SCVCST - Synchro-Check/ Voltage-Check Function Stage 1 (Scvcst1) Stage 2 (Scvcst2)
SCVCST - Synchro-Check/ Voltage-Check Function Stage 1 (Scvcst1) Stage 2 (Scvcst2)
Synchro-Check/
Issued: 10/1998
Version: G/23.06.2005
Voltage-Check Function
Stage 1 (SCVCSt1)
Data subject to change without notice Stage 2 (SCVCSt2)
Contents
1. Introduction ................................................................................................ 2
1.1 Features................................................................................................ 2
1.2 Application ............................................................................................ 2
1.3 Input description ................................................................................... 3
1.4 Output description................................................................................. 3
2. Description of operation............................................................................ 4
2.1 Configuration ........................................................................................ 4
2.2 Operation criteria .................................................................................. 4
2.3 Operation .............................................................................................. 5
2.3.1 Synchro-check ............................................................................. 5
2.3.2 Voltage-check .............................................................................. 7
2.3.3 Bypass mode ............................................................................... 8
2.3.4 Operation mode ........................................................................... 8
2.3.5 Operation with phase-to-earth voltage measurements.............. 12
2.4 Setting groups..................................................................................... 15
2.5 Resetting............................................................................................. 16
1. Introduction
1.1 Features
1.2 Application
This document specifies the functions of the synchro-check function blocks SCVCSt1
and SCVCSt2 used in products based on the RED 500 Platform.
The function block SCVCSt_ is designed to be used for checking the conditions for
circuit-breaker closing. The function can be used for closing ring mains,
interconnecting busbars and connecting generators to the network. The harmonics are
suppressed.
For IEC symbols used in single line diagrams, refer to the manual “Technical
Descriptions of Functions, Introduction”, 1MRS750528-MUM.
2
Distribution Automation SCVCSt_
3
SCVCSt_ Distribution Automation
2. Description of operation
2.1 Configuration
The measuring devices and signal types for analogue channels are selected and
configured in a special dialogue box of the Relay Configuration Tool included in the
CAP 505 Tool Box. Digital inputs are configured in the same programming
environment (the number of selectable analogue inputs, digital inputs and digital
outputs depends on the hardware variant used).
The special measurements dialogue box in the configuration tool is used for selecting
frequency protection for the voltage inputs.
When the analogue channels and digital inputs have been selected and configured in
the dialogue box, the inputs and outputs of the function block can be configured on a
graphic worksheet of the configuration tool. The phase-to-phase voltage U12 is
connected to the U1 input and correspondingly U12b is connected to the U2 input.
Furthermore, digital inputs are connected to the boolean inputs of the function block,
and in the same way the outputs of the function block are connected to the output
signals.
If the relay is connected to measure phase-to-earth voltages on one side of the breaker,
there are two ways to connect them to SCVCSt_:
If phase-to-earth voltages are measured on both sides of the breaker, connect the
virtual phase-to-phase voltage channels U12s and U12bs to SCVCSt_.
4
Distribution Automation SCVCSt_
2.3 Operation
The function tacts of the circuit-breaker close. This duration is determined on the basis
of the frequency of the voltages on opposite sides of the CB. The synchro-check
function block has two parallel functions: a synchro-check function and a voltage-
check function.
2.3.1 Synchro-check
The synchro-check function can be used for two different operating conditions. The
most typical case is one where both sides of the circuit breaker to be closed are live
and thus the synchronism is always checked before the circuit breaker is given the
permission to close. In the other situation one or both sides of the circuit breaker to be
closed are dead and, consequently, the frequency and phase differences cannot be
measured, in which case the relay checks the energizing direction.
The purpose of the synchro-check function is to find the instant when the voltages on
both sides of the circuit breaker are synchronized, i.e. they have the same frequency,
are in phase and are of such a magnitude that the concerned busbars or lines can be
regarded as live. When the frequency, phase angle and voltage conditions are fulfilled,
the duration of the synchronized state is checked on the basis of the frequency and
phase differences measured so as to ensure that the conditions will still be met when
the CB closes. Depending on the circuit breaker and the closing system, the delay
from the moment the closing signal is given until the circuit breaker finally closes is
about 50 - 250 ms. The CB operate time selected tells the relay for how long the
conditions at least have to persist.
