JXCX OMT0006 A

Download as pdf or txt
Download as pdf or txt
You are on page 1of 87

No.

JXC※-OMT0006-A

PRODUCT NAME

PROFINET Direct input type


Step Motor Controller
(Servo 24VDC)
Model / Series / Product Number

JXCP1
Table of Contents

1. Safety Instructions .............................................. 4


2. Outlines of Product ............................................. 6
2.1 Features....................................................................................6
2.2 How to Order ............................................................................7
2.3 Product configuration .............................................................8
2.4 Start up procedure ...................................................................9
(1) Checking the contents of the package............................9
(2) Mounting the controller ....................................................9
(3) Wiring and Connection.....................................................9
(4) Supply of power ................................................................9
(5) Configuration ..................................................................10
(6) Setup of the operation parameters................................10
(7) Test run ............................................................................10

3. Specifications .....................................................11
3.1 Specifications.........................................................................11
3.2 Parts Description ...................................................................12
3.3 External Dimensions .............................................................13
(1) Screw mounting (JXCP17-□) ..........................................13
(2) DIN rail mounting (JXCP18-□) ........................................14
3.4 Mounting.................................................................................15
(1) Mounting..........................................................................15
(2) Grounding........................................................................15
(3) Mounting location ...........................................................16

4. Initial Setting method ........................................ 17


4.1 GSDML file and icons ............................................................17
4.2 GSDML file installation ..........................................................17
4.3 Addition of JXCP1 controller to PROFINET network ..........18
4.4 Registration of the device name of the JXCP1....................19

5. External Connections........................................ 21
5.1 PWR: Power supply connector.............................................21
5.2 MOT: Motor connector, ENC: Encoder connector ............21
5.3 SI: Serial I/O Connector.........................................................21
(1) Connecting the teaching box.........................................21
(2) Connection with a PC .....................................................22
5.4 P1, P2: PROFINET communication connector..................22

6. Details of Power Supply Plug ........................... 23


6.1 PWR: Power supply plug specifications..............................23
6.2 Electrical Wiring Specifications............................................23
6.3 Power Supply Plug Wiring ....................................................24
(1) Wiring of power supply (C24V, M24V, 0V) .....................24
(2) Wiring of the stop switch (EMG) ....................................24
(3) Wiring of the lock release (LK RLS) ..............................24

-1-
6.4 Wiring of stop circuit .............................................................25
(1)Stop (example of recommended circuit)........................25
(2) Stop (relay contact (1)) ...................................................26
(3) Motor power shutdown (relay contact (2)) ....................27

7. LED display ........................................................ 28


7.1 LED display ............................................................................28
7.2 LED and Controller Status ....................................................28

8. Operation methods............................................ 29
8.1 Outline ....................................................................................29
8.2 Operation by Step No. ...........................................................29
8.3 Position/speed monitor .........................................................29
8.4 Operation by numerical instruction .....................................29

9. Memory map ...................................................... 30


9.1 Memory allocation .................................................................30
(1) Input Area Mapping.........................................................30
(2) Input area details.............................................................31
(3) Output area mapping ......................................................35
(4) Output area details..........................................................36
(5) Record data .....................................................................40

10. Settings and Data Entry .................................. 41


10.1 Step Data ..............................................................................41
10.2 Basic parameters .................................................................44
10.3 Return to origin parameter..................................................46

11. Operations........................................................ 47
11.1 Return to Origin....................................................................47
11.2 Positioning Operation..........................................................47
11.3 Pushing Operation ...............................................................48
(1) Pushing operation is successfully performed. ............48
(2) Pushing operation fails (empty pushing)......................48
(3) Movement of the workpiece after the completion of the pushing process 48
11.4 Controller signal response time .........................................49
11.5 Methods of interrupting operation......................................49

12. Operation Examples ........................................ 50


12.1 Positioning Operation .........................................................50
12.2 Pushing Operation...............................................................51

13. Operation Instructions .................................... 52


13.1 Overview of the Operation Instructions.............................52
13.2 Operation procedure for Operation by Step No. ...............52
[1] Power on and Return to Origin position .......................52
[2] Positioning operation .....................................................53
[3] Pushing Operation ..........................................................54
[4] HOLD................................................................................54
[5] Reset ................................................................................55
[6] Stop ..................................................................................55

-2-
[7] Area output ......................................................................56
13.3 Operation procedure for Operation by numerical instruction 57

14. Options ............................................................. 58


14.1 Actuator cable [5m or shorter]............................................58
14.2 Actuator cable [8 to 20m] ....................................................58
14.3 Actuator cable for with lock [5m or less] ...........................59
14.4 Actuator cable for with lock [8 to 20m] ..............................59
14.5 Controller Set up kit.............................................................60
14.6 Conversion Cable ................................................................60
/14.7 Power supply plug ..............................................................60
14.8 Teaching box ........................................................................61

15. Alarm for Motor Control .................................. 62


15.1 Alarm group signals ............................................................62
15.2 Reading PROFINET Diagnostics from the JXCP1.............63
15.3 Alarms and countermeasures.............................................64

16. Precautions for wiring and cable ................... 69


17. Electric Actuators/Common Precautions ...... 70
17.1 Design and selection ...........................................................70
17.2 Mounting...............................................................................71
17.3. Handling Precautions .........................................................72
17.4 Operating environment .......................................................73
17.5 Maintenance Precautions....................................................74
17.6 Precautions for actuator with lock .....................................74

18. Controller and Peripheral Devices/Specific Product Precautions 75


18.1 Design and selection ...........................................................75
18.2 Handling Precautions ..........................................................76
18.3 Mounting...............................................................................77
18.4 Wiring....................................................................................77
18.5 Power supply .......................................................................78
18.6 Grounding ............................................................................78
18.7 Maintenance .........................................................................78

19. Troubleshooting .............................................. 79


20. Handling of sent/received data....................... 84
21. Definitions and terminology ........................... 85

-3-
JXCP1/Controller
1. Safety Instructions
These safety instructions are intended to prevent hazardous situations and/or equipment damage.
These instructions indicate the level of potential hazard with the labels of "Caution", "Warning" or
"Danger". They are all important notes for safety and must be followed in addition to International
Standards (ISO/IEC) ∗1) and other safety regulations.
∗1) ISO 4414: Pneumatic fluid power -- General rules relating to systems
ISO 4413: Hydraulic fluid power -- General rules relating to systems
IEC 60204-1: Safety of machinery -- Electrical equipment of machines (Part 1: General requirements)
IEC 10218-1992: Manipulating industrial robots -- Safety

CAUTION indicates a hazard with a low level of risk which, if not avoided, could
Caution result in minor or moderate injury.
WARNING indicates a hazard with a medium level of risk which, if not avoided, could
Warning result in death or serious injury.
Danger indicates a hazard with a high level of risk which, if not avoided, could result
Danger in death or serious injury.

Warning
(1) The compatibility of the product is the responsibility of the person who designs the equipment or
decides its specifications.
Since the product specified here is used under various operating conditions, its compatibility with
specific equipment must be decided by the person who designs the equipment or decides its
specifications based on necessary analysis and test results.
The expected performance and safety assurance of the equipment will be the responsibility of the
person who has determined its compatibility with the product.
This person should also continuously review all specifications of the product referring to its latest
catalog information, with a view to giving due consideration to any possibility of equipment failure
when configuring the equipment.
(2) Only personnel with appropriate training should operate machinery and equipment.
The product specified here may become unsafe if handled incorrectly.
The assembly, operation and maintenance of machines or equipment including our products must
be performed by an operator who is appropriately trained and experienced.
(3) Do not service or attempt to remove product and machinery/equipment until safety is confirmed.
1. The inspection and maintenance of machinery/equipment should only be performed after
measures to prevent falling or runaway of the driven objects have been confirmed.
2. When the product is to be removed, confirm that the safety measures as mentioned above are
implemented and the power from any appropriate source is cut, and read and understand the
specific product precautions of all relevant products carefully.
3. Before machinery/equipment is restarted, take measures to prevent unexpected operation and
malfunction.
(4) Contact SMC beforehand and take special consideration of safety measures if the product is to be
used in any of the following conditions.
1. Conditions and environments outside of the given specifications, or use outdoors or in a place
exposed to direct sunlight.
2. Installation on equipment in conjunction with atomic energy, railways, air navigation, space,
shipping, vehicles, military, medical treatment, combustion and recreation, or equipment in
contact with food and beverages, emergency stop circuits, clutch and brake circuits in press
applications, safety equipment or other applications unsuitable for the standard specifications
described in the product catalog.
3. An application which could have negative effects on people, property, or animals requiring
special safety analysis.
4. Use in an interlock circuit, which requires the provision of double interlock for possible failure by
using a mechanical protective function, and periodical checks to confirm proper operation.
Please perform periodic inspection to confirm proper operation.
-4-
JXCP1/Controller
1. Safety Instructions
Caution
The product is provided for use in manufacturing industries.
The product herein described is basically provided for peaceful use in manufacturing industries.
If considering using the product in other industries, consult SMC beforehand and provide
specifications or a contract, if necessary.
If anything is unclear, contact your nearest sales branch.

Limited Warranty and Disclaimer/


Compliance Requirements
The product used is subject to the following "Limited Warranty and Disclaimer" and "Compliance
Requirements".
Read and accept them before using the product.

Limited Warranty and Disclaimer


(1) The warranty period of the product is 1 year in service or 1.5 years after the product is delivered,
whichever is first. ∗3)
Also, the product may have specified durability, running distance or replacement parts.
Please consult your nearest sales branch.

(2) For any failure or damage reported within the warranty period, which is clearly our responsibility, a
replacement product or necessary parts will be provided.
This limited warranty applies only to our product independently, and not to any other damage
incurred due to the failure of the product.

(3) Prior to using SMC products, please read and understand the warranty terms and disclaimers
noted in the specified catalog for the particular products.

∗3) Vacuum pads are excluded from this 1 year warranty.


A vacuum pad is a consumable part, so it is warranted for a year after it is delivered.
Also, even within the warranty period, the wear of a product due to the use of the vacuum pad or failure due
to the deterioration of rubber material are not covered by the limited warranty.

Compliance Requirements
1. The use of SMC products with production equipment for the manufacture of weapons of mass
destruction (WMD) or any other weapon is strictly prohibited.
2. The exports of SMC products or technology from one country to another are governed by the
relevant security laws and regulation of the countries involved in the transaction. Prior to the
shipment of a SMC product to another country, assure that all local rules governing that export are
known and followed.
-5-
2. Outlines of Product
2.1 Features
Features of the controller.

●PROFINET compatible
This device can be directly connected to a PROFINET fieldbus network. It will then be possible to
establish communication with a PROFINET Master (PLC).

●Actuator control
Positioning operation and operation at a specific speed and force for the actuator are possible by
controlling the Step motor (servo 24VDC).

●Specified force operation


Control the pushing force or the pressing force of the actuator.

●Separated power supply


Power supply input is separated into the motor power supply and control power supply. Even if the
power supply for the motor is turned OFF, the information from the encoder position is retained whilst
the control power supply is ON, and PROFINET communication and serial communication is available.

●Return to origin
Returning to origin is possible by a signal from PROFINET.

●Alarm detection function


Abnormal conditions are self-detected. Alarms are output by PROFINET communication and serial
communication.
Alarm history can be stored in the memory in the controller.

●Positioning / pushing operation is available with step data and numerical operation mode
It is possible to operate the actuator by using the saved step data and by numeric data operation
instruction by using PROFINET communication.
In the step data operation mode, the operation is instructed by manipulating the memory which is
relevant to input/output port such as DRIVE signal and INP signal. The actuator operates in
accordance with the step data operating pattern of the specified step data.
In the numerical operation mode, the operation is executed by specifying the releveant numeric data.

●Area output
The AREA output bit will be activated if the actuator position is within the range specified by "Area 1"
and "Area 2" in the step data.

●Data input method


It is possible to perform status monitoring, reset alarms and set Step data via PROFINET
communication, ACT controller software or teaching box. In addition the ACT controller software or
teaching box can be used for parameter setup and trial run.

●Easy mode and Normal mode


There are two available modes for the controller setting software and the teaching box. In Easy mode,
you can start the operation by only setting the speed, position, etc. In Normal mode, further detailed
setup can be performed.

Caution
When the device is set up or failure occurs, please refer the operation manual of the actuator and
the teaching box as well as this operation manual.
Keep this operation manual accessible for reference when necessary.

-6-
2.2 How to Order
How to order is shown below.

JX C P 1 -
Electric equipment
Controller Actuator Model

Controller type (Enter from the actuator model to "stroke")


E.g.) LEFS16B-100B-S1CP17,
P PROFINET input “LEFS16B-100”.

Number of shaft/ Mounting


Type of power supply
7 Direct mounting
1 axis, Power supply
1 8 DIN rail
(24VDC)

Caution
Single controllers are also shipped after setting the actuator
specification parameters.
Confirm the combination of the controller and the actuator is
correct.

<Check the following before use.>


•Check the actuator label for the actuator model number.
Check that the actuator model matches the label on the
controller.

LEHZ10K2-4

Caution
Refer to the chart of LECPMJ for checking the chart of <Speed - Work load> of actuator.
A high peak current is required to be supplied by the controller when the actuator motor is turned ON.
Please use a power supply with a current capacity of at least 1.5 times the peak power that is required
by the actuator motor

-7-
2.3 Product configuration
An example of the controller structure is shown below.
∗1
Electric actuator PROFINET

●Controller PLC

To P1, P2

(Option)

•Conversion cable
∗1
Product no.: P5062-5 •Communication cable
•Actuator cable
(Robotic type cable)
Model number: To ENC •Conversion ∗2
•LE-CP-□-□
unit
To SI
(Robotic type cable)
•LE-CP-□-□-S
(Standard cable) モニ タ

To MOT
現 在位 置 120.3 mm 動作 中

現 在速 度 200 mm/s ア ラーム

設定 位置 速度

1 テスト 100 500


2 テスト 200 1000
3 テスト 50 200

To PWR PC
Controller power or •USB cable
supply (A-miniB type)
24VDC •Power supply plug (Included)
Part No.: JXC-CPW
<Applicable wire size> •Controller set up kit
2 (Controller setting software,
AWG20 (0.5mm )
•Teaching box communication cable,
(3m cable is provided.) conversion unit, USB cable
Part No: LEC-T1-3□G□ are included)
Part No: LEC-W2

∗1. These items are included when ordered using the part number for an actuator set.
∗2. Latest version of the controller setting software must be used.
Software can be downloaded from SMC website. http://www.smcworld.com/

Warning
Refer to 5. External Connections (P.21) for wiring.
Refer to 16. Precautions for wiring and cable (P.69) when handling the wiring and cables.

The Communication cable must be connected to a PC using a USB cable through a conversion unit.
Do not connect the teaching box to a PC.
Do not use LAN cable to connect to the SI connector of the controller, as this may cause damage to
the personal computer and the JXC.

-8-
2.4 Start up procedure
Install, wire, set and operate the controller referring to the procedure below when the product is used
for the first time.

(1) Checking the contents of the package


After unpacking everything, check the description on the label to identify the controller and the
number of accessories. If any parts are missing or damaged, please contact your distributor.
Power supply plug
Product name Quantity Controller
(JXC-CPW)

Controller (JXCP1□-□) 1 pc.


Power supply plug (JXC-CPW) 1 pc.
∗1
Actuator 1 pc.
∗1. These items are included when ordered
using the part number for an actuator set.

[Options] Teaching box Controller setting kit


•Teaching box (Part No: LEC-T1-3G)
•Controller setting kit (Part No: LEC-W2)
(Controller set up software, communication cable,
USB cable and conversion unit are included) Conversion cable
•Conversion cable (Part No: P5062-5)

(2) Mounting the controller


Refer to section 3.4 Mounting (P.15) for instructions on how to mount the controller.

(3) Wiring and Connection


Connect the cables to the controller.
Refer to 5. External Connections (P.21) for the wiring of the connectors.

(4) Supply of power


Supply power 24VDC.
If the condition is normal, LED on the front of the controller turns ON as shown on the table below
Items LED condition Status
PWR Green LED is ON Supply power
ALM OFF No alarm

Refer to 7. LED display (P.28) for the explanation of LED lamps.


If the red [ALM] LED on the front of the controller (JXC) is ON, an alarm has been triggered.

Caution
When an alarm is generated
Refer to a corresponding memory of PROFINET or connect a PC or teaching box to the SI serial I/O
connector and check the details of the alarm. Then, remove the cause of the error referring to the
15. Alarm for Motor Control (P.62).
∗ Please refer to the manuals of the controller setting software or the teaching box for details of the
alarms.

-9-
(5) Configuration
Using the PLC setting software, the following steps are required to use the JXCP1 on a PROFINET
network.
- Install the GSDML file and icon.
- Using the hardware configurator, create a PROFINET network then add the device
(JXCP1 controller).
- Using hardware configurator, assign a device name and IP address to the device
(JXCP1 controller).
- Write a device name directly into the physical device (JXCP1), this should match the name used in
the hardware configuration.
When the setting of the PLC and JXCP1 controller is completed and the PROFINET communication
is established, the LED’s on the front of the controller will be set as shown in the table below.
Items LED condition Status
PWR Green LED is ON Supply power
ALM OFF No alarm
SF OFF Controller is operating correctly.
BF OFF PROFINET connection is established.

Refer to 7 LED display (P.28) for the explanation of the LED’s.


Communication between PLC and controller is not established when the BF red LED is on or is
flashing red.

Caution
Communication between PLC and controller is not established.
Refer to 19. Troubleshooting (P.79)
Check if the communication speed of the PLC and controller and the information of the host computer
are correctly set.

