GRT200 Brochure - 16001-G2A-1.04

Download as pdf or txt
Download as pdf or txt
You are on page 1of 47

Transformer Protection IED

GR-200 series -
The GR-200 Series is Toshiba’s next generation of protection and control IED’s, designed for
transmission/distribution networks and providing a platform for distributed and renewable energy
systems and railway applications. Flexible adaptation is enabled using extensive hardware and
modular software combinations facilitating an application oriented solution.
Meeting your needs -
Extensive hardware and modular software combinations provide the flexibility to meet your
application and engineering requirements.
Future upgrade paths and minor modifications are readily achievable on demand.
Powerful and wide application -
In addition to protection & control, GR-200 has been designed to meet the challenges and take
advantage of developments in information & communications technology. Process bus capability
and teleprotection based upon packet-based communications are just two of the features of GR-
200.

APPLICATION
GRT200 transformer protection is implemented on Toshiba’s next generation GR-200 series IED
platform and has been designed to provide comprehensive protection and control applications
for transformers in all types of network. This powerful and user-friendly IED will provide you with
the flexibility to meet your application and engineering requirements in addition to offering
outstanding performance, high quality and operational peace of mind.

- Current differential protection is applied for fast and selective main protection for two-
winding or three-winding power transformers, auto-transformers and generator- transformer
units. This protection requires no interposing CTs and provides stability against
magnetizing inrush, overexcitation and CT saturation.
- Up to five current inputs for the phase segregated differential protection
- Restricted earth fault protection incorporating enhanced stability against CT saturation
detects internal earth faults where the transformer star point is directly or low impedance
earthed.
- Comprehensive back up protections
- Bay control and monitoring functions
- Communications with substation automation system, IEC 61850-8-1 [Station bus], IEC
60870-5-103 and IEC62439/PRP/HSR

1
FEATURES

• Application
- Application for two-winding or three-winding • Functionality
power transformers, auto-transformers and - Eight settings groups
generator-transformer units. - Automatic supervision
- Current differential protection is applied - Metering and recording functions
- Time synchronization by external clock
for fast and selective main protection.
such as IRIG-B and system network
This protection requires no interposing
• Communication
CTs and provides stability against
- System interface - RS485, Fiber optic,
magnetizing inrush, overexcitation and
100BASE-TX/1000BASE-T, 100BASE-
CT saturation.
FX, 1000BASE-LX
- Restricted earth fault protection detects - Multi protocol - IEC 60870-5-103, IEC
internal earth faults where the 61850 and IEC62439/PRP/HSR
transformer star point is directly or low • Security
impedance earthed and can be applied on - Password protection
high-voltage and low-voltage sides • Flexibility
respectively. - Various models and hardware options for
- Time-overcurrent protection is mainly flexible application depending on system
used as backup protection and can be requirement and controlled object
applied on high- and low-voltage sides - Mixed 1A / 5A phase and neutral current
respectively. inputs
- Phase and neutral CT polarity settings
- Thermal overload protection protects the
- DC power supply: 110 to 240V, 24 to 60V
transformer against thermal stress and
or 48 to 125V
provides two independently set levels for
- Configurable binary inputs and outputs
alarm and tripping. - Programmable control, trip and alarm
GRT200 can be applied to the various kinds of logic with PLC tool software
transformer configuration as per the • Human Machine Interface
transformer configuration and applicable - Graphical LCD and 26 LEDs
model: - 7 configurable function keys
- USB port for local PC connection
Configuration Analog inputs Model
- Direct control buttons for open/close (O/I)
I1 and control authority (43R/L)
V In1 3 x three-phase CT + - Help key for supporting operation
In2 2 x zero-phase CT + GRT200-3-*
- Monitoring terminals for testing
1 x three-phase VT
I2 I3

I1 I3
V 4 x three-phase CT +
GRT200-4-*
1 x one-phase VT
I2 I4

V1 I1 I4 In1
In2 5 x three-phase CT +
In3
3 x zero-phase CT + GRT200-5-*
V2 2 x three-phase VT
I2 I5 I3

2
FUNCTIONS

• Protection
- Current differential protection for two • Monitoring
or three winding transformers (DIF) - Status and condition monitoring of primary
incorporating stability against inrush, apparatus
over-excitation and CT saturation - Switchgear operation monitoring
- No interposing CTs required - Plausibility check
- Mixed 1A/5A inputs for phase and - Measurement s of I, V, P, Q, S, PF, f, Wh,
neutral currents varh
- CT ratio, vector and zero-sequence - VT failure detection (VTF)
compensation - Current and voltage circuit supervision
- Trip circuit supervision (TCS)
- Restricted earth fault protection (REF)
incorporating enhanced stability • HMI function
against CT saturation - Selection of HMI: Standard LCD / large
LCD / Separate large LCD
- Breaker failure protection (CBF)
- Large LCD supports single line diagram
- Directional / non-directional
indication and touch-type operation
overcurrent protection for phase faults
- 24 configurable tri-state LEDs selectable
(OC)
red/green/yellow
- Non-directional overcurrent protection
- 7 Programmable function keys for user
for earth faults using neutral current
configurable operation
(EFIn)
• Recording
- Directional / nondirectional overcurrent
- Fault record
protection for earth faults using phase
- Event record
currents (EF)
- Disturbance record
- Negative phase sequence overcurrent
• Communication
protection (OCN)
- IEC 60870-5-103 / IEC 61850
- Thermal overload protection (THM)
- IEC62439 PRP/HSR
- Broken conductor protection (BCD)
• General functions
- Inrush current detector (ICD)
- Eight settings groups
- Overexcitation protection (VPH)
- Automatic supervision
- Under/over frequency and rate of - Time synchronization by external clock
change of frequency protection (FRQ) using IRIG-B or system network
- Trip and/or Indication of external - Password protection for settings and
devices (MECH. TRIP) selection of local / remote control
- Synchronism voltage check - Checking internal circuit by forcible signal
- Checking internal circuit using monitoring
jacks

APPLICATIONS

PROTECTION with a dual-slope, percentage differential characteristic


as shown in Figure 1. GRT200 also provides high-set
 Current Differential Protection (DIF)
unrestrained differential elements (DIF-Stage 2).

GRT200 provides fast, selective protection for two and


three winding transformers. It has three phase-
segregated differential elements (DIF-Stage 1), each

3
IA Id = Ires point current, restricted earth fault protection (REF)
provides a highly sensitive differential protection for
Id
earth faults in a transformer which has a star point
directly earthed or low impedance earthed.
IB IC
Operating zone
Large current The REF-DIF element has a dual slope, percentage
characteristic
characteristic as shown in Figure 2 and the
(DIF-S1-Slope2
= 5 - 100%) independent elements can be applied for each
DIF- Small current transformer winding.
S1-I1 characteristic
(DIF-S1-Slope1= 5 - 50%)
3I0 I0d = Ires
0 DIF-S1-I2 Ires IN
Id: Differential current (|IA + IB + IC |)
Ires: Restraining current (|IA| + |IB| + |IC|) I0d
DIF-S1-I1: Minimum operating value
DIF-S1-I2: Knee point
Operating
Figure 1: DIF-Stage1 characteristic zone
REF-Slope2
= 50 – 100%
The small current characteristic provides sensitivity to REF
-I1 REF-Slope1
low level faults. For higher level faults, the large = 10%
current characteristic with increased bias REF-I2 Ires
compensates for the effects of CT saturation. Iod: Residual differential current (|3I0 + IN|)
Ires: Restraining current (Max(|IA|, |IB|, |IC|, |IN|))
Furthermore, GRT200 provides a CT saturation
REF-I1: Minimum operating value
countermeasure function against a very large through- REF-I2: Knee point (: 1, 2, 3)
fault current.
Figure 2: REF-DIF characteristic

GRT200 incorporates internal CT ratio and vector


The REF provides a directional check element
compensation, so that the relay requires no interposing
REF-DEF to discriminate between internal and
CTs.
external faults to enhance stability against CT
saturation as shown in Figure 3. The REF_DEF
Mixed 1A/5A inputs for phase currents are available.
characteristic consists of both of the characteristics
as shown in Figure 4 (a) and (b).
CT polarities for each three-phase CT can be set
flexibly within GRT200 in accordance with external
physical connections to each three-phase CT. REF_DIF

REF
REF_DEF &
During periods of transformer energization, the use of
internal fault detection
a second harmonic restraint method blocks the relay & ≥1

operation. Ires≦2.0×Max_kct

[REF_DEF] ON
+
When the transformer is overexcited due to a transient OFF

power system disturbance, the use of a fifth harmonic Figure 3: REF block diagram
restraint method blocks the relay operation.
Figure 4: REF-DEF characteristic
90°
GRT200 also provides high-set unrestrained
differential elements (DIF-Stage2) and ensures rapid 3I0
clearance of heavy internal faults.
IN 3I0
180° 0 0°
ik2 (Fixed)
Operating
GRT200 provides differential current supervision zone
functions for 87T elements to monitor erroneous
differential current under normal conditions. 270°
ik1

 Restricted Earth Fault Protection (REF) (a) Directional characteristic (b) Non directional characteristic

Mixed 1A/5A inputs for phase and neutral currents are


Employing residual current of each winding and neutral available.

4
CT polarities for each neutral CT can be set flexibly for earth faults which can be applied flexibly for each
within GRT200 in accordance with external physical transformer winding, utilizing neutral current values
connections to each neutral CT.
observed.

 Breaker Failure Protection (CBF) GRT200 also provides up to 8 directional or non-


directional overcurrent protections (EF) with inverse
When an overcurrent element remains in operation time and definite time for earth faults which can be
longer than a pre-determined length of time following applied flexibly for each transformer winding, utilizing
the output of a trip signal the associated circuit breaker residual current values calculated by phase currents
is judged to have failed and adjacent circuit breakers observed.
can be tripped as a back-up measure.

Two independent timers are available, one of which


can be used to control the RETRIP of the original
circuit breaker(s). The second timer is used to control
the back-tripping of adjacent circuit breakers.

For high-speed protection, an overcurrent element with


high-speed reset time is used to prevent a spurious re-
trip or back-trip following a successful trip or re-trip
action.

 Overcurrent Protection (OC / EFIn / EF)

GRT200 provides up to 8 directional or non-directional


overcurrent protections (OC) with inverse time and
definite time for phase faults which can be applied
flexibly for each transformer winding.

Inverse time overcurrent protection consists of an


IDMT (inverse definite minimum time) element. IDMT
is available in conformity with the IEC 60255-151
standard which encompasses both the IEC and
IEEE/ANSI standard characteristics as shown in
Figure 3. Alternatively, a user-configurable curve may
be created.

The IDMT element has a programmable reset feature,


selectable for instantaneous, definite time or
dependent time operation. This feature can be used to
protect against flashing/intermittent fault conditions, or
to grade correctly with electromechanical overcurrent Figure 5: Characteristics of inverse time delayed
relays. overcurrent element

Definite time overcurrent protection is enabled by the


 Negative Phase Sequence Overcurrent
instantaneous overcurrent element and pickup-delay
Protection (OCN)
timer.

