Sensitive Stator and Rotor Earth Fault Protection at Hydro Generators
Sensitive Stator and Rotor Earth Fault Protection at Hydro Generators
Generators
Large hydro power plants are designed in a unit connection. The neutral point of the generator is
isolated or high ohmic earthed. The probability of a phase to earth fault - the stator earth fault - is
much higher than the other fault types. To detect this type of fault within a generator is one of the
important protection tasks. This contribution focuses on the stator earth fault protection in general
and highlights a principle which covers 100 % of the stator winding.
By virtue of the galvanic isolation of the rotor, an earth fault in the rotor leads to very small fault
currents and doesn’t damage the rotor. If a second earth fault occurs at another location in the field
system, the current will be flowing through the affected turns. The field current from a large machine
can be high causing serious damage on the rotor and the exciter. If a large part of the field-winding
is short-circuited, the flux may result in a mechanical force which is strong on one pole but weak on
the opposite one. The result is an unbalanced force which in large machines may be of the order of
50-100 tons. This causes violent vibrations which may damage bearings or even displace the rotor
to damage the stator. Therefore it is important to design the protection as sensitive as possible.
Keywords: Stator earth fault protection, 100% protection range, 20-Hz-injection method, rotor earth
fault protection, sensitivity, numerical protection
1. Stator Earth Fault Protection
Step-up
Possible region of
transformer
earth faults
Auxiliary
transformer
Figure 1: Typical plant design Figure 2: Influence of fault current and duration on
damage of a stator core
1
In praxis there exist two ways of calculating the necessary load resistance R L. In literature [1] the
argumentation starts with the possibility of transient overvoltages during intermittent earth faults at
isolated generator star points. A grounding of the star point only serves for limiting these transient
overvoltages, but a compromise must be found between the permitted fault current and the allowed
transient overvoltage. The general design rule describes equation (1).
1
RL (1)
ω CE
CCoup.
1 U 1 20 103
K N;G 0,1
2 3 2 3 721
RL
IC 0,8
The factor Fearth =1 is used for isolated networks. For safety reasons the factor 0.8 (possibility of
open transformer star point) is recommended in solidly earthed networks. Normally the actual
displacement voltage will be lower and the required load resistor may be higher than calculated.
2
The final discussion to this topic is the location of the load resistor. Normally a secondary resistor
with a transformer is used. One way is the connection on the neutral side of the generator with a
neutral transformer. This cost optimized solution lives with the risk of failures on the high voltage
side of the neutral transformer due to transient overvoltages, e.g. lightning overvoltages. Earthing of
the generator is then possible. Therefore this application requires unconditionally a 100% stator
earth fault protection.
A different preferred solution is an absolutely free neutral point of the generator. Nothing is
connected on generator star point and this minimizes the additional risk of unintentional earthing of
the star point. The secondary load resistor is connected on a five-limb earthing transformer which is
located on the generator main leads (see chapter 1.3, figure 5).
1.2 Protection based on the displacement voltage
The measurement of the displacement voltage on the generator side is the standard application of
stator earth fault protection at unit connection schemes. Due to harmonics (especially the 3 rd
harmonics) and the requirement for a high sensitivity the measurement of the fundamental
frequency should be used. With a correct selection of the load resistor a protective range of 90% or
95% can be reached. There exist no limitations from the numerical relay. An accurate measurement
of a low voltage is always possible.
In applications at pump storage power stations the protection should cover a wide frequency
operating range, especially at starting conditions with U/f = const. Only the frequency tracking
guarantees the same accuracy over a wide frequency band. In [3] this function is active from 11Hz.
1.3 100%-stator-earth-fault protection with 20-Hz-injection method
Due to the risk of an earth fault close to the generator star point a secure protection principle is
required and shall be based on a different measuring method to avoid common mode failures. A
further requirement is the independence from the operating conditions of the generator. It was found
out that the risk of an earth fault during a startup process or after refurbishment is sometimes higher
than at continuous operation.
During the construction of the large power plants in Germany in the seventies the utilities demanded
a secure measuring principle. The injection principle based on the 20-Hz-frequency was developed
and within the numerical technology permanently improved.
The basic principle is explained in figure 4. A 20-Hz-voltage with a low magnitude (< 1% of rated
generator voltage) operates as an electromotive force (e.m.f) on the neutral point of the generator.