(6) Setup of the operation parameters


Set up the operation pattern (step data, basic parameters and return to origin parameters) to specify
the target position, speed, etc. by using a PC (with the controller setting software) or the teaching
box.
■PC (Normal mode) ■Teaching box

Please refer to the manuals of the controller setting software or the teaching box for how to set up the
operation pattern.

(7) Test run


Refer to 9. Memory map (P.30) for the assignment of the memory.
Input signals from PLC for checking the operation. Refer to 13. Operation Instructions (P.52) for
the operation.

- 10 -
3. Specifications
3.1 Specifications
Basic specifications of the product.
Item Specifications
Compatible motor Step motor (servo 24VDC)
Power supply specification Power supply voltage: 24VDC±10%
200mA or less (Controller)
Current consumption Refer to the specification of actuator to be connected for total power
consumption.
Compatible encoder Incremental A/B phase (800 pulse/rotation)
Memory EEPROM
LED Details
PWR Supply power
LED display ALM Alarm status
SF Controller status
BF PROFINET communication status.
Locked With unlocking terminal
Cable length Actuator cable: 20m or less
Cooling method Air-cooling type
Operating temperature range: 0oC to 40oC (No freezing)
Operating humidity range 90% RH or less (No condensation)
Between the external terminals and case
Insulation resistance
50MΩ (500VDC)

220g (Thread mounting type)


Weight
240g (DIN rail mounting type)

[PROFINET communication type]


Items Specification
Protocol PROFINET (Specification Version 2.32)
IP address setting range 0.0.0.0 to 255.255.255.255 (set using DCP service)
Communication speed 100Mbps
Communication method Full duplex/ Half duplex (automatic negotiation)
Communication cable Standard Ethernet cable (CAT5 or higher, 100BASE-TX)
Setup file GSDML file (Please download from SMC website).
Occupied area Input 36 byte / Output 36 byte
Vendor ID 83h(SMC Corporation)
Device ID 0Fh
I/O data
Record data
Applicable function MRP
Device_Access
Conformance Class C (RT/IRT)

- 11 -
3.2 Parts Description
Details of the parts of the controller.

No. Display Name Details


1 - Display The LED’s to indicate the controller status.
PROFINET
2 P1, P2 communication Connect to the PROFINET network.
connectors
Serial I/O connector The connector which connect the teaching box
3 SI
(8 poles) (LEC-T1) or the setting software (LEC-W2).
Encoder connector
4 ENC
(16 poles)
Connect to the actuator cable.
Motor driving connector
5 MOT
(6 poles)
Connect to the controller power supply (24VDC)
Power supply connector using the power supply plug.
6 PWR
(5 poles) Control power (+), Stop signal (+), Motor power (+),
Lock release (+), Common power (-)
Controller part number
7 - Label indicating the controller part number.
label
Applicable actuator
8 - Applicable actuator
model number label
9 - MAC address PROFINET MAC address is displayed.
Functional earth
10 - FE When the controller is mounted, tighten screws and
connect the grounding cable.

- 12 -
3.3 External Dimensions
The appearance of this product is as shown in the diagram below:

(1) Screw mounting (JXCP17-□)

- 13 -
(2) DIN rail mounting (JXCP18-□)

- 14 -
3.4 Mounting
(1) Mounting
The controller can be direct mounted using screws or mounted on a DIN rail.
Details of the controller mounting options are shown below.

[1]Thread mounting (JXCP17-□) [2]DIN rail mounting (JXCP18-□)


(Mounting with two M4 screws) (Mounting with DIN rail)
Before locked onto DIN rail Locked onto DIN rail

(2) Grounding
Place the grounding cable with crimped terminal between the M4 screw and shakeproof washer as
shown below and tighten the screw.

M4 screw
Cable with crimping terminal
Shakeproof washer

Controller

Caution
The M4 screw, cable with crimped terminal and shakeproof washer must be prepared by the user.
The controller must be connected to Ground to reduce noise.

- 15 -
Caution
(1) A dedicated Ground connection must be used. Grounding should be to a D-class ground
(ground resistance of 100Ω or less).
(2) The cross sectional area of the grounding cable shall be 2mm2 minimum.
The Grounding point should be as near as possible to the controller. Keep the grounding cable as
short as possible.

Other Other
Controller Controller
equipment equipment

D-class
grounding

Dedicated grounding --- Good Shared grounding --- Not acceptable

(3) Mounting location


Design the size of the control panel and the installation type so that the temperature surrounding the
controller is 40oC or less.
Mount the controller vertically on the wall with 30mm or 50 more of space on the top and bottom of
the controller as shown below.
Allow 60mm or more of space between the front of the controller and the cover of the control cabinet
to allow access to the connectors.
Leave enough space between the controllers so that the operating temperatures of the controllers
stay within the specification range.
Avoid mounting the controller near a vibration source, such as a large electromagnetic contactor or
circuit fuse breaker on the same panel, or keep it away from the controller.
0mm or more (Actuator body size 16 or less, ∗ all size of LEH series is applicable)
10mm or more (Actuator body size 25 or more)
Door (Lid)
Controller
30mm or longer

Controller

30mm or more (screw mounting) 60mm or longer


50mm or more (DIN rail mounting)

Caution
If the mounting surface for the controller is not flat or is uneven, excessive stress can be applied to
the case, which can cause failure. Mount on a flat surface.

- 16 -
4. Initial Setting method
Appropriate setting is required in order to establish the communication of the controller (JXCP1) on the
PROFINET network.
The required initial setting and setting method are explained below. Please refer to the SIEMENS PLC
setting software "SIMATIC Manager Version 5.5 (hereinafter referred to as STEP7)", the representative
PROFINET master device as an example.
Please note that this controller, PLC and PC should be wired correctly in accordance with "5. External
Connections", "6.CN1: Power Supply Plug".
The required setting method such as GSDML file installation varies depending on which setting software
will be used, so if the software other than STEP7 is used, please refer to the operation manual of the
applicable setting software.

4.1 GSDML file and icons


A GSDML file is required by the setting software, to configure the JXCP1 for a PROFINET network
Furthermore, special icons are necessary for the display of the JXCP1 controller within the setting
software.
GSDML file and special icons can be downloaded from the URL below.

URL http://www.smcworld.com
Document/ download→ Operation Manuals → Electric Actuator → JXCP1 → Configuration
File

4.2 GSDML file installation


The following instructions describe how to install a GSDML file using the STEP7(SIMATIC Manager)
setting software.

(1) Start the STEP7 application, and insert the applicable station from the menu [Insert] → [Station]. Click
on the Station icon to see the Hardware icon. Please double-click this icon to start [HW Config], a
new window will open.

Fig. 4.1 HW Config startup screen

(2) Select [Options/ Install GSD file...] from the HW Config menu.

- 17 -
Fig. 4.2 Selection of [Install GSD file] of HW Config

(3) Specify the path of the JXCP1 GSDML file and click the [Install] button.
(The GSDML file for JXCP1 can be downloaded from the SMC website (http://www.smcworld.com).

JXCP.xm
l

Fig.4.3 Installation of GSDML file

4.3 Addition of JXCP1 controller to PROFINET network


(1) Start [HW Config] from STEP7(SIMATIC Manager). (Refer to 4.2(1).)

Add the appropriate master (PLC) and the PROFINET bus to the hardware configuration screen.
(please refer to the STEP 7 user manual for instructions).

Locate the JXCP1 controller icon in the hardware catalogue (right screen), it is under [PROFINET IO],
[Additional Field Device], [Controllers], [SMC JXC])
Drag the icon from the hardware catalogue and drop it on the PROFINET-IO-System line
(PROFINET network).

PROFINET-IO-System line (Bus)

JXCP1

Hardware Catalogue

Fig. 4.4 Addition of JXCP1 to PROFINET network

- 18 -
(2) Double-click the JXCP1 icon on the PROFINET network.
When the Properties screen appears, set an arbitrary name in the [device Name] field. To set the IP
address, click [Ethernet] button and enter an arbitrary address.
Note: when the Properties screen below appears for the first time, it may automatically
display a device name and an IP address. If the default description is acceptable, it is
not necessary to change it.
Click [OK].

Fig.4.5 Device name and IP address input screen

(3) When other settings such as master and device are added and their settings are complete, please
select [PLC/Download] and download (1) to (3) setting to the PLC.

4.4 Registration of the device name of the JXCP1 controller to be connected


(1) Start [HW Config] from STEP7(SIMATIC Manager). (Refer to 4.2(1).)
Select [PLC]→[Ethernet]→[Edit Ethernet Node] from the menu bar of [HW Config].

Fig.4.6 [Edit Ethernet Node] screen is selected.

- 19 -
(2) When Edit Ethernet Node screen appears, click [Browse] button to display the devices that are
connected to the PROFINET network.
Select the MAC address of the JXCP1 controller for which the Device name must be set, and click
[OK].
Note: the MAC address can be found on the label attached to the side of the JXCP1 controller.

JXCP

Fig.4.7 Specification of connected JXCP1 controller

(3) In the [Device name] box, enter the device name which was set in 4.2(1).
Click [Assign Name] and register the input device name to the specified JXCP1 controller.

JXCP

Fig.4.8 Device Name registration screen

<Initial setting completed>

- 20 -
5. External Connections
An example of standard wiring of the controller is shown for each connector.

5.1 PWR: Power supply connector


Controller
Controller input power supply
24VDC

Wire
PWR

(The Controller power supply (24VDC) and wires must be prepared by the user.)

∗ Refer to 6. CN1: Power supply plug (P.23) for wiring.

Caution
Do not use an inrush current limited type of power supply for the controller.

5.2 MOT: Motor connector, ENC: Encoder connector


Connect the controller and the actuator with the actuator cable (LE-CP-□)
Controller

ENC Actuator
Actuator cable
Motor

MOT

5.3 SI: Serial I/O Connector


(1) Connecting the teaching box

Controller

SI Teaching box
(3m cable is provided)
Conversion cable

- 21 -
(2) Connection with a PC

Controller set up kit


(Controller set up software, communication cable,
USB cable and conversion unit are included)

Controller
Conversion unit モニタ
現在 位 置 120.3 mm 動 作中

現在 速 度 200 mm/s アラーム

USB cable
設定 位置 速度

1 テ スト 100 500

Conversion cable 2 テ スト 200 1000

(A-miniB type)
3 テ スト 50 200

SI
(Communication cable)
PC
(PC is prepared by the user.)

5.4 P1, P2: PROFINET communication connector

Standard Ethernet cable


(CAT5 or higher, 100BASE-TX)

P1
PLC
P2
The standard Ethernet cable with CAT5 or
higher and 100BASE-TX and PLC need to
be prepared by the user.

∗ Cable can be connected to either P1 or P2.


Follow the topology of PROFINET communication for details.

- 22 -
6. Details of Power Supply Plug
6.1 PWR: Power supply plug specifications
The specifications of the power supply plug supplied with the controller are shown below.

Power supply plug Pin No. Terminal Function Functional explanation

1 C24V Power supply (+) The positive control power.


The positive power for the actuator
2 M24V Motor power (+)
motor to be supplied via the controller.
3 EMG Stop (+) The positive power for Stop signal
The negative common power for M24V,
4 0V Common power (-)
C24V, EMG and BK RLS.
5 - NC N/A
6 LK RLS Unlocking (+) The positive power for lock release.

∗ Equivalent to Phoenix Contact: DFMC1, 5/3-ST-LR

6.2 Electrical Wiring Specifications


Prepare the electrical wiring according to the following specifications (to be prepared by the user).

Item Specifications
Single, stranded wire → AWG20 (0.5mm2)
Applicable wire size ∗ The rated temperature of the insulation coating should be 60oC or more.
The O.D. should be ø2.5mm or less.

Stripped wire length


ø2.5mm or less 8mm

Caution
Do not connect multiple wires to one terminal.

After wiring the power supply plug, connect it to PWR power connector of the controller.
∗ Refer to 6.3 Power Supply Plug Wiring (P.24) for wiring.
Controller Power supply plug inserted into CN1

- 23 -
6.3 Power Supply Plug Wiring
Connect the power supply plug to the 24VDC controller power supply according to instructions (1) (2)
and (3) and then insert it into the PWR connector of the controller.

(1) Wiring of power supply (C24V, M24V, 0V)


Connect the positive of the 24VDC controller power supply to the C24V and M24V and connect the
negative of that power supply to the 0V terminal.

(2) Wiring of the stop switch (EMG)


Stop switch must be installed by the user to stop the actuator in abnormal situations.
Refer to 6.4 Wiring of stop circuit (P.25) for wiring.

(3) Wiring of the lock release (LK RLS)


Install an unlocking switch for adjustment or recovery during an emergency of the locking actuator.
∗ Switch (24V DC, contact capacity 0.5A or more) is provided by customer.
One terminal of the lock release switch should be connected to the 24VDC power supply and the
other should be connected to the LK RLS terminal. When this is switched on, the lock will be
released.
External shut Unlocking
down circuit Switch

Power supply plug


(3) EMG LK RLS (6)
(2) M 24V
Controller (1) C 24V 0V (4)
Input power
supply 24VDC
0V

Caution
(1) Do not use a power supply with "inrush-current control" for the controller power supply.
(2) It is unnecessary to connect LK RLS terminal when the actuator does not have locking mechanism.
(3) The LK RLS terminal is only used for adjustment and emergency return. It must not be energized during normal
operation.

- 24 -
6.4 Wiring of stop circuit
The actuator stops its operation when the external stop switch or the stop switch of the teaching box is
activated.

(1)Stop (example of recommended circuit)


When the controller recognizes the connection of the teaching box, the stop of the teaching box is
activated.
(Circuit example)

Teaching box
(Cable 3m) Controller
Connected to the
Stop teaching box
Switch
SI

Judged to
stop

Not connected to
the teaching box

External stop circuit


PWR
(3) EMG
(2) M 24V
(1) C 24V 0V (4)
Controller
Input power 24VDC Power supply plug
supply 0V

Warning
The teaching box’s stop switch is effective only for the controller that is connected to it.

- 25 -
(2) Stop (relay contact (1))
If the system where this controller is installed has a stop circuit for the whole system, or if the system
has multiple controllers with individual power supply, relay contacts should be made between the
24VDC controller power supply and the EMG terminal of the power supply plug.
(Circuit example)
24VDC 0V

The stop is Ry
released switch

Stop
Switch
Ry: Relay Surge suppressor
U

Power supply plug 1


Ry (3) EMG LK RLS (6)
(2) M 24V

Controller (1) C 24V 0V (4)


Input power 24VDC
supply
0V

Power supply plug 2


Ry (3) EMG LK RLS (6)
(2) M 24V

Controller (1) C 24V 0V (4)


Input power 24VDC
supply
0V

Power supply plug 3


Ry (3) EMG LK RLS (6)
(2) M 24V
Controller (1) C 24V 0V (4)
Input power 24VDC
supply
0V

Caution
When shutdown is input, the controller stops with maximum deceleration, then the motor is turned
OFF.

- 26 -
(3) Motor power shutdown (relay contact (2))
If it is necessary to have a circuit to shutdown the motor power externally, relay contacts should be
made between the 24VDC controller power supply and the M24V and EMG terminal of the power
supply plug.

(Circuit example)

24VDC 0V

The stop is Ry
released switch

Stop
Switch
Surge suppressor
Ry: Relay U

Power supply plug 1


(3) EMG
LK RLS (6)
Ry (2) M 24V
(1) C 24V
Controller 0V (4)
Input power 24VDC
supply 0V

Power supply plug 2


(3) EMG
LK RLS (6)
Ry (2) M 24V
(1) C 24V
Controller 0V (4)
Input power 24VDC
supply 0V

Power supply plug 3


(3) EMG
LK RLS (6)
Ry (2) M 24V
(1) C 24V
Controller 0V (4)
Input power 24VDC
supply
0V

Warning
(1) Relay contacts should be made between the 24VDC controller power supply and the M24V and
EMG terminal of the power supply plug. The actuator may make unexpected movement.
(2) Do not perform return to origin (SETUP input ON) when motor drive power (M24V) is disconnected.
The controller cannot recognize the correct origin point if a return to origin instruction is made with
the motor drive power (M24V) disconnected.
(3) Do not energize the LK RLS terminal while the motor drive power (M24V) is disconnected.

- 27 -
7. LED display
7.1 LED display
Refer to the table below for the details of the LED status.
LED Details
Power supply OFF Power is not supplied
PWR
status is displayed Green LED is ON Power is supplied
Controller alarm OFF Normal operation
ALM
status. Red LED is ON Alarm generated
OFF Normal operation
SF Controller status.
Red LED is ON Alarm generated (Linked to ALM)

PROFINET OFF PROFINET communication is established.


BF communication Red LED is flashing PROFINET communication is not established.
status
Red LED is ON Both Port1 and Port2 are not Linked.

7.2 LED and Controller Status


Refer to the table below for the LED and the controller status.
LED description
Controller status
PWR ALM SF BF
Green LED
When power is supplied OFF - -
is ON
When PROFINET communication is
- - OFF OFF
normal
Red LED is Red LED is
Controller alarm generated OFF -
ON ON
Motor Controller system error Green LED Red LED is
- -
controller generated is ON ON
Green LED
Writing controller EEPROM - - -
is flashing
-: LED display is unstable

Caution
Do not turn OFF the input power supply for the controller or disconnect and connect the cable while
data is being written to EEPROM (PWR LED (green) is flashing).
∗ This is to avoid the possibility of incorrect / corrupted data (step data, parameter)

- 28 -
8. Operation methods
8.1 Outline
Two types of operation method are available for this product. The first method is “Operation by Step No.”.
When using this method, step data stored in the product can be driven by sending specific commands
over the network. The second method is “Operation by numerical instruction”. When using this method
the numerical data (e.g. Position, speed etc.) is changed based on the already set step data.

