GRT200 Brochure - 16001-G2A-1.04
GRT200 Brochure - 16001-G2A-1.04
GRT200 Brochure - 16001-G2A-1.04
GR-200 series -
The GR-200 Series is Toshiba’s next generation of protection and control IED’s, designed for
transmission/distribution networks and providing a platform for distributed and renewable energy
systems and railway applications. Flexible adaptation is enabled using extensive hardware and
modular software combinations facilitating an application oriented solution.
Meeting your needs -
Extensive hardware and modular software combinations provide the flexibility to meet your
application and engineering requirements.
Future upgrade paths and minor modifications are readily achievable on demand.
Powerful and wide application -
In addition to protection & control, GR-200 has been designed to meet the challenges and take
advantage of developments in information & communications technology. Process bus capability
and teleprotection based upon packet-based communications are just two of the features of GR-
200.
APPLICATION
GRT200 transformer protection is implemented on Toshiba’s next generation GR-200 series IED
platform and has been designed to provide comprehensive protection and control applications
for transformers in all types of network. This powerful and user-friendly IED will provide you with
the flexibility to meet your application and engineering requirements in addition to offering
outstanding performance, high quality and operational peace of mind.
- Current differential protection is applied for fast and selective main protection for two-
winding or three-winding power transformers, auto-transformers and generator- transformer
units. This protection requires no interposing CTs and provides stability against
magnetizing inrush, overexcitation and CT saturation.
- Up to five current inputs for the phase segregated differential protection
- Restricted earth fault protection incorporating enhanced stability against CT saturation
detects internal earth faults where the transformer star point is directly or low impedance
earthed.
- Comprehensive back up protections
- Bay control and monitoring functions
- Communications with substation automation system, IEC 61850-8-1 [Station bus], IEC
60870-5-103 and IEC62439/PRP/HSR
1
FEATURES
• Application
- Application for two-winding or three-winding • Functionality
power transformers, auto-transformers and - Eight settings groups
generator-transformer units. - Automatic supervision
- Current differential protection is applied - Metering and recording functions
- Time synchronization by external clock
for fast and selective main protection.
such as IRIG-B and system network
This protection requires no interposing
• Communication
CTs and provides stability against
- System interface - RS485, Fiber optic,
magnetizing inrush, overexcitation and
100BASE-TX/1000BASE-T, 100BASE-
CT saturation.
FX, 1000BASE-LX
- Restricted earth fault protection detects - Multi protocol - IEC 60870-5-103, IEC
internal earth faults where the 61850 and IEC62439/PRP/HSR
transformer star point is directly or low • Security
impedance earthed and can be applied on - Password protection
high-voltage and low-voltage sides • Flexibility
respectively. - Various models and hardware options for
- Time-overcurrent protection is mainly flexible application depending on system
used as backup protection and can be requirement and controlled object
applied on high- and low-voltage sides - Mixed 1A / 5A phase and neutral current
respectively. inputs
- Phase and neutral CT polarity settings
- Thermal overload protection protects the
- DC power supply: 110 to 240V, 24 to 60V
transformer against thermal stress and
or 48 to 125V
provides two independently set levels for
- Configurable binary inputs and outputs
alarm and tripping. - Programmable control, trip and alarm
GRT200 can be applied to the various kinds of logic with PLC tool software
transformer configuration as per the • Human Machine Interface
transformer configuration and applicable - Graphical LCD and 26 LEDs
model: - 7 configurable function keys
- USB port for local PC connection
Configuration Analog inputs Model
- Direct control buttons for open/close (O/I)
I1 and control authority (43R/L)
V In1 3 x three-phase CT + - Help key for supporting operation
In2 2 x zero-phase CT + GRT200-3-*
- Monitoring terminals for testing
1 x three-phase VT
I2 I3
I1 I3
V 4 x three-phase CT +
GRT200-4-*
1 x one-phase VT
I2 I4
V1 I1 I4 In1
In2 5 x three-phase CT +
In3
3 x zero-phase CT + GRT200-5-*
V2 2 x three-phase VT
I2 I5 I3
2
FUNCTIONS
• Protection
- Current differential protection for two • Monitoring
or three winding transformers (DIF) - Status and condition monitoring of primary
incorporating stability against inrush, apparatus
over-excitation and CT saturation - Switchgear operation monitoring
- No interposing CTs required - Plausibility check
- Mixed 1A/5A inputs for phase and - Measurement s of I, V, P, Q, S, PF, f, Wh,
neutral currents varh
- CT ratio, vector and zero-sequence - VT failure detection (VTF)
compensation - Current and voltage circuit supervision
- Trip circuit supervision (TCS)
- Restricted earth fault protection (REF)
incorporating enhanced stability • HMI function
against CT saturation - Selection of HMI: Standard LCD / large
LCD / Separate large LCD
- Breaker failure protection (CBF)
- Large LCD supports single line diagram
- Directional / non-directional
indication and touch-type operation
overcurrent protection for phase faults
- 24 configurable tri-state LEDs selectable
(OC)
red/green/yellow
- Non-directional overcurrent protection
- 7 Programmable function keys for user
for earth faults using neutral current
configurable operation
(EFIn)
• Recording
- Directional / nondirectional overcurrent
- Fault record
protection for earth faults using phase
- Event record
currents (EF)
- Disturbance record
- Negative phase sequence overcurrent
• Communication
protection (OCN)
- IEC 60870-5-103 / IEC 61850
- Thermal overload protection (THM)
- IEC62439 PRP/HSR
- Broken conductor protection (BCD)
• General functions
- Inrush current detector (ICD)
- Eight settings groups
- Overexcitation protection (VPH)
- Automatic supervision
- Under/over frequency and rate of - Time synchronization by external clock
change of frequency protection (FRQ) using IRIG-B or system network
- Trip and/or Indication of external - Password protection for settings and
devices (MECH. TRIP) selection of local / remote control
- Synchronism voltage check - Checking internal circuit by forcible signal
- Checking internal circuit using monitoring
jacks
APPLICATIONS
3
IA Id = Ires point current, restricted earth fault protection (REF)
provides a highly sensitive differential protection for
Id
earth faults in a transformer which has a star point
directly earthed or low impedance earthed.
IB IC
Operating zone
Large current The REF-DIF element has a dual slope, percentage
characteristic
characteristic as shown in Figure 2 and the
(DIF-S1-Slope2
= 5 - 100%) independent elements can be applied for each
DIF- Small current transformer winding.
S1-I1 characteristic
(DIF-S1-Slope1= 5 - 50%)
3I0 I0d = Ires
0 DIF-S1-I2 Ires IN
Id: Differential current (|IA + IB + IC |)
Ires: Restraining current (|IA| + |IB| + |IC|) I0d
DIF-S1-I1: Minimum operating value
DIF-S1-I2: Knee point
Operating
Figure 1: DIF-Stage1 characteristic zone
REF-Slope2
= 50 – 100%
The small current characteristic provides sensitivity to REF
-I1 REF-Slope1
low level faults. For higher level faults, the large = 10%
current characteristic with increased bias REF-I2 Ires
compensates for the effects of CT saturation. Iod: Residual differential current (|3I0 + IN|)
Ires: Restraining current (Max(|IA|, |IB|, |IC|, |IN|))
Furthermore, GRT200 provides a CT saturation
REF-I1: Minimum operating value
countermeasure function against a very large through- REF-I2: Knee point (: 1, 2, 3)
fault current.
Figure 2: REF-DIF characteristic
REF
REF_DEF &
During periods of transformer energization, the use of
internal fault detection
a second harmonic restraint method blocks the relay & ≥1
operation. Ires≦2.0×Max_kct
[REF_DEF] ON
+
When the transformer is overexcited due to a transient OFF
power system disturbance, the use of a fifth harmonic Figure 3: REF block diagram
restraint method blocks the relay operation.