In case of an earth fault a closed loop exists and a 20-Hz-fault current flows. The detection of the
earth fault is independent of the fault location in the stator winding. A further feature is the activation
of the protection before a plant goes into service. The 20-Hz-generator must be switched on and
then the protection becomes automatically active.
max. 20 Hz
200 V
RE
I
3
Figure 5 represents a more detailed drawing with the necessary additional accessories. The band
pass smoothes the 20-Hz-square voltage and additionally protects the 20-Hz-generator in the case
of an earth fault with a full displacement voltage. The 20-Hz-e.m.f. on the load side results from the
voltage divider: load resistor and 20-Hz-series resistance of the band pass (8). Therefore a design
requirement for the load resistor exists. The resistor shall be higher than 0.5 (worst case 0.3). In
this case the secondary injected 20-Hz-voltage is close to (0.5/8.5)*25 V 1.5 V. The
requirement for a higher secondary load resistor can be easy fulfilled, if a higher secondary voltage
on the neutral transformer is used or the primary voltage is the same as the phase to earth voltage
of the generator (saturation degree shall be according the rated generator voltage). A reduced
transformer ratio by the factor of 3 automatically leads to a 3 times higher load resistor.
Bandpass 20-Hz-Generator
Earthing transformer Low ohmic (8 at 20 Hz) (appr. 25 V)
a
DC or AC
RL
b Blocking
400A
5A
Relay
U
a I
Neutral
transformer b
4
Frequency operating range
0Hz 10Hz 40Hz 70Hz
90% Stator earth fault protection with displacement voltage 90% Stator earth fault protection with displacement voltage
200
200
150
REm
k
R in Ohm
SES100Aus
k 100
86
GAnr
k
60
50
0 0
100 200 300 400 500 600 700
100 k ta 687.5
t in ms
Resistance
Trip
Pickup
Figure 8: Offline calculation of the earth fault resistance form the fault record
With this fault record the measured fault resistance could be calculated offline and figure 8 shows
the result. The measured resistance was for a certain time below the threshold which is marked by
the dotted lines (pickup at 60 and dropout at 86 - these are secondary setting values).
5
2. Rotor Earth Fault Protection
6
Change
over
contact
Group 1
Ucontrol
7XT71
Rotor 7XR6004 7UM62
Umeas
Group 2
Ucontrol
7XT71
Connection on 7UM62
earthing brush Umeas
Rotor RS t
Uout
Ucontrol Relay
40 k
Umeas
U ~ 1R
7
Figure 12: Record during a commissioning test
A standard question is always the connection to different excitation systems. With static exciters a
symmetrical connection is recommended. An asymmetrical connection is also possible, but the
series resistors or capacitors must always be connected in parallel. Figure 13 summarizes the
different ways of interfacing.
Rotor Excitation
machine 50/60 Hz
1 - 3 Hz
a) Rotating Diodes
50/60 Hz
Rotor
Excitation transformer
1 - 3 Hz
b) Static Exciter
8
3. Summary
The contribution dealt with two important topics for hydro generators, the stator and rotor earth fault
protection. These protection principles are basic functions in each large power plant. At hydro
power plants there exist special operating conditions particularly in pump storage power station
applications.
One major attention in the paper was the sensitivity and the protective range which can be covered.
It was clearly shown, that the 100 % stator earth fault protection with the 20-Hz-injection method
covers the full stator winding and is nearly independent from the operating conditions of the
generator.
The rotor earth fault protection with a low frequency square wave injection is characterized by a
high sensitivity. High ohmic rotor earth faults can be detected. Two stages with different settings
shall be the standard, one for alarm and the other for trip.
With practical examples the performance of both protection functions was shown.
4. Literature
[1] IEEE Guide for the application of neutral grounding in electrical utility systems.
Part II – Grounding of synchronous generator systems, published by IEEE, New York, 1989
[2] Planning Machine Protection Systems, Siemens application guide,
No. E50400-U0089-U412-A2-7600
[3] SIPROTEC 7UM62 V4.6, Multifunction Generator, Motor and Transformer Protection
Relay, Manual No C5300-G1176-C149-4
Author Resume
Dr. Hans-Joachim Herrmann
Born in 1952 and have 29-year’s protection experience. He graduated from Technical University of Dresden in 1977.During
1977-1991, worked as Assistant Professor on the Technical University of Zittau. Then join SIEMENS as Member of Product
Management Protection in the Energy Automation Division. Up to now, there are totally approx. 60 Contributions in Papers
and Conferences published. He is also the Co-author of a Protection Book (in Russian) and the author of a Book “Numerical
Protection” (in German).
Diego Gao
Born in 1975 and have 8-year’s protection experience. In 2004, he joined Siemens Power Automation Ltd. (SPA) serving as
a technical support engineer on generator-transformer protection.