5
SCVCSt_ Distribution Automation
• The network sections on both sides of the CB must be energized. The voltage
magnitudes of the energized networks are determined by the set value for the upper
threshold voltage Umax.
• The voltage difference over the CB must be small enough. The voltage difference
allowed is determined by the set voltage difference value dU.
• The frequencies of the network sections (voltages) to be connected shall not differ
too much from each other. The frequency conditions are fulfilled when the allowed
frequency difference of the networks to be connected is smaller than the set
frequency difference value df.
• The network sections to be connected (voltages) have the same phase angle. The
phase angle conditions are fulfilled when the allowed phase angle difference
between the network voltages is smaller than the set phase angle difference dphi.
• The validity time for CB closing conditions, achieved from frequency and phase-
angle differencies, must have a duration of at least the time needed for the closing
of the circuit breaker to be operated (operate time of CB).
When the closing conditions mentioned above are fulfilled simultaneously, the
network voltages are considered to be synchronized and a closing command signal
SC_OK is delivered to the CB.
• The threshold voltage Umax, above which the measured bus/line network voltage
must be before the network is considered to be energized.
• Voltage difference allowed, absolute value dU. The set value determines the
maximum allowed voltage difference for the synchro-check function.
• Frequency difference allowed, absolute value df. The set value determines the
maximum allowed frequency difference for the synchro-check function.
• The phase-angle difference allowed, dphi, is an absolute value which means that
there are no demands concerning the phase-angle direction. The set value
determines the maximum allowed phase-angle difference for the synchro-check
function.
• The operate time of a circuit breaker is set via the parameter “Oper. time of CB”.
In asynchronous mode the synchro-check function checks that the voltage, frequency
and phase differences are within the set limits. From the frequency slip (∆f) the
function predicts the time remaining to the moment when the phase difference exceeds
the setting. CB closing is only allowed if the time required for CB closing is shorter
than the predicted time.
6
Distribution Automation SCVCSt_
In synchronous mode the aim is that the phase difference at the moment of CB closing
is zero. The mode is only possible when the frequency slip on the network is below
0,04% of fn and all the other conditions are fulfilled. If the time required for reaching a
synchronized state exceeds the maximum check time, the function will fail.
2.3.2 Voltage-check
The energizing direction in the voltage-check function is chosen via the parameter
“Energizing mode”. When the value of the parameter is 0, the voltage-check function
is not in use.
When the energizing direction corresponds to the settings, the situation has to remain
constant for a certain period of time before the close signal is permitted. The purpose
of the operate time (dead time) is to ensure that the dead side remains de-energized
and that the situation is not due to a temporary interference. Should the conditions not
persist for the specified time, the operate time is reset and the procedure is started over
when the conditions are fulfilled again. Circuit-breaker closing is thus not permitted
until the energizing situation has remained constant throughout the set operate time.
• The threshold voltage Umax, above which the measured bus/line network voltage
must be before the network is considered to be energized. The set threshold value
applies to the synchro-check function as well.
• The threshold value Umin, below which the measured bus/line network voltage
must be before the network is considered to be non-energized.
7
SCVCSt_ Distribution Automation
Note!
Because the setting ranges of the threshold voltages Umax and Umin partly overlap
each other, the setting conditions may be such that the setting of the non-energized
threshold value Umin is higher than that of the energized threshold value Umax. The
parameters should be set carefully by the user to avoid the setting conditions
mentioned above.
If the parameters “SynchroMode” and “Energizing mode” are both set to “Not in use”,
the SCVCSt_ function block is in bypass mode. This means that in command mode,
the command input is wired straight through to the SC_OK output and in continuous
mode, the SC_OK output is continuously FALSE.
Note!
In bypass mode events are sent as in normal operation (i.e. when output changes
occur).
The closing command conditions for the circuit breaker are checked by the synchro-
check and voltage-check functions. In addition to the closing command conditions, the
delivering of the final closing signal depends on the operation mode selected for the
synchro-check function. Selection of the operation mode depends on whether the
synchro-check function itself directly uses the output signal to close the circuit breaker
(command mode operation) or if another function block (for example a control
function block) performs the closing operation after having received a command
signal from the synchro-check function (continuous mode operation).