Figure 4: REF-DEF characteristic
90°
GRT200 also provides high-set unrestrained
differential elements (DIF-Stage2) and ensures rapid 3I0
clearance of heavy internal faults.
IN 3I0
180° 0 0°
ik2 (Fixed)
Operating
GRT200 provides differential current supervision zone
functions for 87T elements to monitor erroneous
differential current under normal conditions. 270°
ik1
Restricted Earth Fault Protection (REF) (a) Directional characteristic (b) Non directional characteristic
4
CT polarities for each neutral CT can be set flexibly for earth faults which can be applied flexibly for each
within GRT200 in accordance with external physical transformer winding, utilizing neutral current values
connections to each neutral CT.
observed.
Tripping by each element can be disabled by the Up to 4 negative phase sequence overcurrent
scheme switches, and overcurrent backup protection protections (OCN) can be applied flexibly for each
transformer winding. OCN can be used in applications
can be blocked by a binary input signal.
where certain fault conditions may not be detected by
GRT200 provides up to 4 non-directional overcurrent the normal phase and earth overcurrent protections,
protections (EFIn) with inverse time and definite time for example, in the case of a relay applied on the delta
5
side of a delta-star transformer, to detect an earth fault may be selected as either having a definite time or an
on the star side. inverse time delay as shown in Figure 6.
The inrush current detector (ICD) is used to prevent an Up to 16 external signals such as overpressure
incorrect operation of the aforementioned OC, EF, devices and Buchholz relay operations can be applied
OCN and BCD against a magnetizing inrush current through binary input circuits. Logic can be arranged for
during transformer energization. ICD detects second alarms, event recording and tripping.
harmonic inrush currents during transformer
energization.
6
HMI FUNCTION
Front Panel
The local human machine interface includes an LCD
GRT200 provides the following front panel options. which can display the single line diagram for the bay.
- Standard LCD
The local human machine interface is simple and easy
- Large LCD (optional separate LCD type is also
to understand with the following facilities and
available)
indications.
The standard LCD panel incorporates the user - Status indication LEDs (IN SERVICE, ERROR and
interfaces listed below. Setting the relay and viewing 24 configurable LEDs)
stored data are possible using the Liquid Crystal - 7 Function keys for control, monitoring, setting
Display (LCD) and operation keys. group change and screen jump functions of which
- 21 characters, 8 lines LCD with back light operation is configurable by the user
- Support of English language - Test terminals which can monitor three different
signals from the front panel without connection to
The large LCD panel incorporates a touch type screen
the rear terminals.
for control and navigation purposes.
- USB port
- 40 character, 40 line LCD with back light
Local PC Connection
MONITORING
Metering Status Monitoring
The open or closed status of each switchgear device
The following power system data is measured
and failure information concerning power apparatus
continuously and can be displayed on the LCD on the
and control equipment are monitored by GRT200.
relay fascia, and on a local or remotely connected PC.
Both normally open and normally closed contacts are
- Measured analog voltages, currents, used to monitor the switchgear status. If an unusual
frequency, active- and reactive-power.
status is detected, a switchgear abnormality alarm is
The accuracy of analog measurement is ±0.5% for I,
generated.
V, P, Q at rated input and ±0.03Hz for frequency
measurement.
7
RECORDING
Event Record - Pre-fault and post-fault current and voltage data
(phase, phase to phase, symmetrical
Continuous event-logging is useful for monitoring of
components)
the system from an overview perspective and is a
complement to specific disturbance recorder
functions. Up to 1,024 time-tagged events are stored Disturbance Record
with 1ms resolution. The Disturbance Recorder function supplies fast,
Fault Record complete and reliable information for disturbances in
the power system. It facilitates understanding of
Information about the pre-fault and fault values for
system behavior and performance of related primary
currents and voltages are recorded and displayed for
and secondary equipment during and after a
trip event confirmation. The most recent 8 time-
disturbance.
tagged faults with 1ms resolution are stored. Fault
record items are as follows. The Disturbance Recorder acquires sampled data
- Date and time from all selected analogue inputs and binary signals.
- Faulted phase The data can be stored in COMTRADE format.
- Phases tripped
- Tripping mode
COMMUNICATION
■ Station bus ■ Serial communication
Ethernet port(s) for the substation communication Serial ports (RS485 and fiber optic) for communicating
standards IEC 61850 is provided for the station bus. with legacy equipment or protection relays over IEC
GRT200 also support Ethernet redundancy scheme 60870-5-103 protocol are provided. The GRT200 can
protocols defined in the IEC 62439-3 standard: function as a protocol converter to connect SAS.
PRP/HSR.
GENERAL FUNCTION
Self Supervision one group for normal conditions, while the other
groups may be set to cover alternative operating
Automatic self-supervision of internal circuits and
conditions.
software is provided. In the event of a failure being
detected, the ALARM LED on the front panel is Password Protection
illuminated, the ‘UNIT FAILURE’ binary output
Password protection is available for the execution of
operates, and the date and time of the failure is
setting changes, executing control, clearing records
recorded in the event record.
and switching between local/remote control.
Current time can be provided with time synchronization GRT200 provides simulation and test functions to
via the station bus by SNTP (Simple Network Time check control functions without modification to wiring
Protocol) with the IEC 61850 protocol. provided by a dummy circuit breaker (virtual
equipment), and the capability to test communication
IRIG-B port is also available as an option.
signals by forced signal status change.
8
TOOLS & ACCESSORY
The PC interface GR-TIEMS allows users to access
GRT200 and other Toshiba GR-200 series IEDs from LCD configuration
a local personal computer (PC) to view on-line or The user can configure and customize the MIMIC data
stored data, to change settings, to edit the LCD screen, displayed on the LCD of GRT200 using GR-TIEMS
to configure sequential logics and for other purposes. software.
9
TECHNICAL DATA
HARDWARE
Analog Inputs
Rated current In 1A / 5A (selectable by user)
Rated voltage Vn 100V to 120V
Rated Frequency 50Hz / 60Hz (specified when order)
Overload Rating
Current inputs 4 times rated current continuous
5 times rated current for 3 mins
6 times rated current for 2 mins
30 times rated current for 10 sec
100 times rated current for 1 second
250 times rated current for one power cycle (20 or 16.6ms)
Voltage inputs 2 times rated voltage continuous
2.5 times rated voltage for 1 second
Burden
Phase current inputs ≤ 0.1VA at In = 1A, ≤ 0.2VA at In = 5A
Earth current inputs ≤ 0.3VA at In = 1A, ≤ 0.4VA at In = 5A
Sensitive earth fault inputs ≤ 0.3VA at In = 1A, ≤ 0.4VA at In = 5A
Voltage inputs ≤ 0.1VA at Vn
Power Supply
Rated auxiliary voltage 24/48/60Vdc (Operative range: 19.2 – 72Vdc),
48/125Vdc (Operative range: 38.4 – 150Vdc),
110/250Vdc or 100/220Vac (Operative range: 88 – 300Vdc
or 80 – 230Vac)
<Notes>
1) Binary inputs are intended for use with DC power source
only.
2) The power supply supervision function is intended for use
with DC power source only. It should be disabled when
AC power supply is applied in order to prevent spurious
alarms.
Superimposed AC ripple on DC supply ≤ 15%
Power supply interruption 24/48/60Vdc rating: 20ms
withstand period 48/125Vdc rating: 35ms
(IEC 60255-11) 110/125Vdc rating: 50ms
Power consumption ≤ 15W (quiescent)
≤ 25W (maximum)
Binary Inputs
Input circuit DC voltage 24/48/60Vdc (Operating range: 19.2 – 72Vdc),
48/125Vdc (Operating range: 38.4 – 150Vdc),
110/125/220/250Vdc (Operating range: 88 – 300Vdc)
Note: Variable threshold settings are available for BI2 from
14V to 154V in various steps.
