0 ratings0% found this document useful (0 votes) 140 views32 pagesCEGB Generator Performance Chart Pages 1 To 31
Central Electricity Generation Board, UK
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content,
claim it here.
Available Formats
Download as PDF or read online on Scribd
NOT SUBTECT TO REVGION
Central Electricity Generating Board
Planning Department
PLANNING MEMORANDUM PLM-ST-6
GENERATOR PERFORMANCE CHARTS
Issue 1 June 1976PLANNING MEMORANDUM PLM-ST-6
ISSUE 1 JUNE 1976
GENERATOR PERFORMANCE CHARTS
CONTENTS
Foreword
Scope eens sas
Generator Arrangements
Limits of Generator Performance
Construction of Performance Charts.
Presentation of Performance Charts
References i
APPENDICES
‘A Symbols, Units and Sign Convention Used in the
Appendices
8 ~ General Methods of Chart Plotting...
(© = Worked Example — For 8 Case in which the Terminal
Voltage is Constant...
1D — Worked Example ~ For 8 Case in which the Terminal
Voltage Varies
— General Equations for Generator Having» Trenstormer
with Onsoad Taps
F ~ General Equations for a Generator Having « Transformer
with Off-load Taps...
G ~ Comparison of the Methods of
‘those of Computer Program CHRT
§ Document with
Issuing Branch: Systm Technical
proved by
re ;
frrlCokindy
Director of Planning
Printed by Technical Documentstion Branch. Engineering Services. CEGBPLANNING MEMORANDUM PLM-ST-6
GENERATOR PERFORMANCE CHARTS
SUMMARY
It is desirable that there should be, within the CEGB, 2 common method for the
construction and presentation of generator performance charts. This Planning Memorandum
describes such a method.
Recognizing present and immediate future system requirements, the accent is placed
on the accurate definition of generator performance at leading power factors and less effort
is devoted to the lagging power factor region.
‘Two types of generator arrangement are identified for the purpose of calculating
operating limits, the classification depending upon whether the terminal voltage can remain
constant or must vary as part of normal operation: directly connected generators are treated
as a special case. Each possible performance limit is defined and the assumptions introduced
to simplify chart construction are explained.
The step-by-step procedure for plotting a performance chart is given in Appendix B.
Other appendixes list the symbols used, demonstrate the construction of performance charts
for machines at Drakelow ‘B’ and Blyth “A’ Power Stations, and show the derivation of the
equations used. Appendix G compares the manually prepared charts for the Drakelow and
Blyth examples with those produced from the same data using a South Eastem Region
computer program (CHRT) and a graphical plotter.
HOW TO USE THIS DOCUMENT TO PLOT A PERFORMANCE CHART
(1) Identify Generator Arrangement (Clause 2)
Isit onload tap, off-load tap or directly connected?
(2) Select Recommended Presentation (see $.1 to 5.3)
Decide values of system and terminal voltage and tap position to be used, location
of metering points for which HV and LV charts will be drawn and whether
additional charts will be used for other conditions.
(3) Assemble Data (Appendix A, clause Al)
(4) Use Appropriate Construction Method (Appendix
On-load taps ~ Clauses B1-B3
Off-load taps ~ Clauses B4~B6
Direct Connection — Clause B1, as directed in introductory paragraphs to
Appendix B.PLM-ST~6
Page 3 Issue 1
June 1976
GENERATOR PERFORMANCE CHARTS
FOREWORD
The parameters of any generator and its associated plant may be used to plot a
performance chart which will display the MW and MVAr operating limits for that generator.
In the past, performance charts have been either supplied by the generator
manufacturer or plotted by CEGB Regional Technical Department staffs. The result has
been that several methods have evolved for plotting performance charts and for selecting the
practical generator stability limit and, in some cases, charts have shown generator MW and
MVAr capabilities that cannot be obtained in practice.
