REF4 - Stabilized Restricted Earth-Fault Protection Ref4A Ref4B
REF4 - Stabilized Restricted Earth-Fault Protection Ref4A Ref4B
Contents
1. Introduction ................................................................................................ 3
1.1 Features................................................................................................ 3
1.2 Application ............................................................................................ 3
1.3 Input description ................................................................................... 4
1.3.1 REF4A (high voltage side)........................................................... 4
1.3.2 REF4B (low voltage side) ............................................................ 5
1.4 Output description................................................................................. 5
2. Description of operation............................................................................ 6
2.1 Configuration ........................................................................................ 6
2.1.1 Setting the rated values of the protected unit .............................. 6
2.2 Measuring mode ................................................................................... 6
2.3 Operation criteria .................................................................................. 7
2.3.1 Blocking based on the second harmonic of the neutral current... 9
2.4 Delayed reset facility and Drop-off time in DT Mode ............................ 9
2.5 Setting groups....................................................................................... 9
2.6 Test mode ........................................................................................... 10
2.7 START and TRIP outputs ................................................................... 10
2.8 Delayed trip output CBFP ................................................................... 10
2.9 Resetting............................................................................................. 10
2.10 Connection of current transformers .................................................... 11
2.11 Recorded Data.................................................................................... 12
2.11.1 General...................................................................................... 12
2.11.2 Date and time ............................................................................ 12
2.11.3 Duration ..................................................................................... 13
2.11.4 Status data ................................................................................ 13
2.11.5 Currents..................................................................................... 13
2
Distribution Automation REF4_
1. Introduction
1.1 Features
1.2 Application
∆Io>
Figure 1. Protection diagram symbol of REF4A and REF4B
For IEC symbols used in single line diagrams, refer to the manual “Technical
Descriptions of Functions, Introduction”, 1MRS750528-MUM.
3
REF4_ Distribution Automation
4
Distribution Automation REF4_
5
REF4_ Distribution Automation
2. Description of operation
2.1 Configuration
Phase currents and neutral current are measured via conventional current
transformers. The measuring devices and signal types for analog channels are
selected and configured in a special dialog box of the Relay Configuration
Tool. The digital inputs are configured in the same programming environment
(the number of selectable analog inputs, digital inputs and digital outputs
depends on the hardware used).
When the analog channels and digital inputs have been selected and
configured in the dialog box, the inputs and outputs of the function block can
be configured on a graphic worksheet of the configuration tool. The phase
currents IL1, IL2, IL3 (IL1b, IL2b, IL3b) and neutral current Io (Iob) are connected to
the corresponding IL1, IL2, IL3 (IL1b, IL2b, IL3b) and Io (Iob) inputs of the
function block. Binary inputs are connected to the boolean inputs of the
function block, and the outputs of the function block are connected to the
output signals in the same way.
A separate scaling factor can be set for each analog channel. The factors
enable differences between the ratings of the protected unit and those of the
measuring device (CTs, VTs, etc.). A setting of 1.000 means that the rated
value of the protected unit is exactly the same as that of the measuring device.
For more information, refer to the technical reference manual of the product in
question.
Note! When the function blocks REF4A and REF4B are used, the 2nd
harmonic restraint must be selected for the channels connected to the Io and
Iob inputs of the function block. This selection is made in the Special
measurements dialog box of the Configuration tool.
6
Distribution Automation REF4_
I d = ΣI − I O (1)
An earth fault occurring in the protected area (that is, between the phase CTs
and the neutral connection CT) will cause a differential current. The directions,
i.e. the phase difference of the residual current and the neutral current are
considered in the operation criteria in order to maintain selectivity.
During an earth fault in the protected area, the currents ΣI and Io are directed
towards the protected area. The calculation of the directional differential
current, Idcosϕ, is specified to be 1 when the phase difference of the residual
current and the neutral current is 180°, that is, when the currents are in
opposite direction at earth faults within the protected area. Similarly, cosϕ is
specified to be 0 when the phase difference between the residual current and
the neutral current is less than 90° in situations with no earth fault in the
protected area. Thus tripping is possible when the phase difference between
the residual current and the neutral current is above 90°.
The stabilizing current Ib used with the stabilizing current principle is calculated
as an average of the phase currents in the windings to be protected:
7
REF4_ Distribution Automation
Figure 4. Setting range of the operation characteristic for the stabilized differential
current principle of the earth-fault protection function.
The setting Basic setting is used for defining the characteristic of the
function, shown in Figure 3. In the figure the Basic setting value is
indicated as Id1/In. The differential current value required for tripping is constant
at the stabilizing current values 0.0 < Ib/In < 1.0. When the stabilizing current is
higher than 1.0, the slope of the operation characteristic (Id2/Ib2) is constant at
50%, as shown in Figure 3.
8
Distribution Automation REF4_
Two different groups of setting values, group 1 and group 2, are available for
the function block. Switching between the two groups can be done in the
following ways:
9
REF4_ Distribution Automation
3. By means of the input signal GROUP when allowed via the parameter
"Group selection" (i.e. when V2 = 2*))
The control parameter "Active group" indicates that the setting group is
valid at a given time.
The digital outputs of the function block can be activated with separate control
settings for each output either locally via the HMI or externally via the serial
communication. When an output is activated with the test parameter, an event
indicating the test is generated.
The protection functions operate normally while the outputs are tested.
The output signal START is always pulse-shaped. The minimum pulse width
of the START and TRIP output signals is set via a separate parameter on the
HMI or on serial communication. If the start situation is longer than the set
pulse width, the START signal remains active until the start situation is over.