Capacitive discharge immunity 10μF charged to maximum supply voltage and discharged into
the input terminals, according to ENA TS 48-4 with an external
resistor
Maximum permitted voltage 72Vdc for 24/48/60Vdc rating,
300Vdc for 110/250Vdc rating
Power consumption ≤ 0.5W per input at 220Vdc
Binary Outputs
Fast operating contacts:
Make and carry 5A continuously
10
30A, 290Vdc for 0.2s (L/R=5ms)
Break 0.15A, 290Vdc (L/R=40ms)
Operating time Typically 3 ms
Semi-fast operating contacts:
Make and carry 8A continuously
30A, 240Vdc for 1s (L/R=5ms)
Break 0.1A, at 250Vdc (L/R=40ms)
0.2A, at 110Vdc (L/R=40ms)
Operating time Typically 6 ms
Auxiliary contacts:
Make and carry 8A continuously
30A, 240Vdc for 1s (L/R=5ms)
Break 0.1A, at 250Vdc (L/R=40ms)
0.2A, at 110Vdc (L/R=40ms)
Operating time Typically 8 ms
Hybrid contacts (10 A breaking):
Make and carry 8A continuously
10A, 220Vdc for 0.5s (L/R=5ms)
Break 10A, 220Vdc (L/R=20ms)
10A, 110Vdc (L/R=40ms)
Operating time 1 ms
Durability ≥ 10,000 operations (loaded contact)
≥ 100,000 operations (unloaded contact)
Measuring input capability
Full scale
Standard current input ≥ 60A (1A rating) or 300A (5A rating)
Sensitive current input ≥ 3A (1A rating) or 15 A (5A rating)
Voltage input ≥ 200V
Sampling rate 48 samples / cycle
Frequency response < 5% deviation over range 16.7Hz to 600Hz
Mechanical Design
Installation Flush mounting
Weight Approx. 12kg (1/2 size), 15kg (3/4 size), 25kg (1/1 size)
Case colour 2.5Y7.5/1 (approximation to Munsell value)
LED
Number 26 (Fixed for “In service” and “ERROR”)
Colour Red / Yellow / Green (configurable) except “In service” (green)
and “Error” (red)
Function keys
Number 7
Local Interface
USB Type B
Maximum cable length 2m (max.)
System Interface (rear port)
100BASE-TX/1000BASE-T For IEC 61850-8-1 and GR-TIEMS
Connector type RJ-45
Cable type CAT5e STP cable
- enhanced category 5 with Shielded Twisted Pair cable
100BASE-FX For IEC 61850-8-1
Connector type SC duplex type
Cable type Multi-mode fibre, 50/125 or 62.5/125µm fibre
Wave length 1300nm
1000BASE-LX For IEC 61850-8-1
11
Connector type LC duplex connector
Cable type Single-mode fibre
Wave length 1310nm
RS485 For IEC 60870-5-103
Cable type Shielded twisted pair cable
Connector type Push-in spring terminal (PCB connector)
Fibre optical (for serial communication) For IEC 60870-5-103
Cable type Multi-mode fibre, 50/125 or 62.5/125µm
Connector type ST type
Wave length 820nm
IRIG-B (for time synchronization)
Cable type Shielded twisted pair cable
Connector type Push-in spring terminal (PCB connector)
Terminal Block
CT/VT input M3.5 Ring terminal (ring lug type terminal only)
Binary input, Binary output Compression plug type terminal
12
ENVIRONMENTAL PERFORMANCE
Atmospheric Environment
Temperature IEC 60068-2-1/2 Operating range: -10°C to +55°C.
IEC 60068-2-14 Storage / Transit: -25°C to +70°C.
Cyclic temperature test as per IEC 60068-2-
14
Humidity IEC 60068-2-30 56 days at 40°C and 93% relative humidity.
IEC 60068-2-78 Cyclic temperature with humidity test as per
IEC 60068-2-30
Enclosure Protection IEC 60529 IP52 - Dust and Dripping Water Proof
IP20 for rear panel
Mechanical Environment
Vibration IEC 60255-21-1 Response - Class 1
Endurance - Class 1
Shock and Bump IEC 60255-21-2 Shock Response Class 1
Shock Withstand Class 1
Bump Class 1
Seismic IEC 60255-21-3 Class 1
Electrical Environment
Dielectric Withstand IEC 60255-27 2kVrms for 1 minute between all terminals
and earth.
2kVrms for 1 minute between independent
circuits.
1kVrms for 1 minute across normally open
contacts.
High Voltage Impulse IEC 60255-5 Three positive and three negative impulses of
IEEE C37.90 5kV(peak), 1.2/50µs, 0.5J between all
terminals and between all terminals and
earth.
Voltage Dips, IEC 60255-11, 1. Voltage dips:
Interruptions, IEC 61000-4-29, 0 % residual voltage for 20 ms
Variations and Ripple IEC 61000-4-17 40 % residual voltage for 200 ms
on DC supply IEC 60255-26 Ed 3 70 % residual voltage for 500 ms
2. Voltage interruptions:
0 % residual voltage for 5 s
3. Ripple:
15 % of rated d.c. value, 100 / 120 Hz
4. Gradual shut-down / start-up:
60 s shut-down ramp, 5 min power off, 60s
start-up ramp
5. Reversal of d.c. power supply polarity:
1 min
Capacitive Discharge ENA TS 48-4 10μF charged to maximum supply voltage
and discharged into the input terminals with
an external resistance
13
Electromagnetic Environment
High Frequency IEC 60255-22-1 Class 3, 1 MHz burst in common / differential modes
Disturbance / IEC 61000-4-18 Auxiliary supply and I/O ports: 2.5 kV / 1 kV
Damped Oscillatory IEC 60255-26 Ed 3 Communications ports: 1 kV / 0 kV
Wave
Electrostatic Discharge IEC 60255-22-2 Class 4, Contact: 2, 4, 6, 8kV
IEC 61000-4-2 Air: 2, 4, 8, 15kV
IEEE C37.90.3-2001
IEC 60255-26 Ed 3
Radiated RF IEC 60255-22-3, Sweep test ranges: 80 MHz to 1 GHz and 1.4
Electromagnetic GHz to 2.7 GHz.
IEC 61000-4-3 Level 3
Disturbance IEC 60255-26 Ed 3 Spot tests at 80, 160, 380, 450, 900, 1850
and 2150 MHz.
Field strength: 10 V/m
IEEE C37.90.2-1995 Field strength 35V/m for frequency sweep of
25MHz to 1GHz.
Fast Transient IEC 60255-22-4 5 kHz, 5/50ns disturbance
Disturbance IEC 61000-4-4 Auxiliary supply and input / output ports: 4 kV
IEC 60255-26 Ed 3 Communications ports: 2 kV
Surge Immunity IEC 60255-22-5 1.2/50µms surge in common/differential
IEC 61000-4-5 modes:
IEC 60255-26 Ed 3 Auxiliary supply and input / output ports: 4,
2, 1, 0.5 kV / 1, 0.5 kV
Communications ports: up to 1, 0.5 kV / 0 kV
Surge Withstand IEEE C37.90.1-2002 3kV, 1MHz damped oscillatory wave
4kV, 5/50ns fast transient
Conducted RF IEC 60255-22-6 Sweep test range: 150 kHz to 80MHz
Electromagnetic IEC 61000-4-6 Spot tests at 27 and 68 MHz.
Disturbance IEC 60255-26 Ed 3 Voltage level: 10 V r.m.s
Power Frequency IEC 60255-22-7 50/60 Hz disturbance for 10 s in common /
Disturbance IEC 61000-4-16 differential modes
IEC 60255-26 Ed 3 Binary input ports: 300 V / 150 V
Power Frequency IEC 61000-4-8 Class 4 Field applied at 50/60Hz with strengths of:
Magnetic Field IEC 60255-26 Ed 3 30A/m continuously,
300A/m for 1 second.