It is desirable that there should be a common method for the construction of generator
performance charts throughout the CEGB, and this Planning Memorandum describes such a
method
1. SCOPE
This Memorandum determines a method of plotting and presenting performance charts
for various generator arrangements, It is valid for round-rotor machines only and should not
be used for salient pole generators.
‘The operation of a generator at leading power factors must be restricted, both to
ensure that it will remain stable in the event of a system disturbance and to prevent
overheating. At lagging power factors, operation need only be restricted to prevent
overheating The method recommended for plotting charts recognizes the difference
between these operational extremes and lays emphasis on factors which give the most
accurate definition of the leading power factor limit. taking account of physical restrictions
(e.g. transformer tap range) which may make it impossible for a generator to operate at its
practical stability limit. In contrast, the lagging power factor limit has been treated simply:
the effects of iron saturation, stator heating and rotor heating have been ignored and
reliance has been placed on the relatively long times available during which excessive
temperatures can be corrected.
2. GENERATOR ARRANGEMENTS
Generators are connected to the system either directly, through a reactor, or through a
transformer. Generator excitation may be controlled manually or by AVR; transformer tap
changing may be by on-load or off-load tap changer. A unit transformer may be connected
to the generator terminals to provide auxiliary supplies.
Despite the multiplicity of possible generator arrangements, the method used for
plotting performance charts depends only on whether the generator terminal voltage stays
constant or varies throughout its operating range.PLM-sT-6
Page 4 Issue 1
June 1976
TABLE 1
‘Type of Generator Arrangement
TT
Type Generator Method of Connection
Terminal Voltage
eee
1 Remeins Constant (i) On-load tap transformer
(i) Direct
ee
2 Varies ()Off-toag tap transformer
(i) Resetor*
eset
Sit the generator ermine! conditions are not metered, the hart shoul be
Dotted for 9 ect connected generator, TYBe il Wa, te resctor
‘raated ae par of the generator
For transformer-conmiected generators, variation of the load or the excitation will cause
a change in generator terminal voltage which can be corrected by altering the transformer
tapping. Thus. if the generator transformer has an on-load tap changer, it will be possible to
operate at constant terminal voltage anywhere within a range of MW and MVAr loading for
various values of HV voltage but, if the taps can only be changed off load, a similar
‘operating range will only be achieved by allowing the terminal voltage to vary.
The Type I construction used for directly connected generators assumes that the
terminal/system voltage can be regarded as constant. While this may not be strictly true. itis
recommended that high, normal and low system voltage limits should be shown on the chart
(clause 4.1) s0 that itis possible to interpolate for intermediate voltages if the voltage varies
The generator-reactor arrangement is usually treated as a directly connected generator
of higher reactance and the conditions at the terminals of the generator itself are not
metered. However, if a chart is required for terminal metering for such an arrangement. it
would have to be treated as Type 2 with a I : | transformer ratio.
Synchronous compensators and declutched gas turbines operating as synchronous
compensators are not included in the above table; the performance chart would be 2
horizontal line along the MVAr axis.
3. LIMITS OF GENERATOR PERFORMANCE
Fig. | shows the limitations on generator performance which. together. form the
performance chart. While it is unlikely that all of these limits would apply to any one
machine, they are shown here for completeness (e.g. if a tap limit (PQ) applied, the practical
stability limit (BC) would become irrelevant). The limits are discussed in the subsequent
paragraphs.
3.1. Minimum Excitation
The portions AB and A'B! are the minimum continuous excitation loci. These will
depend upon the minimum generator-rotor currents that can be achieved. with the main
field switch closed, under AVR and manual excitation control. respectively. These curves
will normally be coincident but may differ on some generators. Care should be taken to
ensure that this minimum value is not limited by incorrect setting of the main exciter
negative field, where fitted, and that the brushes are of suitable grade for these low values of
rotor current.PLM-ST-6
Page S Issue 1
June 1976
K
STATOR END
HEATING
ang um /\\ naeo——\
/ N EXCITATION \
practica+——— / Mannan
‘STABILITY RATED EXCITATION:
ure / CURR \\ a
\
ven! sf ngs ne | \
excrete] Hy bi
G Q LEAD MVAr Lac
FIG. 1
3.2. Rated Current
Lines CD and EF are portions of the locus of the rated current for the generator stator
or transformer, whichever is the smaller, bearing in mind that for a Type 2 arrangement the
terminal voltage of the generators may be depressed, particularly when operating at leading
power factors.
