGOV2 -- -- TGOV2 --
(DSA1)
TGOV3
1973 IEEE General w/ fast valving TGOV3 tgov3 TGOV3 tgov3 tgov3 (DSA1) TGOV3 tgov3
(DSA1)
TGOV5 -- TGOV5 -- -- -- TGOV5 --
1973 IEEE General Steam Non-reheat (fig. 4 (B) & 7
[6] IEESGO -- IEESGO -- IEESGOV -- IEESGO --
(B))
Cross compound turbine-governor CRCMGV crcmgv CRCMGV crcmgv CRCMGV crcmgv CRCMGV crcmgv
Gas turbine-governor GAST -- GAST_PTI -- GAST -- GAST --
Heavy duty gas turbine [12] GAST2A (3) -- GAST2A -- GAST2A -- GAST2A --
Gas turbine-governor GASTWD -- GASTWD -- GASTWD -- GASTWD --
Woodward P.I.D. hydro WPIDHY -- WPIDHY -- WPIDHY -- WPIDHY --
WESGOV -- WESGOV -- WESGOV -- WESGOV --
WEHGOV -- WEHGOV -- WEHGOV -- WEHGOV --
Woodward diesel governor DEGOV -- DEGOV -- -- -- DEGOV --
Woodward diesel governor DEGOV1 degov1 DEGOV1 -- DEGOV1 -- DEGOV1 --
Brown-Boveri turbine-governor BBGOV1 -- -- -- -- -- BBGOV1 --
TURCZT -- -- -- -- -- -- --
-- h6b -- -- -- -- -- --
-- ccbt1 -- ccbt1 -- -- -- ccbt1
-- w2301 -- w2301 -- w2301 -- w2301
a) Load controller
[7] LCFB1 lcfb1 (4) LCFB1_PTI lcfb1 LCFB1 lcfb1 LCFB1 lcfb1
(1) Software model has additional lead-lag block in temperature limit control loop, and temperature feedback signal has upper limit of 1.0.

(2) Software model uses windup limits for gate position, has two additional deadband blocks, includes a piecewise linear power-gate position characteristic (up to 6 points), and different parameters in Pmech output block.

(3) Software model has non-windup limits on speed governor and temperature control outputs instead of windup limits. Software model lacks acceleration control. Software model has additional block for fuel control delay.

(4) Software model has additional gain block following windup limits of PI controller.
4. Power System Stabilizer
ST2CUT wsccst ST2CUT wsccst ST2CUT wsccst ST2CUT wsccst
PSS2A pss2a PSS2A pss2a PSS2A pss2a PSS2A pss2a
1981 IEEE Power System Stabilizer [5] IEEEST (1) ieeest (4) IEEEST ieeest IEEEST ieeest IEEEST ieeest
-- psssb -- psssb -- psssb -- psssb
IEEE Std 421.5 PSS1A [3] (PSS1A) (2) pss1a PSS1A pss1a -- pss1a -- pss1a
IEEE Std 421.5 PSS2B [3] PSS2B pss2b (5) PSS2B pss2b PSS2B pss2b PSS2B pss2b
IEEE Std 421.5 PSS3B [3] PSS3B pss3b -- pss3b -- pss3b PSS3B pss3b
IEEE Std 421.5 PSS4B [3] PSS4B (3) -- -- -- -- -- -- --
STAB1 -- STAB1 -- STAB1 -- STAB1 --
STAB3 -- STAB3 -- STAB3 -- STAB3 --
STAB4 -- STAB4 -- STAB4 -- STAB4 --
IEE2ST -- IEE2ST -- IEE2ST -- IEE2ST --
PTIST1 -- -- -- PTIST1 -- PTIST1 --
PTIST3 -- -- -- PTIST3 -- PTIST3 --
STBSVC -- STBSVC -- STBSVC -- STBSVC --
(1) Software model has extra output block
(2) PSS1A "model" is actually a template for placing PSS1A parameters into IEEEST model

(3) Software model has option for quadratic term in numerator of frequency digital transducer transfer function and allows choice of coefficients of transducer transfer functions.

(4) Software model has additional time delay and output limiter blocks.
(5) Software model has additional lead-lag block.
5. Demand (consistent with system load representation (composite load model) and components as a function of frequency and voltage)
IEEL__ _lwscc IEEL -- IEELxx xLWSCC IEEL__ --
LDFR__ -- LDFR -- LDFRxx -- LDFR__ --
WECC Composite Load Model [8] CMLDBLU1 cmpldw -- cmpldw CMLDBLU1 cmpldw CMLDBLU1 cmpldw
ACMTBLU1 ld1pac -- ld1pac -- -- -- --
CIMTR1 -- CIMTR1 -- CIMTR1 -- CIMTR1 --
CIMTR2 -- CIMTR2 -- CIMTR2 -- CIMTR2 --
CIMTR3 -- CIMTR3 -- CIMTR3 -- CIMTR3 --
CIMTR4 motor1 CIMTR4 motor1 CIMTR4 motor1 CIMTR4 motor1
CIMTR5 -- -- -- -- -- -- --
CIMWBL motorw -- motorw CIMWBL motorw CIMWBL motorw
CLOD__ -- CLOD -- CLODxx -- CLOD__ --
area __=AR __=a
bus __=BL __=b
zone __=ZN __=z
all __=AL __=w
6. Wind Machine and Photovoltaic Data