Tripping by each element can be disabled by the Up to 4 negative phase sequence overcurrent
scheme switches, and overcurrent backup protection protections (OCN) can be applied flexibly for each
transformer winding. OCN can be used in applications
can be blocked by a binary input signal.
where certain fault conditions may not be detected by
GRT200 provides up to 4 non-directional overcurrent the normal phase and earth overcurrent protections,
protections (EFIn) with inverse time and definite time for example, in the case of a relay applied on the delta

5
side of a delta-star transformer, to detect an earth fault may be selected as either having a definite time or an
on the star side. inverse time delay as shown in Figure 6.

VPH-L: Low level i.e. Pick up level


 Thermal Overload Protection (THM)
VPH-H: High level i.e. Definite time
tripping level
The thermal overload feature provides protection for
VPH-LT: Operate time at low level
V/Hz
cables and other plant against the effects of prolonged VPH-HT: Operate time at high level
operation under excess load conditions. A thermal VPH-H TVPHH: Definite time delay at high level
VPH-A: Alarm level
replica algorithm is applied to create a model for the
TVPHA: Definite time delay for alarm
thermal characteristics of the protected plant. Tripping
times depend not only on the level of overload current,
but also on the level of prior load current, the thermal VPH-L
VPH-A
replica providing ‘memory’ of previous conditions.
0 TVPHA VPH-HT VPH-LT sec
The thermal characteristics of the system are defined TVPHH (log T)
by entering settings for full load current and thermal Figure 6: VPH characteristic
time constant. The GRT200 issues a trip in accordance
with the ‘cold’ and ‘hot’ curves specified in IEC 60255-
149 to prevent the protected system from exceeding  Under/Over Frequency and Rate of Change of
its thermal capacity. The cold curve tripping times are Frequency Protection (FRQ)
applicable when the system is first energized, while the
GRT200 provides up to 6 stage frequency protections
hot curves are relevant when the system has already
where over/under frequency protections or rate-of-
been carrying some prior load for a period of time. An
change-of-frequency protections can be selected
alarm output is also available to give early warning of
flexibly.
high load current, set as a percentage of thermal
capacity. These protections provide independent frequency
protection stages. The over/under frequency
protection is programmable for either under- or over-
 Broken Conductor Detection (BCD)
frequency operation, and each has an associated
GRT200 provides up to 3 broken conductor detections delay timer. The rate-of-change-of-frequency
(BCD). Detects unbalance conditions in each protection calculates the gradient of frequency change
transformer winding caused by an open circuited (df/dt).
conductor. An unbalance threshold with
programmable definite time delay is provided.
 Trip and/or Indication of External Devices
 Inrush Current Detector (ICD) (MECH. TRIP)

The inrush current detector (ICD) is used to prevent an Up to 16 external signals such as overpressure
incorrect operation of the aforementioned OC, EF, devices and Buchholz relay operations can be applied
OCN and BCD against a magnetizing inrush current through binary input circuits. Logic can be arranged for
during transformer energization. ICD detects second alarms, event recording and tripping.
harmonic inrush currents during transformer
energization.

 Overexcitation Protection (VPH)

Alarms and tripping for overexcitation, based on a


measurement of the voltage/frequency ratio are
provided.
The alarm is definite time delayed whilst the characteristic

6
HMI FUNCTION
 Front Panel
The local human machine interface includes an LCD
GRT200 provides the following front panel options. which can display the single line diagram for the bay.
- Standard LCD
The local human machine interface is simple and easy
- Large LCD (optional separate LCD type is also
to understand with the following facilities and
available)
indications.
The standard LCD panel incorporates the user - Status indication LEDs (IN SERVICE, ERROR and
interfaces listed below. Setting the relay and viewing 24 configurable LEDs)
stored data are possible using the Liquid Crystal - 7 Function keys for control, monitoring, setting
Display (LCD) and operation keys. group change and screen jump functions of which
- 21 characters, 8 lines LCD with back light operation is configurable by the user
- Support of English language - Test terminals which can monitor three different
signals from the front panel without connection to
The large LCD panel incorporates a touch type screen
the rear terminals.
for control and navigation purposes.
- USB port
- 40 character, 40 line LCD with back light

 Local PC Connection

The user can communicate with GRT200 from a local


PC via the USB port on the front panel. Using GR-200
series engineering tool software (called GR-TIEMS),
the user can view, change settings and monitor real-
time measurements.

Figure 7: HMI Panel (large LCD type)

MONITORING
 Metering  Status Monitoring
The open or closed status of each switchgear device
The following power system data is measured
and failure information concerning power apparatus
continuously and can be displayed on the LCD on the
and control equipment are monitored by GRT200.
relay fascia, and on a local or remotely connected PC.
Both normally open and normally closed contacts are
- Measured analog voltages, currents, used to monitor the switchgear status. If an unusual
frequency, active- and reactive-power.
status is detected, a switchgear abnormality alarm is
The accuracy of analog measurement is ±0.5% for I,
generated.
V, P, Q at rated input and ±0.03Hz for frequency
measurement.

7
RECORDING
 Event Record - Pre-fault and post-fault current and voltage data
(phase, phase to phase, symmetrical
Continuous event-logging is useful for monitoring of
components)
the system from an overview perspective and is a
complement to specific disturbance recorder
functions. Up to 1,024 time-tagged events are stored  Disturbance Record
with 1ms resolution. The Disturbance Recorder function supplies fast,
 Fault Record complete and reliable information for disturbances in
the power system. It facilitates understanding of
Information about the pre-fault and fault values for
system behavior and performance of related primary
currents and voltages are recorded and displayed for
and secondary equipment during and after a
trip event confirmation. The most recent 8 time-
disturbance.
tagged faults with 1ms resolution are stored. Fault
record items are as follows. The Disturbance Recorder acquires sampled data
- Date and time from all selected analogue inputs and binary signals.
- Faulted phase The data can be stored in COMTRADE format.
- Phases tripped
- Tripping mode

COMMUNICATION
■ Station bus ■ Serial communication

Ethernet port(s) for the substation communication Serial ports (RS485 and fiber optic) for communicating
standards IEC 61850 is provided for the station bus. with legacy equipment or protection relays over IEC
GRT200 also support Ethernet redundancy scheme 60870-5-103 protocol are provided. The GRT200 can
protocols defined in the IEC 62439-3 standard: function as a protocol converter to connect SAS.
PRP/HSR.

GENERAL FUNCTION
 Self Supervision one group for normal conditions, while the other
groups may be set to cover alternative operating
Automatic self-supervision of internal circuits and
conditions.
software is provided. In the event of a failure being
detected, the ALARM LED on the front panel is  Password Protection
illuminated, the ‘UNIT FAILURE’ binary output
Password protection is available for the execution of
operates, and the date and time of the failure is
setting changes, executing control, clearing records
recorded in the event record.
and switching between local/remote control.

 Time Synchronization  Simulation and Test

Current time can be provided with time synchronization GRT200 provides simulation and test functions to
via the station bus by SNTP (Simple Network Time check control functions without modification to wiring
Protocol) with the IEC 61850 protocol. provided by a dummy circuit breaker (virtual
equipment), and the capability to test communication
IRIG-B port is also available as an option.
signals by forced signal status change.

The simulation and test can work on in the test mode


 Setting Groups
only.
8 settings groups are provided, allowing the user to set

8
TOOLS & ACCESSORY
The PC interface GR-TIEMS allows users to access
GRT200 and other Toshiba GR-200 series IEDs from  LCD configuration
a local personal computer (PC) to view on-line or The user can configure and customize the MIMIC data
stored data, to change settings, to edit the LCD screen, displayed on the LCD of GRT200 using GR-TIEMS
to configure sequential logics and for other purposes. software.

 Remote Setting and Monitoring


The engineering tool supports functions to change
settings and to view and analyze fault and disturbance
records stored in GRT200. Waveform data in the
disturbance records can be displayed, edited,
measured and analyzed in detail. An advanced version
of the engineering tool can provide additional and
powerful analysis tools and setting calculation support
functions.

Figure 9: PC Display of MIMIC configuration

 Programmable Logic Editor


The programmable logic capability allows the user to
configure flexible logic for customized application and
operation. Configurable binary inputs, binary outputs
and LEDs are also programmed by the programmable
logic editor. This complies with IEC61131-3 standard.

Figure 8: PC Display of GR-TIEMS


Figure 10: PC display of PLC editor

9
TECHNICAL DATA

HARDWARE
Analog Inputs
Rated current In 1A / 5A (selectable by user)
Rated voltage Vn 100V to 120V
Rated Frequency 50Hz / 60Hz (specified when order)
Overload Rating
Current inputs 4 times rated current continuous
5 times rated current for 3 mins
6 times rated current for 2 mins
30 times rated current for 10 sec
100 times rated current for 1 second
250 times rated current for one power cycle (20 or 16.6ms)
Voltage inputs 2 times rated voltage continuous
2.5 times rated voltage for 1 second
Burden
Phase current inputs ≤ 0.1VA at In = 1A, ≤ 0.2VA at In = 5A
Earth current inputs ≤ 0.3VA at In = 1A, ≤ 0.4VA at In = 5A
Sensitive earth fault inputs ≤ 0.3VA at In = 1A, ≤ 0.4VA at In = 5A
Voltage inputs ≤ 0.1VA at Vn
Power Supply
Rated auxiliary voltage 24/48/60Vdc (Operative range: 19.2 – 72Vdc),
48/125Vdc (Operative range: 38.4 – 150Vdc),
110/250Vdc or 100/220Vac (Operative range: 88 – 300Vdc
or 80 – 230Vac)
<Notes>
1) Binary inputs are intended for use with DC power source
only.
2) The power supply supervision function is intended for use
with DC power source only. It should be disabled when
AC power supply is applied in order to prevent spurious
alarms.
Superimposed AC ripple on DC supply ≤ 15%
Power supply interruption 24/48/60Vdc rating: 20ms
withstand period 48/125Vdc rating: 35ms
(IEC 60255-11) 110/125Vdc rating: 50ms
Power consumption ≤ 15W (quiescent)
≤ 25W (maximum)
Binary Inputs
Input circuit DC voltage 24/48/60Vdc (Operating range: 19.2 – 72Vdc),
48/125Vdc (Operating range: 38.4 – 150Vdc),
110/125/220/250Vdc (Operating range: 88 – 300Vdc)
Note: Variable threshold settings are available for BI2 from
14V to 154V in various steps.
Capacitive discharge immunity 10μF charged to maximum supply voltage and discharged into
the input terminals, according to ENA TS 48-4 with an external
resistor
Maximum permitted voltage 72Vdc for 24/48/60Vdc rating,
300Vdc for 110/250Vdc rating
Power consumption ≤ 0.5W per input at 220Vdc
Binary Outputs
Fast operating contacts:
Make and carry 5A continuously