ROTOR
I ANGLE L
3.3 Rated MW Output
The portion DE is the rated MW output limit of the main generator. This is not
necessarily the name plate rating of the generator as it may have been re-rated,
3.4 90° Rotor Angle
The line GH represents the 90° load angle of the generator to its own terminal voltage
vector and is used in the construction of the practical stability limit line. Ths line does not
represent the theoretical stability fimit line of the generator at constant excitation or under
AVR control because the generator terminals are not connected to infinite busbars but to a
finive power system with varying generating demand and system conditions.
The line will not be vertical for generator arrangements where the terminal voltage
| varies (Type 2)
3.5. Practical Stability Limit
| Lines BC and B'C! are the arbitrary stability limits for a machine under AVR and
manual control respectively. The stability margins used depend on the category of the
| excitation control system as defined in Generation Design Circular No. 14 as follows:PLM-ST-6
Page 6 Issue 1
June 1976
Category 1
Continuously acting automatic regulators (having no dead-band) with VAr limiters.
MW margins: 4 per cent at full load: 10 per cent at no load.
Category 2
Automatic regulators having some dead-band and with VAr limiters.
MW margins: 10 per cent at full load; 10 per cent at no load.
Category 3
(Any type of regulator which is not fitted with a VAF limiter or has limiter not in
operation.
(i) Any excitation control system which is not automatic (e.g. the hand’ control
position on an excitation system)
MW margins: 20 per cent at full load; 20 per cent or 10 per cent at no load.
(Generation Design Circular No. 14 gives requirements to be satisfied for 10 per cent.)
Whatever the category of AVR, the arbitrary practical stability limit line should be
checked to ensure that it can be achieved in practice. The AVR control ranges provided may
make it impossible to follow the arbitrary line: this applies particularly to machines that
have offload taps on the generator transformer. Similarly, it may not be possible to make
the excitation limiter match the arbitrary limit line throughout its range.
If for these or similar reasons the arbitrary line does not coincide with what can be
achieved in practice, then the actual practical stability limit line should be shown on the
chart,
Tests have indicated that the use of high-speed continuously acting AVRs can allow
stable steady-state operation at rotor angles in the region of 130°—140°, However. transient
stability considerations, taking account of network impedance and the disposition and
performance of other generators on the system. make operation at these high angles
unacceptable. Therefore, the limits listed above must be observed. (These give rotor angles
of about 75°, 70° and 60° for Category 1, 2 and 3 machines, respectively.)
3.6 Maximum Excitation Limit
The most useful representation of this limit is the curve EK, which is an arc of @ circle
with centre G. This is. in fact, the locus of the excitation current for rated load and power
factor, ignoring the effect of saturation; the true maximum excitation current may be
slightly higher (J'K!). The exclusion of saturation, and the avoidance of the associated
calculations, simplifies the construction of the chart but results in an overstatement of the
lagging MVAr capability by an amount varying from zero at full-load to about 10 per cent
of the MVA rating at no-load. This is considered acceptable since generators are only likely
to require maximum excitation when operated at or near fullload. Since a generator is
designed to operate at a particular rating or over a certain range without exceeding Bri
Standard temperature rises. no part of the generator or associated circuits should be allowed
to operate above the specified levels during the guarantee period. Therefore. if the
manufacturer’s twelve-month guarantee has not expired. the excitation current must not
‘exceed that for rated load and power factor.