8.2 Operation by Step No.


The function of this mode is to read/write the memory bits corresponding to the input/output port signals
(e.g. DRIVE, INP) using a master (PLC) on the PROFINET network.
When an operation is based on the preset step data, select the step data No. from the PROFINET
communication output data bits then activate the DRIVE signal.
Refer to 13.2 Operation procedure for Operation by Step No. (P.52).

8.3 Position/speed monitor


Reads the current position and current speed for monitoring.
Refer to 9. Memory map (P.30) for the current position and speed.

8.4 Operation by numerical instruction


When numerical data relating to the actuator speed, position etc. is sent, the actuator will execute this
data provided it is within the allowable range of values.
For the JXCP1 controller, it is possible to instruct all step data items (operation method, speed, position,
acceleration, deceleration, pushing force, switch point, pushing speed, positioning thrust, area 1, area 2,
positioning width) by numeric values.
Preparatory operations such as turning the servo on and performing a return to origin are required
before the actuator may execute step data or numerical data.
Refer to 13.3 Operation procedure for operation by numerical instruction (P.57).

- 29 -
9. Memory map
9.1 Memory allocation
(1) Input Area Mapping

●Input area mapping list (data sent from JXCP1 controller to PROFINET master)
SUBSLOT
SLOT

Offset
Size Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
(Byte)

0 BYTE - - OUT5 OUT4 OUT3 OUT2 OUT1 OUT0


1 BYTE ALARM ESTOP WAREA AREA INP SETON SVRE BUSY
2 BYTE - - - READY - - - -
3 BYTE - - - - - - - -
4
5
DWORD Current position
6
7
8
WORD Current speed
9
10
WORD Current pushing force
11
12
13
DWORD Target position
14
15
16 BYTE Alarm 1
17 BYTE Alarm 2
1 1
18 BYTE Alarm 3
19 BYTE Alarm 4
20 - Reserved
21 - Reserved
22 - Reserved
23 - Reserved
24 - Reserved
25 - Reserved
26 - Reserved
27 - Reserved
28 - Reserved
29 - Reserved
30 - Reserved
31 - Reserved
32 - Reserved
33 - Reserved
34 - Reserved
35 - Reserved

- 30 -
(2) Input area details

●Byte0: Input port equivalent signal details


Byte Bit Signal name Description

0 OUT0 When the operation is started and DRIVE input is turned


OFF, the step No. executed by the DRIVE signal will be
refreshed/updated by the combination of OUT0 to OUT5
1 OUT1 (binary digit).
E.g. (Step data No.3 is output)
2 OUT2 OUT5 OUT 4 OUT 3 OUT 2 OUT 1 OUT 0
OFF OFF OFF OFF ON ON

0 3 OUT3
Caution
(1) When RESET is turned ON, these signals are turned OFF.
4 OUT4 (2) During the alarm, these signals output the alarm group.
(3) During the pushing operation, if the actuator runs over
the defined pushing width, these signals will be turned
5 OUT5 OFF.

6 - -
7 - -

- 31 -
●Byte1: Input port equivalent signal details
Byte Bit Signal name Description
This terminal is ON during the movement of the actuator
(during the positioning operation, etc.).

1 0 BUSY Caution
During the pushing operation without movement (no
movement but the actuator generating the pushing force),
BUSY is OFF.
When the servo motor is OFF, SVRE is OFF. Turns on when
1 SVRE
the servo motor is ON.
When the actuator is in the SETON status (the position
information is established) after returning to origin, this
2 SETON terminal is turned ON.
When the actuator has not returned to origin, this terminal is
turned OFF.

The condition when the INP output is ON depends on the


actuator action.
- Return to origin
After stopping the actuator operation (BUSY output is turned
OFF), the INP is turned ON when the actuator is within the
range defined in the origin +/-“Default In position” in the basic
parameter.
- During positioning operation
Turns ON when the current position is within "Step data
position +/- positioning range".
- During pushing operation-
Turns ON when the pushing force exceeds the value set in
the step data “Trigger LV”.
Caution
After the pushing operation is completed, even if it switches
3 INP automatically to energy saving mode, the INP output signal
stays ON.
When movement starts again from the pushing stopped state,
pushing operation is repeated with the normal pushing force.

(E.g.) Step data “force” is 100%


Step data “Trigger LV” is 80%
The energy saving setting of the actuator is 40% (∗ 1)
1 The actuator model determines the energy settings.
Please
Pushing forcerefer to the manual of the actuator for more details.
(%) INP output [ON]

100
80 Switch point
Energy saving mode
40
Time

When the actuator is within the output range between Area1


4 AREA and Area2 in the step data, this terminal will turned ON.
The area output setting range changes depending on the
active step data.

- 32 -
When the actuator is within the output range between "W area
5 WAREA
1 and W area 2" of basic parameter, this terminal will turn ON.
During activation of Teaching Box stop switch, this terminal is
6 ESTOP ON. During the normal operation, this is OFF. This is
synchronized to the EMG stop signal input.
Alarm generated when abnormal conditions occur to the
7 ALARM actuator or its controlling status. OFF when there are no
alarms. ON in alarm condition.

The table below shows the changes in the output signal with respect to the state of the controller.
Status Output signal BUSY INP SVRE Lock SETON OUT0 to 5
Controller powered down [SVOFF] with no
OFF OFF OFF Lock OFF OFF
motion
Controller powered down [SVON] with no
OFF OFF ON Unlock OFF OFF
motion
During returning to origin ON OFF ON Unlock OFF OFF
The actuator is at the origin. On completion
OFF ON(∗1) ON Unlock ON OFF
of [SETUP]
During movement by positioning/pushing
ON OFF ON Unlock ON ON(∗2)
operation
The actuator is paused by [HOLD] OFF OFF ON Unlock ON ON(∗2)
On completion of the positioning operation. OFF ON(∗4) ON Unlock ON ON(∗2)
Stopped due to pushing a workload in
OFF ON ON Unlock ON ON(∗2)
pushing operation.
Stopped due to no detection of workload
OFF OFF ON Unlock ON OFF
during a pushing operation.
Servo is OFF after returning to Origin. OFF OFF(∗4) OFF Lock ON ON(∗3)
EMG signal stop from the CN1 connector
OFF OFF(∗4) OFF Lock ON OFF
after the actuator is at the origin.
∗1. The output turns on when the actuator is within the "Default in position" defined in the basic
parameter setup.
∗2. The output is updated on the transition of (ON -> OFF) of the DRIVE input signal.
∗3. Retains the previous state.
∗4. The output turns on when the actuator is within the "In position" of the step data.

●Byte2,3: Controller information flag


Byte Bit Signal name Description
0-3 (Unused) -
READY turns ON when no alarm is generated with Servo ON.
4 READY
2 READY flag turns ON.
5 (Unused) -
6-7 (Unused) -
3 0-7 (Unused) -

●Byte4-7: Current position


Byte Signal name Description
4 Current position of the actuator is shown in multiples of 0.01mm when
numerical data can be read. (∗5)
5
E.g.) 800.00[mm](80000d=13880h) is output.
Current position
“Byte4” = 00h
6 “Byte5” = 01h
“Byte6” = 38h
7 “Byte7” = 80h

- 33 -
●Byte8, 9: Current speed
Byte Signal name Description
Current speed of the actuator is shown in multiples of 1mm/s when
8
numerical data can be read. (∗5)
Current speed E.g.) 300[mm/s](300d=012Ch) is output.
“8Byte” = 01h
9 “9Byte” = 2Ch
∗5 Please refer to 20. Handling of sent/received data (P.84) for handling of the data.

●Byte10, 11: Current pushing force


Byte Signal name Description
10 Current pushing force of the actuator is shown in multiples of 1%
Current pushing force
11 when numerical data can be read. (∗5)

●Byte12-15: Target position


Byte Signal name Description

12 Target position of the actuator is shown in multiples of 0.01mm when


numerical data can be read. 5
13
E.g.) When 800.00[mm](80000d=13880h) is input.
Target position
“Byte12” = 00h
14 “Byte13” = 01h
“Byte14” = 38h
15 “Byte15” = 80h

●Byte16-19: Alarm
Byte Signal name Description

Alarm code shown as a 3 digit decimal number when read numerical


16 Alarm 1 data is valid and alarm is generated. 5

Latest alarm code generated will be output to alarm 1. Alarm is


updated by another alarm. The code of the alarm generated in the
past will be shifted as alarm1 -> 2 -> 3 -> 4 ->.
When the number of alarm generated exceeds the maximum alarm
17 Alarm 2 output of each mode, the oldest alarm code is deleted from the
record.

E.g.) Alarm was generated in order of (1) -> (5)


Alarm 1 (Latest) (1) (2) (3) (4) (5)
18 Alarm 3 Alarm 2 0 (1) (2) (3) (4)
Alarm 3 0 0 (1) (2) (3)
Alarm 4 0 0 0 (1) (2)
(1) to (5) in the table indicate the alarm codes which are generated.
19 Alarm 4 Refer to “15.3. Alarms and countermeasures (P.64)” for detailed
alarm information.

∗5 Please refer to 20. Handling of sent/received data (P.84) for handling of the data.

- 34 -
(3) Output area mapping

●Output area mapping list (data sent from PROFINET master to JXCP1 controller)
SUBSLOT
SLOT

Offset
Size Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
(Byte)

0 BYTE - - IN5 IN4 IN3 IN2 IN1 IN0


1 BYTE FLGTH JOG+ JOG- SETUP RESET DRIVE SVON HOLD
Movement Speed
2 BYTE Acceleration Position Speed
mode - - restriction -
"In-Position"
Area Area Moving Pushing Pushing
3 BYTE tolerance
output 2 output 1 force speed
Trigger LV
force
Deceleration
range

4 BYTE Start flag


5 BYTE Movement mode
6
WORD Speed
7
8
9
DWORD Position
10
11
12
WORD Acceleration
13
14
WORD Deceleration
15
16
WORD Pushing force
2 1 17
18
WORD Trigger LV
19
20
WORD Pushing speed
21
22
WORD Moving force
23
24
25
DWORD Area1
26
27
28
29
DWORD Area2
30
31
32
33
DWORD "In-Position" tolerance range
34
35

- 35 -
(4) Output area details

●Byte0,1: Output port to which signal is allocated


Byte Bit Signal name Description

0 IN0
The step data No. instruction the drive will be specified by the
combination of IN0 to 5 (binary digit).
1 IN1
E.g.) Step data No.3 has been assigned
2 IN2 IN5 IN4 IN3 IN2 IN1 IN0
OFF OFF OFF OFF ON ON

0 3 IN3
Caution
Be sure to decide the step data No. by signal before
4 IN4 instructing the operation (DRIVE turns ON).
Otherwise, the actuator might operate with unexpected step
data.
5 IN5

6 - Normally, leave it OFF


7 - Normally, leave it OFF

- 36 -
●Byte1: Output port to which signal is allocated
Byte Bit Signal name Description
If HOLD input is ON during operation, the speed decreases at
maximum deceleration of the basic parameter until the
actuator stops. The remaining stroke will be on hold as long
as HOLD is ON and when HOLD is turned OFF, the actuator
restarts to travel the remaining stroke.
•When DRIVE or SETUP is ON
On hold
DRIVE
or ON
SETUP OFF
Restart
ON
0 HOLD HOLD OFF

Speed

Caution
(1) As long as HOLD is ON, the DRIVE input will be
disabled.
(2) The output signals are rendered invalid whilst hold is in
operation.
The SVON signal turns the servo motor ON.
When SVON is ON, the servo motor will be turned ON. When
this is OFF, the servo motor will be turned OFF.

1. SVON Caution
(1) When SVON is ON, the actuator may move 2 to 3mm to
improve the controlling accuracy.
(2) When SVON is OFF, turn OFF the DRIVE and SETUP.
When DRIVE is turned ON, the system scans the input IN0 to
1
IN5 and starts the operation of the actuator.
2 DRIVE
Then, when this signal is turned OFF, the number of the active
step data will be output via the signals OUT0 to OUT5.
The signal to reset the alarm and the operation.
After RESET, the speed decreases at maximum deceleration
of the basic parameter until the actuator stops.
3 RESET
INP and OUT0 to OUT5 will be turned OFF (however, if the
actuator is stopped within the in-position range, the INP will
be turned ON).
When SVRE (B11) is ON, the SETUP operation (return to origin
operation) will be performed. During the SETUP operation, BUSY
4 SETUP
(B7) will be turned ON and after completion of the SETUP
operation, SETON (B9) and INP (B10) will be turned ON.
Jogging to (-) direction.
Moves during the signal is ON. Stops during the signal is OFF.
When FLGTH (signal for switching Jogging and Inching) is
ON, movement towards (-) side is made at the time of
5 JOG(-)
"JOG(-)" signal.
INP output, OUT0 to 5 are OFF after Jogging/Inching started.
INP output, OUT0 to 5 are not turned ON after
Jogging/Inching completes.
6 JOG(+) Operation is the same as JPG(-). "-" is changed to "+"
Switches the function (Jogging and Inching) of Jogging signal
"JOG(-)" and "JOG(+)".
Inching starts when this signal is ON and when the Jogging
7 FLGTH
signal is ON.
Jogging starts when this signal is OFF. Inching amount is set
by operation parameter.
- 37 -
●Byte2,3: Controlling of the controller/numerical data flag
Byte Bit Signal name Description
0 - Unused

Flags for controller


Speed is restricted for all operations. Value for speed limit
1 Speed restriction
varies depending on actuator type.
2 (Unused) -
2 3 (Unused) -
4 Movement mode
5 Speed
6 Position
Numerical data input flag

7 Acceleration
0 Deceleration
1 Pushing force When the operation is commanded numerically, values can
2 Trigger LV be changed while the set values are ON.
3 Pushing speed
3
4 Moving force
5 AREA 1
6 AREA 2
7 In-Position

●Byte4,5: Movement mode/Start flag


Byte Bit Signal name Description
Data transmission flag during numerically instructed
0 Start flag operation. Turn OFF during waiting for transmitting. Turn ON
4 when transmitting numerical data to the controller. (∗1)
1-7. (Unused) -
0-1. Movement mode 1: ABS (Absolute) 2: INC (Relative) (∗)
5
2-7. (Unused) -
∗1: The data is sent while the start flag is ON, so if numerical instruction data is changed when the
start flag is ON, the changed data will be sent, which might lead to unexpected operation.
After changing the numerical instruction data, please wait until the PLC processing time has
passed, then turn ON the start flag.
∗2 Do not input numbers other than [1(ABS)] and [2(INC)].

●Byte6, 7: Speed
Description
Byte Signal name
Input range Min. unit
6 1 to Basic parameters
Speed 1mm/s
7 "Maximum speed"(∗3) (∗4)

●Byte8-11: Target position


Description
Byte Signal name
Input range
Min. unit
8
9 Basic parameter
Target position 0.01mm
10 "Stroke(-)" - "Stroke (+)"(∗3) (∗4)
11
∗3 The actuator model determines the available input values. Refer to the operation manual of the
actuator for details.
∗4 Please refer to 20. Handling of sent/received data (P.84) for handling of the data.

- 38 -
●Byte12,13: Acceleration
Description
Byte Signal name
Input range Min. unit
12 1 ~ Basic parameters
Acceleration "Maximum acceleration/deceleration 1mm/s2
13 speed" (∗1) (∗2)

●Byte14,15: Deceleration
Description
Byte Signal name
Input range Min. unit
14 1 ~ Basic parameters
Deceleration "Maximum deceleration speed" 1mm/s2
15 (∗1) (∗2)

●Byte16,17: Pushing force


Description
Byte Signal name
Input range Min. unit
16
Pushing force (∗1) (∗2) 1%
17

●Byte18,19: Trigger LV
Description
Byte Signal name
Input range Min. unit
18
Trigger LV (∗1) (∗2) 1%
19

●Byte20,21: Pushing speed


Description
Byte Signal name
Input range Min. unit
20
Pushing speed (∗1) (∗2) 1mm/s
21

●Byte22,23: Moving force


Description
Byte Signal name
Input range Min. unit
22
Moving force (∗1) (∗2) 1%
23

●Byte24-27: AREA 1
Description
Byte Signal name
Input range Min. unit
24
25 Basic parameter
AREA 1 0.01mm
26 "Stroke (-)" - "Stroke (+)"(∗1) (∗2)
27
∗1 The actuator model determines the available input values. Refer to the operation manual of the
actuator for details.
∗2 Please refer to 21. Handling of sent/received data (P.84) for handling of the data.

- 39 -
●Byte28-31: AREA 2
Description
Byte Signal name
Input range Min. unit
28
29 Basic parameter
AREA 2 0.01mm
30 "Stroke (-)" - "Stroke (+)"(∗1) (∗2)
31
●Byte32-35: In-Position
Description
Byte Signal name
Input range Min. unit
32
33
In-Position (∗1) (∗2) 0.01mm
34
35
∗1 The actuator model determines the limit for the input values. Please refer to the manual of the
actuator for more details.
∗2 Please refer to 21. Handling of sent/received data (P.84) for handling of the data.

(5) Record data (request sent from PROFINET master to JXCP1 controller)
A record request is used to update the Step No items stored in the JXCP1 controller.

●Record data object


SUB Record Data
SLOT Index Details
SLOT Length (BYTE)
5 32 bytes Step data No.0 ∗3
6 32 bytes Step data No.1 ∗3
2 1

68 32 bytes Step data No.63 ∗3


∗3 Refer to Details of Record Data Index for details of each index.