10
30A, 290Vdc for 0.2s (L/R=5ms)
Break 0.15A, 290Vdc (L/R=40ms)
Operating time Typically 3 ms
Semi-fast operating contacts:
Make and carry 8A continuously
30A, 240Vdc for 1s (L/R=5ms)
Break 0.1A, at 250Vdc (L/R=40ms)
0.2A, at 110Vdc (L/R=40ms)
Operating time Typically 6 ms
Auxiliary contacts:
Make and carry 8A continuously
30A, 240Vdc for 1s (L/R=5ms)
Break 0.1A, at 250Vdc (L/R=40ms)
0.2A, at 110Vdc (L/R=40ms)
Operating time Typically 8 ms
Hybrid contacts (10 A breaking):
Make and carry 8A continuously
10A, 220Vdc for 0.5s (L/R=5ms)
Break 10A, 220Vdc (L/R=20ms)
10A, 110Vdc (L/R=40ms)
Operating time 1 ms
Durability ≥ 10,000 operations (loaded contact)
≥ 100,000 operations (unloaded contact)
Measuring input capability
Full scale
Standard current input ≥ 60A (1A rating) or 300A (5A rating)
Sensitive current input ≥ 3A (1A rating) or 15 A (5A rating)
Voltage input ≥ 200V
Sampling rate 48 samples / cycle
Frequency response < 5% deviation over range 16.7Hz to 600Hz
Mechanical Design
Installation Flush mounting
Weight Approx. 12kg (1/2 size), 15kg (3/4 size), 25kg (1/1 size)
Case colour 2.5Y7.5/1 (approximation to Munsell value)
LED
Number 26 (Fixed for “In service” and “ERROR”)
Colour Red / Yellow / Green (configurable) except “In service” (green)
and “Error” (red)
Function keys
Number 7
Local Interface
USB Type B
Maximum cable length 2m (max.)
System Interface (rear port)
100BASE-TX/1000BASE-T For IEC 61850-8-1 and GR-TIEMS
Connector type RJ-45
Cable type CAT5e STP cable
- enhanced category 5 with Shielded Twisted Pair cable
100BASE-FX For IEC 61850-8-1
Connector type SC duplex type
Cable type Multi-mode fibre, 50/125 or 62.5/125µm fibre
Wave length 1300nm
1000BASE-LX For IEC 61850-8-1

11
Connector type LC duplex connector
Cable type Single-mode fibre
Wave length 1310nm
RS485 For IEC 60870-5-103
Cable type Shielded twisted pair cable
Connector type Push-in spring terminal (PCB connector)
Fibre optical (for serial communication) For IEC 60870-5-103
Cable type Multi-mode fibre, 50/125 or 62.5/125µm
Connector type ST type
Wave length 820nm
IRIG-B (for time synchronization)
Cable type Shielded twisted pair cable
Connector type Push-in spring terminal (PCB connector)
Terminal Block
CT/VT input M3.5 Ring terminal (ring lug type terminal only)
Binary input, Binary output Compression plug type terminal

12
ENVIRONMENTAL PERFORMANCE

Atmospheric Environment
Temperature IEC 60068-2-1/2 Operating range: -10°C to +55°C.
IEC 60068-2-14 Storage / Transit: -25°C to +70°C.
Cyclic temperature test as per IEC 60068-2-
14
Humidity IEC 60068-2-30 56 days at 40°C and 93% relative humidity.
IEC 60068-2-78 Cyclic temperature with humidity test as per
IEC 60068-2-30
Enclosure Protection IEC 60529 IP52 - Dust and Dripping Water Proof
IP20 for rear panel
Mechanical Environment
Vibration IEC 60255-21-1 Response - Class 1
Endurance - Class 1
Shock and Bump IEC 60255-21-2 Shock Response Class 1
Shock Withstand Class 1
Bump Class 1
Seismic IEC 60255-21-3 Class 1
Electrical Environment
Dielectric Withstand IEC 60255-27 2kVrms for 1 minute between all terminals
and earth.
2kVrms for 1 minute between independent
circuits.
1kVrms for 1 minute across normally open
contacts.
High Voltage Impulse IEC 60255-5 Three positive and three negative impulses of
IEEE C37.90 5kV(peak), 1.2/50µs, 0.5J between all
terminals and between all terminals and
earth.
Voltage Dips, IEC 60255-11, 1. Voltage dips:
Interruptions, IEC 61000-4-29, 0 % residual voltage for 20 ms
Variations and Ripple IEC 61000-4-17 40 % residual voltage for 200 ms
on DC supply IEC 60255-26 Ed 3 70 % residual voltage for 500 ms
2. Voltage interruptions:
0 % residual voltage for 5 s
3. Ripple:
15 % of rated d.c. value, 100 / 120 Hz
4. Gradual shut-down / start-up:
60 s shut-down ramp, 5 min power off, 60s
start-up ramp
5. Reversal of d.c. power supply polarity:
1 min
Capacitive Discharge ENA TS 48-4 10μF charged to maximum supply voltage
and discharged into the input terminals with
an external resistance

13
Electromagnetic Environment
High Frequency IEC 60255-22-1 Class 3, 1 MHz burst in common / differential modes
Disturbance / IEC 61000-4-18 Auxiliary supply and I/O ports: 2.5 kV / 1 kV
Damped Oscillatory IEC 60255-26 Ed 3 Communications ports: 1 kV / 0 kV
Wave
Electrostatic Discharge IEC 60255-22-2 Class 4, Contact: 2, 4, 6, 8kV
IEC 61000-4-2 Air: 2, 4, 8, 15kV
IEEE C37.90.3-2001
IEC 60255-26 Ed 3
Radiated RF IEC 60255-22-3, Sweep test ranges: 80 MHz to 1 GHz and 1.4
Electromagnetic GHz to 2.7 GHz.
IEC 61000-4-3 Level 3
Disturbance IEC 60255-26 Ed 3 Spot tests at 80, 160, 380, 450, 900, 1850
and 2150 MHz.
Field strength: 10 V/m
IEEE C37.90.2-1995 Field strength 35V/m for frequency sweep of
25MHz to 1GHz.
Fast Transient IEC 60255-22-4 5 kHz, 5/50ns disturbance
Disturbance IEC 61000-4-4 Auxiliary supply and input / output ports: 4 kV
IEC 60255-26 Ed 3 Communications ports: 2 kV
Surge Immunity IEC 60255-22-5 1.2/50µms surge in common/differential
IEC 61000-4-5 modes:
IEC 60255-26 Ed 3 Auxiliary supply and input / output ports: 4,
2, 1, 0.5 kV / 1, 0.5 kV
Communications ports: up to 1, 0.5 kV / 0 kV
Surge Withstand IEEE C37.90.1-2002 3kV, 1MHz damped oscillatory wave
4kV, 5/50ns fast transient
Conducted RF IEC 60255-22-6 Sweep test range: 150 kHz to 80MHz
Electromagnetic IEC 61000-4-6 Spot tests at 27 and 68 MHz.
Disturbance IEC 60255-26 Ed 3 Voltage level: 10 V r.m.s
Power Frequency IEC 60255-22-7 50/60 Hz disturbance for 10 s in common /
Disturbance IEC 61000-4-16 differential modes
IEC 60255-26 Ed 3 Binary input ports: 300 V / 150 V
Power Frequency IEC 61000-4-8 Class 4 Field applied at 50/60Hz with strengths of:
Magnetic Field IEC 60255-26 Ed 3 30A/m continuously,
300A/m for 1 second.
Conducted and IEC 60255-25 Conducted emissions:
Radiated Emissions EN 55022 Class A, 0.15 to 0.50MHz: <79dB (peak) or <66dB
EN 61000-6-4 (mean)
IEC 60255-26 Ed 3 0.50 to 30MHz: <73dB (peak) or <60dB
(mean)
Radiated emissions
30 to 230 MHz: < 40 dB(uV/m)
230 to 1000 MHz: < 47 dB(uV/m)
Measured at a distance of 10 m

14
Performance and Functional Standards
Category Standards
General
Common requirements IEC 60255-1
Data Exchange IEC 60255-24 / IEEE C37.111 (COMTRADE)
Product Safety IEC 60255-27
European Commission Directives
2014/30/EU Compliance with the European Commission
Electromagnetic Compatibility Directive is
demonstrated according to EN 60255-26:2013.
2015/35/EU Compliance with the European Commission Low
Voltage Directive for electrical safety is
demonstrated according EN 60255-27:2014.

15
FUNCTIONAL DATA

Current differential protection (87T)


Stage 1: Biased current differential element
Minimum operating value (DIF-S1-I1) 0.10 to 1.00pu in 0.01pu steps
Small current region slope (DIF-S1-Slope1) 10 to 100% in 1% steps
Large current region slope (DIF-S1-Slope2) 10 to 200% in 1% steps
Knee point (DIF-S1-I2) 1.00 to 20.00pu in 0.01pu steps
2nd harmonic sensitivity for Inrush currents
(DIF-2f) 10 to 50% in 1% steps
5th harmonic sensitivity for Overexcitation (DIF-
5f) 10 to 100% in 1% steps
Operate time Typical 25ms

Stage 2: High-set unrestrained differential


element
Overcurrent (DIF-S2-I) 2.00 to 20.00pu in 0.01pu steps
Operate time Typical 20ms
Restricted earth fault element (87N)
[Low-impedance scheme]
Minimum operating value (REF-I1) 0.05 to 0.50pu in 0.01pu steps
Small current region slope (REF-Slope1) 10 %
Large current region slope (REF-Slope2) 50 to 100% in 1% steps
Knee Point (REF-I2) 0.50 to 2.00pu in 0.01pu steps
: 1, 2, 3
Non-directional and Directional Phase Overcurrent Protection (50, 51, 67)
Definite time overcurrent threshold 0.02 to 50.00A in 0.01A steps (1A rating)
0.10 to 250.00A in 0.01A steps (5A rating)
Inverse time overcurrent threshold 0.02 to 5.00A in 0.01A steps (1A rating)
0.10 to 25.00A in 0.01A steps (5A rating)
Direction characteristic Non Directional / Forward / Backward
Characteristic angle 0 – 180 degs in 1 deg steps
Delay type DT / IEC-NI / IEC-VI / IEC-EI / UK-LTI / IEEE-MI / IEEE-VI / IEEE-
EI / US-CO2 / US-CO8 / Original
Drop-out/pick-up ratio 10 to 100% in 1% steps
DTL delay 0.00 to 300.00s in 0.01s steps
IDMTL Time Multiplier Setting TMS 0.010 to 50.000 in 0.001 steps
Reset type Definite Time or Dependent Time
Reset definite delay 0.00 to 300.00s in 0.01s steps
Reset Time Multiplier Setting RTMS 0.010 to 50.000 in 0.001 steps