It may be acceptable when the guarantee has expired to operate at higher excitation
currents provided that Regions are satisfied that this will not result in overheating
(Generation Division would be prepared to advise Regions if required). The lagging limit is
then defined by EJK!PLM-ST~6
Page 7 Issue 1
June 1976
3.7 Minimum MW Output Limit
The portion AF is a minimum MW line below which sustained operation of the
generator is not possible. Some of the factors which prevent operation at lower loads are as
follows:
(Low turbine vacuum, resulting in high temperatures of turbine LP stages
(i) Expansion and clearances of prime mover parts.
(iii) Rate-of-reloading.
(iv) Boiler minimum steaming conditions; varies with range or unit construction,
(%) De-aerator problems associated with permissible oxygen content of feed water.
In those cases where it is difficult to establish the minimum line precisely, the best
estimate should appear on the chart. but other constraints at lower loading should be shown
as well (e.g. minimum excitation limit).
3.8 Stator End Heating
The portion LM js a restriction which may occur on some generators at leading. and
possibly lagging. power factors due to local stator-end heating.
The limit can be established only on those generators fitted with statorend iron
thermocouples. and the determination of the locus would require a special test on the
specific generator.
3.9 Tap Limit
A condition may arise where a generator operating at constant terminal voltage. with
an on-load-tap transformer, cannot achieve full MVAr absorption at a given HV system
yoltage because the transformer has reached its extreme negative tap (minimum tums ratio),
This restriction is represented by line PQ.
Operation at a more leading power factor could only be achieved by reducing the
terminal voltage: this in turn would cause the practical stability limit line BC to move to the
Fight until an optimum operating point was reached.
3.10 Generator Transformer Overfluxing Limit
Operation at maximum generator MVAr absorption and constant terminal voltage
entails tap changing to reduce the tums ratio of the transformer (i.e. removal of tums from
the HV winding). Dependent on the HV voltage and the nominal working flux density of
the transformer, a tap position may be reached at which the transformer iron becomes
progressively more saturated, causing high iron losses, high iron/oil temperature gradients or
excessive core bolt temperatures. Modem generator transformer cores are designed with a
nominal density of 1.8 tesla, using cold rolled steel, and a limit of 1.9 tesla is regarded by
the CEGB as the maximum permissible density,
CEGB Design Memorandum 099/61 describes the fundamental aspects of transformer
overfluxing, the operational circumstances in which it may occur and the measures taken to
minimize its adverse effects. Appendix A to that Design Memorandum deals specifically
with overfluxing in generator transformers and defines an equation for the limiting value of
Feactive power to prevent overfluxing. That equation is used in the Appendixes to this
Planning Memorandum to determine the overfluxing limit on the generator performance
chartPLM-ST-6
Page 8 Issue 1
June 1976
While the location of the overfluxing limit should be checked for all generator
transformers, the older transformers which have cores of hot-rolled steel and which operate
at lower flux densities are unlikely to impose a limit,
If overfluxing restricts generator MVAr absorption capability, reduction of the
jerator terminal voltage will cause the overfluxing limit line and practical stability limit
line to move left and right, respectively, until maximum possible MVAr absorption is
achieved. ‘
4, CONSTRUCTION OF PERFORMANCE CHARTS
The following clauses define a number of assumptions which simplify the construction
of a generator performance chart, without significantly reducing its accuracy, and then refer
to the procedure used to determine the various limits which together produce the outline of
the chart,
4.1 Assumptions
411 Losses
It is assumed that the mechanical shaft input power equals the electrical power
delivered to the network.
4.1.2 Saliency
In view of the small degree of saliency of most machines on the system (rarely more
than 5 per cent), saliency has been ignored and the generator has been assumed to have a
round rotor. (It has been estimated that the inclusion of 5 per cent saliency when plotting a
chart would show an improvement in MVAr absorption of about 2% per cent at 5 per cent
oad falling to much less than | per cent at 50 per cent load.)
If it is necessary to plot a performance chart for a hydro machine with high saliency,
‘guidance on the effect of saliency is given in IEE Paper 4699P,
4.1.3 System Frequency
Assumed to be constant $0 Hz.