Conducted and IEC 60255-25 Conducted emissions:
Radiated Emissions EN 55022 Class A, 0.15 to 0.50MHz: <79dB (peak) or <66dB
EN 61000-6-4 (mean)
IEC 60255-26 Ed 3 0.50 to 30MHz: <73dB (peak) or <60dB
(mean)
Radiated emissions
30 to 230 MHz: < 40 dB(uV/m)
230 to 1000 MHz: < 47 dB(uV/m)
Measured at a distance of 10 m
14
Performance and Functional Standards
Category Standards
General
Common requirements IEC 60255-1
Data Exchange IEC 60255-24 / IEEE C37.111 (COMTRADE)
Product Safety IEC 60255-27
European Commission Directives
2014/30/EU Compliance with the European Commission
Electromagnetic Compatibility Directive is
demonstrated according to EN 60255-26:2013.
2015/35/EU Compliance with the European Commission Low
Voltage Directive for electrical safety is
demonstrated according EN 60255-27:2014.
15
FUNCTIONAL DATA
16
Non-directional and Directional Earth Fault Protection (50G, 51G, 67G)
Definite time earth fault threshold 0.02 to 50.00A in 0.01A steps (1A rating)
0.10 to 250.00A in 0.01A steps (5A rating)
Inverse time earth fault threshold 0.02 to 5.00A in 0.01A steps (1A rating)
0.10 to 25.00A in 0.01A steps (5A rating)
Direction characteristic Non Directional / Forward / Backward
Characteristic angle 0 to 180° in 1° steps
Polarising voltage (3V0) 0.5 to 100.0V in 0.1V steps
Delay type DT / IEC-NI / IEC-VI / IEC-EI / UK-LTI / IEEE-MI / IEEE-VI / IEEE-
EI / US-CO2 / US-CO8 / Original
Drop-out/pick-up ratio 10 to 100% in 1% steps
DTL delay 0.00 to 300.00s in 0.01s steps
IDMTL Time Multiplier Setting TMS 0.010 to 50.000 in 0.001 steps
Reset type Definite Time or Dependent Time
Reset definite delay 0.00 to 300.00s in 0.01s steps
Reset Time Multiplier Setting RTMS 0.010 to 50.000 in 0.001 steps
Non-directional Earth Fault Protection(Using neutral current) (50N, 51N)
Definite time earth fault threshold 0.02 to 50.00A in 0.01A steps (1A rating)
0.10 to 250.00A in 0.01A steps (5A rating)
Inverse time earth fault threshold 0.02 to 5.00A in 0.01A steps (1A rating)
0.10 to 25.00A in 0.01A steps (5A rating)
Delay type DT / IEC-NI / IEC-VI / IEC-EI / UK-LTI / IEEE-MI / IEEE-VI / IEEE-
EI / US-CO2 / US-CO8 / Original
Drop-out/pick-up ratio 10 to 100% in 1% steps
DTL delay 0.00 to 300.00s in 0.01s steps
IDMTL Time Multiplier Setting TMS 0.010 to 50.000 in 0.001 steps
Reset type Definite Time or Dependent Time
Reset definite delay 0.00 to 300.00s in 0.01s steps
Reset Time Multiplier Setting RTMS 0.010 to 50.000 in 0.001 steps
Negative Phase sequence overcurrent Protection (46)
Definite time NOC threshold 0.02 to 50.00A in 0.01A steps (1A rating)
0.10 to 250.00A in 0.01A steps (5A rating)
Inverse time NOC threshold 0.02 to 5.00A in 0.01A steps (1A rating)
0.10 to 25.00A in 0.01A steps (5A rating)
Direction characteristic Non Directional / Forward / Backward
Characteristic angle 0 to 180° in 1° steps
Polarising voltage 0.5 to 25.0V in 0.1V steps
Delay type DT / IEC-NI / IEC-VI / IEC-EI / UK-LTI / IEEE-MI / IEEE-VI / IEEE-
EI / US-CO2 / US-CO8 / Original
Drop-out/pick-up ratio 10 to 100% in 1% steps
DTL delay 0.00 to 300.00s in 0.01s steps
IDMTL Time Multiplier Setting TMS 0.010 to 50.000 in 0.001 steps
Reset type Definite Time or Dependent Time
Reset definite delay 0.00 to 300.00s in 0.01s steps
Reset Time Multiplier Setting RTMS 0.010 to 50.000 in 0.001 steps
17
Thermal Overload Protection (49)
Thermal setting (THM = k.IFLC) 0.40 to 2.00A in 0.01A steps (1A rating)
2.0 to 10.0A in 0.1A steps (5A rating)
Time constant (τ) 0.5 to 500.0mins in 0.1min steps
Thermal alarm OFF, 50% to 100% in 1% steps
Pre-load current setting 0.00 to 1.00A in 0.01A steps (1A rating)
0.00 to 5.00A in 0.01A steps (5A rating)
Broken conductor protection (46BC)
Broken conductor threshold 0.10 to 1.00 in 0.01 steps
DTL delay 0.00 to 300.00s in 0.01s steps
Inrush Current Detection
Second harmonic detection 10 to 50% in 1% steps
Inrush current thresholds 0.10 to 5.00A in 0.01A steps (1A rating)
0.5 to 25.00A in 0.01A steps (5A rating)
CBF Protection (50BF)
Overcurrent element 0.1 to 2.0A in 0.1A steps (1A rating)
0.5 to 10.0A in 0.1A steps (5A rating)
BF timer for retry-trip of failed breaker 50 to 500ms in 1ms steps
BF timer for related breaker trip 50 to 500ms in 1ms steps
Overexcitation Protection (24)
Pickup voltage 100.0 to 120.0V in 0.1V steps
Alarm level (A) 1.03 to 1.30pu in 0.01pu steps
High level (H) 1.10 to 1.40pu in 0.01pu steps
Low level (L) 1.05 to 1.30pu in 0.01pu steps
LT (Definite time) 1 to 600s in 1s steps
HT (Definite time) 1 to 600s in 1s steps
TVFH (Definite time) 1 to 600s in 1s steps
TVFA (Definite time) 1 to 600s in 1s steps
Start time less than 130ms
RT (Definite time) 60 to 3600s in 1s steps
Frequency Protection (81U/O)
Under/overfrequency threshold (Fnom to 10.00Hz) to (Fnom + 10.00Hz) in 0.01Hz steps
Fnom: nominal frequency
DTL delay: 0.00 to 300.00s in 0.01s steps
Frequency UV Block 40.0 to 100.0V in 0.1V steps
Rate-of-change frequency threshold 0.1 to 15.0Hz/s in 0.1Hz/s steps
Metering Function
Current Accuracy ± 0.5% (at rating)
Voltage Accuracy ± 0.5% (at rating)
Power (P, Q, S) Accuracy ± 0.5% (at rating)
Power factor (PF) Accuracy ± 0.5% (at rating)
Energy (Wh, VArh) Accuracy ± 1.0% (at rating)
Frequency Accuracy ± 0.03Hz
Time Synchronisation
Protocol SNTP
18
Accuracy
Current differential protection
Pick-ups ±5% of setting value
Reset ±5% of setting value
Operating time
Operating time of biased current typical 25ms + BO operating time (*1)
differential protection
Operating time of high-set current typical 20ms + BO operating time (*1)
differential protection
Restricted Earth Fault element
Pick-ups ±5% of setting value (at I ≥ 0.5pu)
Operating time typical 30ms + BO operating time (*1)
Overcurrent protection
Pick-ups ±3% of setting value (at I ≥ 0.5pu)
Operating time with definite timer typical 35ms + BO operating time (*1)
Operating time with inverse timer IEC curve:±5% of theoretical value
for 2 ≤ Multiple of threshold value ≤ 10 and TMS=1
IEEE curve: ±10% of theoretical value
for 2 ≤ multiple of threshold value ≤ 10 and TMS=1s
19
ORDERING INFORMATION
Outline
Standard LCD, 1/2 x 19" rack for flush mounting 2
Large LCD, 1/2 x 19" rack for flush mounting 6
Standard LCD, 1/2 x 19" rack for rack mounting (See (*4)) F
Large LCD, 1/2 x 19" rack for rack mounting (See (*4)) J
(*1) Binary inputs are intended for use with DC power source only.