The operation mode is selected via the parameter “Operate mode”. In continuous
mode, the synchro-check function is running continuously checking the synchronism.
When synchronism is detected i.e. the conditions are fulfilled according to the
settings, the output SC_OK is set to TRUE and will remain so as long as the
conditions remain fulfilled.
A distinctive difference between the two operation modes is that in the command
mode operation the synchro-check function is controlled by an external command
signal but in the continuous mode operation no external signal is needed. In the
command mode operation the synchro-check function delivers the closing signal
directly to the object to be controlled (a circuit breaker) whereas in the continuous
8
Distribution Automation SCVCSt_
mode operation the closing signal is delivered via another function block that delivers
the final closing signal.
In the continuous mode operation the closing signal output of the synchro-check
function stays active as long as the closing conditions remain fulfilled and the signal
disappears when the conditions cease. The operation of the synchro-check function
can be blocked by applying a blocking signal to the function.
The continuous mode can be used to provide extra information on synchronism for an
external operating device.
In command mode operation, an external command signal, besides the normal closing
conditions, is needed for delivering the closing signal. The command signal shall
remain active for the set checking time. The closing signal from the synchro-check
function can be blocked by applying the blocking signal to the function.
In command mode operation, the synchro-check function itself controls the selected
object directly via its own output signal. In this case the control function block
delivers the command signal for closing to the synchro-check function for releasing of
a closing signal pulse to the circuit breaker. If, after the delivered command signal for
closing, the closing conditions are fulfilled during a permitted check time, the
synchro-check function delivers a closing signal to the circuit breaker.
9
SCVCSt_ Distribution Automation
If the command signal delivered to the synchro-check function is too long, the alarm
ALARM_CO is given and the alarm state will persist until the closing command
signal is removed. A failed closing attempt produces the alarm signal ALARM_NC of
about 500 ms, after which the synchro-check function is ready for a new operation
sequence.
The most essential features of the command mode operation are shown in Figures 6, 7
and 8.
10
Distribution Automation SCVCSt_
Conditions OK
Command
SC_DUE
Conditions OK
SC_DUE
5s
ALARM_CO commsign
Conditions OK
SC_DUE
SC_OK
11
SCVCSt_ Distribution Automation
When phase-to-earth voltages U1 and U2 are measured, the virtual channel U12s can
be connected to SCVCSt_ in Relay Configuration Tool. Correspondingly, the virtual
channel U12bs can be used when the phase-to-earth voltages U1b and U2b are
measured. Virtual U12s or U12bs can be used, for example, when phase-to-earth
voltages are measured on one side of the circuit breaker and the phase-to-phase
voltages on the other side (see Figure 8).
L1
L2
L3
X1.1
27 100V Ch 10, VT4
A
N
n
25
24
100V Ch 9, VT3
22
21
100V Ch 8, VT2
19
18
100V Ch 7, VT1
16
S1 15 0,2A
P1 14 1A Ch 6, CT5
13
12 1A
11 5A Ch 5, CT4
P2 10
S2
9 1A
8 5A Ch 4, CT3
7
6 1A
5 5A Ch 3, CT2
4
3 1A
2 5A Ch 2, CT1
1
DIFF
X2.2 Ch 9, sensor
DIFF
X2.3 Ch 8, sensor
DIFF
X2.4 Ch 7, sensor
DIFF
A
N
n
a
X2.5 Ch 5, sensor
L1
L3
L2
DIFF
X2.6 Ch 4, sensor
DIFF
X2.7 Ch 3, sensor
DIFF
X2.8 Ch 2, sensor
DIFF
X2.9 Ch 1, sensor
synchro9
DIFF
REF 541
(1MRS 090115-AABA/BABA/CABA)
12
Distribution Automation SCVCSt_
synchro_ab
synchro_cd
synchro11
13
SCVCSt_ Distribution Automation
When voltage combine function is in use, the function block calculates phase-to-phase
voltage U12 internally from phase-to-earth voltages U1 and U2.