4.14 Generator Saturation
No allowance has been made for variation of the synchronous reactance (x4) with
loading or terminal voltage. This assumption makes little difference at leading power factors
but may cause appreciable over-estimates at lagging power factors. (See also 3.6.)
4.1.5 HV System Voltage
It is assumed that the HV system voltage (or the switching voltage in the case of a
directly connected machine) remains constant irrespective of generator loading. This is
acceptable because the chart should show limits for more than one system voltage (see
clause 4) and limits at intermediate system voltages can be determined by interpolation.?
PLM~ST-6
Page 9 Issue 1
June 1976
4.1.6 Short-circuit Level and Transient Stability
Report PL~ST/28/72 describes an approximate method for the rapid assessment of
transient stability limits on large generators. The report demonstrates that, at time of light
load when system post-fault short-circuit levels are low, operation at the practical stability
limit could result in generator instability in the event of a fault close to the busbar at which
the generator is switched. It is not intended that transient stability limit lines should be
added to all performance charts, although they may be useful on charts for generators likely
to be running at light load times on weakened systems.
4.1.7 Unit Transformer Loading
This is assumed to be constant at all levels of generator output,
4.1.8 Voltage Indication
In order to use the performance chart it is necessary to know the generator terminal
voltage and the HV system voltage. It is assumed that indication of either or both of these
voltages is available to the user.
4.2 Steps in Construction
A detailed step-by-step description of the determination of each performance limit and
the subsequent construction of a generator performance chart is given in Appendix B. Six
separate sets of instructions cover the possible need to plot a chart for either a Type 1 or
Type 2 generator arrangement (i.e. terminal voltage remains constant or varies) relating to
either the HV or LV side of the generator transformers or the generator terminals.
‘As described in the introductory paragraphs to Appendix B, the chart for a directly
connected generator should be constructed using the equations for the Type 1 generator
arrangement, i.e. @ generator connected through a transformer with onload tap change
facilities. Reactor-connected generators can be treated in the same way if the reactor is
regarded as part of the generator reactance but, if there is metering at the generator
terminals, the chart must be constructed as for a Type 2 generator.
The symbols used, the data needed and the sign convention adopted are described in
Appendix A and the derivation of the equations used in Appendix B is given in
Appendixes E and F. Appendixes C and D show worked examples of the construction of
performance charts for actual Type | and Type 2 generator arrangements at Drakelow ‘B’
and Blyth ‘A’.
South Eastem Region have developed a computer program (CHRT) for use in
conjunction with this Memorandum, The program calculates the performance limits for 2
generator using the same data and generally the same theory as this Memorandum. The
output of the program can be fed into a graphical plotter to obtain a performance chart
Appendix G describes the differences between CHRT and the methods detailed in this
Memorandum and includes computer drawn charts for the Drakelow ‘B’ and Blyth ‘A°
machines used as worked examples..The charts are compared with those constructed
manually in Appendixes C and D.PLM-ST-6
Page 10 Issue 1
June 1976
5. PRESENTATION OF PERFORMANCE CHARTS
It would be possible to prepare a chart showing the limits of generator performance for
all possible values of system voltage, transformer tap position and, for Type 1 arrangements,
generator terminal voltage. However, such a chart would have so many lines that it would be
difficult for the user to interpret it. The presentation can be simplified by excluding
variations of parameters that are normally kept constant, e.g. terminal voltage in Type |
arrangements and tap position in Type 2 arrangements. While it is unlikely that the terminal
voltage will be varied regularly during normal operation, it is possible that a different
terminal voltage may be adopted, for a period, to satisfy a particular system condition. In
this event, another performance chart should be plotted for the new terminal voltage. The
same applies to an off-load tap position other than that in normal use.
In Type | arrangements it is only necessary to take account of the tap limit for
extreme negative tap (minimum turns ratio) since this is the tap position which permits
operation at the most leading power factor. Adjustment of the loading, excitation or
onload tap will enable the operator to move the operating point of the generator anywhere
within the limits of the chart and there is no need to define the limit of operation for each
tap position.