●Details of Record Data Index ∗5 ∗6


Offset
Size Setting items: Set range Min. unit
(Byte)
0-1. WORD Movement mode 1:ABS (Absolute) 2:INC (Relative) ∗4 -
2-3. WORD Speed 1 to “Max speed” of the basic parameter 1mm/s
Basic parameter
4-7. DWORD Position "Stroke(-)" - "Stroke (+)" 0.01mm
8-9. WORD Acceleration 1 to “Max ACC” of the basic parameter 1mm/s2
10-11. WORD Deceleration 1 to “Max DEC” of the basic parameter 1mm/s2
12-13. WORD Pushing force ∗5 ∗6 1%
14-15. WORD ( Trigger LV ∗5 ∗6 1%
16-17. WORD Pushing speed ∗5 ∗6 1mm/s
18-19. WORD Moving force ∗5 ∗6 1%
Basic parameter
20-23. DWORD Area1 "Stroke(-)" - "Stroke (+)" 0.01mm
Basic parameter
24-27. DWORD Area2 "Stroke(-)" - "Stroke (+)" 0.01mm
"In-Position" Basic parameter
28-31. DWORD "Stroke(-)" - "Stroke (+)" 0.01mm
tolerance range
∗4 Do not input numbers other than [1(ABS)] and [2(INC)].
∗5 The actuator model determines the available input values. Refer to the operation manual of the
actuator for details.
∗6 Please refer to 20. Handling of sent/received data (P.84) for handling of the data.
- 40 -
10. Settings and Data Entry
In order to move the actuator to a specific position, it is necessary to setup the patterns of operations
with a PC (with the controller setting software) or the teaching box or record data. This setup data input
by the software or teaching box will be recorded in the memory of the controller.

For the controller setting software and the teaching box, there are two available modes (the Easy mode
and the Normal mode).
You can select the appropriate one depending on the operation.

•Easy mode
In Easy mode, you can start up the actuator by entering only a limited number of settings with the
controller setting software and the teaching box.
The combination of settings you need to set up will change depending on the type of actuator.
(A combination of data can be selected.)

•Normal mode
In Normal mode, you can make a further detailed setup (conditions for actuator and controller, etc.)
than the Easy mode.
You can change three kinds of setting data, "Step data", "Basic parameter" and "Return to origin
parameter" in this mode.

10.1 Step Data


A "step data" is the setting data mainly describing the movement of the actuator. Total 64 step data (12
attributes per step) can be handled with this controller. Each step data will become effective as soon as it
is recorded into the controller.

E.g.) Step data on the PC (controller setting software) screen [Normal mode]

Pushing Pushing Moving


Movement Speed Position Acceleration Deceleration Trigger LV Area 1 Area 2 In pos
No. 2 mm/s
2 force speed force
mode mm/s (mm) mm/s % (mm) (mm) (mm)
% mm/s %

0 Absolute 100 20.00 1000 1000 0 0 0 100 18.00 22.50 0.5


1 Absolute 50 10.00 1000 1000 70 60 5 100 6.0 12.0 1.5
┆ ┆ ┆ ┆ ┆ ┆ ┆ ┆ ┆ ┆ ┆ ┆ ┆
63 Absolute 20 5.00 500 500 0 0 0 100 3.0 8.0 1.2

- 41 -
Step Data details
Description
Controller Teaching Range Explanation
setting box
software (TB)
No. Step No. 0 to 63 Number of the step data.
Specifies the co-ordinate system for the target position.
Software TB PLC Details
3 types
Blank Disable 0 The step data is ineffective.
Movement Movement (Refer to the
mode mode The target position will be defined in
table on the Absolute Absolute 1
relation to the absolute origin point.
right)
The target position will be defined
Relative Relative 2
relative to the current position.

Speed Speed ∗1 The speed to move to the target position. (Unit: mm/s)

Basic parameter
Position Position "Stroke (-)" - The target position (unit: mm)
"Stroke (+)"
1 ~ Basic
parameters
"Maximum
Acceleration Acceleration Sets the acceleration to reach to travel speed. (Unit: mm/s2)
acceleration/
deceleration
speed"
1 ~ Basic
parameters
"Maximum
Deceleration Deceleration Sets the deceleration from travel speed to stop. (Unit: mm/s2)
acceleration/
deceleration
speed"

The setting to define the pushing operation or the positioning


operation.
For the positioning operation, the value specifies the force as a
percentage of the maximum force (Unit: %).
∗ The maximum force depends on the actuator. Please refer to the
manual and the rated force of the actuator.
Movement
Pushing Pushing Value Details
force force ∗1 mode

Positioning The actuator moves to the position


0
operation specified in the "Position".
The actuator moves to the position
Pushing specified in the "Position" and then,
1 to 100
operation performs a pushing action with a force
not more than the set force.

■Effective only for the pushing operation


(when the value for the "Pushing force" is from 1 to 100).
This is the setting to define the conditions where the INP output will
be turned ON. When the actuator generates a force over this value,
Trigger LV Trigger LV ∗1
INP will be turned ON.
This parameter is set to the value of the pushing force or lower.
(Unit: %)
For the positioning operation, this value is ignored.

- 42 -
■Effective only for the pushing operation
(when the value for the "Pushing force" is from 1 to 100).
This defines the movement speed during the pushing operation. If
this Speed is too high, it may cause damage to the actuator or work
Pushing Pushing
∗1 piece due to impacts. Therefore, enter a value within the range
speed speed
appropriate for the actuator. (Unit: mm/s)
Please refer to the actuator manual for the appropriate range of the
speed.
For the positioning operation, this value is ignored.

The setting to define the maximum torque during the positioning


operation. (Unit: %)
Moving Moving Enter a value within the range appropriate for the actuator.
∗1
force force (Unit: mm/s)
Please refer to the actuator manual for the appropriate range of the
speed.

Basic parameter The setting to define the conditions where the AREA output will be
Area 1 AREA 1 "Stroke (-)" - turned ON (Unit: mm)
"Stroke (+)" If the current position is within the range between the Area1 and
Area2, the AREA output will be turned ON.
Basic parameter ∗ If Area1 >Area2, the alarm "Step Data ALM1" will be activated.
Area 2 AREA 2 "Stroke (-)" - (However, no alarm is generated if "Area1"= "Area2"= 0, the AREA
"Stroke (+)" output will be turned OFF)

The functions of this will be different between the pushing operation


and the positioning operation.
∗ Positioning operation: Positioning range (Unit: mm)
∗ Pushing operation: Pushing distance (Unit: mm)
Movement
Details
mode
This is the setting to define the conditions where
the INP output will be turned ON.
When the actuator enters within this range from
the target position, the INP will be turned ON.
(It is unnecessary to change this from the initial
Positioning value.)
In position In position ∗1
operation If it is required to get a signal before the actuator
completes the positioning operation, this value
should be larger.
∗ The INP output will be turned ON.
Target position - in position ≤ actuator position
≤ target position + in position
This is the setting to define the distance pushed by
the actuator during the pushing operation. When
Pushing the actuator pushed exceeding this distance, the
operation pushing operation will end. In case of such stop
exceeding the pushing distance, the INP will not be
turned ON.

∗1 The range varies depending on the actuator. Please refer to the manual of the actuator for more
details.

- 43 -
10.2 Basic parameters
The "Basic parameter" is the data to define the operating conditions of the controller, conditions of the
actuator, etc.

Details of basic parameters


Activation: "■" = Effective as soon as it is recorded into the controller
"○" = Become effective after restarting the controller
"-" = The parameter cannot be changed (fixed value)
Description
Controller Range Explanation Write
Teaching
configuration
box
software
Identification number (axis) parameters of serial
Controller ID Controller ID 1 to 32 ○
communications are set.
This is the fixed value for this controller.
IO pattern IO pattern Fixed value (∗ Do not change the setting) -
The value for this should be 64 (Standard).
Acceleration/ Acceleration/ This is the fixed value for this controller.
deceleration deceleration Fixed value (∗ Do not change the setting) -
pattern pattern This defines the trapezoidal acceleration/deceleration parameter.
S-motion S-motion This is the fixed value for this controller.
Fixed value -
rate rate (∗ Do not change the setting)
This defines the positive (+) side limit of the position. (Unit:
mm)
Stroke (+) Stroke (+) ∗1 ■
Any value greater than the [stroke(+)] value cannot be entered in
the "Position" field data of step parameter setup.
This defines the positive (+) side limit of the position. (Unit:
mm)
Stroke (-) Stroke (-) ∗1 ■
Any value less than the [stroke(-)] value cannot be entered in the
"Position" field data of step parameter setup.
This defines the maximum limit of the speed. (Unit: mm/s)
Maximum Maximum
∗1 Any value greater than the [Max speed] value cannot be entered ■
velocity velocity
in the "Speed" field data of step parameter setup.
Maximum Maximum This defines the maximum limit of the ACC/DEC. (Unit:
Acceleration/ Acceleration/ mm/s2)
∗1 ■
Deceleration Deceleration Any value greater than the [Max ACC/DEC] value cannot be
speed speed entered in the "Accel" field data of step parameter setup.
This defines the range to activate the INP output when the
Default In Default In
∗1 actuator is within it after the return to origin operation. (Unit: ■
position positioning
mm)

- 44 -
This defines the position of the actuator after the return to
origin operation. (Unit: mm)
■The ORIG offset is 0 (mm). In the examples on the
left, the actuator positions
M Actuator
are not different but the
The position is identified by the controller after reference point that the
the return to the origin operation (0mm). controller recognizes will
■The ORIG offset is 100 (mm). be changed after the
ORIG offset ORIG offset ∗1 return to origin operation. ■
M Actuator
The position is identified by the controller after
the return to the origin operation (100mm).

Caution
If the value for the "ORIG offset" is changed, the "Stroke
(+)" and "Stroke (-)" of the basic parameters should be
checked.
Maximum Maximum
∗1 The maximum force for the pushing operation. (Unit %) ■
pushing force pushing force
Sets the range in which parameter and step data can be
changed.
1. Basic parameter + Step data (Basic parameter + Return to
Para protect Para protect 1 to 2 ■
origin parameter + Step data)
2. Basic parameter (Basic parameter + Return to origin
parameter)
This defines the status of the Enable switch of the teaching
box.
Enable SW Enable SW 1 to 2 ■
1. Enabled
2. Disabled
Indication of actuator type compatible with the controller.
Unit name Unit name Fixed value -
(Do not change the setting)
This is the setting to define the conditions where the WAREA
Basic parameter will be turned ON. [Unit: mm]
W-AREA1 W-AREA1 "Stroke (-)" - If the current position is within the range between the W area ■
"Stroke (+)" end 1 and W area end 2, the WAREA output will be turned
ON.
∗ If W area output end 1 >W area output end 2, the alarm
Basic parameter
"Parameter ALM" will be activated. However no alarm is
W-AREA2 W-AREA2 "Stroke (-)" - ■
generated if W area end 1= W area end 2 = 0, the WAREA
"Stroke (+)"
output will be turned OFF
ORG This is the fixed value for this controller.
Link Offset Fixed value -
Correct (∗ Do not change the setting)
This is the fixed value for this controller.
Sensor type Sensor type Fixed value -
(∗ Do not change the setting)
This is the fixed value for this controller.
Option 1 Option 1 Fixed value ○
(∗ Do not change the setting)
Undefine Undefine This is the fixed value for this controller.
Fixed value ○
No. 11 No. 11 (∗ Do not change the setting)
Undefine Undefine This is the fixed value for this controller.
Fixed value -
No. 12 No. 12 (∗ Do not change the setting)
∗1 The range varies depending on the actuator. Please refer to the manual of the actuator for more
details.

- 45 -
10.3 Return to origin parameter
The "Return to origin parameter" is the setting data for the return to origin operation.

Details of Return to origin parameter


Activation: "■" = Effective as soon as it is recorded into the controller
"O" = Become effective after restarting the controller
"-" = The parameter cannot be changed (fixed value)
Description
Controller Range Explanation Write
Teaching
configuration
box
software
Sets the direction of return to origin operation.
ORIG ORIG
1 to 2 1. CW ○
direction direction
2. CCW
The setting for the return to origin operation.
Return to
ORIG mode 1 to 2 1. Pushing origin operation [Stop] ■
origin mode
2. Limit switch origin [Sensor]
ORIG limit ORIG limit ∗1 A pushing force level at which to set the origin. ■
This is the fixed value for this controller.
ORIG time ORIG time Fixed value -
(∗ Do not change the setting)
ORIG ORIG
∗1 The allowable speed to move to origin. ■
speed speed
ORIG
ORIG ACC ∗1 The acceleration and deceleration during finding origin. ■
ACC/DEC
Creep Creep This is the fixed value for this controller.
Fixed value -
speed speed (∗ Do not change the setting)
The setting for ORIG sensor.
ORIG ORIG 0. The origin sensor is not effective. [Disable]
0 to 2 ■
sensor sensor 1. The origin sensor is N.O type. [N.O].
2. The origin sensor is N.C type. [N.C.]

Did not
detect
Origin
sensor This is the fixed value for this controller.
switch Fixed value -
when (∗ Do not change the setting)
direction
returning to
ORIG.

Undefine Undefine This is the fixed value for this controller.


Fixed value -
No. 21 No. 21 (∗ Do not change the setting)

∗1 The range varies depending on the actuator. Please refer to the manual of the actuator for more
details.

- 46 -
11. Operations
11.1 Return to Origin
After entering the setting data, it is necessary to perform a return to origin operation (to establish the
origin point) before starting the positioning or pushing operation. (To ensure the position of origin)

■Return to origin
The actuator moves in the return to origin direction (∗ this direction is dependent on the actuator) from
the initial position at the moment of power-on: Refer to (1) in the figure below.
When the actuator reaches the end of travel limit it pauses for a short time. The controller recognizes the
position as the end of travel limit of the actuator. Then, the actuator moves at a low speed in the direction
opposite to the return to origin direction: Refer to (2) in the figure below.
The position after the travel becomes the origin.

Return to Origin position command → Travels in the set Origin position direction →
Stops traveling → Reverse travel → Sets the Origin position

E.g.) Return to Origin position reference example


Basic parameter
Load "Def in position"

Actuator

Motor M
(2)
Actuator end Origin position Initial position
(1)

Caution
This direction is dependent on the actuator.

11.2 Positioning Operation


Step data "Pushing force" is set to 0.
The actuator moves to the target position specified by the step data "Position".

•Positioning Operation (E.g.) •Positioning operation [Speed/Position] (E.g.)


Step Data
"Positioning range"
Load "Positioning range"
Actuator
Speed
Step Data
"Speed"

M
Position

Motor Target
Origin position Target position position
→ Step Data "Position"

- 47 -
11.3 Pushing Operation
The pushing operation is active when the value of the "Pushing F%" in the Step data is set to "1" or more.
Similar to the positioning operation, the actuator moves according to the settings of "Position" and
"Speed" in the step data and then, when it reaches the target position, it starts the pushing process.
The actuator pushes the load with a force no more than the maximum force set in the "Pushing force" of
the step data.

(1) Pushing operation is successfully performed.


During the pushing operation, if the pushing force is kept higher than the value specified by "Trigger
LV" of the step data for a certain time, the INP output will be turned ON. Even after the completion of
the pushing operation, the actuator keeps generating the force set in the step data.
•Pushing operation example •Pushing operation (Speed/Position)
Step Data
"Positioning range"

Pushing
Step Data process
Load "Pushing speed" Pushing
Speed
Actuator force
Step Data
"Speed"

M
Position
Position of
Pushing operation
Motor pushing start
In position
Origin position Position of pushing start
→ Step Data "Position"

(2) Pushing operation fails (empty pushing).


If the pushing process is not completed even after the actuator runs over the range specified in
the step data from the target position (the starting point of the pushing process), the operation will
be completed. In this case, the INP output will be turned OFF.
Pushing
Speed process

Position

Position of pushing start


In position

(3) Movement of the workpiece after the completion of the pushing process
[1] The workpiece moves in the pushing direction.
After completion of the pushing operation, if the reaction force from the workpiece becomes
smaller, the actuator may move with a force smaller than that specified in the "Trigger LV" of the
step data.
In this case, the INP output will be turned OFF and the actuator moves within the positioning
range according to the balance of the force.
If the pushing force is kept higher than the value specified by "Trigger LV" of the step data for a
certain time again, the INP output will be reactivated.
Pushing
Speed process

Position
Position of pushing start

- 48In- position
[2] Movement of the workpiece in the direction opposite to the pushing direction (The actuator is
pushed back since the reaction force from the workpiece is too large.)
After completion of the pushing operation, if the reaction force from the workpiece becomes
larger, the actuator may be pushed back. In this case, while the INP output is kept ON, the
actuator will be pushed back to the point where the reaction force and the actuator pushing
force are balanced (pushed back toward the target position).
If the actuator is pushed back over the target position, the alarm (ORIG ALM) will be activated.

Reaction
Speed
force

Position
Position of pushing start

In position

11.4 Controller signal response time


The controller signal response delay include the following factors.
(1) Controller signal scan delay
(2) Delay due to signal analysis
(3) Delay of command analysis
Set the time more than twice the communication cycle time for the interval between the signals, when
the signals are continuously input, as PLC processing delays and controller scanning delays can occur.

11.5 Methods of interrupting operation


There are 3 methods of interrupting operation and stopping the actuator during positioning operation and
pushing operation, as shown below. The state after the interruption is different, therefore use the method
appropriate to the application.

•Stopping by EMG signal


If the EMG signal is turned OFF during operation, after the actuator decelerates and stops, the servo will
turn OFF so the stopped position is not held.
(For an actuator with lock, it is held by the lock function.)