Generator for WECC WT1 Generic Wind Model


[9] WT1G1 wt1g WT1G1 wt1g WT1G1 wt1g WT1G1 wt1g
(Fixed-speed induction generator)

Generator for WECC WT2 Generic Wind Model


(Variable slip induction generator with variable rotor [9] WT2G1 wt2g WT2G1 wt2g WT2G1 wt2g WT2G1 wt2g
resistance)

Generator/converter for WECC WT3 Generic Wind


[9] WT3G1 -- WT3G1 -- WT3G1 -- WT3G1 --
Model, PSSE (Doubly-fed induction generator)

Generator/converter for WECC WT3 Generic Wind


[9] WT3G2 wt3g WT3G2 wt3g WT3G2 wt3g WT3G2 wt3g
Model, PSLF (Doubly-fed induction generator)

Generator/converter for WECC WT4 Generic Wind


Model, PSSE (Variable speed generator with full [9] WT4G1 -- WT4G1 -- WT4G1 -- WT4G1 --
converter)
Generator/converter for WECC WT4 Generic Wind
Model, PSLF (Variable speed generator with full [9] WT4G2 wt4g -- wt4g -- wt4g WT4G2 wt4g
converter)
Renewable energy generator/converter [10] REGCAU1 regc_a -- regc_a REGCAU1 regc_a -- --
Rotor resistance control for WECC WT2 Generic Wind
[9] WT2E1 wt2e WT2E1 wt2e WT2E1 wt2e WT2E1 wt2e
Model

Electrical control for WECC WT3 Generic Wind Model [9] WT3E1 wt3e WT3E1 wt3e WT3E1 wt3e WT3E1 wt3e

Electrical control for WECC WT4 Generic Wind Model,


[9] WT4E1 -- WT4E1 -- WT4E1 -- WT4E1 --
PSSE
Electrical control for WECC WT4 Generic Wind Model,
[9] WT4E2 wt4e -- wt4e -- wt4e WT4E2 wt4e
PSLF
Renewable energy electrical controls [10] REECAU1 reec_a -- reec_a REECAU1 reec_a REECAU1 reec_a
PV electrical controls [10] REECBU1 reec_b -- reec_b REECBU1 reec_b REECBU1 reec_b
Energy storage electrical controls [15] -- reec_c -- -- -- -- -- --
Two mass turbine model for WECC WT1 Generic Wind
[9] WT12T1 wt1t WT12T1 wt1t WT12T1 wt1t WT12T1 wt1t
Model
Two mass turbine model for WECC WT2 Generic Wind
[9] WT12T1 wt2t WT12T1 wt2t WT12T1 wt2t WT12T1 wt2t
Model
Turbine model for WECC WT3 Generic Wind Model [9] WT3T1 wt3t WT3T1 wt3t WT3T1 wt3t WT3T1 wt3t

Power converter model for WECC WT4 Generic Wind


[9] -- wt4t -- wt4t -- wt4t -- wt4t
Model

Pitch control model for Type 1 and 2 wind generators [9] WT12A1 wt1p WT12A1 wt1p WT12A1 wt1p WT12A1 wt1p

Pitch control model for Type 3 wind generator [9] WT3P1 wt3p WT3P1 wt3p WT3P1 wt3p WT3P1 wt3p
Pitch control model for Type 4 wind generator [9] -- wt4p -- -- -- wt4p -- wt4p

Pitch control model for Type 1 and 2 wind generators [10] -- wt1p_b -- wt1p_b -- -- -- --

Drive train model for Type 3 and 4 wind generators [10] WTDTAU1 wtgt_a -- wtgt_a WTDTAU1 wtgt_a WTDTAU1 wtgt_a

Aerodynamics model for Type 3 and 4 wind


[10] WTARAU1 wtga_a -- wtgar_a WTARAU1 wtgar_a WTARAU1 wtga_a
generators

Pitch control model for Type 3 and 4 wind generators [10] WTPTAU1 wtgp_a -- wtgpt_a WTPTAU1 wtgpt_a WTPTAU1 wtgpt_a