16
Non-directional and Directional Earth Fault Protection (50G, 51G, 67G)
Definite time earth fault threshold 0.02 to 50.00A in 0.01A steps (1A rating)
0.10 to 250.00A in 0.01A steps (5A rating)
Inverse time earth fault threshold 0.02 to 5.00A in 0.01A steps (1A rating)
0.10 to 25.00A in 0.01A steps (5A rating)
Direction characteristic Non Directional / Forward / Backward
Characteristic angle 0 to 180° in 1° steps
Polarising voltage (3V0) 0.5 to 100.0V in 0.1V steps
Delay type DT / IEC-NI / IEC-VI / IEC-EI / UK-LTI / IEEE-MI / IEEE-VI / IEEE-
EI / US-CO2 / US-CO8 / Original
Drop-out/pick-up ratio 10 to 100% in 1% steps
DTL delay 0.00 to 300.00s in 0.01s steps
IDMTL Time Multiplier Setting TMS 0.010 to 50.000 in 0.001 steps
Reset type Definite Time or Dependent Time
Reset definite delay 0.00 to 300.00s in 0.01s steps
Reset Time Multiplier Setting RTMS 0.010 to 50.000 in 0.001 steps
Non-directional Earth Fault Protection(Using neutral current) (50N, 51N)
Definite time earth fault threshold 0.02 to 50.00A in 0.01A steps (1A rating)
0.10 to 250.00A in 0.01A steps (5A rating)
Inverse time earth fault threshold 0.02 to 5.00A in 0.01A steps (1A rating)
0.10 to 25.00A in 0.01A steps (5A rating)
Delay type DT / IEC-NI / IEC-VI / IEC-EI / UK-LTI / IEEE-MI / IEEE-VI / IEEE-
EI / US-CO2 / US-CO8 / Original
Drop-out/pick-up ratio 10 to 100% in 1% steps
DTL delay 0.00 to 300.00s in 0.01s steps
IDMTL Time Multiplier Setting TMS 0.010 to 50.000 in 0.001 steps
Reset type Definite Time or Dependent Time
Reset definite delay 0.00 to 300.00s in 0.01s steps
Reset Time Multiplier Setting RTMS 0.010 to 50.000 in 0.001 steps
Negative Phase sequence overcurrent Protection (46)
Definite time NOC threshold 0.02 to 50.00A in 0.01A steps (1A rating)
0.10 to 250.00A in 0.01A steps (5A rating)
Inverse time NOC threshold 0.02 to 5.00A in 0.01A steps (1A rating)
0.10 to 25.00A in 0.01A steps (5A rating)
Direction characteristic Non Directional / Forward / Backward
Characteristic angle 0 to 180° in 1° steps
Polarising voltage 0.5 to 25.0V in 0.1V steps
Delay type DT / IEC-NI / IEC-VI / IEC-EI / UK-LTI / IEEE-MI / IEEE-VI / IEEE-
EI / US-CO2 / US-CO8 / Original
Drop-out/pick-up ratio 10 to 100% in 1% steps
DTL delay 0.00 to 300.00s in 0.01s steps
IDMTL Time Multiplier Setting TMS 0.010 to 50.000 in 0.001 steps
Reset type Definite Time or Dependent Time
Reset definite delay 0.00 to 300.00s in 0.01s steps
Reset Time Multiplier Setting RTMS 0.010 to 50.000 in 0.001 steps

17
Thermal Overload Protection (49)
Thermal setting (THM = k.IFLC) 0.40 to 2.00A in 0.01A steps (1A rating)
2.0 to 10.0A in 0.1A steps (5A rating)
Time constant (τ) 0.5 to 500.0mins in 0.1min steps
Thermal alarm OFF, 50% to 100% in 1% steps
Pre-load current setting 0.00 to 1.00A in 0.01A steps (1A rating)
0.00 to 5.00A in 0.01A steps (5A rating)
Broken conductor protection (46BC)
Broken conductor threshold 0.10 to 1.00 in 0.01 steps
DTL delay 0.00 to 300.00s in 0.01s steps
Inrush Current Detection
Second harmonic detection 10 to 50% in 1% steps
Inrush current thresholds 0.10 to 5.00A in 0.01A steps (1A rating)
0.5 to 25.00A in 0.01A steps (5A rating)
CBF Protection (50BF)
Overcurrent element 0.1 to 2.0A in 0.1A steps (1A rating)
0.5 to 10.0A in 0.1A steps (5A rating)
BF timer for retry-trip of failed breaker 50 to 500ms in 1ms steps
BF timer for related breaker trip 50 to 500ms in 1ms steps
Overexcitation Protection (24)
Pickup voltage 100.0 to 120.0V in 0.1V steps
Alarm level (A) 1.03 to 1.30pu in 0.01pu steps
High level (H) 1.10 to 1.40pu in 0.01pu steps
Low level (L) 1.05 to 1.30pu in 0.01pu steps
LT (Definite time) 1 to 600s in 1s steps
HT (Definite time) 1 to 600s in 1s steps
TVFH (Definite time) 1 to 600s in 1s steps
TVFA (Definite time) 1 to 600s in 1s steps
Start time less than 130ms
RT (Definite time) 60 to 3600s in 1s steps
Frequency Protection (81U/O)
Under/overfrequency threshold (Fnom to 10.00Hz) to (Fnom + 10.00Hz) in 0.01Hz steps
Fnom: nominal frequency
DTL delay: 0.00 to 300.00s in 0.01s steps
Frequency UV Block 40.0 to 100.0V in 0.1V steps
Rate-of-change frequency threshold 0.1 to 15.0Hz/s in 0.1Hz/s steps
Metering Function
Current Accuracy ± 0.5% (at rating)
Voltage Accuracy ± 0.5% (at rating)
Power (P, Q, S) Accuracy ± 0.5% (at rating)
Power factor (PF) Accuracy ± 0.5% (at rating)
Energy (Wh, VArh) Accuracy ± 1.0% (at rating)
Frequency Accuracy ± 0.03Hz
Time Synchronisation
Protocol SNTP

18
Accuracy
Current differential protection
Pick-ups ±5% of setting value
Reset ±5% of setting value
Operating time
Operating time of biased current typical 25ms + BO operating time (*1)
differential protection
Operating time of high-set current typical 20ms + BO operating time (*1)
differential protection
Restricted Earth Fault element
Pick-ups ±5% of setting value (at I ≥ 0.5pu)
Operating time typical 30ms + BO operating time (*1)
Overcurrent protection
Pick-ups ±3% of setting value (at I ≥ 0.5pu)
Operating time with definite timer typical 35ms + BO operating time (*1)
Operating time with inverse timer IEC curve:±5% of theoretical value
for 2 ≤ Multiple of threshold value ≤ 10 and TMS=1
IEEE curve: ±10% of theoretical value
for 2 ≤ multiple of threshold value ≤ 10 and TMS=1s

Earth fault protection


Pick-ups ≤ ±3% of setting value (at I ≥ 0.5pu)
Operating time with definite timer typical 35ms + BO operating time (*1)
Operating time with inverse timer IEC curve:±5% of theoretical value
for 2 ≤ Multiple of threshold value ≤ 10 and TMS=1
IEEE curve: ±10% of theoretical value
for 2 ≤ multiple of threshold value ≤ 10 and TMS=1s
Thermal overload protection
Pick-ups ±5% of setting value
Operating time ±10% of setting value
Over/Under frequency protection
Pick-ups ±0.03Hz (at f0±1Hz)
Start time Typical 150ms (at 60Hz,4H/s)
Typical 180ms(50Hz,4Hz/s)
Overexcitation protection
Pick-ups ±2% of pick-up voltage at f0 ±2%
Start time Typical 150ms
(*1)Typically 3~6ms

19
ORDERING INFORMATION

[Hardware selection (1)] Positions


- 7 8 - 9 A B - C D - E F - G H - J K L
Configurations G R T 2 0 0 - 3 - - 0 0 - - 3 -

Application of power system


3 x three-phase CT + 2 x zero-phase CT
3
1 x three-phase VT (Module No. 49)
DC rated voltage
110-250 Vdc or 100-220Vac (See (*1)) 1
24-60 Vdc 3
System Frequency
50Hz 1
60Hz 2
Rated Phase Currents (Default settings) (*2)
1A 1
5A 2

Rated Neutral Currents (Default settings) (*2)


1A 1
5A 2

Number of Serial and /or Ethernet Communication


and/or Time Sync Port(s)
Refer to Number of Communication port Table (See (*3))

Outline
Standard LCD, 1/2 x 19" rack for flush mounting 2
Large LCD, 1/2 x 19" rack for flush mounting 6
Standard LCD, 1/2 x 19" rack for rack mounting (See (*4)) F
Large LCD, 1/2 x 19" rack for rack mounting (See (*4)) J

Terminal block for BIO and PWS


Compression plug type terminal 0
BI/BO module
Choice from BI/BO table page 27 to 28 1×BIO module 1 *
2×BIO modules 2 *
3×BIO modules 3 *

Terminal block for BIO and PWS


Ring type terminal 1
BI/BO module
Choice from BI/BO table page 27 1×BIO modules 1 *
2×BIO modules 2 *

Configuration to be continued to page 21.

(*1) Binary inputs are intended for use with DC power source only.
The power supply supervision function is intended for use with DC power source only. It should be disabled
when AC power supply is applied in order to prevent spurious alarms.
(*2) Refer to pages 25 – 26, and select the appropriate CT configuration when you require another rated current
configuration.
(*3) Refer to page 32. For PRP/HSR/RSTP protocol with IEC 61850, choose “L” or “N” code at position E. For
hot/standby configuration or single port configuration with IEC 61850, choose other codes at position E.
(*4) For 19” rack panel mounting, accessories of joint kits are available. (See Figure 14 on page-38)

20
[Hardware selection (1)] continue Positions
- 7 8 - 9 A B - C D - E F - G H - J K L
Configurations G R T 2 0 0 - 3 - - 0 0 - - 3 -

Outline
Standard LCD, 3/4 x 19" rack for flush mounting 3
Large LCD, 3/4 x 19" rack for flush mounting 7
Standard LCD, 3/4 x 19" rack for rack mounting (See (*4)) G
Large LCD, 3/4 x 19" rack for rack mounting (See (*4)) K

Terminal block for BIO and PWS


Compression plug type terminal 0
BI/BO module
Choice from BI/BO table page27 to 30 1×BIO module 1 *
2×BIO modules 2 *
3×BIO modules 3 *
4×BIO modules 4 *
5×BIO modules 5 *
6×BIO modules 6 *

Terminal block for BIO and PWS


Ring type terminal 1
BI/BO module
Choice from BI/BO table page 27 to 29 1×BIO module 1 *
2×BIO modules 2 *
3×BIO modules 3 *
4×BIO modules 4 *

Outline
Standard LCD, 1/1 x 19" rack for flush/rack mounting 4
Large LCD, 1/1 x 19" rack for flush/rack mounting 8

Terminal block for BIO and PWS


Compression plug type terminal 0
BI/BO module
Choice from BI/BO table page 27 to 31 1×BIO module 1 *
2×BIO modules 2 *
3×BIO modules 3 *
4×BIO modules 4 *
5×BIO modules 5 *
6×BIO modules 6 *
7×BIO modules 7 *
8×BIO modules 8 *

Terminal block for BIO and PWS


Ring type terminal 1
BI/BO module
Choice from BI/BO table page 27 to 31 1×BIO module 1 *
2×BIO modules 2 *
3×BIO modules 3 *
4×BIO modules 4 *
5×BIO modules 5 *
6×BIO modules 6 *
7×BIO modules 7 *

21
[Hardware selection (2)] Positions
- 7 8 - 9 A B - C D - E F - G H - J K L
Configurations G R T 2 0 0 - 4 - - 0 0 - - 3 - 0

Application of power system


4 x three-phase CT
4
1 x one-phase VT (Module No. 44)
DC rated voltage
110-250 Vdc or 100-220Vac (See (*1)) 1
24-60 Vdc 3
System Frequency
50Hz 1
60Hz 2
Rated Phase Currents (Default settings) (*2)
1A 1
5A 2

Rated Neutral Currents


None 0

Number of Serial and /or Ethernet Communication


and/or Time Sync Port(s)
Refer to Number of Communication port Table (See (*3))

Outline
Standard LCD, 1/2 x 19" rack for flush mounting 2
Large LCD, 1/2 x 19" rack for flush mounting 6
Standard LCD, 1/2 x 19" rack for rack mounting (See (*4)) F
Large LCD, 1/2 x 19" rack for rack mounting (See (*4)) J

Terminal block for BIO and PWS


Compression plug type terminal 0
BI/BO module
Choice from BI/BO table page 27 to 28 1×BIO module 1 *
2×BIO modules 2 *
3×BIO modules 3 *

Terminal block for BIO and PWS


Ring type terminal 1
BI/BO module
Choice from BI/BO table page 27 1×BIO modules 1 *
2×BIO modules 2 *

Configuration to be continued to page 23.