The power supply supervision function is intended for use with DC power source only. It should be disabled
when AC power supply is applied in order to prevent spurious alarms.
(*2) Refer to pages 25 – 26, and select the appropriate CT configuration when you require another rated current
configuration.
(*3) Refer to page 32. For PRP/HSR/RSTP protocol with IEC 61850, choose “L” or “N” code at position E. For
hot/standby configuration or single port configuration with IEC 61850, choose other codes at position E.
(*4) For 19” rack panel mounting, accessories of joint kits are available. (See Figure 14 on page-38)
20
[Hardware selection (1)] continue Positions
- 7 8 - 9 A B - C D - E F - G H - J K L
Configurations G R T 2 0 0 - 3 - - 0 0 - - 3 -
Outline
Standard LCD, 3/4 x 19" rack for flush mounting 3
Large LCD, 3/4 x 19" rack for flush mounting 7
Standard LCD, 3/4 x 19" rack for rack mounting (See (*4)) G
Large LCD, 3/4 x 19" rack for rack mounting (See (*4)) K
Outline
Standard LCD, 1/1 x 19" rack for flush/rack mounting 4
Large LCD, 1/1 x 19" rack for flush/rack mounting 8
21
[Hardware selection (2)] Positions
- 7 8 - 9 A B - C D - E F - G H - J K L
Configurations G R T 2 0 0 - 4 - - 0 0 - - 3 - 0
Outline
Standard LCD, 1/2 x 19" rack for flush mounting 2
Large LCD, 1/2 x 19" rack for flush mounting 6
Standard LCD, 1/2 x 19" rack for rack mounting (See (*4)) F
Large LCD, 1/2 x 19" rack for rack mounting (See (*4)) J
(*1) Binary inputs are intended for use with DC power source only.
The power supply supervision function is intended for use with DC power source only. It should be disabled
when AC power supply is applied in order to prevent spurious alarms.
(*2) Refer to pages 25 – 26, and select the appropriate CT configuration when you require another rated current
configuration.
(*3) Refer to page 32. For PRP/HSR/RSTP protocol with IEC 61850, choose “L” or “N” code at position E. For
hot/standby configuration or single port configuration with IEC 61850, choose other codes at position E.
(*4) For 19” rack panel mounting, accessories of joint kits are available. (See Figure 14 on page-38)
22
[Hardware selection (2)]continue Positions
- 7 8 - 9 A B - C D - E F - G H - J K L
Configurations G R T 2 0 0 - 4 - - 0 0 - - 3 - 0
Outline
Standard LCD, 3/4 x 19" rack for flush mounting 3
Large LCD, 3/4 x 19" rack for flush mounting 7
Standard LCD, 3/4 x 19" rack for rack mounting (See (*4)) G
Large LCD, 3/4 x 19" rack for rack mounting (See (*4)) K
Outline
Standard LCD, 1/1 x 19" rack for flush/rack mounting 4
Large LCD, 1/1 x 19" rack for flush/rack mounting 8
23
[Hardware selection (3)] Positions
- 7 8 - 9 A B - C D - E F - G H - J K L
Configurations G R T 2 0 0 - 5 - - 0 0 - - 3 - 0
Outline
Standard LCD, 1/1 x 19" rack for flush/rack mounting 4
Large LCD, 1/1 x 19" rack for flush/rack mounting 8
(*1) Binary inputs are intended for use with DC power source only.
The power supply supervision function is intended for use with DC power source only. It should be disabled
when AC power supply is applied in order to prevent spurious alarms.
(*2) Refer to pages 25 – 26, and select the appropriate CT configuration when you require another rated current
configuration.
(*3) Refer to page 32. For PRP/HSR/RSTP protocol with IEC 61850, choose “L” or “N” code at position E. For
hot/standby configuration or single port configuration with IEC 61850, choose other codes at position E.
24
CT configuration
25
5 x three-phase CT (When position “7“ = 5)
1CT group 2CT group 3CT group 4CT group 5CT group Ordering No.
(1Ia, 1Ib, 1Ic) (2Ia, 2Ib, 2Ic) (3Ia, 3Ib, 3Ic) (4Ia, 4Ib, 4Ic) (5Ia, 5Ib, 5Ic) (Position “K”)
1A 1A 1A 1A 1A 1
5A 5A 5A 5A 5A 2
1A 1A 1A 1A 5A 3
1A 1A 1A 5A 1A 4
1A 1A 1A 5A 5A 5
1A 1A 5A 1A 1A 6
1A 1A 5A 1A 5A 7
1A 1A 5A 5A 1A 8
1A 1A 5A 5A 5A 9
1A 5A 1A 1A 1A A
1A 5A 1A 1A 5A B
1A 5A 1A 5A 1A C
1A 5A 1A 5A 5A D
1A 5A 5A 1A 1A E
1A 5A 5A 1A 5A F
1A 5A 5A 5A 1A G
1A 5A 5A 5A 5A H
5A 1A 1A 1A 1A J
5A 1A 1A 1A 5A K
5A 1A 1A 5A 1A L
5A 1A 1A 5A 5A M
5A 1A 5A 1A 1A N
5A 1A 5A 1A 5A P
5A 1A 5A 5A 1A Q
5A 1A 5A 5A 5A R
5A 5A 1A 1A 1A S
5A 5A 1A 1A 5A T
5A 5A 1A 5A 1A U
5A 5A 1A 5A 5A V
5A 5A 5A 1A 1A W
5A 5A 5A 1A 5A X
5A 5A 5A 5A 1A Y
26
Number of BI/BO
1 x I/O module
Number of BI/BO Ordering No.
(Position “A” to
Semi-fast BO
“B”)
Independent
Independent
BI (variable)
Hybrid BO
Common Configuration
Fast-BO
BO
BI
BI
7 - - - 6 4 - 11 1xBIO1
12 - - - 3 2 - 12 1xBIO2
8 - - 6 - 2 - 13 1xBIO3
- 6 - - - 2 6 14 1xBIO4
18 - - - - - - 15 1xBI1
- 12 - - - - - 16 1xBI2
- - 32 - - - - 17 1xBI3
2 x I/O module
Number of BI/BO Ordering No.
(Position “A” to
Semi-fast BO
“B”)
Independent
Independent
BI (variable)
Heavy duty
Configuration
Common
Fast-BO
BO
BO
BI
BI
- - 32 - 6 12 - 21 1xBI3+1xBO1
7 - 32 - 6 4 - 22 1xBI3+1xBIO1
12 - 32 - 3 2 - 23 1xBI3+1xBIO2
18 - - - 6 12 - 24 1xBI1+1xBO1
25 - - - 6 4 - 25 1xBI1+1xBIO1
30 - - - 3 2 - 26 1xBI1+1xBIO2
8 - - 6 6 14 - 27 1xBO1+1xBIO3
15 - - 6 6 6 - 28 1xBIO1+1xBIO3
7 - - - 12 16 - 29 1xBO1+1xBIO1
16 - - 12 - 4 - 2A 2xBIO3
- - 32 - - - 16 2B 1xBI3+1xBO2
- 12 - - 6 12 - 2C 1xBI2 +1xBO1
20 - - 6 3 4 - 2E 1xBIO2 +1xBIO3
12 - - - 9 14 - 2F 1xBO1+1xBIO2
8 12 6 2 2G 1xBI2 +1xBIO3
27
3 x I/O module
Number of BI/BO Ordering No.