Torque control model for Type 3 and 4 wind


[10] WTTQAU1 wtgq_a -- wtgtrq_a WTTQAU1 wtgtrq_a WTTQAU1 wtgtrq_a
generators
Renewable energy plant controller [10] REPCAU1 repc_a -- repc_a REPCAU1 repc_a REPCAU1 repc_a
Distributed photovoltaic system [10] -- pvd1 -- pvd1 -- -- -- --
7. Static Var Systems and FACTS
Template
[11] SVSMO1U2 svsmo1 -- svsmo1 svsmo1 -- svsmo1
UDM
Template
[11] SVSMO2U2 svsmo2 -- svsmo2 svsmo2 -- svsmo2
UDM
Template
[11] SVSMO3U2 svsmo3 -- svsmo3 svsmo3 -- svsmo3
UDM
CSVGN1 -- CSVGN1 -- CSVGN1 -- CSVGN1 --
CSVGN3 -- CSVGN3 -- CSVGN3 -- CSVGN3 --
CSVGN4 -- CSVGN4 -- CSVGN4 -- CSVGN4 --
CSVGN5 vwscc CSVGN5 vwscc CSVGN5 vwscc CSVGN5 vwscc
SWSHNT msc1 SWSHNT msc1 SWSHNT -- -- --
CDSMS1 -- -- -- -- -- -- --
CSTATT -- CSTATT -- CSTATT -- CSTATT --
CSTCNT -- -- -- CSTCNT -- -- --
ABBSVC1 -- -- -- -- -- -- --
CHSVCT -- -- -- CHSVCT -- CHSVCT --
CSSCST -- CSSCST -- CSSCST -- CSSCST --

deprecated model; use of this model is not recommended


interim model; replacement recommended

NOTE: Some of the models in this list may not be acceptable for use in all Interconnections. The modeling requirements for each Interconnection supercede this list and should be consulted directly. The Western Interconnection
in particular has a library of dynamics models [W1] that are approved for use in Western Interconnection base cases.

References
[1] "IEEE Guide for Synchronous Generator Modeling Practices and Applications in Power System Stability Analyses," IEEE Std 1110-2002.
[2] Undrill, J., "The gentpj model," November 19, 2007 (updated June 19, 2012). http://www.wecc.biz/
[3] "IEEE Recommended Practice for Excitation System Models for Power System Stability Studies," IEEE Std 421.5-2005.

[4] “Computer Representation of Excitation Systems," IEEE Transactions on Power Apparatus and Systems, Vol. PAS-87, No. 6, pp. 1460-1468, 1968 (Committee Report).
[5] "Excitation System Models for Power System Stability Studies," IEEE Transactions on Power Apparatus and Systems, Vol. PAS-100, No. 2, pp. 494-509, 1981 (Committee Report).

[6] IEEE Task Force on Overall Plant Response, “Dynamic Models for Steam and Hydro Turbines in Power System Studies”, IEEE Trans. on PAS, Vol PAS-92, Nov-Dec 1973, pp. 1904-1915.

[7] Task Force on Turbine-Governor Modeling, "Dynamic Models for Turbine-Governors in Power System Studies," IEEE Technical Report, PES-TR1, Jan. 2013.

[8] WECC M&VWG, "Composite Load Model for Dynamic Simulations" Ver 1.0, June 12, 2012.
[9] WECC M&VWG, "WECC Wind Power Plant Dynamic Modeling Guide," November 2010.
[10] EPRI, "Specification of the Second Generation Generic Models for Wind Turbine Generators," September 20, 2013.
and WECC M&VWG, "Generic Solar Photovoltaic System Dynamic Simulation Model Specification," September 2012.
[11] WECC, "Generic Static Var System Models for the Western Electricity Coordinating Council" April 18, 2011.

[12] W. I. Rowen, “Simplified Mathematical Representations of Heavy Duty Gas Turbines”, ASME Paper 83‐GT‐63 and ASME Journal of Engineering for Power, October 1983, pages 865‐869. [GAST2A reference]

[13] Periera, L. et al, "A New Thermal Governing Approach in the WECC," IEEE Transaction on Power System, Vol. 18, No. 2, pp. 819-829, May 2003.
[14] WECC M&VWG, "Cross-current Compensation Model Specification," August 2015.
[15] EPRI, "Simple Model Specification for Battery Energy Storage System," March 6, 2015.

[W1] WECC Approved Dynamic Model Library. http://www.wecc.biz/

Additional Reading
WECC M&VWG, "WECC Wind Power Plant Dynamic Modeling Guide," April 2014.
WECC M&VWG, "WECC PV Power Plant Dynamic Modeling Guide," April 2014.
EPRI, "Proposed Changes to the WECC WT3 Generic Model for Type 3 Wind Turbine Generators," September 27, 2013.
EPRI, "Proposed Changes to the WECC WT4 Generic Model for Type 4 Wind Turbine Generators," January 23, 2013.

You might also like