The document provides information about the electrical loads in a small shop receiving 3-phase, 400 VLN power. It lists various lighting, fan, heater, air conditioning, and outlet loads. It asks to: (1) calculate the total maximum demand using provided diversity factors, (2) recommend the proper rating for a residual current circuit breaker, and (3) calculate the proper rating for miniature circuit breakers serving different circuits according to wiring rules and standard ratings given in tables.

Uploaded by

Aidi Redza
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
70 views1 page

Exercise

The document provides information about the electrical loads in a small shop receiving 3-phase, 400 VLN power. It lists various lighting, fan, heater, air conditioning, and outlet loads. It asks to: (1) calculate the total maximum demand using provided diversity factors, (2) recommend the proper rating for a residual current circuit breaker, and (3) calculate the proper rating for miniature circuit breakers serving different circuits according to wiring rules and standard ratings given in tables.

Uploaded by

Aidi Redza
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Exercise 1

A small shop receives a three-phase, 400 VLN, 50 Hz from incoming supply. The switch board
located at shop supplies fixed loads and socket outlet circuits as follows:
i. 10 units incandescent lamp, each rated at 60 Watts and 10 units of incandescent
lamps, each rated at 100 Watts.
ii. 6 units ceiling fan, each rated 80 Watts.
iii. Two 5 kW heater ovens.
iv. 1 units 1.5 hp air-conditioning.
v. 10 units of 13 A switch socket outlet, each rated 400 Watts
By applying diversity factor provided in Table 1,
(a) Calculate the total maximum demand for this domestic installation.
(6 Marks)

(b) Recommend the proper rating of residual current circuit breaker (RCCB). (Refer Table 2)
(4 Marks)

(c) Calculate the proper rating of each miniature circuit breaker (MCB) used in accordance
with the information shown in the Table 2. The wiring rule is restricted to the following:

- One outgoing MCB serving 10 lighting/fan point.


- One outgoing MCB serving 4 SSO 13 A
- One outgoing MCB serving 1 air conditioning / oven point.
(10 Marks)

Table 1 Diversity factor


Load Type Allowance (%)
Lighting / Fan 66 % of total demand
Switch socket outlet 100 % of first largest circuit + 40 % of
remaining
AC / heater 100 % of total demand

Table 2 Standard rating of protective device


Type of Protective Device Standard Rating (A)
MCB 1, 3, 6, 10, 16, 20, 25, 32, 40, 50, 63
RCCB/Main switch 40, 63