•Stopping by RESET signal


If the RESET signal is turned ON during operation, after the actuator decelerates and stops, the
stopped position is held.
(The servo does not turn OFF.)

•Stopped by HOLD signal


The actuator decelerates to stop when HOLD signal is ON during operation.
(The servo does not turn OFF.)

Caution
If instructed to stop by EMG signal and RESET signal, all OUT signals will turn OFF.

- 49 -
12. Operation Examples
12.1 Positioning Operation
E.g.) Move an actuator from the origin to 100mm point at 50mm/s. (Step No.1 instruction)
Next, move the actuator from the 50mm point to 100mm point by moving it 5 times continuously,
10mm at a time, at a speed of 50mm/s. (Step No. 2)

■[Normal mode] Step data (e.g.)


Threshold Pushing
Pushing Moving
Movement Speed Position Acceleration Deceleration Force speed Area 1 Area 2 In pos
No. 2 2 force force
mode mm/s (mm) mm/s mm/s Value Speed (mm) (mm) (mm)
% %
% mm/s

0 - - - - - - - - - - - -
1 Absolute 100 50.00 1000 1000 0 0 0 100 0 0 0, 1
2 Relative 50 10.00 1000 1000 0 0 0 100 0 0 0, 1

Flow chart (E.g.)


Controller
(1) Select/input Step No.1. (Turn on "IN0")
Signal name Category ↓
(2), (5), (10), (13) (2) Turn ON "DRIVE" input.
DRIVE ↓
(1) Start moving to the position of Step No.1.
IN0 Input ↓
(9) (3) "INP" output turns OFF.
PLC

IN1 ↓
(7) (4) "BUSY" output turns ON.
OUT0 ↓
(15) (5) The "DRIVE" input turns OFF.
OUT1 ↓
(14), (11), (6), (3) Output (6) Step No.1 output turns ON. ("OUT1" output turns ON)
INP ↓
(16), (12), (8), (4) (7) "INP" output turns ON.
BUSY ↓
(8) "BUSY" output turns OFF.

The move to the position set in Step Data No.1
is completed.

Operation (E.g.) (9) Select/input Step No.2. Turn the "IN0" input OFF,
and the "IN1" input ON.

Load Actuator (10) Turn the "DRIVE" input ON.

Motor
Start moving to 10mm away from the current position.
--- ↓
(11) "INP" output turns OFF.
M ↓
(12) "BUSY" output turns ON.
5 times ↓
・・・ (13) The "DRIVE" input turns OFF.

0mm 50mm 60mm 100mm (14) Step No.2 output turns ON. ("OUT1" output turns ON)
Origin position End position ↓
(15) "INP" output turns ON.

(16) "BUSY" output turns OFF.

Completed to move to 10mm away.

- 50 -
12.2 Pushing Operation
E.g.) Move an actuator from the origin to 100mm point at 100mm/s. (Step Data No.1 is used for this
operation.)
From the 100mm point, the actuator starts the pushing operation of 10mm/s speed and 50% or less
force.
(the pushing distance is up to 5mm).
Then, the actuator moves from the position where the pushing operation was completed (where INP
was turned ON) to the 50mm point with 50mm/s.
(Step Data No.2 is used for this operation.)

■[Normal mode] Step data example


Threshold
Pushing Pushing Moving
Movement Speed Position Acceleration Deceleration Force Area 1 Area 2 In pos
No. 2 2 force speed force
mode mm/s (mm) mm/s mm/s Value (mm) (mm) (mm)
% mm/s %

0 - - - - - - - - - - - -
1 Absolute 100 100.00 1000 1000 50 40 10 100 0 0 5
2 Absolute 50 50.00 1000 1000 0 0 0 100 0 0 0, 1

Flow chart (E.g.)


Controller
(1) Select/input Step No.1. (Turn on "IN0")
Signal name Category

(2), (5), (10), (13) (2) Turn ON "DRIVE" input.
DRIVE ↓
(1) Start moving to the position of Step No.1.
IN0 Input ↓
(9) (3) "INP" output turns OFF.
PLC

IN1 ↓
(7) (4) "BUSY" output turns ON.
OUT0 ↓
(15) (5) The "DRIVE" input turns OFF.
OUT1 ↓
(14), (11), (6), (3) Output (6) Step No.1 output turns ON. ("OUT1" output turns ON)
INP ↓
(16), (12), (8), (4) Move at low speed after passing the "Position"
BUSY of the Step No.1.

Push the workpiece with the specified pushing force.
Step No.1 Pushing operation (E.g.) ↓
(7) "INP" output turns ON.
Load ↓
Actuator
Motor
(8) "BUSY" output turns OFF.

The move to the position set in Step No.1 is completed.

M (9) Select/input Step No.2. (Turn the "IN0" input OFF,
Pushing operation and the "IN1" input ON.)
with pushing force ↓
0mm 100mm (10) Turn ON "DRIVE" input.

Origin position
Start moving to the position of Step No.2.

(11) "INP" output turns OFF.
Step No. 2 positioning operation (E.g.) ↓
(12) "BUSY" output turns ON.
Load Actuator ↓
Motor (13) The "DRIVE" input turns OFF.

(14) Step No.1 output turns ON. ("OUT1" output turns ON)

M (15) "INP" output turns ON.

(16) "BUSY" output turns OFF.
50mm ↓
End position Pushing completed
The move to the position set in Step No. 2 is completed.
position
- 51 -
13. Operation Instructions
13.1 Overview of the Operation Instructions
Shows operation instruction method of each function shown in 8. Operation methods (P.29).

13.2 Operation procedure for Operation by Step No.


Refer to the following "Procedures" and "Timing charts" for details of the Return to Origin, operation
mode procedures and the signal timing. Refer to 9.1 Memory allocation (P.30) for the memory
allocation of signals.

[1] Power on and Return to Origin position


- Procedure - - Timing chart -
(1) Turn the power supply ON. Timing chart/Return to origin
(2) Turn ON the "SVON".
Power supply 24V
0V
(3) "SVRE" turns ON.
∗ The time [SVRE] turns ON is SVON
ON
dependent on the type of Input OFF
actuator and the customer signal .
usage. SETUP .
∗ The actuator with lock is
BUSY ON
unlocked. OFF

(4) Turn ON the "SETUP". SVRE .


Output .
signal .
(5) "BUSY" turns ON. SETON
(The actuator starts the .
operation.) INP .
After "BUSY" turns ON, "SETUP" .
turn OFF.

(6) "SETON", "INP" turn ON. Unlock


External lock
Return to origin is completed
Held
when "INP" turns ON.
Speed 0mm/s

Return to origin

INP signal is ON when the current


position is within the step data position
range. Otherwise, the signal is OFF

- 52 -
[2] Positioning operation
- Procedure - - Timing chart -
(1) Input step data No. (IN0 to IN5)
Input Step Data No. Read Step data No.
(2) Turn ON the "DRIVE".
( All OUT signal and INP signals 24V
Power supply
being output are not care.) 0V
Scan the specified step data ON
number (from "IN0" to "IN5"). IN0 to 5
OFF
-
(3) "BUSY" turns ON. Input SVON -
signal
(and the positioning movement More than twice -
starts.) the communication Output Step
cycle time Data No.
∗ After "BUSY" turns ON, if DRIVE -
"DRIVE" is turned OFF, the
step data number will be OUT0 to 5 ON
output (from "OUT0" to OFF
"OUT5"). Don’t care
BUSY -
-
(4) When "INP" turns ON and -
"BUSY" turns OFF, the Output SVRE
signal -
positioning operation will be -
completed. SETON -
-
INP -

External lock Unlock


Held

0mm/s
Speed Positioning
operation

If the current position is inside of step


data positioning, the INP signal is ON.
Otherwise, the signal is OFF

- 53 -
[3] Pushing Operation
- Procedure - - Timing chart -
Input Step Data Read Step data
(1) Input of step data No. (IN0 to IN5) No. No.

24V
(2) Turn ON the "DRIVE". Power supply 0V
("INP" turns OFF.)
→Scan the step data number ON
IN0 to 5
OFF
(from "IN0" to "IN5").
Input -
SVON More than twice
the communication -
(3) "BUSY" is ON when pushing signal cycle time Output Step
Data No. -
starts. DRIVE -
∗ After "BUSY" turns ON, if
"DRIVE" is turned OFF, the ON
OUT0 to 5 OFF
step data number will be
output (from "OUT0" to Don’t care -
BUSY -
"OUT5"). -
Output -
4) When "INP" turns ON and SVRE
signal -
"BUSY" turns OFF, the pushing -
operation will be completed SETON -
(the actuator generates the -
force larger than that specified INP --
in "TriggerLV" of the step data). Unlock
External lock
Held
-

Speed 0mm/s
Pushing
operation

INP signal turns ON when pushing


force exceeds the "Trigger LV" value of
[4] HOLD step data.
- Procedure - - Timing chart -
(1) During operation ("BUSY" is ON), Input ON
turn ON "HOLD". signal HOLD OFF
Output ON
(2) "BUSY" turns OFF. signal BUSY OFF
Deceleration
(The actuator stops.) Start point

(3) Turn OFF "HOLD". Speed 0mm/s

HOLD during operation


(4) "BUSY" turns ON.
(The actuator restarts.)

- 54 -
[5] Reset
-Procedure- [Driving reset] - Timing chart - Reset
(1) During operation ("BUSY" is ON), Input ON
turn ON "RESET". signal RESET
OFF

OUT0 to 5 ON
(2) The actuator stops after BUSY output OFF
and “OUT0” to “OUT5” turn OFF. Output
BUSY ON
signal OFF
INP ON
OFF

Deceleration
Start point 0mm/s
Speed
∗ INP is ON when stop position is within the positioning range.

-Procedure- [Alarm Reset]


(1) Alarm generated
ALARM output turns ON. - Timing chart - Alarm Reset
Alarm group is output to OUT0 to OUT3.
Alarm code is output. Input ON
For memory to be checked and detailed, signal RESET
OFF
Please refer to 9. Memory map (P.30) ON
OUT0 to 3
15.1 Alarm group signals (P.62) Output OFF
15.3 Alarms and countermeasures (P.64) signal
ON
ALARM Alarm generated OFF
(2) Turn ON "RESET".

(3) "ALARM" turns OFF, OUT0 to


OUT3 turn OFF. (The alarm is
deactivated.)

[6] Stop
- Procedure - - Timing chart -
(1) During operation ("BUSY" is ON), 24V
Power supply 0V
turn OFF "EMG". (Stop command)
ON
EMG OFF
(2) "ESTOP" turns ON.
Input ON
signal SVON OFF
(3) "BUSY" turns OFF. (The actuator stops.)
ON
“SVRE” turns OFF. BUSY
OFF
∗ The actuator with lock is locked. -
SVRE
-
(4) Turn ON "EMG".(The stop release -
SETON -
command) Output
signal -
INP -
(5) "ESTOP" turns OFF. -
"SVRE" turns ON. ALARM -
∗ The actuator with lock is unlocked. -
ESTOP -

Unlock
Condition of external lock Held
Deceleration
Start point If the now position is inside of step
data positioning, the INP signal is
ON.
Speed Otherwise OFF.

0mm/s
Emergency stop during operation

∗ When "EMG" is OFF, the stop is activated.

- 55 -
[7] Area output
- Procedure - Timing chart
●Step data No.1 operation The initial position: 50mm
(1) Input step data No. (IN0 to IN5)
Operation of Step Data No.1: Position: 200mm AREA1 to AREA 2: 150 to 250mm
(2) Turn ON the "DRIVE". Operation of Step Data No.2: Position: 100mm AREA 1 to AREA 2: 130 to 170mm
→ Receive the step data no.1 IN0 to 5
ON

(from the input IN0 to IN5). Input More than twice


OFF
signal the communication -
DRIVE cycle time
(3) "BUSY" turns ON. -
(The actuator starts the OUT0 to 5
ON
OFF
operation.) -
BUSY Don’t care
"INP" turns OFF. Output Don’t care -
∗ After "BUSY" turns OFF, if signal
INP -
the "DRIVE" is turned OFF, -
AREA -
the step data No.1 ("OUT0"
-
to "OUT5") will be output. -
Speed 0mm/s
50mm 150mm 200mm 100mm
(4) "AREA" of step data No.1 turns 170mm 130mm
ON. (at 150mm from the origin If the current position is within the In Operation of Operation of
point) position range, the INP signal is ON.
Otherwise, the signal is OFF
Step Data No.1 Step Data No.2
If the current position is inside of 1, and 2
area scope for step data., the AREA signal

(5) "BUSY" turns OFF. is ON. Otherwise, the signal is OFF

(The actuator stops.)


"INP" turns ON.

●Step data No.2 operation


(6) Input of step data No. ("IN0" to "IN5")

(7) Turn ON the "DRIVE".


→ Read step data No. 2 ("IN0" to "IN5")

(8) "AREA" turns OFF.


The "BUSY" turns ON. (The actuator starts the operation.)
"INP" is turned OFF.
∗ After "BUSY" turns OFF, if the "DRIVE" turns OFF, the step data No.2 ("OUT0" to "OUT5") will be
output.

(9) "AREA" of step data No.2 turns ON. (at 170mm from the origin point)

(10) "AREA" of step data No.2 turns OFF. (at 130mm from the origin point)

(11) "BUSY" output turns OFF. (The actuator stops.)


"INP" turns ON.

- 56 -
13.3 Operation procedure for Operation by numerical instruction
E.g.) Input 50.00 [mm] to the position parameter of the specified step data and start the actuator.For parameters other
than position which are numerically specified (speed, acceleration/deceleration), values set to the specified step data
are used.
Before starting the operation by numerical instruction, make sure that the servo is on and returning to origin has
completed.

(1) Confirm that Byte4,Bit0: Timing chart/numerically instructed operation


Start flag = OFF
24V
Input OFF when Byte4,Bit0: Power supply
Start flag = ON.
0V
(2) ON
IN0 to 5
(2) Input the step data No. to be specified OFF
by Byte0:IN0 to 5(bit0 to 5) -
SVON -
Byte0,Bit0:IN0=ON
-
Byte0,bit1-5:IN1-5= OFF -
DRIVE (DRIVE signal is not used)
Input
OFF
(3) Byte2,Bit4-7,Byte3,bit0-7: With a (1) (5)
signal
numerical input flag, input ON to Start flag More than twice
the parameter bit which is the communication -
(3) cycle time
numerically instructed by specified -
Numerical data input flag -
step data. -
(4)
Input OFF to the parameter bit which
is not numerically instructed. Data (position)
E.g.) Only [position] of the numerical
data input flag is specified by BUSY ON
OFF
number. -
→Byte2,Bit6=ON、 Output -
SVRE
Byte2,Bit4-5=OFF signal -
Byte3,Bit0-7=OFF ON
SETON -
(7)
(4) Byte5,Bit0-1: Input operation -
method and numerical parameter INP -
data for Byte6-35. -
E.g.) Input [Position] 50.00 [mm]. Held
External lock
5000[0.01mm]=(00001388)h Unlock
→Byte8: Position (HH)= (00) h
Byte9: Position (HL)= (00) h
Byte10: Position (LH)= (13) h Speed
Byte11: Position (LL)= (88) h
0mm/s
(5) Input the numerical data input
flag bit and numerically specified
parameter data, and then, input
Word2, bit0: Start flag=ON.
Operation instruction data will be transmitted with the start flag ON.

(6) During the actuator operation, Word0: BUSY=ON is output.

(7) When the actuator reached the target position, Word0: INP=ON is output.
(Refer to "INP" section (P.32) for signal ON conditions)
When the actuator operation completes, Word0: BUSY=OFF is output.
The completion of the specified operation is validated when both Word0: INP=ON and
Word0: BUSY=OFF are established at the same time.