(*1) Binary inputs are intended for use with DC power source only.
The power supply supervision function is intended for use with DC power source only. It should be disabled
when AC power supply is applied in order to prevent spurious alarms.
(*2) Refer to pages 25 – 26, and select the appropriate CT configuration when you require another rated current
configuration.
(*3) Refer to page 32. For PRP/HSR/RSTP protocol with IEC 61850, choose “L” or “N” code at position E. For
hot/standby configuration or single port configuration with IEC 61850, choose other codes at position E.
(*4) For 19” rack panel mounting, accessories of joint kits are available. (See Figure 14 on page-38)

22
[Hardware selection (2)]continue Positions
- 7 8 - 9 A B - C D - E F - G H - J K L
Configurations G R T 2 0 0 - 4 - - 0 0 - - 3 - 0

Outline
Standard LCD, 3/4 x 19" rack for flush mounting 3
Large LCD, 3/4 x 19" rack for flush mounting 7
Standard LCD, 3/4 x 19" rack for rack mounting (See (*4)) G
Large LCD, 3/4 x 19" rack for rack mounting (See (*4)) K

Terminal block for BIO and PWS


Compression plug type terminal 0
BI/BO module
Choice from BI/BO table page 27 to 30 1×BIO module 1 *
2×BIO modules 2 *
3×BIO modules 3 *
4×BIO modules 4 *
5×BIO modules 5 *
6×BIO modules 6 *

Terminal block for BIO and PWS


Ring type terminal 1
BI/BO module
Choice from BI/BO table page 27 to 29 1×BIO module 1 *
2×BIO modules 2 *
3×BIO modules 3 *
4×BIO modules 4 *

Outline
Standard LCD, 1/1 x 19" rack for flush/rack mounting 4
Large LCD, 1/1 x 19" rack for flush/rack mounting 8

Terminal block for BIO and PWS


Compression plug type terminal 0
BI/BO module
Choice from BI/BO tablepage 27 to 31 1×BIO module 1 *
2×BIO modules 2 *
3×BIO modules 3 *
4×BIO modules 4 *
5×BIO modules 5 *
6×BIO modules 6 *
7×BIO modules 7 *
8×BIO modules 8 *

Terminal block for BIO and PWS


Ring type terminal 1
BI/BO module
Choice from BI/BO table page 27 to 31 1×BIO module 1 *
2×BIO modules 2 *
3×BIO modules 3 *
4×BIO modules 4 *
5×BIO modules 5 *
6×BIO modules 6 *
7×BIO modules 7 *

23
[Hardware selection (3)] Positions
- 7 8 - 9 A B - C D - E F - G H - J K L
Configurations G R T 2 0 0 - 5 - - 0 0 - - 3 - 0

Application of power system


5 x three-phase CT + 3 x zero-phase CT
5
2 x three-phase VT (Module No. 44 and 48)
DC rated voltage
110-250 Vdc or 100-220Vac (See (*1)) 1
24-60 Vdc 3
System Frequency
50Hz 1
60Hz 2
Rated Phase Currents (Default settings) (*2)
1A 1
5A 2

Rated Neutral Currents (Default settings) (*2)


1A 1
5A 2

Number of Serial and /or Ethernet Communication


and/or Time Sync Port(s)
Refer to Number of Communication port Table (See (*3))

Outline
Standard LCD, 1/1 x 19" rack for flush/rack mounting 4
Large LCD, 1/1 x 19" rack for flush/rack mounting 8

Terminal block for BIO and PWS


Compression plug type terminal 0
BI/BO module
Choice from BI/BO tablepage 27 to 31 1×BIO module 1 *
2×BIO modules 2 *
3×BIO modules 3 *
4×BIO modules 4 *
5×BIO modules 5 *
6×BIO modules 6 *
7×BIO modules 7 *
8×BIO modules 8 *

Terminal block for BIO and PWS


Ring type terminal 1
BI/BO module
Choice from BI/BO table page 27 to 30 1×BIO module 1 *
2×BIO modules 2 *
3×BIO modules 3 *
4×BIO modules 4 *
5×BIO modules 5 *

(*1) Binary inputs are intended for use with DC power source only.
The power supply supervision function is intended for use with DC power source only. It should be disabled
when AC power supply is applied in order to prevent spurious alarms.
(*2) Refer to pages 25 – 26, and select the appropriate CT configuration when you require another rated current
configuration.
(*3) Refer to page 32. For PRP/HSR/RSTP protocol with IEC 61850, choose “L” or “N” code at position E. For
hot/standby configuration or single port configuration with IEC 61850, choose other codes at position E.

24
CT configuration

Rated phase currents

3 x three-phase CT (When position “7“ = 3)


1CT group 2CT group 3CT group Ordering No.
(1Ia, 1Ib, 1Ic) (2Ia, 2Ib, 2Ic) (3Ia, 3Ib, 3Ic) (Position “K”)
1A 1A 1A 1
5A 5A 5A 2
1A 1A 5A 6
1A 5A 1A A
1A 5A 5A E
5A 1A 1A J
5A 1A 5A N
5A 5A 1A S

4 x three-phase CT (When position “7“ = 4)


1CT group 2CT group 3CT group 4CT group Ordering No.
(1Ia, 1Ib, 1Ic) (2Ia, 2Ib, 2Ic) (3Ia, 3Ib, 3Ic) (4Ia, 4Ib, 4Ic) (Position “K”)
1A 1A 1A 1A 1
5A 5A 5A 5A 2
1A 1A 1A 5A 4
1A 1A 5A 1A 6
1A 1A 5A 5A 8
1A 5A 1A 1A A
1A 5A 1A 5A C
1A 5A 5A 1A E
1A 5A 5A 5A G
5A 1A 1A 1A J
5A 1A 1A 5A L
5A 1A 5A 1A N
5A 1A 5A 5A Q
5A 5A 1A 1A S
5A 5A 1A 5A U
5A 5A 5A 1A W

25
5 x three-phase CT (When position “7“ = 5)
1CT group 2CT group 3CT group 4CT group 5CT group Ordering No.
(1Ia, 1Ib, 1Ic) (2Ia, 2Ib, 2Ic) (3Ia, 3Ib, 3Ic) (4Ia, 4Ib, 4Ic) (5Ia, 5Ib, 5Ic) (Position “K”)
1A 1A 1A 1A 1A 1
5A 5A 5A 5A 5A 2
1A 1A 1A 1A 5A 3
1A 1A 1A 5A 1A 4
1A 1A 1A 5A 5A 5
1A 1A 5A 1A 1A 6
1A 1A 5A 1A 5A 7
1A 1A 5A 5A 1A 8
1A 1A 5A 5A 5A 9
1A 5A 1A 1A 1A A
1A 5A 1A 1A 5A B
1A 5A 1A 5A 1A C
1A 5A 1A 5A 5A D
1A 5A 5A 1A 1A E
1A 5A 5A 1A 5A F
1A 5A 5A 5A 1A G
1A 5A 5A 5A 5A H
5A 1A 1A 1A 1A J
5A 1A 1A 1A 5A K
5A 1A 1A 5A 1A L
5A 1A 1A 5A 5A M
5A 1A 5A 1A 1A N
5A 1A 5A 1A 5A P
5A 1A 5A 5A 1A Q
5A 1A 5A 5A 5A R
5A 5A 1A 1A 1A S
5A 5A 1A 1A 5A T
5A 5A 1A 5A 1A U
5A 5A 1A 5A 5A V
5A 5A 5A 1A 1A W
5A 5A 5A 1A 5A X
5A 5A 5A 5A 1A Y

Rated neutral currents

(When position “7“ =3) Ordering No.


1NCT 2NCT (Position “L”)
1A 1A 1
5A 5A 2
1A 5A A
5A 1A J

(When position “7“ =5) Ordering No.


1NCT 2NCT 3NCT (Position “L”)
1A 1A 1A 1
5A 5A 5A 2
1A 1A 5A 6
1A 5A 1A A
1A 5A 5A E
5A 1A 1A J
5A 1A 5A N
5A 5A 1A S

26
Number of BI/BO

1 x I/O module
Number of BI/BO Ordering No.
(Position “A” to

Semi-fast BO
“B”)
Independent

Independent
BI (variable)

Hybrid BO
Common Configuration

Fast-BO

BO
BI

BI

7 - - - 6 4 - 11 1xBIO1
12 - - - 3 2 - 12 1xBIO2
8 - - 6 - 2 - 13 1xBIO3
- 6 - - - 2 6 14 1xBIO4
18 - - - - - - 15 1xBI1
- 12 - - - - - 16 1xBI2
- - 32 - - - - 17 1xBI3

Other Configuration ZZ To be specified at


ordering

2 x I/O module
Number of BI/BO Ordering No.
(Position “A” to
Semi-fast BO

“B”)
Independent

Independent
BI (variable)

Heavy duty

Configuration
Common

Fast-BO

BO

BO
BI

BI

- - 32 - 6 12 - 21 1xBI3+1xBO1
7 - 32 - 6 4 - 22 1xBI3+1xBIO1
12 - 32 - 3 2 - 23 1xBI3+1xBIO2
18 - - - 6 12 - 24 1xBI1+1xBO1
25 - - - 6 4 - 25 1xBI1+1xBIO1
30 - - - 3 2 - 26 1xBI1+1xBIO2
8 - - 6 6 14 - 27 1xBO1+1xBIO3
15 - - 6 6 6 - 28 1xBIO1+1xBIO3
7 - - - 12 16 - 29 1xBO1+1xBIO1
16 - - 12 - 4 - 2A 2xBIO3
- - 32 - - - 16 2B 1xBI3+1xBO2
- 12 - - 6 12 - 2C 1xBI2 +1xBO1
20 - - 6 3 4 - 2E 1xBIO2 +1xBIO3
12 - - - 9 14 - 2F 1xBO1+1xBIO2
8 12 6 2 2G 1xBI2 +1xBIO3