The tap limit line plotted for the opposite end of the tap range (i.e. extreme positive
tap — maximum turns ratio) is unlikely to prove a restriction on lagging power factor
operation except at high system voltage (say. 1.05 p.u. or above). Since the chance of
requiring maximum MVAr generation at a time of high system voltage is remote, the limit
line for this condition is not considered relevant.
It is usually sufficient to perform the leading power factor tap limit calculation for
only two values of system voltage ~ say, high and nominal. A third calculation for low
system voltage would reveal the maximum reactive absorption possible at a time of low
system voltage, but as it is most unlikely that reactive absorption will be needed at such 2
time the limit line for this condition is not considered relevant.
Appendix A to Design Memorandum 099/61 recommends that. where generator
transformer overfluxing imposes a limit, the performance chart should show the overfluxing
limit for various values of generator terminal voltage. This differs from the recommendation
in this Memorandum that each chart should relate to one terminal voltage only: it is
considered inadvisable to show overfluxing limits for reduced terminal voltages on a chart
drawn for, say, 1.0 p.u. terminal voltage because reduction in voltage also alters the rest of
the chart (e.g. the practical stability limit moves to the right).
The procedure described in Design Memorandum 099/61 is useful as part of an
investigation of overfluxing, leading to the determination of the normal terminal voltage
Tequired to avoid such a condition. The performance chart would then be constructed in
detail, for that terminal voltage, in accordance with this Memorandum
The number of lines on the chart could be further reduced by plotting separate charts
for AVR and manual control. However, this is not recommended unless the presence of
both control lines on one chart seriously impairs its intelligibility.
It is recommended that two separate charts should be plotted to show conditions at
the generator terminals (LV chart) and at the HV side of the generator transformer (HV
chart). (The equations of Appendix B allow for the LV metering point being on either side
of the unit transformer.) While the planning engineer or system operation engineer might
find it useful to have both HV and LV limit lines on a single chart, the station operator only
requires information for the metering point which is used to monitor the performance of
the generator. If, as is sometimes the case, the metering point is on the HV side of the
generator transformer, there is no need to prepare an LV chart.PLM-sT-6
Page 11 Issue 1
June 1976
The recommended methods for presenting generator performance charts for the
Type | and 2 generator arrangements, and the special case of the directly connected
machine are summarized as follows:
5.1 Generators Having Transformers with On-load Taps (Type 1)
‘Two charts are required — one HV and one LV — unless there is no generator terminal
metering, when the LV chart can be omitted,
Each chart should show operating limits for the following conditions:
Tap Position — Extreme negative tap (minimum turns ratio).
Terminal Voltage — 1.0 p.u. or nominal voltage.
System Voltage — G) nominal: (ii) high*.
Control — @ AVR; (il) manual,
‘Choice of high voltage should suit local conditos
In general, limit lines will not be shown for a third (low) value of V, nor for the tap
limit for extreme positive tap. It is possible that additional charts may be required for
alternative values of terminal voltage.
5.2. Generators Having Transformers with Off-load Taps (Type 2)
Two charts are required — one HY and one LV — unless there is no generator terminal
metering, when the LV chart can be omitted.
Each chart should show operating limits for the following conditions:
Tap Position — Tap in normal use.
Terminal Voltage — Not specified (varies during operation).
System Voltage ~ (i) nominal; (i) high*.
Control — @ AYR; (il) manual.
*Choice of high voltage should suit local conditions.
‘In general, limit lines will not be shown for a third (low) value of V,. It is possible that
additional charts may be required for alternative off-load tap positions.
5.3. Directly Connected Generators
Only one chart is required since HV and LV conditions are identical for a directly
connected machine. The chart should show limits for the upper and lower extremes of
system voltage which are likely in normal operation. If the resulting performance ‘envelopes’
are widely separated, the limits should also be drawn for an intermediate system voltage.
Charts for reactor-connected generators with generator terminal metering should be
plotted as in 5.2, and those without terminal metering should be treated as directly
connected generators of higher reactance.