- 57 -
14. Options
14.1 Actuator cable [5m or shorter]
LE-CP- □ - □ (1) (2)
Signal name Terminal number Cable color Terminal number
A B-1 Brown 2
Cable length (L) A A-1 Red 1
B B-2 Orange 6
1 1.5m B A-2 Yellow 5
COM-A/COM B-3 Green 3
3 3m
COM-B/ - A-3 Blue 4
5 5m (3)
Shield Cable color Terminal number
Vcc B-4 Brown 12
Actuator cable type GND A-4 Black 13
A B-5 Red 7
Nil Robotic type cable A A-5 Black 6
S Standard cable B B-6 Orange 9
B A-6 Black 8
- 3

Actuator side Controller side


(14.2)
(ø8) 1 (2) 2
A1 (1) B1

(14)
(17.7)

5 6
1 (3) 2

(18)
A6 B6

15 16
(30.7) L (11)

14.2 Actuator cable [8 to 20m]


(1) (2)
LE-CP- □ Signal name Terminal number Cable color Terminal number
A B-1 Brown 2
Cable length (L) A A-1 Red 1
B B-2 Orange 6
8 8m ∗ B A-2 Yellow 5
COM-A/COM B-3 Green 3
A 10m ∗
COM-B/ - A-3 Blue 4
B 15m ∗ (3)
Shield Cable color Terminal number
C 20m ∗ Vcc B-4 Brown 12
Produced upon receipt of order GND A-4 Black 13
A B-5 Red 7
∗ Only "Robotic type cable" can
A A-5 Black 6
be selected. B B-6 Orange 9
B A-6 Black 8
- 3

Controller side
Actuator side
(14.2)
1 (2) 2
(ø5.5)
(14)

A1 (1) B1
5 6
(17.7)

1 (3) 2
A6 B6
(18)

(ø6.3)
15 16
(30.7) L (11)

- 58 -
14.3 Actuator cable for with lock [5m or less]
(1) (2)
LE-CP- □ - B- □ Signal name Terminal No. Cable color Terminal No.
A B-1 Brown 2
A A-1 Red 1
Cable length (L) B B-2 Orange 6
B A-2 Yellow 5
1 1.5m
COM-A/COM B-3 Green 3
3 3m COM-B/ - A-3 Blue 4

5 5m (3)
Shield Cable color Terminal No.
Vcc B-4 Brown 12
GND A-4 Black 13
A B-5 Red 7
Actuator cable type A A-5 Black 6∗
B B-6 Orange 9
Nil Robotic type cable B A-6 Black 8
S Standard cable (4) - 3
Signal name Terminal No.
Lock (+) B-1 Red 4
Lock (-) A-1 Black 5
Sensor (+) B-3 Brown 1
Sensor (-) A-3 Blue 2
Actuator side Controller side
(1) B1 (ø8)
A1 (14.2) (2)
1 2
(10.2) (17.7)

(14)
6
A6
A1
B6 5
1
(3) 2
B1

(18)
A3 B3
(4) (ø5.7)
15 16
(30.7) L (11)
14.4 Actuator cable for with lock [8 to 20m]
(1) (2)
LE-CP- □ - B Signal name Terminal No. Cable color Terminal No.
A B-1 Brown 2
A A-1 Red 1
Cable length (L) B B-2 Orange 6
B A-2 Yellow 5
8 8m ∗ COM-A/COM B-3 Green 3
A 10m ∗ COM-B/ - A-3 Blue 4
(3)
B 15m ∗ Shield Cable color Terminal No.
Vcc B-4 Brown 12
C 20m ∗
GND A-4 Black 13
∗ Produced upon receipt of order
A B-5 Red 7
∗Only "Robotic type cable" can be selected. A A-5 Black 6
B B-6 Orange 9
B A-6 Black 8
(4) - 3
Signal name Terminal No.
Lock (+) B-1 Red 4
Lock (-) A-1 Black 5
Sensor (+) B-3 Brown 1
Sensor (-) A-3 Blue 2
Actuator side Controller side
1 2
(ø5.5)
(14)

(1) B1 (ø6.3)
A1
6
5 (2)
(10.2) (17.7)

(14.2)
A6 B6 (3)
A1 B1 1 2
(18)

///////
A3 B3

15 16
- 59 -
14.5 Controller Set up kit
/

LEC – W2
Controller set up kit

Contents
(1) Controller set up software (CD-ROM)
(2) Communication cable
(3) Conversion unit
(4) USB cable

Operating environment
PC/AT converter with WindowsXP, Windows7 or Windows 8 with USB1.1 or USB2.0 port.
∗ Windows, WindowsXP, and Windows7 are registered trademarks of Microsoft Corporation.

/Caution
The latest version of the controller setting software must be used.
Upgrade software can be downloaded from SMC website. http://www.smcworld.com/

14.6 Conversion Cable

/P5062-5(Cable length: 0.3m)

/14.7 Power Supply Plug


/ Power Supply Plug
JXC-CPW Terminal Function Functional explanation
/ M24V terminal/C24V terminal/
Common power
0V EMG terminal /LK RLS
/ (-)
terminal Common (-)
Controller motor power (+)
M24V Motor power (+)
side
Control power Controller motor power (+)
C24V
supply (+) side
Connection terminal of
EMG Stop (+)
external stop circuit
Lock release switch
LK RLS Unlocking (+)
connection terminal

- 60 -
14.8 Teaching box

LEC- T1 - 3 □ G □
Teaching box Enable switch
Cable length No enable
Nil
3 3m switch

S Equipped with
Original language enable switch
J Japanese Stop switch
E English G With Stop switch

Dimensions
//////// (2)
No Indication Function
(1) LCD Liquid crystal display (with backlight)

(1) (2) Ring The ring to hang the teaching box.


When the switch is pressed, the switch
(4) Stop switch locks and it stops.
(3)
Turn clockwise to release the lock.
(5)
(4) Stop guard Protector for the stop switch
Switch to prevent unintentional
(3) Enable
(6) operation of Jog test function.
switch
(5) ∗ Does not apply to other functions
(Option)
E.g.) data change

(6) Key switch Entry switches


(7) Cable 3m length
The connector to be connected to the
(8) Connector
(7) (8) CN4 of the controller

- 61 -
15. Alarm for Motor Control
The details of the alarm for motor control can be checked using a PC (the controller setting software) or
the teaching box.
∗ Please refer to the manuals of the controller setting software or the teaching box for details of the
alarms.
When an alarm is generated, deactivate the alarm after troubleshooting and correcting the error with
reference to chapter "15.3 Alarms and countermeasures" (P.64).
Alarms are divided into two types. One is an alarm group B to D which can be cleared by inputting the
signal RESET. The other is group E which cannot be cleared unless the power supply control (24 VDC)
is turned OFF once.

15.1 Alarm group signals


This product outputs a signal to distinguish the type of the alarm when an alarm is generated.
Alarms are classified into 5 groups. When an alarm is generated, it is output in OUT0 to 3.
Table below shows the combination of the alarm group and signal (OUT0 to OUT3).
Signal
Alarm group
ALARM OUT0 OUT1 OUT2 OUT3
Alarm group B ON OFF ON OFF OFF
Alarm group C ON OFF OFF ON OFF
Alarm group D ON OFF OFF OFF ON
Alarm group E ON OFF OFF OFF OFF

After generation of the alarm, SVRE or SETON are output according to the contents of the alarm as
shown below.
Signal
Alarm group How to start test run.
SVRE SETON
Alarm group B No change No change Input RESET
Alarm group C No change No change Input RESET
Alarm group D OFF No change Input RESET, then SVON.
Power supply for control is turned OFF
Alarm group E OFF OFF
→ Supply again

- Procedure to restart operation when alarm group D is generated -


Procedure 1 Alarm group D is generated → "SVRE" changes to OFF (Servo is OFF)
Procedure 2 Input RESET → (Alarm is canceled) → After inputting SVON, SVRE is turned ON
(Servo is on)

- 62 -
15.2 Reading PROFINET Diagnostics from the JXCP1
When an alarm is generated in the JXCP1, a PROFINET alarm is also sent to the PLC.
The SF LED on the PLC will be solid red to indicate a problem has occurred within the JXCP1.
However it is possible to determine the exact cause of the problem by using STEP7(SIMATIC Manager)
to read diagnostic information from the JXCP1.

(1) Start [HW Config] from STEP7(SIMATIC Manager). (Refer to 4.2(1).)


Select [Station]→[Open ONLINE] from the menu bar of [HW Config].
A red cross will be shown in the HW Config screen (may need to refresh screen by selecting [View] →
[Update] from menu bar).

(2) R/Click on JXCP1 icon and select [Module Information]

JXCP

JXC

Fig.15.1 Selection of [Module Information] of HW Config

(3) In the Module Information screen, select the [IO Device Diagnostics] tab to display details on the
error.
Can view additional information on the error by clicking on the [Display] box.
( The numbers displayed in brackets correspond to the alarm codes shown in "15.3 Alarms and
countermeasures" (P.64).)

Fig.15.2 Display of [Diagnostics] screen

- 63 -
15.3 Alarms and countermeasures

Name of the
controller Teaching
How to
setting box Group Alarm contents/Countermeasure
deactivate
software description
(code) ∗1
<Condition>The step data is incorrect for the following conditions
(Settable range)
(1) Area1 <Area2
(If both Area1 and Area2 is 0, the alarm will not be activated.)
(2) Trigger LV ≤ Pushing force
(3) Minimum speed of actuator ≤ Pushing speed ≤ Speed
Drive data (4) Pushing speed ≤ Maximum pushing speed of actuator
Step
value is (5) Pushing force ≤ Minimum pushing force of actuator
data B RESET
wrong (6) Basic parameter "Maximum pushing force" ≥Minimum pushing force of
ALM1
(01-048) the actuator
(7) Basic parameters "Max pushing force" ≥ Threshold
<Countermeasure> Modify the step data and basic parameters setting
/Caution
Please refer to the manual or the catalogue of the actuator for the
max/min pushing force/speed for the actuator.

<Contents> The basic parameter is not correct for the following condition:
(Settable range)
(1) Stroke(-) < Stroke (+)
Parameter (2) W-Area 1 < W-Area 2
Parame (∗ If both W-Area1 and W-Area2 is 0, the alarm will not be activated.)
value is
ter B RESET (3) Maximum pushing force < Maximum pushing force of actuator
wrong
ALM <Countermeasure> Modify the basic parameter setting.
(01-049)
/Caution
Please refer to the manual or the catalogue of the actuator for the
maximum pushing force for the actuator.
<Contents> For an operation for a specific step data no., the requested
number of the step data is not registered. (When operation is commanded
through PLC, this alarm will be generated depending on the input signal
interval and the holding time of signals)
Set step
< Countermeasure >
data is not Step
(1) Check if "Operation" of the step data which is commanded to start is
registered data B RESET
"Blank (Invalid data)".
on list. ALM2
(2) Set the time more than twice the communication cycle time for the
(01-051)
interval between the signals, when the signals are continuously input,
because PLC processing delays and controller scanning delays can
occur.
Refer to 13.2[2] Positioning operation (P.53)
<Contents> The actuator goes outside the stroke limit specified by the
basic parameters, "Stroke (+)" and "Stroke (-)" if it performs the requested
operation. (Including JOG operation after return to origin)
<Countermeasure> Make sure that the basic parameters, "Stroke (+)" and
Set stroke "Stroke (-)" are consistent with the distance of actuator movement
is outside specified in the step data.
Stroke
the stroke B RESET
limit.
limit /Caution
If the operation method of step data is "relative coordinated
(01-052)
movement", note the location where the operation starts and the
distance traveled. If the location is out of the stroke range when the
power is supplied, this alarm is generated. Move the table within
stroke range, and supply power.

- 64 -
<Content> This alarm occurs when the following parameter is
outside of the settable range during the numerical instruction
operation. (Settable range)
(1) Area1 < Area2
(If both Area1 and Area2 is 0, the alarm will not be activated.)
(2) Trigger LV ≤ Pushing force
(3) Minimum speed of actuator ≤ Pushing speed ≤ Speed
(4) Pushing speed ≤ Maximum pushing speed of actuator
Alarm (5) Pushing force ≤ Minimum pushing force of actuator
_Comment Input (6) Basic parameter "Maximum pushing force" ≥Minimum
3A B
_058 RESET pushing force of the actuator
(01-058) (7) Basic parameters "Max pushing force" ≥ Switch point

<Countermeasure>Modify the basic parameter setting.


/Caution
Please refer to the operation manual or catalog of the
actuator for the maximum pushing speed, minimum pushing
force, and minimum speed for the actuator.

<Content> This alarm occurs when specifying step data based on


the unregistered No. of the step data or when the numbers of the
Movement MOD specify outside of range during numerical
instruction operation. (When operation is commanded through
PLC, this alarm will be generated depending on the input signal
Alarm interval and the holding time of signals)
_Comment Input <Countermeasures>
3D B
_061 RESET (1) Make sure that the “Movement MOD” of the step data is not
(01-061) "Blank (Disabled)" or the numbers other than [1(ABS)] and
[2(INC)] are input in the numerical instruction operation.
(2) Both PLC processing delay and controller scan delay are
generated. Ensure that 2 times or more of the communication
cycle time should be maintained between the input signals.
Refer to 13.2[2] Positioning (P. 53)

<Content> The actuator goes outside the stroke limit specified by


the basic parameters, "Stroke (+)" and "Stroke (-)" if it performs
the requested operation during numerical instruction operation.

<Countermeasure> Make sure the basic parameters, "Stroke (+)"


Alarm and "Stroke (-)" are consistent with the distance of actuator
_Comment Input movement specified in the step data.
3E B
_062 RESET
(01-062) /Caution
If the operation method of step data is “relative coordinated
movement”, note the location where the operation starts and
the distance traveled.
If the location is out of the stroke range when the power is
supplied, this alarm is generated. Move the table within
stroke range, and supply power.
Reacting
force is <Contents> In the pushing operation, the actuator is pushed back from the
outside limit pushing operation origin position.
when Pushing
C RESET
pushing. ALM
Position is <Countermeasure> Increase the distance from the pushing operation
unstable. origin position to the object being pushed. Or, increase the pushing force.
(01-096)

- 65 -
Return to
ORIG did <Contents> Return to origin is not completed within the set time.
not
ORIG
complete in C RESET
ALM
the set <Countermeasure> Make sure there are no obstructions that interfere with
time. the actuator movement.
(01-097)
Drive is ON <Contents> While the servo motor is OFF, the return to origin operation,
when Servo positioning operation, pushing operation or JOG operation is requested.
SVRE is OFF C RESET
<Countermeasure> Modify the setting so that those operations will be
OFF ALM
requested while the servo motor is ON (the SVON input is ON).
(01-098)
Drive is ON <Contents> A positioning operation or pushing operation is requested
when before the return to origin position is completed.
Drive
SETON is C RESET
ALM <Countermeasure> Modify the setting so that these operations will be
OFF
(01-099) requested after the return to origin position is completed.

<Contents> Alarm is generated when return parameter has the conditions


1, 2 shown below.
Return to origin parameter setting
Did not Return to origin mode ORIG sensor
detect 1 Pushing origin operation [Stop] •Sensor N.O type [N.O]
sensor ORIG •The origin sensor is not
when Sens C RESET effective. [Disabled]
returning to ALM 2 Limit switch origin [Sensor]
or
ORIG. •Sensor N.O type [N.O]
(01-103)
∗ Alarm is generated with the conditions above when the sensor is not
mounted to the actuator.
<Countermeasure> Check the sensor installation and settings of the return
to origin parameter.
<Contents> The motor speed exceeds a specific level due to an external
force, etc.
Speed <Countermeasure> Make improvements so that the motor speed will not
RESET
exceeded Over exceed the maximum speed of the actuator.
D Input
set value speed
(01-144)
SVON /Caution
Please refer to the manual or the catalogue of the actuator for the
maximum speed of the actuator.

<Contents> The motor power supply voltage is out of range during


[SVON].
<Countermeasure> Make sure that the voltage supplied to the motor
power (M24V) of the controller is within specification.
Motor /Caution
power If the power supply is "inrush-current control type", a voltage drop may
supply RESET cause an alarm during acceleration/deceleration.
Over
voltage is D Input
motorVol <Contents> The alarm may be caused by regenerative power depending
outside set SVON
on the method of operation of the actuator.
range.
(01-145) <Countermeasure> Make sure that the operating conditions are within the
specifications.
/Caution
Please refer to the manual or the catalogue of the actuator for the
method of operation of the actuator.
Controller <Details> The temperature around the power element of the controller is
temperatur RESET too high.
Over
e exceeded D Input
Temp <Countermeasures> Make improvements so that the temperature around
set range. SVON
(01-146) the controller is kept appropriate.

- 66 -
<Contents> The control power supply voltage within the controller is outside
the set range.
<Countermeasure> Make sure that the voltage supplied to the control
power (C24V) of the controller is appropriate.
/Caution
Controller If a single power supply is used for both the control power and the
supply motor power, or the power supply is "inrush-current control type", a
RESET power voltage drop may be caused due to a voltage drop during
voltage is Over
D Input acceleration/deceleration.
outside set CrtlVol
SVON
range. <Contents> The alarm may be caused by regenerative power depending on
(01-147) the method of operation of the actuator.
<Countermeasure> Make sure that the operating conditions are within the
specifications.
/Caution
Please refer to the manual or the catalogue of the actuator for the
method of operation of the actuator.
<Contents> The output current accumulated value exceeds the specified
Current value.
RESET
limit is Over
D Input <Countermeasure> Make sure there are no obstructions that interfere with
exceeded load
SVON the actuator movement. Also, make sure that the load, speed, acceleration
(01-148)
and deceleration are within the range of the actuator.
The target
position <Content> Failed to reach the set position within the set time limit.
was not Posn
RESET
reached failed
D Input
within the ALM <Countermeasure> Make sure there are no obstructions that interfere with
SVON
set time the actuator movement. Also, make sure that the load, speed, acceleration
limit and deceleration are within the range of the actuator.
(01-149)
<Contents> The connection with the higher-level devices (such as the PC
and teaching box) is disconnected.
Communic Ctrl RESET
<Contents> The connection with the higher-level devices (such as the PC
ation error. Comm D Input
and teaching box) is disconnected.
(01-150) ALM SVON
In case of the communication failure of PC or teaching box, resetting of
alarm by PC or teaching box is possible after connecting again.

Cycle the
<Contents> Abnormality in communication with the encoder.
Encoder power
Encoder
error E supply
ALM
(01-192) for the
controller <Countermeasure> Check the connection of the actuator cable.

<Contents> Unable to find the motor phase within the set time.
(When the servo motor is turned ON (SVON is turned ON) for the first time
Unable to Cycle the
after the power is applied, the actuator needs to move a little to find the
find motor Polarity power
motor phase. However, if this actuator movement is prevented, this alarm
phase in not E supply
will be activated.)
set time. found for the
(01-193) controller <Countermeasure> Make sure there are no obstructions that interfere with
the actuator movement and then turn ON the servo motor (SVON is turned
ON).
Output <Contents> The output current of the power circuit is abnormally high.
Cycle the
current
power
limit is Over
E supply <Countermeasure> Make sure that there are no short circuits of actuator
exceeded current
for the cables, connectors, etc.
set value
controller In addition, make sure that the actuator is compatible with the controller.
(01-194)

- 67 -
<Contents> An overflow of the position error counter inside of the controller
Cycle the
Error has occurred.
power
counter Err
E supply <Countermeasure> Make sure there are no obstructions that interfere with
overflowed overflow
for the the actuator movement. Also, make sure that the load, speed, acceleration
(01-196)
controller and deceleration are within the range of the actuator.