Other Configuration ZZ To be specified at


ordering

27
3 x I/O module
Number of BI/BO Ordering No.
(Position “A” to

Semi-fast BO
“B”)
Independent

Independent
BI (variable)

Heavy duty
Configuration

Common

Fast-BO

BO

BO
BI

15 - BI- 6 12 18 - 31 1xBO1+1xBIO1+1xBIO3
20 - - 6 9 16 - 32 1xBO1+1xBIO2+1xBIO3
23 - - 12 6 8 - 33 1xBIO1+2xBIO3
26 - - 6 6 14 - 34 1xBI1+1xBO1+1xBIO3
8 - 32 6 6 14 - 35 1xBI3+1xBO1+1xBIO3
24 - - 18 - 6 - 36 3xBIO3
25 - - - 12 16 - 37 1xBI1+1xBO1+1xBIO1
36 - - - 6 12 - 39 2xBI1+1xBO1
- 24 - - 6 12 - 3A 2xBI2+1xBO1
18 6 - - 6 14 6 3B 1xBI1+1xBO1+1xBIO4
7 - 32 - 6 4 16 3C 1xBI3+1xBIO1+1xBO2
7 - 32 - 12 16 - 3D 1xBI3+1xBO1+1xBIO1
- - 32 - 6 12 16 3E 1xBI3+1xBO1+1xBO2
16 - - 12 6 16 - 3G 1xBO1+2xBIO3
- 6 32 - 6 14 6 3H 1xBI3+1xBO1+1xBIO4
26 - - 6 6 14 - 3J 1xBO1+1xBIO3+1xBI1 (*1)
- - 64 - 6 12 - 3K 2xBI3+1xBO1
14 - 32 - 12 8 - 3L 1xBI3+2xBIO1
- - 96 - - - - 3M 3xBI3
8 12 - 6 6 14 - 3N 1xBI2+1xBO1+1xBIO3
- - 32 - 12 24 - 3P 1xBI3 + 2xBO1
8 - 32 6 6 14 - 3Q 1xBO1+1xBIO3+1xBI3 (*2)
16 12 12 4 3S 1xBI2+2xBIO3

Other Configuration ZZ To be specified at ordering


Note:
(*1) module arrangement is different from 34
(*2) module arrangement is different from 35

28
4 x I/O modules
Number of BI/BO Ordering No.
(Position “A” to

Semi-fast BO
“B”)
Independent

Independent
BI (variable)

Heavy duty
Configuration

Common

Fast-BO

BO

BO
BI

BI
26 - - 6 12 26 - 41 1xBI1+2xBO1+1xBIO3
32 - - 24 - 8 - 42 4xBIO3
8 - 32 6 12 26 - 43 1xBI3+2xBO1+1xBIO3
- - 64 - 12 24 - 44 2xBI3+2xBO1
54 - - - 6 12 - 46 3xBI1+1xBO1
1xBI3+1xBO1+1xBIO2
20 - 32 6 9 16 - 47
+1xBIO3
1xBO1+1xBI1+1xBO1
26 - - 6 12 26 - 48
+1xBIO3 (*3)
20 6 15 28 49 2xBO1+1xBIO2+1xBIO3
34 - - 12 6 16 - 4B 1xBI1+1xBO1+2xBIO3
- - 64 - - - 32 4C 2xBI3+2xBO2
21 - 32 - 18 12 - 4D 1xBI3+3xBIO1
- - 128 - - - - 4E 4xBI3
7 96 6 4 4F 3xBI3+1xBIO1
8 24 - 6 6 14 - 4G 2xBI2 +1xBO1 +1xBIO3
- - 32 - 18 36 - 4H 1xBI3 + 3xBO1
1xBI1 + 1xBI2 + 1xBO1
26 12 - 6 6 14 - 4J
+ 1xBIO3
24 - 32 - 12 16 - 4K 1xBI3+1xBO1+2xBIO2
15 - - 6 18 30 - 4L 2xBO1+1xBIO1+1xBIO3
7 - - - 24 40 - 4M 3xBO1+1xBIO1
36 - - - 12 24 - 4N 2xBI1+2xBO1
8 - 64 6 6 14 - 4P 2xBI3+1xBO1+1xBIO3
36 - - - 6 12 16 4Q 2xBI1+1xBO1+1xBO2
44 - - 6 6 14 - 4R 2xBI1+1xBO1+1x BIO3

Other Configuration ZZ To be specified at ordering


Note:
(*3) module arrangement is different from 41.

29
5 x I/O modules
Number of BI/BO Ordering No.
(Position “A” to

Semi-fast BO
“B”)
Independent

Independent
BI (variable)

Heavy duty
Configuration

Common

Fast-BO

BO

BO
BI

BI
1xBI1+1xBIO1+1xBIO3
33 - - 6 6 6 32 51
+2xBO2
44 - - 6 12 26 - 52 2xBI1+2xBO1+1xBIO3
25 - 96 - 6 4 - 53 1xBI1+3xBI3+1xBIO1
8 - 96 6 6 14 - 54 3xBI3+1xBO1+1xBIO3
62 - - 6 6 14 - 56 3xBI1+1xBO1+1xBIO3
54 6 - - 6 14 6 57 3xBI1+1xBO1+1xBIO4
- - 96 - 12 24 - 5B 3xBI3+2xBO1
- - 128 - 6 12 - 5E 4xBI3+1xBO1
- - 160 - - - - 5F 5xBI3
2xBI1+1xBI2+1xBO1
44 12 - 6 6 14 - 5G
+1xBIO3
15 - - 6 24 42 - 5H 3xBO1+1xBIO1+1xBIO3
- - 64 - 18 36 - 5J 2xBI3+3xBO1
- - - - 30 60 - 5L 5xBO1
42 - - 18 6 18 - 5P 1xBI1+1xBO1+3xBIO3
1xBI1+1xBO1+1xBIO1
41 - - 12 12 20 - 5Q
+2xBIO3
8 - 64 6 - 2 32 5R 2xBI3+1xBIO3+2xBO2
1xBI2+2xBI3+1xBIO3
8 12 64 6 - 2 16 5S
+1xBO2

Other Configuration ZZ To be specified at ordering

6 x I/O modules
Number of BI/BO Ordering No.
(Position “A” to
Semi-fast BO

“B”)
Independent

Independent
BI (variable)

Heavy duty

Configuration
Common

Fast-BO

BO

BO
BI

BI

2xBI1+2xBO1+1xBIO1
51 - - 6 18 30 - 61
+1xBIO3
8 - 96 6 12 26 - 62 3xBI3+2xBO1+1xBIO3
- - 128 - 12 24 - 63 4xBI3+2xBO1
8 - 128 6 6 14 - 64 4xBI3+1xBO1+1xBIO3
52 - - 12 - 4 32 69 2xBI1+2xBIO3+2xBO2
52 - - 12 12 28 - 6A 2xBI1+2xBO1+2xBIO3
36 - - - 24 48 - 6B 2xBI1+4xBO1
36 - 64 - 12 24 - 6C 2xBI1+2xBI3+2xBO1
44 - - 6 18 38 - 6D 2xBI1+3xBO1+1xBIO3
- - 160 - 6 12 - 6E 5xBI3+1xBO1
7 - 160 - 6 4 - 6F 5xBI3+1xBIO1
8 - 64 6 - 2 48 6G 2xBI3+1xBIO3+3xBO2

Other Configuration ZZ To be specified at ordering

30
7 x I/O modules
Number of BI/BO Ordering No.
(Position “A” to

Semi-fast BO
“B”)
Independent

Independent
BI (variable)

Heavy duty
Configuration

Common

Fast-BO

BO

BO
BI

BI
80 - - 6 12 26 - 71 4xBI1+2xBO1+1xBIO3
72 6 - - 12 26 6 72 4xBI1+2xBO1+1xBIO4
8 - 96 6 18 38 - 73 3xBI3+3xBO1+1xBIO3
- 6 96 - 18 38 6 74 3xBI3+3xBO1+1xBIO4
- 60 - - 6 12 16 78 5xBI2+1xBO1+1xBO2
- - 160 - 12 24 - 79 5xBI3+2xBO1
54 - 64 - 12 24 - 7B 3xBI1 + 2xBI3 + 2xBO1
- - 128 - 18 36 - 7D 4xBI3+3xBO1
7 - 160 - 12 16 - 7E 5xBI3+1xBO1+1xBIO1
- - 192 - 6 12 - 7F 6xBI3+1xBO1
7 - 192 - 6 4 - 7G 6xBI3+1xBIO1
- - 224 - - - - 7H 7xBI3
8 - 96 6 - 2 48 7L 3xBI3+1xBIO3+3xBO2

Other Configuration ZZ To be specified at ordering

8 x I/O modules
Number of BI/BO Ordering No.
(Position “A” to
Semi-fast BO

“B”)
Independent

Independent
BI (variable)

Heavy duty

Configuration
Common

Fast-BO

BO

BO
BI

BI

- - 160 - 18 36 - 83 5xBI3+3xBO1
- 60 - - 6 12 32 87 5xBI2+1xBO1+2xBO2
8 - 128 6 18 38 - 88 4xBI3+3xBO1+1xBIO3
- - 256 - - - - 8C 8xBI3
7 - 224 - 6 4 - 8G 7xBI3+1xBIO1
- - 192 - 12 24 - 8H 6xBI3+2xBO1
7 - 192 - 12 16 - 8J 6xBI3+1xBO1+1xBIO1
7 - 96 - 30 52 - 8M 3xBI3+4xBO1+1xBIO1
- - 128 - 24 48 - 8N 4xBI3+4xBO1

Other Configuration ZZ To be specified at ordering

Please contact with our sales staffs when you require “other configuration (number: ZZ)” that is not indicated in the ordering
sheet above.

31
Communication port Table
Serial and/or Ethernet and/or Time Synch port
IEC 60870-5-103 IEC 61850-8-1
Ordering No.

100Base-FX

100Base-LX
1000Base-T
(Position “E” Remark

Fibre optic
(for serial)

100Base-
to “F”)
RS485

IRIG-B
TX/
1 14
1 1J
1 1K
1 1 34
1 1 3J
1 1 3K
2 46 Hot/Standby
1 1 4C
1 1 4G
2 4L
Hot/Standby
2 4M
1 1 4N
1 1 4Q
1 1 4S
1 1 4U
2 1 66 Hot/Standby
1 1 1 6C
1 1 1 6G
2 1 6L
Hot/Standby
2 1 6M
1 1 1 6N
1 1 1 6Q
1 1 1 6S
1 1 1 6U
1 2 7D
1 2 7H
1 2 7P
Hot/Standby
1 2 7R
1 2 7T
1 2 7U
2 L6
1 2 LD
1 2 LH
2 LL
2 LM
1 2 LP
1 2 LR
1 2 LT
For
1 2 LV
PRP/HSR/
2 1 N6 RSTP
1 2 1 ND
1 2 1 NH
2 1 NL
2 1 NM
1 2 1 NP
1 2 1 NR
1 2 1 NT
1 2 1 NV

32
[Software Ordering]

1 2 3 4 5 6 7 M G N E F U 9 Q

Configurations G R T 2 0 0 - 0 3 - - E

Analog inputs
Assignment on position “7”
Function Block
Refer to Function Table
Number of Serial and/or Ethernet
Communication and/or Time Sync Port(s)
Assignment on position “E” (See (*1))
Selection of Serial and/or Ethernet
Communication Port(s)
Assignment on position “F” (See (*1))
Protocol
IEC60870-5-103 or IEC61850 1
IEC61850 2
Outline
Assignment on position “9”
Language
English E

(*1) For PRP/HSR/RSTP protocol with IEC 61850, choose “L” or “N” code at position E. For hot/standby configuration
or single port configuration with IEC 61850, choose other codes at position E.

