Tesys Contactors: Selection Guide

This document provides specifications for TeSys contactors, including: 1. It lists the rated operational current from 9A to 80A for various contactor models. 2. The rated operational voltage is listed as 690V. 3. Operating time for closing is 70ms and opening is 25ms at 20°C and rated voltage. 4. Coil consumption is 2.4W for most models and 0.6W for some relay models.

Uploaded by

sulphurdioxide
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
74 views2 pages

Tesys Contactors: Selection Guide

This document provides specifications for TeSys contactors, including: 1. It lists the rated operational current from 9A to 80A for various contactor models. 2. The rated operational voltage is listed as 690V. 3. Operating time for closing is 70ms and opening is 25ms at 20°C and rated voltage. 4. Coil consumption is 2.4W for most models and 0.6W for some relay models.

Uploaded by

sulphurdioxide
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Selection guide TeSys contactors

TeSys D low consumption contactors

Applications Automation systems

2
Rated operational current le max AC-3 (Ue y 440 V) 9A 12 A 18 A

le AC-1 (θ y 60 °C) 20/25 A 20/25 A 25/32 A

3 Rated operational voltage 690 V

Number of poles 3 or 4 3 or 4 3 or 4

4 Rated operational
power in AC-3
220/240 V 2.2 kW 3 kW 4 kW

380/400 V 4 kW 5.5 kW 7.5 kW

415/440 V 4 kW 5.5 kW 9 kW

500 V 5.5 kW 7.5 kW 10 kW

5 660/690 V 5.5 kW 7.5 kW 10 kW

Coil consumption 2.4 W (100 mA - 24 V)

Operating ranges 0.7…1.25 Uc

6
Operating time Closing 70 ms
at 20 °C and at Uc
Opening 25 ms

7 Auxiliary contact block modules 1 N/C and 1 N/O instantaneous contacts incorporated in the contactors, with add-on blocks
common to the whole range, comprising up to 2 N/C or 2 N/O instantaneous standard contacts

Interference suppression Built-in suppression as standard, by bi-directional peak limiting diode

Contactor type 3-pole LC1 D09 LC1 D12 LC1 D18


8 4-pole LC1 DT20/D098 LC1 DT25/D128 LC1 DT32/D188

Reversing contactor type 3-pole LC2 D09 LC2 D12 LC2 D18

4-pole LC2 DT20 LC2 DT25 LC2 DT32


9
Pages Contactors 24501/2 to 24502/5

Reversing contactors 24503/2 to 24510/3

(1) With low consumption kit LA4 DBL (see page 24511/7).
(2) With 2 low consumption kits LA4 DBL (see page 24511/7).
10

2 version: 8.5 0247Q-EN.indd


1

2
25 A 32 A 38 A 40 A 50 A 65 A

25/40 A 50 A 50 A 60 A – 80 A

690 V 690 V
3
3 or 4 3 3 3 3 3

5.5 kW 7.5 kW 9 kW 11 kW 15 kW 18.5 kW


4
11 kW 15 kW 18.5 kW 18.5 kW 22 kW 30 kW

11 kW 15 kW 18.5 kW 22 kW 25/30 kW 37 kW

15 kW 18.5 kW 18.5 kW 22 kW 30 kW 37 kW

15 kW 18.5 kW 18.5 kW 30 kW 33 kW 37 kW 5
2.4 W (100 mA - 24 V) 0.6 W (25 mA - 24 V) for relay LA4 DFB + the power consumed by the
contactor coil
0.7…1.25 Uc – – –

6
70 ms – – –

25 ms – – –

1 N/C and 1 N/O instantaneous contacts incorporated in the contactors, with add-on blocks common to the whole range, comprising up to 2 N/C or 2 N/O
instantaneous standard contacts 7
Built-in suppression as standard, by bi-directional peak limiting diode

LC1 D25 LC1 D32 LC1 D38 LC1 D40A (1) LC1 D50A (1) LC1 D65A (1)

LC1 DT40/D258 – – – 8
LC2 D25 LC2 D32 LC2 D38 LC2 D40A (2) LC2 D50A (2) LC2 D65A (2)

LC2 DT40
9
24501/2 to 24502/5

24503/2 to 24510/3

10

0247Q-EN.indd version: 8.5 3