Memory Cycle the <Contents> An error of the EEPROM has occurred.


Abnormality power
Memory
has E supply
ALM <Countermeasure> Please contact SMC. (The write limit of the EEPROM
occurred for the
(01-197) controller is roughly 100,000 times)

Cycle the <Contents> The CPU is not operating normally.


power (It is possible that the CPU or surrounding circuits has failed, or the CPU is
CPU error CPU malfunctioning due to electrical noise).
E supply
(01-198) failure
for the
<Countermeasure> If the alarm cannot be deactivated even after the
controller
power is reapplied, please contact SMC.
∗1 When alarm is generated, 3-digit numbers after [-] in this table [(code)] are stored to [Alarm code] of Byte16-19 in the
input area of the memory map. The numbers of the alarm code indicated in this table are expressed as decimal numbers.

- 68 -
16. Precautions for wiring and cable
/Warning
(1) Adjusting, mounting or wiring change should never be done before shutting OFF the power
supply to the product.
Electric shock, malfunction and damage can result.
(2) Do not disassemble the cable. Use only specified cables.
(3) Do not connect or disconnect the cable or connector with the power on.

/Caution
(1) Wire the connector securely. Do not apply any voltage to the terminals other than those
specified in the Operation Manual.
(2) Wire the connector securely.
Check for correct connector wiring and polarity.
(3) Take appropriate measures against noise.
Noise in a signal line may cause malfunction.
As a countermeasure, high voltage and low voltage cables should be separated, and keep wiring
lengths short, etc.
(4) Do not route wires or cables together with power or high voltage cables.
The product may malfunction due to interference and surge voltages. Route the wires of the product
separately from power or high voltage cables.
(5) Take care that actuator movement does not damage cables.
(6) Operate with cables secured. Avoid bending cables at sharp angles where they enter the
product.
(7) Avoid twisting, folding, rotating or applying an external force to the cable. Also avoid
operating at sharp angles.
Risk of electric shock, broken wires, contact failure and loss of control of the product can occur.
(8) Fix the motor cable protruding from the product in place before using.
The motor cable is not robotic type cable and can be damaged when moved.
Do not place Part A in the diagram below in a flexible cable duct.
//// Connector
Actuator cable
Robotic type cable
Motor cable (High flexibility cable)

(9) Select "Robotic type cables" when deflecting actuator-cables repeatedly. Do not put cables
into a flexible moving tube with a radius smaller than the specified value (minimum 50mm).
/Risk of electric shock, wire damage, contact failure and loss of control of the product can occur if
"Standard cables" are used in case of inflecting the cables repeatedly.

(10) Confirm proper wiring of the product.


Insulation failure (interference with another circuit, poor insulation between terminals etc.) could
introduce excessive voltage or current to the controller or its peripheral devices and damage them.
(11) The Speed/pushing force may vary, depending on the cable length, load and mounting
conditions etc.
If the cable length exceeds 5m, the speed/pushing force will be reduced 10% per 5 m maximum.
(If cable length is 15m, 20% reduction maximum.)

Transport
/Caution
(1) Do not carry or swing the product by the motor or the cable.

- 69 -
17. Electric Actuators/Common Precautions
17.1 Design and selection
/Warning
(1) Read the Operation Manual before using the product.
Handling or usage/operation other than that specified in the Operation Manual may lead to breakage
and product failure.
Any damage attributed to use beyond the specifications is not guaranteed.
(2) There is a possibility of dangerous sudden action by the product if sliding parts of machinery
are twisted due to external forces etc.
In such cases, human injury may occur, such as catching hands or feet in the machinery, or damage
to the machinery itself may occur. The machinery should be designed to avoid such dangers.
(3) A protective cover is recommended to minimize the risk of personal injury.
If a driven object and moving parts of the product are in close proximity, personal injury may occur.
Design the system to avoid contact with the human body.
(4) Securely tighten all stationary parts and connected parts so that they will not become loose.
When the product operates with high frequency or is installed where there is a lot of vibration, ensure
that all parts remain secure.
(5) Consider a possible loss of power source.
Take measures to prevent injury and equipment damage in the case of a power supply failure.
(6) Consider the behavior of an emergency stop of the whole system.
Design the system so that human injury and/or damage to machinery and equipment will not be
caused, when it is stopped by a safety device for abnormal conditions such as a power outage or a
manual emergency stop of the whole system.
(7) Consider the action when operation is restarted after an emergency stop or abnormal stop of
the whole system.
Design the system so that human injury or equipment damage will not occur upon restart of operation
of the whole system.
(8) Disassembly and modification is prohibited.
Do not disassemble the product or make any modifications, including additional machining. This may
cause human injury and/or an accident.
(9) Do not use the stop signal, "EMG" of the controller and stop switch on the teaching box as the
emergency stop for the system.
The stop signal, "EMG" of the controller and the stop switch on the teaching box are for decelerating
and stopping the actuator. Design the system with an emergency stop circuit which is applied to the
relevant safety standard separately.
(10) When using for vertical applications, it is necessary to build in a safety device.
The rod may fall due to the weight of the work.
The safety device should not interfere with normal operation of the machine.

/Caution
(1) Use the product for the maximum usable stroke.
The product will be damaged if it is used with a stroke exceeding the maximum stroke. Refer to the
specifications of the product.
(2) When the product repeatedly cycles with partial strokes, operate it at a full stroke at least
once a day or every 1,000 strokes.
Otherwise, lubrication can be lost.
(3) Do not use the product in applications where excessive external force or impact force is
applied to it.
The product can be damaged. Components, including the motor, are manufactured to precise
tolerances, so the slight test deformation may cause faulty operation or seizure.
(4) Return to origin cannot be carried out during operating.
This function cannot be carried out during positioning operation or pushing operation.

- 70 -
(5) Refer to a common auto switch (Best Pneumatics No 2), when an auto switch is built and used
within the system.

17.2 Mounting
/Warning
(1) Install and operate the product only after reading the Operation Manual carefully and
understanding its contents.
Keep the manual in a safe place for future reference.
(2) Tighten threads with the proper tightening torque.
Tighten the screws to the recommended torque for mounting the product.
(3) Do not make any alterations to this product.
Alterations made to this product may lead to a loss of durability and damage to the product, which
can lead to human injury and damage to other equipment and machinery.
(4) When using an external guide, the guide axis should be parallel to the actuator axis.
There will be damage/excessive wear on the lead screw if the external guide is not parallel.
(5) When an external guide is used, connect the moving parts of the actuator and the load in such
a way that there is no interference at any point within the stroke.
Do not scratch or dent the sliding parts of the actuator tube or piston rod etc., by striking them with
other objects. Components are manufactured to precise tolerances, so the slightest deformation may
cause faulty operation.
(6) Prevent the seizure of rotating parts (pins, etc.) by applying lubricating grease.
(7) Do not use the product before verifying that the equipment can operate properly.
After mounting or repair, connect the power supply to the product and perform appropriate functional
inspections to check it is mounted properly.
(8) Cantilever
When the actuator is operated at high speeds while it is fixed at one end and free at the other end
(flange type, foot type, double clevis type, direct mount type), a bending moment may act on the
actuator due to vibration generated at the stroke end, which can damage the actuator. In such a case,
install a support bracket to suppress the vibration of the actuator body or reduce the speed so that
the actuator does not vibrate. Use a support bracket also when moving the actuator body or when a
long stroke actuator is mounted horizontally and fixed at one end.
(9) When mounting the actuator or attaching to the work piece, do not apply strong impact or
large moment.
If an external force over the allowable moment is applied, it may cause looseness in the guide unit,
an increase in sliding resistance or other problems.
(10) Ensure sufficient space for maintenance activities.
Allow sufficient space for maintenance and inspection.

- 71 -
17.3. Handling Precautions

Warning
(1) Do not touch the motor while in operation.
The surface temperature of the motor can increase to approx. 90oC to 100oC due to operating
conditions. Energizing alone may also cause this temperature increase. Do not touch the motor when
in operation as it may cause burns.
(2) If abnormal heating, smoking or fire, etc., occurs in the product, immediately shut OFF the
power supply.
(3) Immediately stop operation if abnormal operation noise or vibration occurs.
If abnormal operation noise or vibration occurs, the product may have been mounted incorrectly.
Unless operation of the product is stopped for inspection, the product can be seriously damaged.
(4) Never touch the rotating part of the motor or moving part of the actuator while in operation.
(5) When installing, adjusting, inspecting or performing maintenance on the product, controller
and related equipment, shut OFF the power supply to each of them. Then, lock it so that no
one other than the person can turn the power on, or implement measures such as a safety
plug.
(6) In the case of the actuator that has a servo motor (24VDC), the "motor phase detection step"
is done by inputting the servo on signal just after the controller power is turned ON. The
"motor phase detection step" moves the table/rod for the distance of one screw-lead
maximum. (The motor rotates in the reverse direction if the table hits an obstacle such as the end
stop damper.) Take the "motor phase detection step" into consideration for the installation and
operation of this actuator.
Caution
(1) Keep the controller and actuator combination as delivered for use.
The product parameters are set before shipment. If the controller is combined with a different
actuator, failure can result.
(2) Check the product for the following points before operation.
a) Damage to power supply line and signal line
b) Looseness of the connector to the power and signal lines
c) Looseness of the actuator/cylinder and controller/driver mounting
d) Abnormal operation
e) Emergency stop of the whole system
(3) When more than one person is performing work, decide on the procedures, signals, measures
for emergency and how to start the operation after the measures taken. Also, designate a
person to supervise work other than those performing work.
(4) Actual speed of the product will be changed by the workload.
Before selecting a product, check the catalog for the instructions regarding selection and specifications.
(5) Do not apply a load, impact or resistance, in addition to a transferred load during the "Return
to Origin" operation.
When performing return to origin by pushing force, additional force will cause displacement of the
origin position since it is based on detected motor torque.
(6) Do not remove the name plate.
(7) An operation test should be carried out using a low speed. Start operation using the
predefined speed after confirming there are no problems.
[Grounding]
Warning
(1) Provide a good earth connection to the actuator.
(2) The earth should be a dedicated earth connection. Class D dedicated grounding should be
used. (Ground resistance 100Ω or less)
(3) The earth cable length should be as short as possible.
[Unpacking]
Caution
(1) Check that the received product is as ordered.
If a different product is installed, other than that ordered, injury or damage can result.
- 72 -
17.4 Operating environment
/ Warning
(1) Avoid use in the following environments.
1. Locations where a large amount of dust and cutting chips are airborne.
2. Locations where the ambient temperature is outside the range of the temperature specification
(refer to specifications).
3. Locations where the ambient humidity is outside the range of the humidity specification (refer to
specifications).
4. Locations where corrosive gas, flammable gas, seawater, water and steam are present.
5. Locations where strong magnetic or electric fields are generated.
6. Locations where direct vibration or impact is applied to the product.
7. Areas that are dusty, or are exposed to splashes of water and oil drops.
8. Areas exposed to direct sunlight (ultraviolet rays).
9. Environment at an altitude of 1000 meters or higher Heat dissipation and withstand voltage will
decrease.
Contact your SMC representative for details.
(2) Do not use in an environment where the product is directly exposed to liquid, such as cutting
oils.
If cutting oils, coolant or oil mist contaminates the product, failure or increased sliding resistance can
result.
(3) Install a protective cover when the product is used in an environment directly exposed to
foreign matter such as dust, cutting chips and spatter.
Play or increased sliding resistance can result.
(4) Shade the sunlight in the place where the product is applied with direct sunshine.
(5) Shield the product if there is a heat source nearby.
When there is a heat source surrounding the product, the radiated heat from the heat source can
increase the temperature of the product beyond the operating temperature range. Protect it with a
cover, etc.
(6) Grease oil can be reduced due to the external environment and operating conditions. The
lubrication performance may deteriorate and shorten the life of the product.

[Storage]
/ Warning
(1) Do not store the product with direct contact to rain or water drops. Do not store the product
where it is exposed to harmful gases or liquid.
(2) Store in an area that is shaded from direct sunlight and has a temperature and humidity within
the specified range (-10oC to 60oC and up to 85%. No condensation or freezing.)
(3) Do not apply vibration and impact to the product during storage.

- 73 -
17.5 Maintenance Precautions
Warning
(1) Do not disassemble or repair the product.
Fire or electric shock can result.
(2) Before modifying or checking the wiring, the voltage should be checked with a tester 5
minutes after the power supply is turned OFF.
Electric shock can result.

Caution
(1) Maintenance should be performed according to the procedure indicated in the Operating
Manual.
Incorrect handling can cause injury, damage or malfunction of equipment and machinery.
(2) Removal of product
When equipment is serviced, first confirm that measures are in place to prevent dropping of work
pieces and run-away of equipment, etc, then cut the power supply to the system. When machinery is
restarted, check that operation is normal with actuators in the proper positions.

[Lubrication]
Caution
(1) The product has been lubricated for life at the manufacturer's and does not require lubrication
in service.
Contact SMC if lubrication is to be applied.

17.6 Precautions for actuator with lock


Warning
(1) Do not use the lock as a safety lock or a control that requires a locking force.
The lock used for the product with a lock is designed to prevent dropping of work pieces.
(2) For vertical mounting, use the product with a lock.
If the product is not equipped with a lock, the product will move and drop the work piece when the
power is removed. If the actuator with lock is not used, preventive measure should be take by the
design of equipment.
(3) "Measures against drops" means preventing a work piece from dropping due to its weight
when the product operation is stopped and the power supply is turned OFF.
(4) Do not apply an impact load or strong vibration while the lock is activated.
If an external impact load or strong vibration is applied to the product, the lock will lose its holding
force and damage to the sliding part of the lock or reduced lifetime can result. The same situations
will happen when the lock slips due to a force over the thrust of the product, as this accelerates the
wear to the lock.
(5) Do not apply liquid or oil and grease to the lock or its surrounding.
If liquid or oil and grease is applied to the sliding part of the lock, its holding force will reduce
significantly.
(6) Take measures against drops and check that safety is assured before mounting, adjustment
and inspection of the product.
If the lock is released with the product mounted vertically, a work piece can drop due to its weight.
(7) When the actuator is operated manually (when SVRE output signal is OFF), supply 24VDC to
the [BK RLS] terminal of the power supply connector.
If the product is operated without releasing the lock, wear of the lock sliding surface will be
accelerated, causing a reduction in the holding force and the life of the locking mechanism.
(8) Do not supply 24VDC power supply constantly to the [BK RLS].
Only supply 24VDC power supply to the [LK RLS(Lock release)] terminal during normal operation. If
power is supplied to the [LK RLS] terminal continuously, the lock will be released, and workpieces
may be dropped at stop (EMG).
/For details of wiring please refer to the operation manual for the controller (LEC series).

- 74 -
18. Controller and Peripheral Devices/Specific Product Precautions
18.1 Design and selection
Warning
(1) Use the specified voltage.
Otherwise, malfunction and damage to the controller may result.
If the applied voltage is lower than the specified voltage, it is possible that the load cannot be moved
due to an internal voltage drop. Check the operating voltage before use.
(2) Do not operate beyond the specifications.
Fire, malfunction or actuator damage can result. Check the specifications before use.
(3) Install an emergency stop circuit.
Install an emergency stop outside of the enclosure so that it can stop the system operation
immediately and intercept the power supply.
(4) In order to prevent danger and damage due to the breakdown and the malfunction of this
product, which may occur at a certain probability, a backup system should be established in
advance by giving a multiple-layered structure or a fail-safe design to the equipment, etc.
(5) If fire or personal injury is expected due to abnormal heat generation, ignition, smoking of the
product, etc., cut OFF the power supply for this product and the system immediately.
(6) The upper limit of writing cycle to EEPROM of the JXCP1 controller is 1,000,000 cycles.
If the upper limit of writing cycle is exceeded, the writing will not be performed correctly.

- 75 -
18.2 Handling Precautions
Warning
(1) The inside of the controller and its connector should not be touched.
It may cause an electric shock or damage to the controller.
(2) Do not perform operation or setting of this equipment with wet hands.
It may cause an electric shock.
(3) A product that is damaged or missing any components should not be used.
Electric shock, fire, and injury can result.
(4) Use only the specified combination of controller and electric actuator.
It may cause damage to the controller or the actuator.
(5) Be careful not to be caught or hit by the workpiece while the actuator is moving.
It may cause an injury.
(6) Do not connect the power supply to the product until it is confirmed that the workpiece
movement area is safe.
The movement of the workpiece may cause an accident.
(7) Do not touch the product when it is energized and for some time after power has been
disconnected, as it can be very hot.
It may cause burns due to the high temperature.
(8) Check for voltage using a tester at least 5 minutes after power-OFF when performing
installation, wiring and maintenance.
Electric shock, fire, and injury can result.
(9) Do not use the product in an area where it could be exposed to dust, metallic powder,
machining chips, or splashes of water, oil or chemicals.
A failure or malfunction can result.
(10) Do not use the product in an area where a magnetic field is generated.
It will cause failure or malfunction.
(11) Do not install the product in an environment where flammable gas, explosive or corrosive
gas, liquids or other substances are present.
It could lead to fire, explosion and corrosion.
(12) Avoid radiant heat from large heat sources such as direct sunlight or hot furnaces.
It will cause failure of the controller or its peripheral devices.
(13) Do not use the product in an environment subjected to cyclic temperature changes.
It will cause failure of the controller or its peripheral devices.
(14) Do not use in a location where surges are generated.
When there are units that generate a large amount of surge around the product (for example
solenoid type lifters, high frequency induction furnaces, motors, etc.), this may cause deterioration
or damage to the product’s internal circuit. Avoid surge generation and crossed lines.
(15) Do not install the product in an environment subjected to vibration and impact.
It will cause failure or malfunction.
(16) If this product is used in conjunction with a relay or solenoid valve, use a type with a surge
absorbing element built-in.