33
FUNCTION TABLE
Function Description Ordering No. (Position 'G & N')
Block 3D 3E 3F
2 x 3ph-CT ● ● ●
DIF 3 x 3ph-CT ● ● ●
Current differential protection
(87) 4 x 3ph-CT - ● ●
5 x 3ph-CT - - ●
REF Low-impedance restricted earth 2 Stage ● - ●
(87N) fault protection 3 Stage - - ●
Non-directional definite / inverse
OC 8 stages ●
time overcurrent protection
(50/51/67) ● ●
Directional definite / inverse time
-
overcurrent protection
Non-directional definite / inverse
EF time earth fault protection 8 stages ●
(50G/51G/ (using phase currents)
● ●
67G) Directional definite / inverse time
overcurrent protection -
(using phase currents)
Non-directional definite / inverse
EFIn
time earth fault protection 4 stages ● - ●
(50N/51N)
(using neutral current)
Non-directional negative-
4 stages ● ● ●
OCN sequence overcurrent protection
(46) Directional negative- sequence
-
overcurrent protection
BCD
Broken conductor protection ● ● ●
(46BC)
THM THM trip
Thermal overload protection ● ● ●
(49) THM alarm
ICD
Inrush current detector function ● ● ●
CBF CBF re-trip
Circuit breaker failure protection ● ● ●
(50BF) CBF trip
Under-frequency /
FRQ/DFRQ
Over-frequency / Rate of change 6 stages ●(*1) ●(*1) ●(*1)
(81U/81O)
of frequency protection
VPH V/f trip
Over-excitation protection ●(*2) ●(*2) ●(*2)
(24) V/f alarm
MECH. Trip and/or Indication of external
32 stages ● ● ●
TRIP devices

(*1) Available for phase-to-phase or


3 x three-phase CT +

4 x three-phase CT +

5 x three-phase CT +
2 x zero-phase CT +

3 x zero-phase CT +
1 x three-phase VT

2 x three-phase VT
phase-to-ground voltage inputs
1 x one-phase VT

(*2) Available for phase-to-phase or


3phase-to-ground voltage inputs

Ordering No. Ordering No. Ordering No.


(Position (Position (Position
'7'=3) '7'=4) '7'=5)

34
DIMENSION AND PANEL CUT-OUT (1/2 size)

(Panel cut-out)
Note: For a rack mount unit, there are holes for joint kits assembling on top and bottom of the unit.
Figure 11 – Dimension and Panel Cut-out – 1/2 x 19’’ case size

- 35 -
DIMENSION AND PANEL CUT-OUT (3/4 size)

(Panel cut-out)
Note: For a rack mount unit, there are holes for joint kits assembling on top and bottom of the unit.
Figure 12 – Dimension and Panel Cut-out – 3/4 x 19’’ case size for flush mounting type

- 36 -
DIMENSION AND PANEL CUT-OUT (1/1 size)

(Panel cut-out)

Note: For a rack mount unit, there


are holes for joint kits assembling on
top and bottom of the unit.

Figure 13 – Dimension and Panel Cut-out – 1/1 x 19” case size for flush mounting type

- 37 -
19” RACK MOUNTING JOINT KITS ATTACHMENT

<Panel mounting kits – only for compressed terminal type racks>


Name Code
Joint kits for single 1/3 x 19” size rack EP-201
Joint kits for two 1/3 x 19” size racks EP-202
Joint kits for three 1/3 x 19” size racks EP-203
Joint kits for single 1/2 x 19” size rack EP-204
Joint kits for two 1/2 x 19” size racks EP-205
Joint kits for single 3/4 x 19” size rack EP-206

EP-204 (single 1/2 x 19” size rack) EP-205 (two 1/2 x 19” size racks)

Figure 14 – Joint kits example for 19” rack panel mounting

- 38 -
CONNECTIONS DIAGRAM (COMPRESSION PLUG TYPE)

BI1 A BI2 A BI3 A BO1 A BO2 A

(+) 1 (+) 1 (+) 1 1 1 (+)


BI1
BI1 BI1 BO1(*2) BO1(*3)
(-) 2 (-) 2 (+) 2 2 2 (-)
BI2
(+) 3 (+) 5 (+) 3 3 3 (+)
BI3
BI2 BI2 BO2(*2) BO2(*3)
(-) 4 (-) 6 (+) 4 4 4 (-)
BI4
(+) 5 (+) 7 (+) 5 5 5 (+)
BI5
BI3 BI3 BO3(*2) BO3(*3)
(-) 6 (-) 8 (+) 6 6 6 (-)
BI6
(+) 7 (+) 11 (+) 7 7 7 (+)
BI7
BI4 BI4 BO4(*2) BO4(*3)
(-) 8 (-) 12 (+) 8 8 8 (-)
BI8
(+) 9 (+) 13 (+) 9 9 9 (+)
BI5 BI9
(-) 10 BI5 (+) 10 BO5(*2) BO5(*3)
(-) 14 10 10 (-)
BI10
(+) 11 (+) 17 (+) 11 11 11 (+)
BI11
BI6 BI6 BO6(*2) BO6(*3)
(-) 12 (-) 18 (+) 12 12 12 (-)
BI12
(+) 13 (+) 21 (+) 13 13 13 (+)
BI13
BI7 BI7 BO7 BO7(*3)
(-) 14 (-) 22 (+) 14 14 14 (-)
BI14
(+) 15 (+) 25 (+) 15 15 15 (+)
BI15
BI8 BI8 BO8 BO8(*3)
(-) 16 (-) 26 (+) 16 16 16 (-)
BI16
(+) 17 (+) 27 (+) 17 17 17 (+)
BI9 BI17
(-) 18 BI9 (+) 18 BO9 BO9(*3)
(-) 28 18 18 (-)
BI18
(+) 21 (+) 31 (+) 21 21 21 (+)
BI19
BI10 BI10 BO10 BO10(*3)
(-) 22 (-) 32 (+) 22 22 22 (-)
BI20
(+) 23 (+) 33 (+) 23 23 23 (+)
BI21
BI11 BI11 BO11 BO11(*3)
(-) 24 (-) 34 (+) 24 24 24 (-)
BI22
(+) 25 (+) 37 (+) 25 25 25 (+)
BI23
BI12 BI12 BO12 BO12(*3)
(-) 26 (-) 38 (+) 26 26 26 (-)
BI24
(+) 27 (+) 27 27 (+)
27
BI25
BI13 BO13 BO13(*3)
(-) 28 (+) 28 28 28 (-)
BI26
(+) 29 (+) 29 29 (+)
29
BI27
BI14 BO14 BO14(*3)
(-) 30 (+) 30 30 30 (-)
BI28
(+) 31 (+) 31 31 (+)
31
BI15 BI29
(-) 32 (+) 32 BO15 BO15(*3)
32 32 (-)
BI30
(+) 33 (+) 33 33 (+)
33
BI31
BI16 BO16 BO16(*3)
(-) 34 (+) 34 34 34 (-)
BI32
(+) 35 (-) 35
35
BI17 BO17
(-) 36 (-) 36
36
(+) 37 (-) 37
37
BI18
(-) 38 (-) 38 BO18
38

(*2) Semi-fast BO
(*3) Hybrid BO

Figure 15 – Binary input board and binary output module (for compression plug type terminal)

- 39 -
CONNECTIONS DIAGRAM (COMPRESSION PLUG TYPE)

BIO1 A BIO2 A BIO3 A BIO4 A

(+) 1 (+) 1 (+) 1 (+) 1


BI1 BI1 BI1 BI1
(-) 2 (-) 2 (-) 2 (-) 2

(+) 3 (+) 3 (+) 3 (+) 3


BI2 BI2 BI2 BI2
(-) 4 (-) 4 (-) 4 (-) 4

(+) 5 (+) 5 (+) 5 (+) 5


BI3 BI3 BI3 BI3
(-) 6 (-) 6 (-) 6 (-) 6

(+) 7 (+) 7 (+) 7 (+) 7


BI4 BI4 BI4 BI4
(-) 8 (-) 8 (-) 8 (-) 8

(+) 9 (+) 9 (+) 9 (+) 9


BI5 BI5 BI5 BI5
(-) 10 (-) 10 (-) 10 (-) 10

(+) 11 (+) 11 (+) 11 (+) 11


BI6 BI6 BI6 BI6
(-) 12 (-) 12 (-) 12 (-) 12

(+) 13 (+) 13 (+) 13


BI7 BI7 BI7
(-) 14 (-) 14 (-) 14

15 (+) 15 (+) 15
BO1(*2) BI8 BI8
16 (-) 16 (-) 16

17 (+) 17 17 (+)
BO2(*2) BI9 BO1(*3)
18 (-) 18 18 (-)

21 (+) 21 21 21 (+)
BO3(*2) BI10 BO1(*1) BO2(*3)
22 (-) 22 22 22 (-)

23 (+) 23 23 23 (+)
BO4(*2) BI11 BO2(*1) BO3(*3)
24 (-) 24 24 24 (-)

25 (+) 25 25 25 (+)
BO5(*2) BI12 BO3(*1) BO4(*3)
26 (-) 26 26 26 (-)

27 27 27 27 (+)
BO6(*2) BO1(*2) BO4(*1) BO5(*3)
28 28 28 28 (-)

29 29 29 29 (+)
BO7 BO2(*2) BO5(*1) BO6(*3)
30 30 30 30 (-)

31 31 31
BO8 BO3(*2) BO6(*1)
32 32 32

33 33 33 33
BO9 BO4 BO7 BO7
34 34 34 34

35 35 35 35
37 37 37 37

36 36 36 36
BO10 BO5 BO8 BO8
38 38 38 38

(*1) Fast BO
(*2) Semi-fast BO
(*3) Hybrid BO

Figure 16 – Combined binary input and output module (for compression plug type terminal)

- 40 -
CONNECTIONS DIAGRAM (COMPRESSION PLUG TYPE)

PWS1 A

2
4

3
FAIL1
1

8
10

9
FAIL2
7

(+) 29
30
DC/DC

(-) 31
32

35

36

37

38
Protective Earth

Figure 17 –DC/DC module

(for compression plug type terminal)