When using the voltage combine function, the voltage connected to the U2 pin should
always be U12 or U12b.
synchro_ef
REF54x
SCVCSt1
U12
U1 U1
U2
U3 U2
U12
U1
U2
U3 voltcomb2
14
Distribution Automation SCVCSt_
The voltage combine function can be taken in use by setting the control parameter
VoltCombine to 1. The VoltCombine is a special parameter that affects the
analogue measurements of the feeder terminal. Therefore, for the parameter to take
effect, the new parameter value has to be stored via the parameter Store and the
relay has to be reset via the parameter Software reset in the MMI menu
Configuration/General.
Note!
Do not reset the relay before the parameter value storing has been completed
successfully.
Two different groups of setting values, group 1 and group 2, are available for
SCVCSt_. Switching between the two groups can be done in the following three
ways:
The control parameter Active group indicates the setting group valid at a given
time.
15
SCVCSt_ Distribution Automation
2.5 Resetting
The recorded data can be reset either via the RESET input, or over the serial bus or the
local MMI.
16
Distribution Automation SCVCSt_
3.1 General
• Each function block has a specific channel number for serial communication
parameters and events. The channel for SCVCSt1 is 70 and that for SCVCSt2 71.
• The data direction of the parameters defines the use of each parameter as follows:
Data direction Description
R, R/M Read only
W Write only
R/W Read and write
• The different event mask parameters (see section “Control settings”) affect the
visibility of events on the MMI or on serial communication (LON or SPA) as
follows:
Event mask 1 (FxxxV101/102) SPA / MMI (LON)
Event mask 2 (FxxxV103/104) LON
Event mask 3 (FxxxV105/106) LON
Event mask 4 (FxxxV107/108) LON
For example, if only the events E3, E4 and E5 are to be seen on the MMI of the
relay terminal, the event mask value 56 (8 + 16 + 32) is written to the “Event mask
1” parameter (FxxxV101).
In case a function block includes more than 32 events, there are two parameters
instead of, for example the Event mask 1 parameter: the parameter Event
mask 1A (FxxxV101) covers the events 0...31 and Event mask 1B
(FxxxV102) the events 32...63.
17
SCVCSt_ Distribution Automation
18
Distribution Automation SCVCSt_
Event mask 1 V101 0...255 - 255 R/W Event mask 1 for event
transmission (E0 ... E7)
Event mask 2 V103 0...255 - 255 R/W Event mask 2 for event
transmission (E0 ... E7)
Event mask 3 V105 0...255 - 255 R/W Event mask 3 for event
transmission (E0 ... E7)
Event mask 4 V107 0...255 - 255 R/W Event mask 4 for event
transmission (E0 ... E7)
1)
Energizing mode 0=Not in use, 1 = U1->U2 or U1<-U2, 2 = U1->U2, 3= U1<-U2,
4 = U1->U2 or U1<-U2 or both "cold"
2)
Operation mode 0 = Command mode, 1 = Continuous mode
3)
Synchro mode 0 = Not in use,1 = Asynchronous mode, 2 = Synchronous mode
4)
Group selection 0 = Group1, 1 = Group2, 2 = GROUP-input
5)
Active group 0 = Group1, 1 = Group2
6)
Voltage combine 0 = Disabled, 1 = Enabled
19
SCVCSt_ Distribution Automation
3.3.3.1 General
The information required for later analysis is recorded when the function block
activates the SC_OK output.
The data of the last three events are stored in Recorded data 1…3, beginning from
Recorded data 1. These registers are updated in a cyclical manner, where the values of
20
Distribution Automation SCVCSt_
the most recent event overwrite the oldest recorded data. If the recorded data has been
reset or the relay has been restarted, the first event is again stored in Recorded data 1.
The time stamp indicates the rising edge of the SC_OK signal.
If the function block trips, the measured voltage, phase angle and frequency values are
updated at the moment of tripping i.e. on the rising edge of the SC_OK signal. Thus
the values of the voltages, phase angles and frequencies always originate from the
same moment.
The voltages are recorded as multiples of the rated voltage Un. The phase angles are
recorded in degrees. The frequencies are recorded in Hertz.
The status data of the Active group parameter is recorded at the rising edge of the
SC_OK signal.
21
SCVCSt_ Distribution Automation
22
Distribution Automation SCVCSt_
3.3.4 Events
23
SCVCSt_ Distribution Automation
4. Technical data
Operation accuracies At the frequency range f/fn = 0.95...1.05:
H -
K -
SCVCSt2 D -
G -
H -
24