(Position “A” to
Semi-fast BO
“B”)
Independent
Independent
BI (variable)
Heavy duty
Configuration
Common
Fast-BO
BO
BO
BI
15 - BI- 6 12 18 - 31 1xBO1+1xBIO1+1xBIO3
20 - - 6 9 16 - 32 1xBO1+1xBIO2+1xBIO3
23 - - 12 6 8 - 33 1xBIO1+2xBIO3
26 - - 6 6 14 - 34 1xBI1+1xBO1+1xBIO3
8 - 32 6 6 14 - 35 1xBI3+1xBO1+1xBIO3
24 - - 18 - 6 - 36 3xBIO3
25 - - - 12 16 - 37 1xBI1+1xBO1+1xBIO1
36 - - - 6 12 - 39 2xBI1+1xBO1
- 24 - - 6 12 - 3A 2xBI2+1xBO1
18 6 - - 6 14 6 3B 1xBI1+1xBO1+1xBIO4
7 - 32 - 6 4 16 3C 1xBI3+1xBIO1+1xBO2
7 - 32 - 12 16 - 3D 1xBI3+1xBO1+1xBIO1
- - 32 - 6 12 16 3E 1xBI3+1xBO1+1xBO2
16 - - 12 6 16 - 3G 1xBO1+2xBIO3
- 6 32 - 6 14 6 3H 1xBI3+1xBO1+1xBIO4
26 - - 6 6 14 - 3J 1xBO1+1xBIO3+1xBI1 (*1)
- - 64 - 6 12 - 3K 2xBI3+1xBO1
14 - 32 - 12 8 - 3L 1xBI3+2xBIO1
- - 96 - - - - 3M 3xBI3
8 12 - 6 6 14 - 3N 1xBI2+1xBO1+1xBIO3
- - 32 - 12 24 - 3P 1xBI3 + 2xBO1
8 - 32 6 6 14 - 3Q 1xBO1+1xBIO3+1xBI3 (*2)
16 12 12 4 3S 1xBI2+2xBIO3
28
4 x I/O modules
Number of BI/BO Ordering No.
(Position “A” to
Semi-fast BO
“B”)
Independent
Independent
BI (variable)
Heavy duty
Configuration
Common
Fast-BO
BO
BO
BI
BI
26 - - 6 12 26 - 41 1xBI1+2xBO1+1xBIO3
32 - - 24 - 8 - 42 4xBIO3
8 - 32 6 12 26 - 43 1xBI3+2xBO1+1xBIO3
- - 64 - 12 24 - 44 2xBI3+2xBO1
54 - - - 6 12 - 46 3xBI1+1xBO1
1xBI3+1xBO1+1xBIO2
20 - 32 6 9 16 - 47
+1xBIO3
1xBO1+1xBI1+1xBO1
26 - - 6 12 26 - 48
+1xBIO3 (*3)
20 6 15 28 49 2xBO1+1xBIO2+1xBIO3
34 - - 12 6 16 - 4B 1xBI1+1xBO1+2xBIO3
- - 64 - - - 32 4C 2xBI3+2xBO2
21 - 32 - 18 12 - 4D 1xBI3+3xBIO1
- - 128 - - - - 4E 4xBI3
7 96 6 4 4F 3xBI3+1xBIO1
8 24 - 6 6 14 - 4G 2xBI2 +1xBO1 +1xBIO3
- - 32 - 18 36 - 4H 1xBI3 + 3xBO1
1xBI1 + 1xBI2 + 1xBO1
26 12 - 6 6 14 - 4J
+ 1xBIO3
24 - 32 - 12 16 - 4K 1xBI3+1xBO1+2xBIO2
15 - - 6 18 30 - 4L 2xBO1+1xBIO1+1xBIO3
7 - - - 24 40 - 4M 3xBO1+1xBIO1
36 - - - 12 24 - 4N 2xBI1+2xBO1
8 - 64 6 6 14 - 4P 2xBI3+1xBO1+1xBIO3
36 - - - 6 12 16 4Q 2xBI1+1xBO1+1xBO2
44 - - 6 6 14 - 4R 2xBI1+1xBO1+1x BIO3
29
5 x I/O modules
Number of BI/BO Ordering No.
(Position “A” to
Semi-fast BO
“B”)
Independent
Independent
BI (variable)
Heavy duty
Configuration
Common
Fast-BO
BO
BO
BI
BI
1xBI1+1xBIO1+1xBIO3
33 - - 6 6 6 32 51
+2xBO2
44 - - 6 12 26 - 52 2xBI1+2xBO1+1xBIO3
25 - 96 - 6 4 - 53 1xBI1+3xBI3+1xBIO1
8 - 96 6 6 14 - 54 3xBI3+1xBO1+1xBIO3
62 - - 6 6 14 - 56 3xBI1+1xBO1+1xBIO3
54 6 - - 6 14 6 57 3xBI1+1xBO1+1xBIO4
- - 96 - 12 24 - 5B 3xBI3+2xBO1
- - 128 - 6 12 - 5E 4xBI3+1xBO1
- - 160 - - - - 5F 5xBI3
2xBI1+1xBI2+1xBO1
44 12 - 6 6 14 - 5G
+1xBIO3
15 - - 6 24 42 - 5H 3xBO1+1xBIO1+1xBIO3
- - 64 - 18 36 - 5J 2xBI3+3xBO1
- - - - 30 60 - 5L 5xBO1
42 - - 18 6 18 - 5P 1xBI1+1xBO1+3xBIO3
1xBI1+1xBO1+1xBIO1
41 - - 12 12 20 - 5Q
+2xBIO3
8 - 64 6 - 2 32 5R 2xBI3+1xBIO3+2xBO2
1xBI2+2xBI3+1xBIO3
8 12 64 6 - 2 16 5S
+1xBO2
6 x I/O modules
Number of BI/BO Ordering No.
(Position “A” to
Semi-fast BO
“B”)
Independent
Independent
BI (variable)
Heavy duty
Configuration
Common
Fast-BO
BO
BO
BI
BI
2xBI1+2xBO1+1xBIO1
51 - - 6 18 30 - 61
+1xBIO3
8 - 96 6 12 26 - 62 3xBI3+2xBO1+1xBIO3
- - 128 - 12 24 - 63 4xBI3+2xBO1
8 - 128 6 6 14 - 64 4xBI3+1xBO1+1xBIO3
52 - - 12 - 4 32 69 2xBI1+2xBIO3+2xBO2
52 - - 12 12 28 - 6A 2xBI1+2xBO1+2xBIO3
36 - - - 24 48 - 6B 2xBI1+4xBO1
36 - 64 - 12 24 - 6C 2xBI1+2xBI3+2xBO1
44 - - 6 18 38 - 6D 2xBI1+3xBO1+1xBIO3
- - 160 - 6 12 - 6E 5xBI3+1xBO1
7 - 160 - 6 4 - 6F 5xBI3+1xBIO1
8 - 64 6 - 2 48 6G 2xBI3+1xBIO3+3xBO2
30
7 x I/O modules
Number of BI/BO Ordering No.
(Position “A” to
Semi-fast BO
“B”)
Independent
Independent
BI (variable)
Heavy duty
Configuration
Common
Fast-BO
BO
BO
BI
BI
80 - - 6 12 26 - 71 4xBI1+2xBO1+1xBIO3
72 6 - - 12 26 6 72 4xBI1+2xBO1+1xBIO4
8 - 96 6 18 38 - 73 3xBI3+3xBO1+1xBIO3
- 6 96 - 18 38 6 74 3xBI3+3xBO1+1xBIO4
- 60 - - 6 12 16 78 5xBI2+1xBO1+1xBO2
- - 160 - 12 24 - 79 5xBI3+2xBO1
54 - 64 - 12 24 - 7B 3xBI1 + 2xBI3 + 2xBO1
- - 128 - 18 36 - 7D 4xBI3+3xBO1
7 - 160 - 12 16 - 7E 5xBI3+1xBO1+1xBIO1
- - 192 - 6 12 - 7F 6xBI3+1xBO1
7 - 192 - 6 4 - 7G 6xBI3+1xBIO1
- - 224 - - - - 7H 7xBI3
8 - 96 6 - 2 48 7L 3xBI3+1xBIO3+3xBO2
8 x I/O modules
Number of BI/BO Ordering No.