- 41 -
CONNECTIONS DIAGRAM

CT/VT module

VCT44B VCT48B VCT49B

1 1 1
V Va-1VT Va
2 2 2

3 3
Vb-1VT Vb
4 4

5 5
5
Ia-1CT Vc-1VT Vc
6 6
6

7 7
Ib-1CT 1Ia
8 8

9 9 9
Ic-1CT Va-2VT 1Ib
10 10 10
11
11 11
Vb-2VT
Ia-2CT 12 1Ic
12 12
13
13 13
Vc-2VT
Ib-2CT 14 2Ia
14 14

15 15
Ic-2CT 2Ib
16 16

17 17 17
Ia-3CT Ia-4CT 2Ic
18 18 18

19 19 19
Ib-3CT Ib-4CT 3Ia
20 20 20

21 21 21
Ic-3CT Ic-1CT 3Ib
22 22 22

23 23 23
IN-1NCT
Ia-5CT 3Ic
24 or Ia-4CT 24 24

25 25 25
IN-2NCT
Ib-5CT 1IN
26 or Ib-4CT 26 26

27 27 27
IN-3NCT
Ic-5CT 2IN
28 or Ic-4CT 28 28

30 30 30

No.35 Module No.44 Module No.48 Module No.49


(CT x 6 + VT (CT x 12 + VT x 1) (CT x 6 + VT x 6) (CT x 11 + VT x 3)
Only fo For 1/2, 3/4 and 1/1 Only for 1/1 rack For 1/2, 3/4 and 1/1

Figure 18 – CT/VT module

- 42 -
Typical arrangement of each module (1/2 rack size)

[IO#3] [IO#2] [IO#1] [VCT#1]


T4 T3 T2 T1 VC1
PWS1 A BIO3 A BO1 A
BI1 A
(+) 1 1 (+) 1
C11 1
VCT44B

2 BI1 BO1(*2) 100BASE-TX


(-) 2 2 BI1 V
4 (-) 2 2
(+) 3 3
3 (+) 3
FAIL1 BI2 BO2(*2)
(-) 4 4 BI2
1 (-) 4
(+) 5 5 (+) 5
5
BI3 BO3(*2) BI3
(-) 6 6 (-) 6 Ia-1CT
8 6
10 (+) 7 7 (+) 7
7
9
BI4 BO4(*2) BI4
(-) 8 8 Ib-1CT
FAIL2
7 (+) 9 9
(-)

(+)
8

9
C12 8

9
BI5 BO5(*2) BI5
(-) 10 10 (-) 10 Ic-1CT
10
(+) 11 11 (+) 11
11
BI6 BO6(*2) BI6
(-) 12 12 (-) 12 Ia-2CT
12
(+) 13 13 (+) 13
13
BI7 BO7 BI7
(-) 14 14 (-) 14 Ib-2CT
14
(+) 15 15 (+) 15

(-) 16
BI8 BO8
16 (-) 16
BI8 C13 15
Ic-2CT
16
17 (+) 17
17
BO9 BI9 Ia-3CT
18 (-) 18
18
21 21 (+) 21 19
BO1(*1) BO10 BI10 Ib-3CT
22 22 (-) 22 20
23 23 (+) 23 21
BO2(*1) BO11 BI11 Ic-3CT
24 24 (-) 24 22

BO3(*1)
25
BO12
25 (+) 25
BI12
C14 23
IN-1NCT
26 26 (-) 26 24 or Ia-4CT
27 27 (+) 27
25
BI13 IN-2NCT
BO4(*1) BO13 (-) 28
28 28 26 or Ib-4CT
(+) 29
29 29 (+) 29
30 27
DC/DC BI14 IN-3NCT
BO5(*1) BO14 (-) 30
30 30 28 or Ic-4CT
(-) 31 31 31 (+) 31
32 BO6(*1) BO15 BI15
32 32 (-) 32 30
35

36
33 33 (+) 33
BI16
C15
BO7 BO16 (-) 34
34 34
37
35 (+) 35
38 35
37 BO17 BI17
36 (-) 36

36 (+) 37
BO8 37
FG
38 BO18 BI18
(-) 38
38

●FG ●FGB ●FGA ●FG1 ●E

Figure 19 – rear view (1/2 rack size)

- 43 -
Typical arrangement of each module (3/4 rack size)

[IO#6] [IO#5] [IO#4] [IO#3] [IO#2] [IO#1] [VCT#1]


T4 T3 T2 T1 VC1
PWS1 A BIO3 A BO1 A BI1 A
C11 VCT44B

(+) 1 1 (+) 1 100BASE-FX 1


2 BI1 BO1(*2) (-) 2
BI1 V
(-) 2 2 2
4
(+) 3 3 (+) 3
3 TX
FAIL1 BI2 BO2(*2) BI2
(-) 4 4 (-) 4
1
(+) 5 5 (+) 5 5
BI3 BI3 RX Ia-1CT
(-) 6
BO3(*2) (-) 6 6
6
8
10

9
(+)

(-)
7

8
BI4 BO4(*2)
7

8
(+)

(-)
7

8
BI4
C12 7

8
Ib-1CT
FAIL2 100BASE-FX
7 (+) 9 9 (+) 9 9
BI5 BO5(*2) BI5 Ic-1CT
(-) 10 10 (-) 10 10

(+) 11 TX
(+) 11 11 11
BI6 BO6(*2) BI6 Ia-2CT
(-) 12 12 (-) 12 12

(+) 13 13 (+) 13 RX 13
BI7 BO7 BI7 Ib-2CT
(-) 14 14 (-) 14 14

(+) 15 15 (+) 15 C13 15


BI8 BO8 BI8 Ic-2CT
(-) 16 16 (-) 16 16

17 (+) 17 17
BO9 BI9 Ia-3CT
18 (-) 18 18

21 21 (+) 21 19
BO1(*1) BO10 BI10 Ib-3CT
22 22 (-) 22 20

23 23 (+) 23 21
BO2(*1)
24
BO11
24 (-) 24
BI11
C14 22
Ic-3CT

25 25 (+) 25 23
IN-1NCT
BO3(*1) BO12 BI12
26 26 (-) 26 24 or Ia-4CT

27 (+) 27 25
27
IN-2NCT
BO4(*1) BO13 BI13
28 28 (-) 28 26 or Ib-4CT
(+) 29
29 (+) 29 27
29
30 IN-3NCT
DC/DC BO5(*1) BO14 BI14
30 30 (-) 30 28 or Ic-4CT
(-) 31
32
31 31
(+) 31
BI15
C15
BO6(*1) BO15 (-) 32
32 32 30
35
(+) 33
33 33
36 BI16
BO7 BO16 (-) 34
34 34
37
(+) 35
38 35 35
37 BI17
BO17 (-) 36
36
36 (+) 37
BO8 37
FG
38 BI18
BO18 (-) 38
38

●FG ●FGD ●FGC ●FGB ●FGA ●FG1 ●E

Figure 20 – rear view (3/4 rack size)

- 44 -
Typical arrangement of each module (1/1 rack size)

[IO#8] [IO#7] [IO#6] [IO#5] [IO#4] [IO#3] [IO#2] [IO#1] [VCT#1] [VCT#2]
T9 T8 T7 T6 T5 T4 T3 T2 T1 VC1 VC2
PWS1 A BIO3 A BO1 A BI1 A VCT44B VCT48B

2
(+) 1
BI1 BO1(*2)
1 (+) 1
BI1
C11 1
No use
1
Va-1VT
(-) 2 2 (-) 2 100BASE-TX/ 2 2
4
1000BASE-T
(+) 3 3 (+) 3 3
3
FAIL1 BI2 BO2(*2) BI2 Vb-1VT
(-) 4 4 (-) 4 4
1
(+) 5 5 (+) 5 5 5

BI3 BO3(*2) BI3 Ia-1CT Vc-1VT


(-) 6 6 (-) 6 6 6
8
10 (+) 7 7 (+) 7 7
BI4 BO4(*2) BI4 Ib-1CT
FAIL2
9

7
(-)

(+)
8

9
8

9
(-)

(+)
8

9
C12 8

9 9

BI5 BO5(*2) BI5 Ic-1CT Va-2VT


(-) 10 10 (-) 10 10 10

(+) 11 11
(+) 11 11 11
BI6 BI6 Ia-2CT Vb-2VT
(-) 12
BO6(*2) (-) 12 12
12
12

(+) 13 13
(+) 13 13 13
BI7 Vc-2VT
BI7 BO7 (-) 14 Ib-2CT 14
(-) 14 14 14

(+) 15 15 (+) 15 15

(-) 16
BI8 BO8
16 (-) 16
BI8 C13 16
Ic-2CT

17 (+) 17 17 17
BO9 BI9 Ia-3CT Ia-4CT
18 (-) 18 18 18

21 21 (+) 21 19 19
BO1(*1) BO10 BI10 Ib-3CT Ib-4CT
22 22 (-) 22 20 20

23 23 (+) 23 21 21
BO2(*1) BO11 BI11 Ic-3CT
24 24 (-) 24 22 Ic-1CT
22

BO3(*1)
25
BO12
25 (+)

(-)
25

26
BI12
C14 23
IN-1NCT
23
Ia-5CT
26 26 24 24

27 (+) 27 25
27 25
BO4(*1) BO13 BI13 IN-2NCT
28 28 (-) 28 26 Ib-5CT
26
(+) 29 (+) 29
29 29 27 27
30
DC/DC BO5(*1) BO14 BI14 IN-3NCT
30 30 (-) 30 28 Ic-5CT
28
(-) 31 31 (+) 31
31
32 BO6(*1) BO15 BI15

35
32

33
32

33
(-)

(+)
32

33
C15 30 30

36 IRIG-B
BI16
BO7
34
BO16
34 (-) 34
•A1
•B1
37
35 35
(+) 35 • SIG
A2DISUSE
38
37 BO17 BI17 •B2
36
(-) 36
• DISUSE
36
BO8 37
(+) 37
•A3
38 BO18
38
(-) 38
BI18
•B3• GND

●FG ●FGE ●FGD ●FGC ●FGB ●FG1 ●FGA ●FG2 ●E

Figure 21 – rear view (1/1 rack size)

- 45 -
©Copyright 2020 Toshiba Energy Systems & Solutions Corporation. All rights reserved.

・The information given in this catalog is subject to change without notice.


・The information given in this catalog is as of 3 March 2020.
・The information given in this catalog is presented only as a guide for the
applications of our products. No responsibility is assumed by TOSHIBA for
any infringements of patents or other rights of the third parties which may
result from its use. No license is granted by implication or otherwise under
any patent or patent rights of TOSHIBA or others.
・TOSHIBA products should not be embedded to the downstream products
which are prohibited to be produced and sold, under any law and
72-34, Horikawa-cho, Saiwai-ku, Kawasaki 212-8585, Japan regulations.
- Toshiba does not take any responsibility for incidental damage (including
Tel +81-44-331-1462 Fax +81-44-548-9540 loss of business profit, business interruption, loss of business information
http://www.toshiba-relays.com and other pecuniary damage) arising out of the use or disability to use the
products.

GKP-99-16001 Rev1.04

You might also like