- 76 -
18.3 Mounting
Warning
(1) The controller and its peripheral devices should be installed on a fire-proof material.
Direct installation on or near a flammable material may cause fire.
(2) Do not install this product in a location subject to vibration and impact.
A failure and malfunction can result.
(3) Take measures so that the operating temperature of this controller and its peripheral devices
are within the range of the specifications.
Also, this controller should be installed with at least 50mm space between each side of it and
other structures or components.
It may cause a malfunction of the controller and its peripheral devices and a fire.
(4) Do not mount the controller and its peripheral devices near a large electromagnetic contactor
or no-fuse breaker which generates vibration on the same panel. Mount them on different
panels, or keep the controller and its peripheral devices away from such a vibration source.
(5) The controller and its peripheral devices should be installed on a flat surface.
If the mounting surface is distorted or not flat, excessive force may be applied to the housing, etc.
causing malfunction.

18.4 Wiring
Warning
(1) Do not damage the cable or apply a heavy object or pinch the cable. Avoid repeatedly
bending or stretching the cable.
It may cause an electric shock, fire, or breaking of wire.
(2) Wire correctly.
Incorrect wiring could damage the controller or its peripheral devices depending on the seriousness.
(3) Do not perform wiring while the power is on.
It can damage the controller or its peripheral devices could be damaged, causing malfunction.
(4) Do not carry this product by holding its cables.
It may cause an injury or damage to the product.
(5) Do not route wires or cables together with power or high voltage cables.
The wires to the controller or its peripheral devices can be interrupted with noise or induced surge
voltage from power lines or high-voltage lines, causing malfunction.
Route the wires of the product separately from power or high voltage cables.
(6) Verify the insulation of wiring.
Insulation failure (interference with another circuit, poor insulation between terminals etc.) could
introduce excessive voltage or current to the controller or its peripheral devices and damage them.

- 77 -
18.5 Power supply
Caution
(1) Use a power supply with low noise between lines and between power and ground.
In cases where noise is high, use an isolation transformer.
(2) The power supplies for the controller power and the I/O signal power should be separate, and
both Power supplies should not be of the "in-rush current limiting type".
If the power supply is of the "in-rush current limiting type", a voltage drop may occur during the
acceleration of the actuator.
(3) Take appropriate measures to prevent lightning surges. Ground the surge absorber for
lightning separately from the ground connection for the controller and its peripheral devices.

18.6 Grounding
Warning
(1) Ensure that the product is grounded to allow the noise tolerance of the controller.
Otherwise it may cause an electric shock or fire.
(2) A dedicated Ground connection must be used.
Grounding should be to a D-class ground connection. (Ground resistance 100Ω or less)
(3) The grounding point should be as near as possible to the controller to keep the cable length
short.
(4) In the unlikely event that malfunction is caused by the ground connection, it may be
disconnected.

18.7 Maintenance
/ Warning
(1) Perform maintenance checks periodically.
Confirm wiring and screws are not loose.
Loose screws or wires may cause unexpected malfunction.
(2) Conduct an appropriate functional inspection and test after completing maintenance.
In case of any abnormalities (if the actuator does not move, etc.), stop the operation of the system.
Otherwise, an unexpected malfunction may occur and it will become impossible to ensure safety.
Give an emergency stop instruction to confirm safety.
(3) Do not disassemble, modify or repair this controller or the peripheral devices.
(4) Do not put anything conductive or flammable inside of the controller.
Fire or explosion can result.
(5) Do not perform an insulation resistance test or insulation withstand voltage test.
(6) Ensure sufficient space for maintenance.
Design the system to allow the required space for maintenance.

- 78 -
19. Troubleshooting
When any failure occurs with this product, the following chart can be used to identify the cause of the
failure. When none of the causes in the troubleshooting can be confirmed, it is presumed that the
product is faulty and normal operation can only be recovered by the replacement of a part.
It is possible that this product may be damaged due to the operating conditions (applications). Please
contact SMC to discuss appropriate measures.
///////////////////////////////

The system
does not work YES
correctly. NO

JXC

LED is OFF. Refer to Failure 1

SF and BF turn
on red or flashing Refer to Failure 2
red.

ALM LED
Refer to Failure 3
turns ON red.

Communication with
the controller cannot Refer to Failure 4
be established.
(LEC-W2)

The actuator
Refer to Failure 5
does not operate.

Contact SMC for details.

- 79 -
Problem Possible Investigation method and location of
Problem Countermeasures
No. causes possible causes
Use an appropriate voltage and power supply
Check that PWR (green) of the controller
capacity in reference to the operation manual
Power turns OFF at either of when power is
of the actuator and controller connected.
fault supplied, SVON ON is instructed or the
→ 3. Specifications (P.11)
actuator is operating.
1 LED is OFF. → 5. External Connections (P.21)
Please correct the wiring in reference to
Check the incorrect wiring, broken wire
Incorrect Controller Operation Manual.
and short circuit of the power supply
wiring → 5. External Connections (P.21)
plug.
→ 6. CN1: Power Supply Plug (P.23)
Check the communication cable in
accordance with the items below.
- The communication cable should be
connected from the PLC to this Correct the wiring or connection of the
controller. communication cable or replace them in
- The PLC communication speed should reference to the controller Operation Manual.
be appropriate. → 5. External Connections (P.21)
- There should be no broken wire or short If the PLC communication speed setting is
Communic
circuit. abnormal, correct the setting in reference with
BF ation data
-There should be no loosening at the the PLC Operation Manual.
Red LED is has not
connection.
ON. been
- There should be no repeated bending
received.
stresses or pulling forces.
Check that there is no equipment or high
Please keep the communication and power
voltage cables which generates noise
cables away from the noise source or cover
around the communication and power
them.
supply cables.
Please correct the power supply and power
Check that there is no abnormality on the
supply cables in reference to the PLC
PLC power supply condition.
Operation Manual.
Set the Device name so that there is no
Check that Device name is correctly set.
duplication.
Check the communication cable in
2 accordance with the items below.
- The communication cable should be
connected from the PLC to this Correct the wiring or connection of the
controller. communication cable or replace them in
- The PLC communication speed should reference to the controller Operation Manual.
PROFINET be appropriate. → 5. External Connections (P.21)
communic - There should be no broken wire or short If the PLC communication speed setting is
BF
ation is circuit. abnormal, correct the setting in reference with
Red LED
abnormal - There should be no loosening at the the PLC Operation Manual.
flashes.
(Bus connection.
Fault). - There should be no repeated bending
stresses or pulling forces.
Check that there is no equipment or high
Please keep the communication and power
voltage cables which generates noise
cables away from the noise source or cover
around the communication and power
them.
supply cables.
Please correct the power supply and power
Check that there is no abnormality on the
supply cables in reference to the PLC
PLC power supply condition.
Operation Manual.
Please take appropriate countermeasures
SF in accordance with alarm content in
Alarm
Red LED is Check the content of alarm reference to the controller Operation
generated
ON. Manual.
→ 15. Alarm for Motor Control (P.62)

Refer to the controller operation manual and


Alarm If it is, check the type of alarm referring to
3 ALM is on take appropriate measures.
generated this manual.
→ 15. Alarm for Motor Control (P.62)

- 80 -
Please install the USB driver of the
communication unit.
The USB The USB driver's installation starts when the
Check that the USB driver for the
driver is not communication unit is connected with PC.
conversion unit is installed.
installed Details of the installation procedure are
shown in "Installation procedure of the
LEC-W2 setting software".

The COM port allocated to the controller is


different for different PC’s. Check and
confirm the COM port number with the
Incorrect controller connected to the PC.
Please confirm if the correct COM
COM port The COM port number can be checked using
port is set to the ACT Controller.
setting the Device Manager of the PC. For details of
the COM port checking and setting methods
refer to the "LEC-W2 Controller Configuration
Communication Software Installation Manual".
4 fault
(LEC-W2)
Please confirm motor controller (LEC) =
communications cable = communication unit
= USB cable = PC is connected. For
example, communication cannot be
established if the connector has been
damaged.
Please confirm the power supply of motor
Connection Please confirm the connection controller (LEC) has been turned ON.
failure status. Communication cannot be established if the
power supply is OFF.
If equipment other than the motor controller
(LEC) (PLC and measurement equipment) is
connected with PC, remove these before
checking. (There is a possibility that the
communication with other equipment
interferes in PC.)

If there is no sound of lock release, the lock


Lock When the unlock switch is turned ON
brake may be broken.
release or OFF there is an unlocking sound
→ If the problem persists, please contact
error made.
SMC.

Check that the PLC connected to the


External Refer to the controller operation manual and
controller operates correctly.
Does not operate equipment take appropriate measures.
5 Test operation of the controller on its
at all. failure → 9.1 Memory allocation (P.30)
own.

Check if the controller’s


specifications are appropriate, the Take appropriate measures according to this
Unsuitable
power supply is suitable and the manual.
spec.
controller is compatible with the → 3. Specifications (P.11)
actuator.

- 81 -
Is the wiring connected correctly? Correct the wiring so that the input/output of
Incorrect Refer to the controller operation each signal is performed appropriately.
wiring manual to confirm wiring, and check → 5. External Connections (P.21)
for broken wires and short-circuits. → 9.1 Memory allocation (P.30)

Refer to the controller operation manual and


Electric Connect to Ground correctly.
take appropriate measures.
noise Avoid bundling the cables.
→ 3.4 Mounting (P.15)

Check that the parameter values are


Take appropriate measures according to this
Incorrect correct.
manual.
parameters Also, check the cables are not
→ 10. Settings and Data Entry (P.41)
bundled.

Check for a temporary voltage drop


in the power supply? There is a possibility of a momentary voltage
(If there is a temporary voltage drop drop because the capacity of the power
Voltage in the power supply, the EMG supply is insufficient, or if the power supply is
drop terminal of CN1 power connector will "inrush-current control" type.
turn OFF so the actuator will stop. If necessary, replace the power supply.
However, this stop will be released → 3. Specifications (P.11)
Operation stops
when the voltage recovers.)
intermittently
Check whether the INP output turns
ON during pushing operation.
Failure of Check the INP output signal before the
(If completion of pushing operation
pushing energy saving mode is turned ON.
is detected by the INP output, the
operation. → 9.1 Memory allocation (P.30)
PLC cannot confirm the completion
of driving.)

Check if the controller’s specifications


Take appropriate measures according to this
5 Unsuitable are appropriate, the power supply is
manual.
spec. suitable and the controller is
→ 3. Specifications (P.11)
compatible with the actuator.

Set the time more than twice the


communication cycle time for the interval
between the signals, when the signals are
Signal Check the timing of the signal from continuously input, because PLC processing
timing the PLC to the controller. delays and controller scanning delays can
occur.
→ 11.4 Controller input signal response
time (P.49)
If it is a pushing operation, repeat
return to origin operations several
Incorrect times to check if the actuator returns to Take measures to make the actuator operate
origin the origin correctly. normally (remove foreign matter that
position Perform the Return to Origin interferes with the actuator movement, etc.)
position operation several times to
check the Origin position.
The actuator Check that the parameter values are
does not move to appropriate and the program is
the correct Incorrect correct. Modify the parameters and test the operation.
position. parameters Review the maximum speed, the → 10. Settings and Data Entry (P.41)
maximum acceleration and the
maximum deceleration of the actuator.
Check if the controller’s
specifications are appropriate, the Take appropriate measures according to this
Unsuitable
power supply is suitable and the manual.
specification
controller is compatible with the → 3. Specifications (P.11)
actuator.

- 82 -
Is the wiring connected correctly? Correct the wiring so that the input/output of
Incorrect Refer to the controller operation each signal is performed appropriately.
wiring manual to confirm wiring, and check → 5. External Connections (P.21)
for broken wires and short-circuits. → 9.1 Memory allocation (P.30)

Check if the controller’s


specifications are appropriate, the Take appropriate measures according to this
Unsuitable
power supply is suitable and the manual.
specification
controller is compatible with the → 3. Specifications (P.11)
actuator.

Set the time more than twice the


The actuator communication cycle time for the interval
does not move between the signals, when the signals are
correctly. Signal Check the timing of the signal from continuously input, because PLC processing
timing the PLC to the controller. delays and controller scanning delays can
occur.
→ 11.4 Controller input signal response
time (P.49)

Check whether data (step data,


parameter) is written correctly. Input correct data (step data, parameter) again
Data not
Do not turn OFF the controller input and confirm operation.
stored
power or remove the cable while → 3.2 Parts Description (P.12)
correctly
data is being written (green light → 10. Settings and Data Entry (P.41)
flashing).

Check that the parameter values are


5
correct. Modify the values of the parameters and test
Incorrect
Review the maximum speed and the the operation.
parameters
maximum acceleration of the → 10. Settings and Data Entry (P.41)
actuator.

Check if a trapezoidal
acceleration/deceleration is
Operation programmed for the actuator Modify the setting to make the moving
pattern is operation. In case of such operation, distance longer or the acceleration larger.
not suitable. the actuator may start slowing down → 10. Settings and Data Entry (P.41)
before it reaches the maximum
speed.

Speed not Check if the controller’s


achieved specifications are appropriate, the Take appropriate measures according to this
Unsuitable
power supply is suitable and the manual.
specification
controller is compatible with the → 3. Specifications (P.11)
actuator.

Check for a temporary voltage drop


in the power supply?
There is a possibility of a momentary voltage
(If there is a temporary voltage drop
drop because the capacity of the power
in the power supply, the EMG
Voltage supply is insufficient, or if the power supply is
terminal of CN1 power connector
drop "inrush-current control" type.
will turn OFF so the actuator will
If necessary, replace the power supply.
stop. However, this stop will be
→ 3. Specifications (P.11)
released when the voltage
recovers.)

- 83 -
20. Handling of sent/received data
There are three types of data, 1byte data, 2bytes data and 4bytes data.
Specifically, handling of 2bytes data, 4bytes data and negative data is explained below.

(1) 2bytes data


Please note following examples for 2 bytes data including speed, acceleration, and deceleration.
E.g.) Output data "speed": When inputting 100mm/s data to Byte6 and Byte7.
100mm/s is 0064h in hexadecimal.
00 64 h data is as shown below.

Speed
Byte6 00 h
Byte7 64 h
Bit7 Bit0

(2) 4bytes data


“Please note following example for 4 bytes data including position.
E.g.) Output data "position": When inputting 700.00mm data to Byte8 to Byte11.
“Position” is based on the unit by 0.01mm.
The value to express 700.00 mm is 70000 in decimal number, and 00011170h in hexadecimal.
Sending of 00 01 11 70 h data is as shown below.

Position
Byte8 00 h
Byte9 01 h
Byte10 11 h
Byte11 70 h
Bit7 Bit

(3) Negative value data


“Please note following example for negative value data.
In the example, 4bytes negative value data is explained.
E.g.) Output data "position": When inputting -700.00mm (negative value) to Byte8 to Byte11.
“Position” is based on the unit by 0.01mm.
Negative values are expressed using two’s complement notation
The value to express -700.00mm is -70000 in decimal number, and FFFEEE90h in
hexadecimal.
Sending of FF FE EE 90 h data is as shown below.

Position
Byte8 FFh
Byte9 FEh
Byte10 EEh
/
Byte11 90 h
Bit7 Bit0

- 84 -
21. Definitions and terminology

The major terminology used in this Operation Manual is stated below.


Terminology Definition
Data transmission speed of a network such as a Fieldbus network.
Communication
The speed is determined by upper devices (PLC etc.). The unit is bit
speed
C per second (bps).
Communication cycle This is a cycle of sending data from masters to slaves (JXCP1
time controller).

An arbitrary name assigned by the user to the PROFINET slave. Every


D Device name
node on the PROFINET network should have a unique name.

The most commonly used LAN technology that was standardized by


E Ethernet
IEEE802.3

An industrial communication system, which uses a defined protocol to


transfer data between devices on a network. A typical automation
F Fieldbus
system will use a fieldbus network to exchange data between a PLC
master and the actuators/sensors.
Allows a device to be configured for a PROFINET network, using PLC
setting software.
G GSDML file
The file describes data exchange, device information and supported
PROFINET features.
A unique address that identifies a device on a network. It is referred to
I IP address as a logical address while the MAC address is known as a physical
address.
This is a physical address, which is uniquely assigned to any hardware
MAC address device on a network.
This address is permanently written to the device before shipment.
M
Media Redundancy Protocol
MRP Performs fast switching to a redundant communication route, when a
problem occurs within a Ring network.
Abbreviation of Programmable Logic Controller, a digital computer
P PLC
used for automation of electromechanical processes.

Connection configuration of the Fieldbus network


T Topology Expresses how each terminal and control components are connected.
The typical topology is star type, linear type and ring type.

Trademark
The company name, system name, and product name described in this document are registered
trademarks of each individual company. In this document TM and (R) are not specified.

- 85 -
Revision history
A : Modify error in writing, and contents revised in several
places

/
4-14-1, Sotokanda, Chiyoda-ku, Tokyo 101-0021 JAPAN
Tel: + 81 3 5207 8249 Fax: +81 3 5298 5362
URL http://www.smcworld.com
/
Note: Specifications are subject to change without prior notice and any obligation on the part of the manufacturer.
© 2016 SMC Corporation All Rights Reserved.

- 86 -