The output signal TRIP may have a non-latching or latching feature. When the
latching mode has been selected, the TRIP signal remains active until the
output is reset even if the operation criteria have reset.
The function block provides a delayed trip signal CBFP after the TRIP signal
unless the fault has disappeared during the set CBFP time delay. In circuit-
breaker failure protection, the CBFP output can be used to operate a circuit
breaker upstream from the circuit breaker of the feeder. The control parameter
"Trip pulse" also sets the width of the CBFP output signal.
2.9 Resetting
The TRIP output signal and the registers can be reset either via the RESET
input, or over the serial bus or the local HMI.
10
Distribution Automation REF4_
The operation indicators, latched trip signal and recorded data can be reset as
follows:
1)
Resets the latched trip signal and recorded data of the particular function block.
2)
Affects all function blocks.
The connections of the main current transformers are designated as type I and
type II. In the case that the earthings of the current transformers are inside or
outside the area to be protected, the setting parameter “CT connection” is
type I (Figure 5). In the case that the earthings of the current transformers are
inside and outside the area to be protected the setting parameter “CT
connection” is type II (Figure 6). The default is type I.
Figure 5. The connected phase currents and the neutral current have opposite
directions at an external E/F situation.
11
REF4_ Distribution Automation
2.11.1 General
The information required for later fault analysis is recorded when the function
block starts or trips (there is no TRIGG input available).
The data of the last three events are stored into the registers Recorded data
1…3, beginning from Recorded data 1. These registers are updated in a
cyclical manner, where the values of the most recent event overwrite the
oldest recorded data. If recorded data has been reset or the relay has been
restarted, first event is again stored to Recorded data 1.
The time stamp indicates the rising edge of the START or TRIP signal.
12
Distribution Automation REF4_
2.11.3 Duration
The status data of the blocking state as well as the "Active group"
parameter are recorded at the moment of recording. The "Active group"
parameter indicates the setting group valid for the recorded data.
2.11.5 Currents
If the function block trips, the current values will be updated at the moment of
tripping i.e. on the rising edge of the TRIP signal. If the function block starts
but does not trip, the current values captured during one fundamental cycle
(20 ms at rated frequency 50 Hz) after the beginning of the start situation are
recorded. So the values of the neutral current I0, the directional differential
current Idcos(ϕ) and the stabilizing current Ib always originate from the same
moment and are recorded as multiples of the rated current In.
13
REF4_ Distribution Automation
3.1 General
• The different event mask parameters (see section “Control settings”) affect
the visibility of events on the HMI or on serial communication (LON or SPA)
as follows:
Event mask 1 (FxxxV101/102) SPA / HMI (LON)
Event mask 2 (FxxxV103/104) LON
Event mask 3 (FxxxV105/106) LON
Event mask 4 (FxxxV107/108) LON
For example, if only the events E3, E4 and E5 are to be seen on the HMI of
the relay terminal, the event mask value 56 (8 + 16 + 32) is written to the
“Event mask 1” parameter (FxxxV101).
In case a function block includes more than 32 events, there are two
parameters instead of e.g. the “Event mask 1” parameter: the parameter
“Event mask 1A” (FxxxV101) covers the events 0...31 and “Event mask
1B”(FxxxV102) the events 32...63.
14
Distribution Automation REF4_
15
REF4_ Distribution Automation
16
Distribution Automation REF4_
17
REF4_ Distribution Automation
1)
Output TRIP O2 0 or 1 - 0 R/M Status of trip signal
1)
Output CBFP O3 0 or 1 - 0 R/M Status of circuit breaker failure
signal
1)
Status 0 = Not active; 1 = Active
18
Distribution Automation REF4_
3.3.3.1 General
The information required for later fault analysis is recorded when the function
block starts or trips.
The data of three last events (events 1...3) are stored and the values of the
most recent event always replace the data of the oldest event. The registers
are updated in the following order: Recorded data 1, Recorded data 2,
Recorded data 3, Recorded data 1, Recorded data 2, and so on. If the
recorded data has been reset or if the relay has been restarted, the first event
is again stored in Recorded data 1.
The time stamp indicates the rising edge of the START or TRIP signal.
3.3.3.3 Duration
3.3.3.4 Currents
If the function block trips, the current values are updated at the moment of
tripping i.e. on the rising edge of the TRIP signal. If the function block starts
but does not trip, the current values captured one fundamental cycle (20 ms at
rated frequency 50 Hz) after the beginning of the start situation is recorded. So
the values of the neutral current I0, the directional differential current
Id cosϕ and stabilizing current Ib always originate from the same moment and
are recorded as multiples of the rated current In.
The status data of the blocking state as well as the "Active group"
parameter are recorded at the moment of recording. The "Active group"
parameter indicates the setting group valid for the recorded data.
19
REF4_ Distribution Automation
20
Distribution Automation REF4_
21
REF4_ Distribution Automation
3.3.4 Events
REF4A
REF4B
22
Distribution Automation REF4_
4. Technical data
Operation accuracies Depends on the frequency of the current measured:
f/fn = 0.95...1.05
1)
Accuracy of differential current measurement:
± 2°
Reset time 40...1000 ms (depends on the minimum pulse width set for the TRIP
output)
Retardation time Total retardation time when the current drops below
3)
the start value < 50 ms
1) Assumes that protected unit setting is 1.000 for all the analog input channels involved.
2) Includes the delay of the signal output relay
3) Includes the delay of the heavy-duty output relay
REF4B A
23