(Position “A” to
Semi-fast BO
“B”)
Independent
Independent
BI (variable)
Heavy duty
Configuration
Common
Fast-BO
BO
BO
BI
BI
- - 160 - 18 36 - 83 5xBI3+3xBO1
- 60 - - 6 12 32 87 5xBI2+1xBO1+2xBO2
8 - 128 6 18 38 - 88 4xBI3+3xBO1+1xBIO3
- - 256 - - - - 8C 8xBI3
7 - 224 - 6 4 - 8G 7xBI3+1xBIO1
- - 192 - 12 24 - 8H 6xBI3+2xBO1
7 - 192 - 12 16 - 8J 6xBI3+1xBO1+1xBIO1
7 - 96 - 30 52 - 8M 3xBI3+4xBO1+1xBIO1
- - 128 - 24 48 - 8N 4xBI3+4xBO1
Please contact with our sales staffs when you require “other configuration (number: ZZ)” that is not indicated in the ordering
sheet above.
31
Communication port Table
Serial and/or Ethernet and/or Time Synch port
IEC 60870-5-103 IEC 61850-8-1
Ordering No.
100Base-FX
100Base-LX
1000Base-T
(Position “E” Remark
Fibre optic
(for serial)
100Base-
to “F”)
RS485
IRIG-B
TX/
1 14
1 1J
1 1K
1 1 34
1 1 3J
1 1 3K
2 46 Hot/Standby
1 1 4C
1 1 4G
2 4L
Hot/Standby
2 4M
1 1 4N
1 1 4Q
1 1 4S
1 1 4U
2 1 66 Hot/Standby
1 1 1 6C
1 1 1 6G
2 1 6L
Hot/Standby
2 1 6M
1 1 1 6N
1 1 1 6Q
1 1 1 6S
1 1 1 6U
1 2 7D
1 2 7H
1 2 7P
Hot/Standby
1 2 7R
1 2 7T
1 2 7U
2 L6
1 2 LD
1 2 LH
2 LL
2 LM
1 2 LP
1 2 LR
1 2 LT
For
1 2 LV
PRP/HSR/
2 1 N6 RSTP
1 2 1 ND
1 2 1 NH
2 1 NL
2 1 NM
1 2 1 NP
1 2 1 NR
1 2 1 NT
1 2 1 NV
32
[Software Ordering]
1 2 3 4 5 6 7 M G N E F U 9 Q
Configurations G R T 2 0 0 - 0 3 - - E
Analog inputs
Assignment on position “7”
Function Block
Refer to Function Table
Number of Serial and/or Ethernet
Communication and/or Time Sync Port(s)
Assignment on position “E” (See (*1))
Selection of Serial and/or Ethernet
Communication Port(s)
Assignment on position “F” (See (*1))
Protocol
IEC60870-5-103 or IEC61850 1
IEC61850 2
Outline
Assignment on position “9”
Language
English E
(*1) For PRP/HSR/RSTP protocol with IEC 61850, choose “L” or “N” code at position E. For hot/standby configuration
or single port configuration with IEC 61850, choose other codes at position E.
33
FUNCTION TABLE
Function Description Ordering No. (Position 'G & N')
Block 3D 3E 3F
2 x 3ph-CT ● ● ●
DIF 3 x 3ph-CT ● ● ●
Current differential protection
(87) 4 x 3ph-CT - ● ●
5 x 3ph-CT - - ●
REF Low-impedance restricted earth 2 Stage ● - ●
(87N) fault protection 3 Stage - - ●
Non-directional definite / inverse
OC 8 stages ●
time overcurrent protection
(50/51/67) ● ●
Directional definite / inverse time
-
overcurrent protection
Non-directional definite / inverse
EF time earth fault protection 8 stages ●
(50G/51G/ (using phase currents)
● ●
67G) Directional definite / inverse time
overcurrent protection -
(using phase currents)
Non-directional definite / inverse
EFIn
time earth fault protection 4 stages ● - ●
(50N/51N)
(using neutral current)
Non-directional negative-
4 stages ● ● ●
OCN sequence overcurrent protection
(46) Directional negative- sequence
-
overcurrent protection
BCD
Broken conductor protection ● ● ●
(46BC)
THM THM trip
Thermal overload protection ● ● ●
(49) THM alarm
ICD
Inrush current detector function ● ● ●
CBF CBF re-trip
Circuit breaker failure protection ● ● ●
(50BF) CBF trip
Under-frequency /
FRQ/DFRQ
Over-frequency / Rate of change 6 stages ●(*1) ●(*1) ●(*1)
(81U/81O)
of frequency protection
VPH V/f trip
Over-excitation protection ●(*2) ●(*2) ●(*2)
(24) V/f alarm
MECH. Trip and/or Indication of external
32 stages ● ● ●
TRIP devices
4 x three-phase CT +
5 x three-phase CT +
2 x zero-phase CT +
3 x zero-phase CT +
1 x three-phase VT
2 x three-phase VT
phase-to-ground voltage inputs
1 x one-phase VT
34
DIMENSION AND PANEL CUT-OUT (1/2 size)
(Panel cut-out)
Note: For a rack mount unit, there are holes for joint kits assembling on top and bottom of the unit.
Figure 11 – Dimension and Panel Cut-out – 1/2 x 19’’ case size
- 35 -
DIMENSION AND PANEL CUT-OUT (3/4 size)
(Panel cut-out)
Note: For a rack mount unit, there are holes for joint kits assembling on top and bottom of the unit.
Figure 12 – Dimension and Panel Cut-out – 3/4 x 19’’ case size for flush mounting type
- 36 -
DIMENSION AND PANEL CUT-OUT (1/1 size)
(Panel cut-out)
Figure 13 – Dimension and Panel Cut-out – 1/1 x 19” case size for flush mounting type
- 37 -
19” RACK MOUNTING JOINT KITS ATTACHMENT
EP-204 (single 1/2 x 19” size rack) EP-205 (two 1/2 x 19” size racks)
- 38 -
CONNECTIONS DIAGRAM (COMPRESSION PLUG TYPE)
(*2) Semi-fast BO
(*3) Hybrid BO
Figure 15 – Binary input board and binary output module (for compression plug type terminal)
- 39 -
CONNECTIONS DIAGRAM (COMPRESSION PLUG TYPE)
15 (+) 15 (+) 15
BO1(*2) BI8 BI8
16 (-) 16 (-) 16
17 (+) 17 17 (+)
BO2(*2) BI9 BO1(*3)
18 (-) 18 18 (-)
21 (+) 21 21 21 (+)
BO3(*2) BI10 BO1(*1) BO2(*3)
22 (-) 22 22 22 (-)
23 (+) 23 23 23 (+)
BO4(*2) BI11 BO2(*1) BO3(*3)
24 (-) 24 24 24 (-)
25 (+) 25 25 25 (+)
BO5(*2) BI12 BO3(*1) BO4(*3)
26 (-) 26 26 26 (-)
27 27 27 27 (+)
BO6(*2) BO1(*2) BO4(*1) BO5(*3)
28 28 28 28 (-)
29 29 29 29 (+)
BO7 BO2(*2) BO5(*1) BO6(*3)
30 30 30 30 (-)
31 31 31
BO8 BO3(*2) BO6(*1)
32 32 32
33 33 33 33
BO9 BO4 BO7 BO7
34 34 34 34
35 35 35 35
37 37 37 37
36 36 36 36
BO10 BO5 BO8 BO8
38 38 38 38
(*1) Fast BO
(*2) Semi-fast BO
(*3) Hybrid BO
Figure 16 – Combined binary input and output module (for compression plug type terminal)
- 40 -
CONNECTIONS DIAGRAM (COMPRESSION PLUG TYPE)
PWS1 A
2
4
3
FAIL1
1
8
10
9
FAIL2
7
(+) 29
30
DC/DC
(-) 31
32
35
36
37
38
Protective Earth
- 41 -
CONNECTIONS DIAGRAM
CT/VT module
1 1 1
V Va-1VT Va
2 2 2
3 3
Vb-1VT Vb
4 4
5 5
5
Ia-1CT Vc-1VT Vc
6 6
6
7 7
Ib-1CT 1Ia
8 8
9 9 9
Ic-1CT Va-2VT 1Ib
10 10 10
11
11 11
Vb-2VT
Ia-2CT 12 1Ic
12 12
13
13 13
Vc-2VT
Ib-2CT 14 2Ia
14 14
15 15
Ic-2CT 2Ib
16 16
17 17 17
Ia-3CT Ia-4CT 2Ic
18 18 18
19 19 19
Ib-3CT Ib-4CT 3Ia
20 20 20
21 21 21
Ic-3CT Ic-1CT 3Ib
22 22 22
23 23 23
IN-1NCT
Ia-5CT 3Ic
24 or Ia-4CT 24 24
25 25 25
IN-2NCT
Ib-5CT 1IN
26 or Ib-4CT 26 26
27 27 27
IN-3NCT
Ic-5CT 2IN
28 or Ic-4CT 28 28
30 30 30
- 42 -
Typical arrangement of each module (1/2 rack size)
(+)
8
9
C12 8
9
BI5 BO5(*2) BI5
(-) 10 10 (-) 10 Ic-1CT
10
(+) 11 11 (+) 11
11
BI6 BO6(*2) BI6
(-) 12 12 (-) 12 Ia-2CT
12
(+) 13 13 (+) 13
13
BI7 BO7 BI7
(-) 14 14 (-) 14 Ib-2CT
14
(+) 15 15 (+) 15
(-) 16
BI8 BO8
16 (-) 16
BI8 C13 15
Ic-2CT
16
17 (+) 17
17
BO9 BI9 Ia-3CT
18 (-) 18
18
21 21 (+) 21 19
BO1(*1) BO10 BI10 Ib-3CT
22 22 (-) 22 20
23 23 (+) 23 21
BO2(*1) BO11 BI11 Ic-3CT
24 24 (-) 24 22
BO3(*1)
25
BO12
25 (+) 25
BI12
C14 23
IN-1NCT
26 26 (-) 26 24 or Ia-4CT
27 27 (+) 27
25
BI13 IN-2NCT
BO4(*1) BO13 (-) 28
28 28 26 or Ib-4CT
(+) 29
29 29 (+) 29
30 27
DC/DC BI14 IN-3NCT
BO5(*1) BO14 (-) 30
30 30 28 or Ic-4CT
(-) 31 31 31 (+) 31
32 BO6(*1) BO15 BI15
32 32 (-) 32 30
35
36
33 33 (+) 33
BI16
C15
BO7 BO16 (-) 34
34 34
37
35 (+) 35
38 35
37 BO17 BI17
36 (-) 36
36 (+) 37
BO8 37
FG
38 BO18 BI18
(-) 38
38
- 43 -
Typical arrangement of each module (3/4 rack size)
9
(+)
(-)
7
8
BI4 BO4(*2)
7
8
(+)
(-)
7
8
BI4
C12 7
8
Ib-1CT
FAIL2 100BASE-FX
7 (+) 9 9 (+) 9 9
BI5 BO5(*2) BI5 Ic-1CT
(-) 10 10 (-) 10 10
(+) 11 TX
(+) 11 11 11
BI6 BO6(*2) BI6 Ia-2CT
(-) 12 12 (-) 12 12
(+) 13 13 (+) 13 RX 13
BI7 BO7 BI7 Ib-2CT
(-) 14 14 (-) 14 14
17 (+) 17 17
BO9 BI9 Ia-3CT
18 (-) 18 18
21 21 (+) 21 19
BO1(*1) BO10 BI10 Ib-3CT
22 22 (-) 22 20
23 23 (+) 23 21
BO2(*1)
24
BO11
24 (-) 24
BI11
C14 22
Ic-3CT
25 25 (+) 25 23
IN-1NCT
BO3(*1) BO12 BI12
26 26 (-) 26 24 or Ia-4CT
27 (+) 27 25
27
IN-2NCT
BO4(*1) BO13 BI13
28 28 (-) 28 26 or Ib-4CT
(+) 29
29 (+) 29 27
29
30 IN-3NCT
DC/DC BO5(*1) BO14 BI14
30 30 (-) 30 28 or Ic-4CT
(-) 31
32
31 31
(+) 31
BI15
C15
BO6(*1) BO15 (-) 32
32 32 30
35
(+) 33
33 33
36 BI16
BO7 BO16 (-) 34
34 34
37
(+) 35
38 35 35
37 BI17
BO17 (-) 36
36
36 (+) 37
BO8 37
FG
38 BI18
BO18 (-) 38
38
- 44 -
Typical arrangement of each module (1/1 rack size)
[IO#8] [IO#7] [IO#6] [IO#5] [IO#4] [IO#3] [IO#2] [IO#1] [VCT#1] [VCT#2]
T9 T8 T7 T6 T5 T4 T3 T2 T1 VC1 VC2
PWS1 A BIO3 A BO1 A BI1 A VCT44B VCT48B
2
(+) 1
BI1 BO1(*2)
1 (+) 1
BI1
C11 1
No use
1
Va-1VT
(-) 2 2 (-) 2 100BASE-TX/ 2 2
4
1000BASE-T
(+) 3 3 (+) 3 3
3
FAIL1 BI2 BO2(*2) BI2 Vb-1VT
(-) 4 4 (-) 4 4
1
(+) 5 5 (+) 5 5 5
7
(-)
(+)
8
9
8
9
(-)
(+)
8
9
C12 8
9 9
(+) 11 11
(+) 11 11 11
BI6 BI6 Ia-2CT Vb-2VT
(-) 12
BO6(*2) (-) 12 12
12
12
(+) 13 13
(+) 13 13 13
BI7 Vc-2VT
BI7 BO7 (-) 14 Ib-2CT 14
(-) 14 14 14
(+) 15 15 (+) 15 15
(-) 16
BI8 BO8
16 (-) 16
BI8 C13 16
Ic-2CT
17 (+) 17 17 17
BO9 BI9 Ia-3CT Ia-4CT
18 (-) 18 18 18
21 21 (+) 21 19 19
BO1(*1) BO10 BI10 Ib-3CT Ib-4CT
22 22 (-) 22 20 20
23 23 (+) 23 21 21
BO2(*1) BO11 BI11 Ic-3CT
24 24 (-) 24 22 Ic-1CT
22
BO3(*1)
25
BO12
25 (+)
(-)
25
26
BI12
C14 23
IN-1NCT
23
Ia-5CT
26 26 24 24
27 (+) 27 25
27 25
BO4(*1) BO13 BI13 IN-2NCT
28 28 (-) 28 26 Ib-5CT
26
(+) 29 (+) 29
29 29 27 27
30
DC/DC BO5(*1) BO14 BI14 IN-3NCT
30 30 (-) 30 28 Ic-5CT
28
(-) 31 31 (+) 31
31
32 BO6(*1) BO15 BI15
35
32
33
32
33
(-)
(+)
32
33
C15 30 30
36 IRIG-B
BI16
BO7
34
BO16
34 (-) 34
•A1
•B1
37
35 35
(+) 35 • SIG
A2DISUSE
38
37 BO17 BI17 •B2
36
(-) 36
• DISUSE
36
BO8 37
(+) 37
•A3
38 BO18
38
(-) 38
BI18
•B3• GND
- 45 -
©Copyright 2020 Toshiba Energy Systems & Solutions Corporation. All rights reserved.
GKP-99-16001 Rev1.04